Multi-function, Built-in Analog
DVP-SX 
I/O, Multiple Commands PLC
Instruction Sheet 
1 
    This Instruction Sheet only provides descriptions for electrical specifications, general specifications, 
installation & wiring, troubleshooting and peripherals. Other detail infromation about programming and 
commands is compatible with SA/SC/SX series; please see PLC Application Manual.  For more information 
about the optional peripherals , please see individual product manual. 
This is an OPEN TYPE PLC.  The PLC should be kept in an enclosure away from airborne dust, humidity, 
electric shock risk and vibration.  Also, it is equipped with protective methods such as some special tools or 
keys to open the enclosure, so as to avoid the hazard to users and the damage to the PLC. 
  Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the 
PLC.  Check all the wiring prior to power up.  To avoid any electromagnetic noise, make sure the PLC is 
properly grounded 
2 
.  Do NOT touch terminals when power on. 
2.1 Model Name Explanation and Peripherals 
Thank you for choosing DELTA’s PLC DVP series. 
TheDVP-SX series is a 10-point (4DI+2DO+2AI+2AO) 
special main processing unit. Besides the same 
commands and functions as DVP-SA/SX/SC series, 
2-CH 12-bit analog voltage/current input and 2-CH 
12-bit analog voltage/current output are all bipolar. 
There is built-in 2-digit 7-segment display corresponds 
to internal register directly to display PLC station or 
user-defined code. 
 Model Name 
Series Name
Points (6DI+2DO+2A I+2AO)
SX Series
R: Relay 
T: Transistor
DC Power Input
 Peripherals 
◎ DVPHPP02: Handheld Programming panel  
◎ WPLSoft: Windows Ladder Logic Programming Software 
◎ DVPACAB115: 1.5M Cable (HPP  PLC, included in DVPHPP02)  
◎ DVPACAB215: 1.5M Cable (PC (DB9+DB25)  PLC)  
◎ DVPACAB230: 3.0M Cable (PC (DB9+DB25)  PLC)  
◎ DVPACAB2A30: 3.0M Cable (PC (DB9)  PLC) 
2.2 Product Profile and Outline 
※ Battery replacement: Please change the battery within 3 minutes, 
or the internal data of the PLC (including the program area, RTC 
and latched registers) could be lost or destroyed. 
Units: mm 
WARNING 
INTRODUCTION 
 Nameplate Explanation 
Input Power Supply Spec.
Barcode and Serial Numbe r
PLC Model
Output Module Spec.
CPU Version
 Serial Number 
MODEL  :  DVP10SX11R
POWER IN PUT    : 24 Vdc 6W 
OUTPUT MODULE : 2.0A 250Vac 50/60Hz RES. LOA D
V1.00
DELTA ELECTRONICS INC.
Status indicator: POWER, RUN, 
1 
ERROR, BAT.LOW 
RUN/STOP switch 
2 
2-digital 7-segment display 
3 
Digital I/O terminal 
4 
DIN rail clip 
5 
Analog I/O terminals 
6 
I/O point indicators 
7 
COM1 (RS-232) (Rx) indicator 
8 
COM2 (RS-485) (Tx) indicator 
9 
COM1 (RS-232) Communication 
10 
port (Slave) 
Nameplate 
11 
Expansion port 
12 
Mounting hold of the expansion unit 
13 
DIN rail (35mm) 
14 
Expansion unit clip 
15 
COM2 (RS-485) Communication 
16 
port 
DC Power input 
17 
10SX11R0T4020001
MADE IN XXXXXX
Production number 
Production week 
Production Year 2004 
Production factory
Version type 
Production model
2 pin removable terminal (standard accessory) 
18 
Power input cable (standard accessory) 
19 
Battery Cover 
20 
3 
FUNCTION SPECIFICATIONS 
Battery socket connection 
21
Battery mount 
22
Items  Specifications  Remarks 
Control Method  Stored program, cyclic scan system   
I/O Processing Method 
Execution Speed  Basic commands (several us) 
Program language  Commands + Ladder Logic + SFC  Including the Step commands 
Program Capacity  7920 STEPS  SRAM + Battery 
Commands  32 Basic sequential commands (including STL/RET)  168 Application commands  
X External input relay  X0~X177, octal number system, 128 points  Correspond to external input point
Y External output relay  Y0~Y177, octal number system, 128 points 
General  M0~M511, 512 points (*1) 
Auxiliary 
M 
T Timer 
Relay (bit mode) 
C Counter 
S 
T Current value of the timer T0~T255, 256 points 
C Current value of the counter
D 
Register (WORD data) 
None File register  0~1599 (1600 points) (*4)  Expansion register for storing data.
