Emerson Fisher C1 Data Sheet

C1 Controllers and Transmitters
D103291X012
Fisherr C1 Pneumatic Controllers and Transmitters
Fisher C1 controllers and transmitters continue the tradition of durable and dependable Fisher pressure instrumentation while addressing air/gas consumption concerns. The C1 is used wherever durable and dependable pressure instrumentation is required. The use of this product in demanding applications, such as those found in chemical process, gas, and oil production industries, demonstrates its versatility. The C1 can reduce steady-state air/gas consumption to as little as 1/10th that of previous products.
C1 controllers compare sensed process pressure (or differential pressure) with an operator-adjusted set point, and send a pneumatic signal to an adjacent control element that maintains the process pressure at or near the set point value. C1 transmitters sense process variables and send out a pneumatic signal, usually to an indicating or recording device that directly indicates the process measurement.
Product Bulletin
34.3:C1
July 2014
Unless otherwise noted, all NACE references are to NACE MR0175 / ISO15156 & NACE MR0103.
Features
nWide Range of Sensing Elements—A Bourdon tube is
available for high pressures or bellows for vacuum and low pressures. Either kind of sensing element can be installed in the case with the controller or transmitter. Two interchangeable ranges of output bellows and gauges also are available.
n Reduced Air/Gas Consumption—The C1 pneumatic
controller is an energy efficient choice, helping to improve profits and uptime. Steady-state consumption rate is less than the 6 scfh requirement set for the oil and gas industry by the US Environmental Protection Agency (New Source Performance Standards Subpart OOOO, EPA‐HQ‐QAR‐2010-0505).
FISHER C1 PNEUMATIC CONTROLLER
YOKE-MOUNTED ON CONTROL VALVE ACTUATOR
n Sour Service Capability—Materials are available for
applications handling sour process fluids. These constructions comply with the metallurgical requirements of NACE MR0175 / ISO15156 & NACE MR0103. Environmental restrictions may apply.
nMounting Versatility—Install the case on a panel,
wall or pipestand, as well as directly on the control valve actuator.
n Reduced Maintenance Costs—A spring-out cleaning
wire, shown in figure 4, provides for in-service cleaning of the relay orifice.
n Proportional-Only, Proportional-Plus-Reset, and
Differential Gap Configurable—The C1 controller
can be configured to provide various modes of control.
(Features continued on page 3)
www.Fisher.com
Product Bulletin
34.3:C1 July 2014
Specifications
C1 Controllers and Transmitters
D103291X012
Available Configurations
See table 1
Input Signal
Pressure
Type:
J Gauge pressure, J vacuum, J compound
pressure, or
J differential pressure of a liquid or gas
Limits: See table 2 or 3
Output Signal
Proportional or Proportional-Plus-Reset Controllers and Transmitters:
J 0.4 to 2.0 bar (6 to 30 psig) pneumatic pressure
J 0.2 to 1.0 bar (3 to 15 psig) or
signal
Differential Gap Controllers:
(0 and 20 psig) or
J 0 and 2.4 bar (0 and 35 psig)
J 0 and 1.4 bar
pneumatic pressure signal Action: Control action is field reversible between
J direct (increasing sensed pressure produces
increasing output signal) and
J reverse (increasing
sensed pressure produces decreasing output signal).
Supply Pressure Requirements
(1)
See table 4
Supply Pressure Medium
Air or natural gas
Air Quality: Supply pressure must be clean, dry air that meets the requirements of ISA Standard 7.0.01. A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air supply should be minimized
Natural Gas: Natural gas must be clean, dry, oil-free, and noncorrosive. H
S content should not exceed 20
2
ppm.
