Emerson Fisher 646 Data Sheet

Product Bulletin
646 Transducer
D101374X012
February 2015
Fisherr 646 Electro-Pneumatic Transducer
62.1:646
The Fisher 646 electro-pneumatic transducer uses a converter module that converts a 4 to 20 milliampere input signal to a proportional 0.2 to 1.0 bar (3 to 15 psig) pneumatic output signal. The converter module uses small parts of minimum mass, which are balanced symmetrically around a pivot point at the center of the mass. This balanced arrangement results in a high performance instrument that reduces sensitivity to vibration.
An integral pneumatic relay provides the high capacity necessary to drive pneumatic control valve/acutator
assemblies without additional boosters or positioners. The transducer also provides stable, accurate operation when its output is transmitted to small volume chambers, such as a pneumatic positioner or other pneumatic instrument. Reduced sensitivity to vibration combined with high capacity and first order lag characteristics make the 646 transducer ideal for direct mounting on control valve/actuator combinations.
Connectors and piping can be installed with each 646 transducer for diagnostic testing.
FISHER 646 ELECTRO-PNEUMATIC TRANSDUCER
WITH FISHER 657 ACTUATOR AND E VALVE
www.Fisher.com
W6783-1
W4908-1
FISHER 646 ELECTRO-PNEUMATIC TRANSDUCER
Product Bulletin
62.1:646 February 2015
Specifications
646 Transducer
D101374X012
Input Signal
4 to 20 mA DC, constant current with 30 VDC maximum compliance voltage
Equivalent Circuit
The 646 equivalent circuit is a series circuit consisting of a constant voltage drop (battery) of approximately
2.1 VDC and a total resistance of 143 ohms. Input is shunted by three 6.8 V zener diodes (see figure 1).
Output Signal
0.2 to 1.0 bar (3 to 15 psig) direct acting only
Supply Pressure
(1)
Recommended: 1.4 bar (20 psig) Minimum: 1.4 bar (20 psig)
Maximum: 3.4 bar (50 psig)
Average Steady‐State Air Consumption
(2)(3)
0.08 m3/hr (3 scfh) at 1.4 bar (20 psi) supply pressure
Maximum Output Air Capacity
(2)
8.0 m3/hr (300 scfh) at 1.4 bar (20 psig) supply pressure
Performance
(4)
Reference Accuracy: ±0.5% of full scale output span; includes combined effects of hysteresis, linearity, and deadband
Independent Linearity: ±0.5% of full scale output span
Hysteresis: 0.4% of full scale output span Frequency Response: Gain is attenuated 3 dB at 10 Hz
with transducer output signal piped to a typical instrument input
Temperature Effect: ±4% of full scale output span per 55_C (100_F) change
Supply Pressure Effect: 0.2% of full scale output span per psi supply pressure change
Vibration Effect: Less than 1% of full scale output span when tested to SAMA PMC 31.1, Condition 3
-continued-
Electromagnetic Compatibility: Meets EN 61326-1 (First Edition) Immunity—Industrial locations per Table 2 of the EN 61326-1 standard. Performance is shown in table 1 below. Emissions—Class A ISM equipment rating: Group 1, Class A
Operating Ambient Temperature Limits
(1)
-40 to 71_C (-40 to +160_F)
Electrical Classification
CSA— Intrinsically Safe, Explosion-proof, Type n, Dust-Ignition proof, Div 2
FM— Intrinsically Safe, Explosion-proof, Type n, Non-incendive, Dust-Ignition proof
ATEX— Intrinsically Safe, Flameproof, Type n IECEx— Intrinsically Safe, Flameproof, Type n
Refer to tables 2, 3, 4, and 5 additional information.
Housing
CSA— Type 3 Encl. FM— NEMA 3, IP54 ATEX— IP64 IECEx— IP54
Mount instrument with vent on side or bottom if weatherproofing is a concern
Other Classifications/Certifications
CUTR— Customs Union Technical Regulations (Russia, Kazakhstan, and Belarus)
INMETRO— National Institute of Metrology, Quality and Technology (Brazil)
KGS— Korea Gas Safety Corporation (South Korea) Contact your Emerson Process Management sales
office for classification/certification specific information
Construction Materials
Housing, Cap, and Relay Body: Die cast aluminum with less than 1% copper
2
646 Transducer
D101374X012
Specifications (continued)
Product Bulletin
62.1:646
February 2015
Adjustments
Zero and Span: Trim potentiometers (20 turn) for zero and span adjustments are located under the housing cap
Mounting Position
Any position is acceptable for standard pipestand, panel, or actuator mounting. For weatherproof housing, mount the transducer to allow the vent to drain.