N 
P For CJ, CALL commands P0~P255, 256 points  The location point of CJ, CALL. 
Pointer 
I 
K Decimal 
H Hexadecimal  H0000 ~ HFFFF (16-bit operation), H00000000 ~ HFFFFFFFF (32-bit operation) 
Constant 
Programming port  COM1: RS-232, COM2: RS-485 (Master/Slave), They can be used at the same time. 
Analog Volume / RTC  MPU built-in bipolar 2-CH A/D, D/A, 12 bits, 2-digital 7-segment display, built-in RTC 
Special Expansion Module  Use the same modules (AD, DA, PT, TC, XA, RT) of SS series. (Max. 8 Expansion Unit points) 
Latched 
Relay 
Special  M1000~M1999, 1000 points (some are latched) 
100ms 
10ms 
1ms  T246~T249, 4 points Accumulative (*4) 
16-bit count up 
up/down 
32bit high-speed 
count up/down 
Initial step point S0~S9, 10 points (*1) 
Zero point reset S10~S19, 10 points (use with IST command) (*1) 
Step 
General  S20~S511, 492 points (*1) 
point 
Latched  S512~S895, 384 points (*3) 
Alarm  S896~S1023, 124 points (*3) 
General  D0~D199, 200 points (*1) 
Data 
register 
For master control nested 
loop 
Latched 
Special  D1000~D1999, 1000 points 
Index  E0~E3, F0~F3, 8 points (*1) 
External interrupt 
Time interrupt 
Hi-speed counter   I010, I020, I030, I040, I050, I060; 6 points 
Interrupt Service 
Communication I150, 1 point 
Batch processing method (when END command is 
executed) 
points
M512~M999, 488 points (*3) 
M2000~M4095, 2096 points (*3) 
T0~T199, 200 points (*1) 
T192~T199 for Subroutine 
T250~T255, 6 points Accumulative (*4) 
T200~T239, 40 points (*2) 
T240~T245, 6 points Accumulative (*4) 
C0~C95, 96 points (*1) 
C96~C199, 104 points (*3) 
C200~C215, 16 points (*1) 32-bit count 
C216~C234, 19 points (*3) 
C235~C245, 1 phase 1 input, 9 points (*3) 
C246~C250, 1 phase 2 inputs, 3 points (*3) 
C251~C254, 2 phase 2 inputs, 3 points (*3) 
C0~C199, 16-bit counter, 200 points 
C200~C254, 32-bit counter, 50 points 
D200~D999, 800 points (*3) 
D2000~D4999, 3000 points (*3) 
N0~N7, 8 points 
I001 (X0), I101 (X1), I201 (X2), I301 (X3), I401 (X4), I501 
(X5); 6 points (all are rising-edge trigger) 
I6□□ (1ms), I7□□ (1ms), (□□=1~99ms) 
K-32,768 ~ K32,767 (16-bit operation) 
K-2,147,483,648 ~ K2,147,483,647 (32-bit operation) 
points
points
points
points
points
I/O refresh command is available 
Application Commands 
(10~hundreds us) 
Tot a l 
256 
Correspond to external output point
Tot a l 
Contacts can switch to On/Off in 
4096 
program 
When the timer that set by TMR 
Tot a l 
command reaches the preset 
256 
value, the T contact with the same 
number will be On. 
When the counter that set by CNT 
Tot a l 
(DCNT) command reaches the 
250 
preset value, the C contact with the 
same number will be On. 