Steady-State Air Consumption
(2)(3)
0.2 to 1.0 bar (3 to 15 psig): 0.08 normal m3/hour (3 scfh)
0.4 to 2.0 bar (6 to 30 psig): 0.12 normal m
3
/hour
(4.5 scfh)
Supply and Output Connections
1/4 NPT internal
Supply and Output Pressure Gauge Ranges
See table 5
Proportional Band Adjustment
For Proportional-Only Controllers: Full output pressure change adjustable from
J 2% to 100% of the
sensing element range for 0.2 to 1.0 bar (3 to 15 psig) or
J 4% to 100% of the sensing element range for 0.4
to 2.0 bar (6 to 30 psig)
For Proportional-Plus-Reset Controllers: Full output pressure change adjustable from
J 3% to 100% of the
sensing element range for 0.2 to 1.0 bar (3 to 15 psig), or
J 6% to 100% of the sensing element range
for 0.4 to 2.0 bar (6 to 30 psig)
Differential Gap Adjustment
For Differential Gap Controllers: Full output pressure change adjustable from 15% to 100% of sensing element range
Reset Adjustment
For Proportional-Plus-Reset Controllers: Adjustable from 0.01 to 74 minutes per repeat (100 to 0.01 repeats per minute)
Zero Adjustment (Transmitters Only)
Continuously adjustable to position span of less than 100% anywhere within the sensing element range
Span Adjustment (Transmitters Only)
Full output pressure change adjustable from 6 to 100% of process sensing element range
Performance
Repeatability: 0.5% of sensing element range Dead Band (Except Differential Gap Controllers
(4)
):
0.1% of sensing element range
Typical Frequency Response at 100% Proportional Band:
Output to Actuator: 0.7 Hz and 110 degree phase shift with 1850 cm
3
(113 inches3) volume actuator at mid-stroke Output to Positioner Bellows: 9 Hz and 130 degree phase shift with 0.2 to 1.0 bar (3 to 15 psig) output to
3
33 cm
( 2 inches3 ) bellows
-continued-
2
C1 Controllers and Transmitters
D103291X012
Specifications (continued)
Ambient Operating Temperature Limits
J
Standard Construction: -40 to 71_C (-40 to 160_F)
J High Temperature Construction: -18 to 104_C
(1)
(0 to 220_F)
Anti-reset windup (differential pressure relief) and process pressure gauge options are only available in the standard construction
Typical Ambient Temperature Operating Influence
Proportional Control only: ±3.0% of output span for each 28_C (50_F) change in temperature between
-40 and 71_C (-40 and 160_F) for a controller set at 100% proportional band Reset Control only: ±2.0% of output span for each 28_C (50_F) change in temperature between -40 and 71_C (-40 and 160_F) for a controller set at 100% proportional band Transmitters only: ±3.0% of output span for each 28_C (50_F) change in temperature between -40 and 71_C (-40 and 160_F) for a transmitter set at 100% span
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. The pressure and temperature limits in this document, and any applicable standard or code limitation should not be exceeded.
2. Normal m
3. To convert from air flow rate to natural gas flow rate multiply by 1.29.
4. An adjustable differential gap (differential gap controllers) is equivalent to an adjustable deadband.
3
/hr: normal cubic meters per hour (m3/hr, 0_C and 1.01325 bar, absolute). Scfh: standard cubic feet per hour (ft3/hr, 60_F and 14.7 psig).
Housing
Designed to NEMA 3 (Weatherproof) and IEC 529 IP54 Specifications
Hazardous Area Classification
Complies with the requirements of ATEX Group II Category 2 Gas and Dust
Construction Materials
See tables 2, 3, and 6
Approximate Weight
8.2 kg (18 pounds)
Product Bulletin
34.3:C1
July 2014
Table 1. Available Configurations
AVAILABLE CONFIGURATIONS
DESCRIPTION
Proportional controller
Proportional-plus-reset controller
Differential-gap controller - - ­Transmitter C1D
1. See figure 4 and 5 for construction details.
Features (continued)
(1)
Without anti-reset windup With anti-reset windup - - -
Bourdon Tube Sensing Element
(Gauge Pressure Only)
C1P C1B
n Easy, More Accurate Adjustments—Make pressure
set point, proportional band, and reset changes
Pressure
Bellows Sensing Element
Gauge Pressure Differential Pressure
with simple dial-knob controls that help to assure
n Field Reversible—Switch action from direct to
positive settings. reverse or vice versa without additional parts. As illustrated in figure 3, transfer the reversing block to the opposite side of the flapper, invert the proportional band assembly and change the feedback bellows tubing connections.
n Sensitive Response—Area ratio of large relay
diaphragm to small relay diaphragm permits small
nozzle pressure changes to induce much greater
output pressure changes.