Connections
Supply and Output Pressure: 1/4 NPT internal connection
Vent: 1/4 NPT internal Electrical:
J Standard 1/2 NPT or, J Optional M20 or
PG13 conduit adapter (see figure 3) Wire Size: 18 to 22 AWG
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. The pressure and temperature limits in this document and any applicable standard or code limitation should not be exceeded.
2. Normal m
3. Average flow rate determined at 12 mA and 0.6 bar (9 psig) output.
4. Performance values are obtained using a transducer with a 4 to 20 mA dc input signal and a 0.2 to 1.0 bar (3 to 15 psig) output signal at an ambient temperature of 24_C (75_F).
3
/hour--Normal cubic meters per hour (0_C and 1.01325 bar, absolute). Scfh--Standard cubic feet per hour (60_F and 14.7 psig).
Approximate Weight (Transducer Only)
1.6 kg (3.5 pounds)
Options
Output pressure gauge
Table 1. EMC Summary Results—Immunity
Port Phenomenon Basic Standard Test Level Performance Criteria
Electrostatic discharge (ESD) IEC 61000-4-2
Enclosure
I/O signal/control
Specification Limit = +/- 1% of span.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
Radiated EM field IEC 61000-4-3
Burst (fast transients) IEC 61000-4-4 1 kV A Surge IEC 61000-4-5 1 kV (line to ground only, each) B Conducted RF IEC 61000-4-6 150 kHz to 80 MHz at 3 Vrms A
4 kV contact 8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80% 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% 2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
(1)
A
A
Figure 1. Equivalent Circuit
4 - 20 mA
+
6.8V 6.8V 6.8V
-
A6013
0.7V
0.7V
0.7V
60 Ohms
60 Ohms
23 Ohms
3
Product Bulletin
62.1:646 February 2015
646 Transducer
D101374X012
Features
n Small Size—The small size and light-weight design of
the transducer facilitate mounting and provide improved space utilization.
n Vibration Resistance—The transducer, used in a
standard valve/actuator mounted application, exhibits an output shift of less than 1 percent of span when tested to SAMA Standard PMC 31.1, Condition 3.
n High Output Capability—The output volume of the
transducer is adequate to drive valve/actuator combinations without requiring a positioner or volume booster.
n Low Air Consumption—The transducer has low air
consumption which cuts operating costs.
nEasy Maintenance—Modular design of the converter
allows easy replacement in the field for reduced maintenance costs.
n Superior Performance—The accuracy, linearity, and
frequency response coupled with minimal hysteresis far exceed the requirements of most control systems.
Figure 2. Output-Time Relationships
100
90 80 70 60 50
OUTPUT
40 30
(% OF 646 OUTPUT SPAN)
20
10
0
0 1020 3040 506070 8090100
A6815
LOADING
EXHAUSTING
TIME (%)
Installation
Refer to figure 3 for location of standard mounting holes in the housing. Standard mounting hardware is provided for mounting on the actuator, a pipestand, or a panel. Field wiring connections are made to the terminal block accessible under the housing cap. Dimensions are shown in figure 3.
Valve Stroking Time
Figure 2 shows relative times for loading and exhausting an actuator. Stroking time depends upon the size of the actuator, travel, relay characteristics and the magnitude and rate of change of the input signal. If stroking time is critical, contact your Emerson Process Management sales office.
4
Ordering Information
To determine what ordering information is required, refer to the specification table. Carefully review the description of each specification. Specify the desired choice whenever there is a selection available. Also, specify options that are applicable to the application.