Usage device of step ladder 
Tot a l 
diagram (SFC) 
1024 
Latched Range: 
Start: D1214 (K512) 
End: D1215 (K895)  
When the timer reaches the preset 
value, the contact of timer will be 
On. 
When the counter reaches the 
preset value, the contact of counter 
will be On. 
Tot a l 
Can be memory area for storing 
5000 
data.  E and F can be used as the 
special purpose of index indication.
Control point of master control 
nested loop 
The location pointer of interrupt 
subroutine 
*1: The non-latched area is fixed, and can’t be changed.  
*2: The non-latched area can be changed to a latched area with parameter setting. 
*3: The latched area can be changed to a non-latched area with parameter setting. 
*4: The latched area is fixed, and can’t be changed. 
M 
Auxiliary 
Relay 
T 
Timer 
C 
Counter 
S 
Step re lay 
D 
Register 
File Register  K0~K1599, Latched (fixed) 
General Latched Special auxiliary relay Latched 
M0~M511 M512~M999 M1000~M1999 M2000~M4095 
Non-latched (fixed) 
100 ms  10 ms  10ms  1 ms  100 ms 
T0 ~T199  T200~T239  T240~T245  T246~T249  T250~T255 
Non-latched (fixed)  Non-latched (fixed)  Accumulative Latched (fixed) 
16-bit count up  32-bit count up/down  32-bit high-speed count up/down 
C0~C95 C96~C199 C200~C215 C216~C234 C235~C245 C246~C255 
Non-latched 
(fixed) 
For general  Latched  Special register Latched  For general 
S0~S9 S10~S19 S20~S511  S512~S895  S896~S1023 
Non-latched (fixed) 
Latched (default)  Latched (default)  Latched (default) 
Start: D1208 (K96)  
End: D1209 (K199) 
It is fixed to be non-latched 
General Latched Special registers Latched 
D0~D199 D200~D999 D1000~D1999 D2000~D4999 
Latched (default)  Latched (default) 
Start: D1200 (K512)  
End: D1201 (K999)  
Non-latched 
(fixed) 
Factory setting is latched. Factory setting is latched.
Start: D1216 (K200)  
End: D1217 (K999)  
Some are latched and can’t 
be changed 
Start: D1210 (K216) 
End: D1211 (K234) 
Factory setting is latched 
Start: D1214(K512) 
End: D1215(K895) 
Some are latched and can’t 
be changed. 
Start: D1202 (K2000) 
End: D1203 (K4095) 
Start: D1212 (K235)  
End: D1213 (K255)  
It is fixed to be latched 
Start: D1218 (K2000)  
End: D1219 (K4999)  
※ When switching between power On/Off or MPU RUN/STOP modes: 
Memory Type 
Non-latched Clear Unchanged 
Latched Unchanged Unchanged Clear 0 
Special M, Special D, 
Index register 
File register  Unchanged  0 
4
POWER 
OffOn 
Initial value  Unchanged  Unchanged 
STOPRUN  RUNSTOP 
M1033=Off, clear 
M103=On, unchanged
BUILT-IN ANALOG I/OAND 7-SEGMENT DISPLAY 
Clear all M1031 
non-latched area 
Clear Unchanged 0 
Clear all M1032 
latched area 
Factory 
Setting
Initial 
value 
Built-in 2-CH 12-bit A/D and 2-CH 12-bit D/A are bipolar. It can read A/D converted digital value and get 
designated analog output by reading special D or writing into special D. Refer following table for corresponding 
special D.  