C1D
3
Product Bulletin
34.3:C1 July 2014
C1 Controllers and Transmitters
D103291X012
Table 2. Bourdon Tube Pressure Ranges and Materials
PRESSURE RANGES
(1)
MAXIMUM ALLOWABLE STATIC PRESSURE LIMITS
Standard With Optional Travel Stop
Bar Psig Bar Psig Bar Psig
0 to 2.0 0 to 4.0 0 to 7.0
0 to 14 0 to 20 0 to 40 0 to 70
0 to 100 0 to 200 0 to 350
0 to 550 0 to 700
1. Range marked on Bourdon tube may be in kPa (1 bar = 100 kPa).
2. Bourdon tube may be pressured to limit shown without permanent zero shift.
3. With travel stop set at 110% of the range.
4. Bourdon tubes are also available in NACE compliant material. Contact your Emerson Process Management sales office for additional information.
0 to 30 0 to 60 0 to 100
0 to 200 0 to 300 0 to 600 0 to 1000
0 to 1500 0 to 3000 0 to 5000
0 to 8000 0 to 10,000
2.0
4.0
7.0
14 20 40 70
100 200 350
550 700
30 60
100
200 300 600
1000 1500
3000 5000
8000
10,000
3.3
6.6 11
19 29 50 83
115 230 380
550 700
(2)
(3)
48 96
160
280 420 720
1200 1650
3300 5500
8000
10,000
Table 3. Bellows Pressure Ranges and Materials
PRESSURE RANGES
0 to 150 mbar (0 to 60 inch wc)
Vacuum
0 to 340 mbar (0 to 10 inch Hg) 0 to 1.0 bar (0 to 30 inch Hg)
Compound pressure
Gauge pressure
Positive pressure
75 mbar vac. to 75 mbar (30 inch wc vac. to 30 inch wc) 1.4 20 6.9 100 500 mbar vac. to 500 mbar (15 inch Hg vac. to 7.5 psig) 2.8 40 6.9 100
1.0 bar vac. to 1.0 bar (30 inch Hg vac. to 15 psig) 2.8 40 - - - - - ­0 to 150 mbar (0 to 60 inch wc)
0 to 250 mbar 0 to 350 mbar
(2)
(0 to 100 inch wc)
(3)
(0 to 140 inch wc) 0 to 0.35 bar (0 to 5 psig) 0 to 0.5 bar (0 to 7.5 psig)
0 to 0.7 bar (0 to 10 psig) 0 to 1.0 bar (0 to 15 psig) 0 to 1.4 bar (0 to 20 psig) 0 to 2.0 bar (0 to 30 psig)
0 to 200 mbar (0 to 80 inch wc)
Differential pressure
(4)
0 to 0.7 bar (0 to 10 psi) 0 to 1.4 bar (0 to 20 psi) 0 to 2.0 bar (0 to 30 psi)
1. Bellows may be pressured to limit shown without permanent zero shift.
2. C1B transmitter only.
3. Except C1B transmitter.
4. The overrange limit for these sensing elements is a differential pressure equal to the maximum allowable static pressure limit.