646 Transducer
D101374X012
Product Bulletin
62.1:646
February 2015
Figure 3. Dimensions
FISHER 67CFR 1/4-18 NPT SUPPLY CONN
6.4
(0.25)
106.4 (4.19)
127.0 (5.00)
102.1 (4.02)
72.8
(2.86)
1/2-14 NPT OR OPTIONAL M20 CONDUIT CONN
OPTIONAL GAUGE
152.4
(6.00)
79.2
(3.12)
(1.88)
47.8
CENTERLINE OF ACTUATOR
9.7
(0.38)
EXHAUST
152.4 (6.00)
(2.25)
35
(1.38)
1/4-18 NPT OUTPUT CONN
1/4-18 NPT OPTIONAL OUTPUT OR GAUGE CONN
57
CAP REMOVAL CLEARANCE
41.1
(1.62)
127.0 (5.00)
62.0
(2.44)
9.5
(0.38)
mm (INCH)
38B3958-A A6816-1
5
Product Bulletin
62.1:646 February 2015
Table 2. Hazardous Area Classifications—CSA (Canada)
Certification Body Certification Obtained Entity Rating Temperature Code
CSA
Intrinsically Safe Ex ia IIC T4/T5 per drawing GE28591 Ex ia Intrinsically Safe Class I, II, Division 1 GP A,B,C,D,E,F,G T4/T5 per drawing GE28591
Explosion-proof Ex d IIC T6 Class I, Division I, GP A,B,C,D T6
Type n
Ex nL IIC T6 Class I, Division 2, GP A,B,C,D T6
Class II, Division 1, Groups E,F,G T6 Class II, Division 2, GP F,G T6
Vmax = 30 VDC Imax = 150 mA Pi = 1.0 W Ci = 0 nF Li = 0 mH
- - - T6 (Tamb 71°C)
- - -
- - - T6 (Tamb 71°C)
Table 3. Hazardous Area Classifications—FM (United States)
Certification Body Certification Obtained Entity Rating Temperature Code
Vmax = 30 VDC Imax = 150 mA Pi = 1.0 W Ci = 0 nF Li = 0 mH
- - - T6 (Tamb 71°C)
- - - T6 (Tamb 71°C)
- - - T6 (Tamb 71°C)
FM
Intrinsically Safe Class 1 Zone 0 AEx ia IIC T4/T5 per drawing GE28590 Class I, II, III Division 1 GP A,B,C,D,E,F,G T4/T5 per drawing GE28590
Explosion-proof Class 1 Zone 1 AEx d IIC T6 Class I, Division I, GP A,B,C,D T6
Type n CL 1 Zone 2 AEx nL IIC T6
Class I, Division 2, GP A,B,C,D T6 Class II, Division 1, Groups E,F,G T6 Class II, Division 2, GP F,G T6
646 Transducer
D101374X012
T4 (Tamb 71°C) T5 (Tamb 40°C)
T6 (Tamb 71°C)
T4 (Tamb 71°C) T5 (Tamb 40°C)
Table 4. Hazardous Area Classifications—ATEX
Certificate Certification Obtained Entity Rating Temperature Code
II 1 G & D
ATEX
Intrinsically Safe Gas Ex ia IIC T4/T5 Ga
Dust Ex ia IIIC T155°C Da (Tamb T124°C (Tamb 40°C)
II 2 G & D
Flameproof Gas Ex d IIC T6 Gb
Dust Ex tb IIIC T74°C Db (T
Type n Gas Ex nA IIC T6 Gc
Dust Ex tc IIIC T74°C Dc (T
amb 71°C)
II 3 G & D
amb 71°C)
≤ 71°C)
Ui = 30 VDC Ii = 150 mA Pi = 1.0 W Ci = 0 nF Li = 0 mH
- - - T6 (Tamb 71°C)
- - - - - -
- - -
T4 (Tamb 71°C) T5 (Tamb 40°C)
T6 (Tamb 71°C)
- - -
- - -
6
Product Bulletin
646 Transducer
D101374X012
Table 5. Hazardous Area Classifications—IECEx
Certificate Certification Obtained Entity Rating Temperature Code
Ui = 30 VDC Ii = 150 mA Pi = 1.0 W Ci = 0 nF Li = 0 mH
T4 (Tamb 71°C) T5 (Tamb 40°C)
- - - T6 (Tamb 71°C)
- - - T6 (Tamb 71°C)
IECEx
Intrinsically Safe Gas Ex ia IIC T4/T5 Ga
Flameproof Gas Ex d IIC T6 Gb
Type n Gas Ex nA IIC T6 Gc
62.1:646
February 2015
7
Product Bulletin
62.1:646 February 2015
646 Transducer
D101374X012
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Process Management
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
E 1988, 2015 Fisher Controls International LLC. All rights reserved.
8
Loading...