Device No. Function 
D1111 
Present value of AD card 
channel 0 (CH0)  
Present value of AD card 
channel 1 (CH1)  
Average value of AD card 
channel 0 (CH0)  
Average value of AD card 
channel 1 (CH1)  
Conversion sampling time 
(ms) 
D1056 
D1057 
D1110 
D1116  DA card channel 0 (CH0) 
D1117  DA card channel 1 (CH1) 
D1118 
5
          Model    
  Item 
Power supply voltage 
Fuse  2A / 250VAC 
Power Consumption  5W 1W 1.5W 1.5W 2W 
Insulation Resistance 
Noise Immunity 
Grounding 
Environment 
Vibration / Shock Resistance  Standard: IEC1131-2, IEC 68-2-6 (TEST Fc) / IEC1131-2 & IEC 68-2-27 (TEST Ea) 
Weight (approx.) (g)  158  128  154 /146  141 /136  162 /154 
Approvals 
Electrical Specification of Input Point  Electrical Specification of Output Point 
Input Type  DC (SINK or SOURCE)  Output Type  Relay-R  Transistor-T 
Input Current 24VDC 5mA 
Active Level 
Responding 
Time 
Off→On, above16VDC 
On→Off, below 14.4VDC 
About 10ms (An 
adjustment range of 0~20 
ms could be selected 
through D1020 and D1021) 
6
Model  Power 
DI  AI  DI  AI  DO  AO  DO  AO 
DVP10SX11R  4 2  2 2 Relay
DVP10SX11T
24VDC 
+20% 
-15% 
4 2 
7
■ Built-in Display 
2-digital 
7-segment di splay
ELECTRICAL SPECIFICATIONS 
DVP10SX11R/T  DVP08SM11N  DVP08SN11R/T DVP08SP11R/T DVP16SP11R/T
MPU: 24VDC (-15%~20%) (with DC input reverse polarity protection),  
Expansion Unit: supplied by the MPU 
ESD: 8KV Air Discharge 
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS: 26MHz~1GHz, 10V/m 
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N 
(All DVP units should be grounded directly to the ground pole). 
Operation: 0℃~55℃ (Temperature), 50~95% (Humidity), Pollution degree 2;  
Storage: -25℃~70℃ (Temperature), 5~95% (Humidity); D/A output operation: 0℃~50℃  
(Temperature) 
> 5 MΩ at 500 VDC (Between all inputs / outputs and earth) 
Current 
Specification 
Voltage 
Specification 
Maximum 
Loading 
Responding 
Time 
MODEL NAME & I/O CONFIGURATION 
Input  Output 
Point  Type  Point  Type 
DC24V/5 mA 
Sink or 
Source 
INSTALLATION & WIRING 
This built-in display corresponds to special D directly. 
User can use it to display error code or station when 
executing PLC LINK. It is great convenience for system 
maintenance. Refer following table for corresponding 
special D.  
Device No. Function 
M1196 
M1197 
M1198 
D1196 Display content  
1.5A/1 point 
(5A/COM) 
Below 250VAC, 
30VDC 
75VA (Inductive) 
90 W (Resistive) 
About 10 ms 
-20~20mA 
range(-1000~+1000)
-10~+10V 
range(-2000~+2000)
Number system setting for display (Off: 
Decimal, On: Hexadecimal) 
The decimal point setting between the middle 
and the right-most numbers  
The decimal point setting after the right-most 
number 
- 
0.3A/1 point @ 40℃; When the output of Y0 
and Y1 is high-speed pulse, Y0 and Y1 = 
30mA 
30VDC 
When the output of Y0 and 
9W/1 point 
Off→On 20us 
On→Off 30us 
2 2 Resistor
Y1 is high-speed pulse, Y0 
and Y1 = 0.9W (Y0 = 32kHz, 
Y1 = 10kHz) 
Y0 and Y1 are specified 
points for high-speed pulse 
(range:-2000~+2000)
(range:-2000~+2000)
-20~20mA 
-10~+10V 
7.1 PLC Mounting Arrangements and Wiring Notes 

Installation of the DIN rail 
The DVP-PLC can be secured to a cabinet by using the DIN 
rail that is 35mm high with a depth of 7.5mm. When 
mounting the PLC on the DIN rail, be sure to use the end 
bracket to stop any side-to-side motion of the PLC, thus to 
reduce the chance of the wires being pulled loose. At the 
bottom of the PLC is a small retaining clip. To secure the 
PLC to the DIN rail, place it onto the rail and gently push up 
the clip. To remove it, pull down the retaining clip and gently 
pull the PLC away from the DIN rail.  As shown on the right: 
Wiring 
22-16AWG
Notes: 
1. Please use 22-16AWG (1.5mm) wiring (either single or multiple core) for I/O 
When installing the DVP series 
PLC, make sure that it is 
installed in an enclosure with 
sufficient space (as shown 
below) to its surroundings so as 
to allow heat dissipation. 