Brass Construction
Bar Psig Bar Psig
1.4
2.8
2.8
1.4
1.4
2.8
2.8
2.8
2.8
2.8
2.8
2.8
1.4
2.8
2.8
- - -
MATERIAL
(4)
316 Stainless Steel
MAXIMUM ALLOWABLE
STATIC PRESSURE LIMITS
Stainless Steel
Construction
20 40 40
20 20 40 40 40
40 40 40 40
20 40 40
- - -
- - -
- - -
6.9
- - -
- - -
- - -
- - -
- - -
- - -
6.9
- - -
6.9
- - -
- - -
- - -
6.9
(1)
- - -
- - -
100
- - -
- - -
- - -
- - -
- - -
- - -
100
- - -
100
- - -
- - -
- - -
100
Table 4. Supply Pressure Data
Output Signal
Bar
Psig
1. If this pressure is exceeded, control may be impaired.
2. If this pressure is exceeded, damage to the controller may result.
4
0.2 to 1.0 or 0 and 1.4 (differential gap) 1.4 2.8
0.4 to 2.0 or 0 and 2.4 (differential gap) 2.4 2.8 3 to 15 or 0 and 20 (differential gap) 20 40 6 to 30 or 0 and 35 (differential gap) 35 40
Normal Operating Supply
Pressure
(1)
Maximum Allowable Supply Pressure To Prevent
Internal Part Damage
(2)
C1 Controllers and Transmitters
D103291X012
Table 5. Supply and Output Pressure Gauge Ranges
Gauge Scale
Single
Dual 0 to 30 psig/0 to 200 kPa 0 to 60 psig/0 to 400 kPa
Triple 0 to 30 psig/0 to 2 kg/cm2/0 to 2 bar 0 to 60 psig/0 to 4 kg/cm2/0 to 4 bar
Table 6. Construction Materials
Part Material
In contact with process
In contact with operating medium
Other
1. NACE materials compliant with the latest versions of NACE MR0175/ISO 15156 and MR0103.
Bourdon tube Stainless steel or NACE compliant N04400 nickel alloy Sensing bellows Brass or stainless steel Pressure block Stainless steel or NACE compliant stainless steel Control tubing (from pressure block to sensing element
and to optional process pressure gauge)
All other interior tubing Stainless steel
Exterior tubing
Exterior fittings Brass or stainless steel Nozzle and reversing block Zinc/stainless steel Relay springs and spring plate Steel Relay diaphragms Nitrile/nylon (standard) or polyacrylate/nylon (high-temperature) Other metal relay parts, proportional bellows,
and exhaust/reset bellows
Reset valve assembly and differential relief valve if used Zinc/steel/ceramic O-rings Nitrile (standard) or fluorocarbon (high-temperature) Gaskets Chloroprene (standard) or silicone (high-temperature) Case and adjustment dial Aluminum Cover Aluminum, except glass for gauge windows Flapper Stainless steel Control link N04400 nickel alloy and/or stainless steel Flexure and pressure/ setting adjustment assemblies Aluminum/steel/stainless steel/plastic Calibration adjustor Zinc O-rings Nitrile
0.2 to 1.0 Bar (3 to 15 Psig) or
0 and 1.4 Bar (0 and 20 Psig) Output
0 to 30 psig 0 to 2 kg/cm 0 to 200 kPa
2
Product Bulletin
34.3:C1
July 2014
0.4 to 2.0 Bar (6 to 30 Psig) or
0 and 2.4 Bar (0 and 35 Psig) Output
0 to 60 psig 0 to 4 kg/cm 0 to 400 kPa
Stainless steel or NACE compliant stainless steel
Copper (with or without PVC plastic lining), stainless steel, or synthetic rubber
Aluminum/stainless steel
2
(1)
(1)
(1)
Principle of Operation
The pressure connections to the controller depend upon the type of pressure sensing, gauge or differential. Gauge pressure controllers use either a Bourdon tube or bellows as the sensing element. Differential pressure controllers use two bellows to sense differential pressure.
The key to C1 controller operation is the pressure­balanced relay with its yoked double-diaphragm assembly, shown in figure 1 or 2.
The relay is connected so that supply pressure bleeds through the fixed orifice before escaping through the nozzle. The nozzle pressure registers on the large relay diaphragm, and loading pressure (controller output) on the small relay diaphragm.
Steady-state sensed process pressure holds the Bourdon tube steady in relation to the nozzle. This allows pressure to escape between the nozzle and beam-flapper assembly at the same rate it bleeds through the orifice.