D
DD
DVP
MP
D
D > 50 mm
wiring terminals. The specification for the terminals is as shown on the left. 
PLC terminal screws should be tightened to between 1.95 kg-cm (1.7 in-lbs). 
<1.5mm
2. I/O signal wires or power supply should not run through the same multi-wire 
cable or conduit. Use Copper Conductor Only, 60/75 °C 
7.2 Wiring Notes 
Power Input Wiring 
DVP-SX series input power supply is DC input. Please take a note of listed items when operating DVP-SX. Series. 
1. Please make sure the power is at terminals 24VDC and 0V (power range is 20.4VDC~28.8VDC). When 
voltage is lower than 20.4VDC, PLC will stop operating, all outputs will turn Off and ERROR LED will flash 
continuously. 
2. If the power-off time is less than 10ms, the PLC still operates unaffectedly.  If the power-off time is too 
long or the power voltage drops, the PLC will stop operating and all the outputs will be Off. Once the 
power is restored, the PLC will return to operate automatically. (There are latched auxiliary relays and 
registers inside of the PLC, please be aware when programming.) 
DC Input Type 
20.4V~28.8V
Safety Wiring 
Since the PLC is in control of numerous devices, motion of either one device could affect the motion of other 
devices, therefore the breakdown of either one device would consequently be detrimental to the whole auto 
control system, and danger will thus be resulted.  Please use the recommended wiring below for the power 
input: 
5
4
8
Guard 
Limit
MC
NL
6
MC
2
3
MC
Input Point Wiring 
The input signal of the input point is the DC power DC input.  There are two types of DC type wiring: SINK and 
SOURCE, defined as follows: 
◎ There are two types of DC type wiring: SINK and SOURCE, defined as follows: 
Sink = Current flows into the common terminal S/S  Source = Current flows out of common terminal S/S 
S/S
Sinking
X0
DC Type 
 (DC Signal IN)  
SINK Mode 
Loop Equivalent Circuit of Input Point  Wiring Loop 
+24V
24G
S/S
X0
7
24VDC
24V
0V
2A
DC/DC
S/S
5V
X0 X1 X2
 
Power supply for AC loads 
 
1
Power Circuit Protection Fuse (3A)  
 
Power On pilot indicator 
 
Emergency stop 
The machinery must provide a quick manual method 
disconnecting all system power. 
 
Circuit isolation device (System Power Disconnect) 
Utilize the electromagnetic contactor and the relay to be 
1
the isolation unit of the power circuit to prevent the 
possible instability of the system when the power is 
supplied on and off.  
 
DVP PLC MPU (main processing unit) 
 
Grounding 
 
Power supply: 
AC: 100~240VAC, 50/60Hz 
DC: 24VDC 
SINK
+5V
+24V OV
24VDC
X0
S/S
Sourcing
X1 X2S/S X0
Sink Type
Loop Equivalent Circuit of Input Point  Wiring Loop 
+24V
24VDC
DC Type 
 (DC Signal IN)  
SOURCE Mode 
24G
SOURCE
+5V
S/S
X0
24VDC
X1 X2S/S X0+24V OV
Source Type
Output Point Wiring 
DVP-**-**-11-R
LED
LOAD
Y0
RY
C0
POWER
1. There are two kinds of DVP-SX Series PLC output modules: 
Relay and Transistor.  For relevant electrical specification, 
please refer to the function specification. 
2.  Be careful with the connection of the common terminals when 
wiring outputs.  For example, when wiring DVP12SX11R, 
output terminal Y0 uses one common terminal C0, Y1 uses C1,  
as shown below: 
C0Y0C1Y1
Action indication: When the output point is active, the 
corresponding indicator at the front will be on. 
3.  Isolated circuit: The optical coupler is used to isolate signals 
DVP-**-**-11-T
LED
RELAY OUTPUT
T 
R 
G
Y0
C0
TRANSISTOR OUTPUT
LOAD
< 0.3A
between PLC internal circuits and input modules. 