A change in the process pressure moves the beam and flapper with respect to the nozzle by either expanding or contracting the Bourdon tube arc. An increasing process pressure with direct action (or decreasing pressure with reverse action) produces a nozzle-flapper restriction that increases the loading on the large relay diaphragm. This causes the relay valve to close at the exhaust end and to open at the inlet end. Additional supply pressure flows through the relay chamber to increase the loading pressure on the
5
Product Bulletin
34.3:C1 July 2014
Figure 1. Schematic of Reverse-Acting Proportional-Only and Proportional-Plus-Reset Controllers
C1 Controllers and Transmitters
D103291X012
CONSTANT SUPPLY PRESSURE
EXHAUST
EXHAUST END OF RELAY
BOURDON TUBE
FIXED PIVOT
TO FINAL CONTROL ELEMENT
BEAM AND FLAPPER
PROPORTIONAL-ONLY CONTROLLER
SENSED PRESSURE OUTPUT PRESSURE NOZZLE PRESSURE RESET PRESSURE
GE23696 GE34724-A E1062
RESET BELLOWS
NOZZLE
PROPORTIONAL BELLOWS
SENSED PRESSURE
control valve actuator. A decreasing process pressure with direct action (or increasing pressure with reverse action) produces a nozzle-flapper opening that bleeds off pressure on the large relay diaphragm. This causes
INLET END OF RELAY VALVE
SMALL DIAPHRAGM
LARGE DIAPHRAGM
RESTRICTION
PROPORTIONAL BAND ADJUSTMENT KNOB
VENT
CANTILEVER SPRING
cantilever spring. The spring rate of the cantilever spring increases as its length shortens, allowing less motion to be transferred from the bellows to the beam
and flapper for a given change in output pressure. the relay valve inlet to close and the exhaust to open, thus exhausting loading pressure from the actuator.
Proportional-Plus-Reset Controllers
PRESSURE-SETTING KNOB
PRESSURE SETTING DIAL
RESET BELLOWS
PROPORTIONAL BELLOWS
PROPORTIONAL-PLUS-RESET CONTROLLER
RESET VALVE
Proportional-Only Controllers
The controller output pressure change feeds back to the proportional bellows, countering the pressure change in the nozzle and equalizing the relay diaphragm pressure differential. The relay valve maintains a new loading pressure according to the change in sensed pressure.
If the proportional band adjustment is at its maximum setting, the cantilever spring in the proportional band assembly has a low spring rate, allowing more feedback motion to be transferred from the proportional bellows for a change in output pressure. As the effective length of the cantilever is reduced, its spring rate increases, causing less feedback motion from proportional bellows. Setting the proportional band knob to its maximum results in a proportional band of 100%. The lower the proportional band adjustment, the shorter the effective length of the
6
Additionally, all proportional-plus-reset C1 controllers
have a two-way reset restriction valve that channels
proportional pressure into a reset bellows to oppose
the proportional bellows action. The action of this
reset pressure occurs on a delayed basis. The reset
valve can be adjusted to vary the time of delay.
Anti-Reset Windup
C1 controllers with anti-reset windup have an
adjustable and reversible differential relief valve to
provide anti-reset windup. As shown in figure 2, the
proportional pressure registers rapidly on the spring
side of the relief valve diaphragm as well as in the
proportional bellows. Reset pressure registers slowly
on the opposite side of the relief valve diaphragm. As
long as controller output pressure changes are slow
enough for normal proportional and reset action, the
relief valve spring keeps the relief valve diaphragm
from opening. However, a large or rapid decrease in
C1 Controllers and Transmitters
D103291X012
Figure 2. Schematic of Reverse-Acting Proportional-Plus-Reset Controller with Anti-Reset Windup
CONSTANT SUPPLY PRESSURE
PRESSURE-SETTING KNOB
PRESSURE SETTING DIAL
PROPORTIONAL BAND ADJUSTMENT KNOB
TO FINAL CONTROL ELEMENT
EXHAUST
RESTRICTION
RESET BELLOWS
Product Bulletin
34.3:C1
July 2014
DIFFERENTIAL RELIEF VALVE
CANTILEVER
SPRING PROPORTIONAL BELLOWS
SENSED PRESSURE
SENSED PRESSURE OUTPUT PRESSURE NOZZLE PRESSURE RESET PRESSURE
GE23697-A GE34724-A E1063-1
controller output pressure causes the relay to rapidly exhaust loading pressure from the control element, and also from the proportional system and spring side of the relief diaphragm. If this decrease on the spring side of the diaphragm is greater than the relief valve spring setting, the diaphragm will move off the relief valve orifice and permit the reset pressure on the opposite side of the relief valve diaphragm to bleed rapidly into the proportional system. The anti-reset
This construction causes the controller output to switch from full supply pressure to zero pressure or vice versa. The difference between the process pressure when the controller output switches to zero and the process pressure when the controller switches to maximum is the differential gap. Adjusting the proportional band adjustment adjusts the width of the gap; adjusting the set point positions the gap within
the process pressure range. windup action also can be reversed to relieve with an increasing proportional pressure.
Transmitters
Differential Gap Controllers
In C1 differential gap controllers, feedback pressure does not counteract the change in flapper position. Instead, the output pressure is piped to the bellows located on the side of the beam and flapper opposite the nozzle. Feedback pressure now reinforces the flapper movement by the sensed pressure change.
Action of a pneumatic transmitter is similar to that of a
proportional-only controller. Since the output pressure
of the transmitter has no effect on the process
pressure, transmitter output pressure is a proportional
measure of the process pressure. The proportional
band adjustment determines the span of the
transmitter and the pressure setting mechanism
determines the zero of the transmitter.
RESET VALVE
7
Product Bulletin
34.3:C1 July 2014
Figure 3. Conversion from Reverse to Direct Action or Proportional to Differential Gap
C1 Controllers and Transmitters
D103291X012
RELAY TUBING
FLAPPER/SCREW
REVERSING
ACTING
POSITION
GE28263-B
RELAY TUBING
PROPORTIONAL
TUBING
REVERSING BLOCK/NOZZLE
REVERSE ACTING
TO CHANGE ACTION OF THE CONTROLLER, REPOSITION THE PROPORTIONAL TUBING,
REVERSING BLOCK/NOZZLE AND PROPORTIONAL BAND ASSEMBLY AS SHOWN ABOVE
PROPORTIONAL-ONLY CONTROLLER OR TRANSMITTER
PROPORTIONAL TUBING
PROPORTIONAL BAND ASSEMBLY
BELLOWS
BELLOWS
RELAY TUBING
REVERSING BLOCK/
DIRECT ACTING
POSITION
FLAPPER/SCREW
RELAY TUBING
REVERSING BLOCK
DIRECT ACTING
POSITION
PROPORTIONAL
TUBING
BELLOWS
NOZZLE
PROPORTIONAL BAND ASSEMBLY
DIRECT ACTING
PROPORTIONAL TUBING
PROPORTIONAL BAND ASSEMBLY
FLAPPER/SCREW
REVERSE ACTING
POSITION
REVERSING BLOCK
REVERSE ACTING
GE34724-B
PROPORTIONAL BAND ASSEMBLY
DIFFERENTIAL-GAP CONTROLLER
Construction Features
Rugged Service Capability
The case and cover are made of weather resistant, die-cast aluminum. Stainless steel tubing and fitting materials provide the capability for operation in ammonia and similar corrosive service conditions. Optional materials for relay diaphragms and other soft parts permit operation at ambient temperatures up to 93_C (200_F).
FLAPPER/SCREW
BELLOWS
DIRECT ACTING
Low-Pressure Precision
Bellows sensing constructions provide better accuracy
in low-pressure, vacuum, or compound ranges. Two
sensing bellows are used where an important variable
is the difference between two sensed pressures.
Conversion From Proportional To
Differential Gap Control
The C1 controller can be configured to provide
differential gap (on-off control) rather than
proportional control. The proportional bellows is
connected so that feedback pressure pushes the beam
8
C1 Controllers and Transmitters
D103291X012
Figure 4. Fisher C1 Constructions
PRESSURE BLOCK
AND TUBING
RELAY ORIFICE
SPRING-OUT CLEANING WIRE
Product Bulletin
34.3:C1
July 2014
PRESSURE ADJUSTMENT DESIGN MINIMIZES BACKLASH FOR MORE POSITIVE SETTINGS
PROPORTIONAL BAND ASSEMBLY
PROPORTIONAL BAND ASSEMBLY KNOB
GE28280-B GE28281-B GE31718-A E1056
REVERSING BLOCK
REVERSE-ACTING CONTROLLER
HIGH-VISIBILITY DIAL ON RESET VALVE
REVERSE-ACTING CONTROLLER
PROPORTIONAL-PLUS-RESET
VENTED BELLOWS
PROPORTIONAL
PROPORTIONAL BELLOWS
PROPORTIONAL BAND ASSEMBLY
PROPORTIONAL BAND ASSEMBLY KNOB
RESET BELLOWS
PROPORTIONAL BELLOWS
ANTI-RESET WINDUP
ASSEMBLY DETAIL
and flapper in the same direction as caused by the sensed pressure change. This reinforcement completely opens the relay valve either to full supply pressure or to full exhaust, allowing no in-between throttling. To change from a proportional to a differential gap controller, or vice versa, just reverse the tubing connection on the mounting base and invert the proportional band assembly, as shown in figure 3.
Reverse/Direct Conversion
Switching the action from reverse to direct or vice
versa is done by moving the reversing block and
feedback bellows connection and inverting the
proportional band assembly as shown in figure 3.
9
Product Bulletin
34.3:C1 July 2014
C1 Controllers and Transmitters
D103291X012
Figure 5. Bellows Details
SENSING BELLOWS
BELLOWS SPRING
GE34727-B E1057
HIGH-PRESSURE SENSING BELLOWS
LOW-PRESSURE SENSING BELLOWS
BELLOWS DETAILS
The differential relief valve has a range of 0.14 to 0.4
bar (2 to 7 psig) and, unless ordered otherwise, is set
by the factory to relieve at a 0.3 bar (5 psi) difference
between proportional and reset pressures.
Manual Backup
As shown in figure 6, a Fisher 670 or 671
panel-mounted loading regulator with changeover
valve permits switching to an alternate loading
pressure, if a C1 controller experiences supply pressure
failure or other malfunction.
Figure 6. Schematic of Manual Backup Changeover Hookup
CONTROLLER LOADING PRESSURE GAUGE
LOADING PRESSURE OUTPUT FROM CONTROLLER
A2111-2
TO ACTUATOR AND VALVE
ALTERNATE LOADING PRESSURE GAUGE
670 OR 671 MANUAL LOADER WITH THREE-WAY CHANGEOVER VALVE
ALTERNATE LOADING PRESSURE SOURCE
GE35157 E1058
Anti-Reset Windup
The anti-reset windup capability of C1 controllers provides quick equalization of reset and proportional pressures. This capability reduces overshoot and the time required for a system to return to the pressure setting after large changes in sensed pressure. This feature is useful when slow reset and broad proportional band settings are used.
Continuous Indication of Process
Pressure
Replacing the supply pressure gauge on a pressure
controller or transmitter by a process pressure gauge
permits indicating process pressure in one of the
ranges shown in table 7. To obtain a supply pressure
indication, install a gauge on the supply regulator. The
process pressure gauge must be specially ordered and
comes with brass trim standard in all ranges and
stainless steel trim optional in some ranges. Adding a
process pressure gauge in the field also requires a
special control pressure block. A process pressure
gauge cannot be added to controllers or transmitters
that use a differential bellows for sensing pressure.
Table 7. Optional Process Pressure Gauges
Sensing Element Gauge Range
Bourdon tube Positive pressure
Bellows Positive pressure 0 to 30 psig
1. Consult your Emerson Process Management sales office for gauges in other units.
2. Also available in stainless steel trim.
(1)
0 to 30 psig 0 to 60 psig 0 to 160 psig
0 to 300 psig 0 to 600 psig 0 to 1000 psig
(2)
(2)
(2)
10
C1 Controllers and Transmitters
D103291X012
Product Bulletin
34.3:C1
July 2014
Bourdon Tube Protection
All Bourdon tube constructions are available with one or both of the following protective devices:
n Barrier Protector for Corrosive or Clogging Process
Fluids—A sealed and fluid-filled barrier (described in
Fisher product bulletin 39:025) may be installed between the process and the Bourdon tube. The barrier fluid transmits sensed pressure on a one-to-one basis into the Bourdon tube.
n Travel Stop for Bourdon Tube—The stop limits
Bourdon tube overtravel when momentary surges in the sensed pressure exceed the Bourdon tube rating. Although it does not permit accurate control or transmission of a pressure higher than the upper range limit listed in table 2, this stop does permit Bourdon tube overpressuring to the maximum static pressure shown in table 2 without damage.
Installation
A C1 controller or transmitter normally comes installed on a final control element or indicating device or equipped for separate surface or pipestand mounting. Usually, a control valve with just a controller or transmitter and one supply regulator has the controller/transmitter and regulator yoke-mounted on opposite sides of the actuator as shown in figure 7. Nipple mounting of the supply regulator (if desired) is available. Specify such mounting if the opposite yoke boss of an actuator will be occupied by a positioner.
Figure 7. Typical Yoke Mounting
FISHER 657 ACTUATOR
FISHER 67 FILTER REGULATOR
C1 CONTROLLER
GE33947-A E1086
2. Composition, pressure, and temperature of measured variable(s).
3. Ambient temperature
4. Pressure in process vessel (if closed)
5. Type number, orientation, and other applicable descriptions of control or indicating device(s).
Install the controller or transmitter so that the vent points down. Figure 8 illustrates the vent location, the location of all case connections, dimensions, and mounting information.
Ordering Information
Application
When ordering, specify:
1. Type of service, such as pressure reduction or pressure relief, throttling or differential gap.
Construction
Refer to the Specifications and the Construction Features sections. Review the description for each specification, construction feature, and in the referenced tables. Specify the desired selection whenever there is a choice.
Always specify the complete type number of the C1 controller or transmitter, direct or reverse action, supply pressure regulator, and other desired equipment. On controllers with anti-reset windup, specify whether the differential relief valve is to relieve with falling or rising output.
11
Product Bulletin
34.3:C1 July 2014
Figure 8. Dimensions
180.8
(7.12)
C1 Controllers and Transmitters
D103291X012
23.1
(0.91)
241.3
(9.50)
1/4 NPT
79.4
(3.12)
FLUSH PANEL
MOUNTING
E1053
15.9
60.3 DIA
(0.62)
(2.38)
RIGHT SIDE VIEW SHOWING
PIPESTAND MOUNTING
6.35 (0.25) DIA SCREWS
SURFACE MOUNTING
LEFT SIDE VIEW
CASE TAPPED 1/4 NPT FOR VENT
29.4
(1.16)
142.7 (5.62)
23.1
(0.97)
1/4 NPT
65.8
(2.59)
23.1
(0.97)
238.1
(9.38)
122.2 (4.81)
63.5
(2.50)
FRONT VIEW
63.5
(2.50)
69.1
(2.72)
122.2 (4.81)
37.6
(1.48)
DETAIL OF PROPORTIONAL-PLUS-RESET
CONTROLLER WITH ANTI-RESET
WINDUP RELIEF VALVE
1/4 NPT
50.8
(2.00)
50.8
(2.00)
1/4 NPT
BACK VIEW
218.9
(8.62)
PANEL CUTOUT DIMENSIONS
FOR PANEL MOUNTING
215.9
(8.50)
14.3 R (0.56)
(INCH)
mm
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Process Management
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
E 2008, 2014 Fisher Controls International LLC. All rights reserved.
12
Loading...