Voltage input
-10V~+10V
Current input
-20mA~+20mA
AC drive, recorder, 
scale valve...
AC drive, recorder, 
scale valve...
terminal of 
power module
8 
Shielded*1
Shielded*1
voltage output
*5
class 3 grounding 
(100 
*3
-10V~+10V
shielding cable *1
current output
-20mA~20mA
shielding cable *4
or less)
CH0
CH1
*2
DC24V
V+
COM
V+
COM
I+
I+
CH0
CH1
250
250
V+
COM
V+
COM
24+ 
24-
100K
100K
AG
100K
100K
AG
Note 1: Please isolate analog input and other 
CH0
power wiring. 
Note 2: If input signal is in current, please short 
out between V+ and I+ terminals. 
Note 3: If the noise interference from loaded 
CH1
input wiring terminal is significant, 
please connect a capacitor with 
0.1~0.47μF 25V for noise filtering. 
Note 4: Please isolate analog output and other 
I+
CH0
power wiring. 
Note 5: If the noise interference from loaded 
input wiring terminal is significant, 
please connect a capacitor with 
I+
CH1
0.1~0.47μF 25V for noise filtering. 
Note 6: Please connect 
terminal and 
 power module 
 analog output module 
terminal to system earth point and 
make system earth point be grounded 
DC/DC
converter
+15V
AG
-15V
or connects to machine cover. 
Warning: DO NOT wire to the No function 
terminal 
TRIAL RUN 
☼ Power Indication 
The “POWER” LED at the front of the MPU or the Expansion Units will be lit (in green) if the power is on. If the 
indicator is not on when the MPU is powered up, it means that the 24V DC power supply of the PLC is 
overloaded.  It is thus necessary to remove the wiring on terminals +24V and 24G, and to use a 24VDC power 
supply instead.  If the ERROR LED is blinking swiftly, it suggests that the +24V power supply of the PLC is 
insufficient. 
☼ Low Voltage Indication 
The “LOW V.” LED on the Expansion Unit is an indication that the input power voltage is insufficient, thus all 
outputs of the expansion unit should be turned off. 
☼ Low Battery Voltage Indication 
There is also a “BAT.LOW” LED at the front of the MPU.  When the LED is on, it indicates that the battery 
voltage is insufficient.  Please change the batter (within 3 minutes) as soon as possible; otherwise the user 
programs and the data in latched area may be lost. 
Preparation 
1. Prior to applying power, please verify that the power lines and the input/output wiring are correct.  And be 
advised not to supply AC110V or AC220V into the I/O terminals, or it might short-circuit the wiring and 
would cause direct damage to the PLC. 
2. After using the peripheral devices to write the program into the MPU and that the ERROR LED of the MPU 
is not on, it means that the program in use is legitimate, and it is now waiting for the user to give the RUN 
command. 
3. Use HPP to execute the forced On/Off test of the output contact.  
Operation & Test 
If the “ERROR” LED of the MPU is not blinking, use RUN/STOP switch or the peripheral devices (HPP or 
WPLSoft) to give the RUN command, and the RUN indicator will then be on.  If the “RUN” LED is not on, it 
indicates that there is no program inside the PLC. 
HPP could be utilized to monitor the settings and the registered values of the timer (T), the counter (C) and the 
data register (D) during operation, and moreover, to force the output contacts to conduct the On/Off action.  If 
the ERROR LED is on (but not blinking), it means that the setting of the user’s program has exceeded the 
preset time-out limit.  At this case, please turn the PLC RUN/STOP switch to STOP, and find out the address 
of the time-out program by special data register D1008. ”WDT” instruction can be used to solve the problem. 
PLC Input/Output Reaction Time 
The total reaction time from the input signal to the output operation is calculated as follows: 
Reaction Time = input delay time + program scan time + output delay time 
Input delay time 
Factory setting: 10 ms. Please refer to the usage of special 
register D1020~1021. 
Program scan time  Please refer to the usage of special register D1010. 
Output delay time  Relay module: 10ms.  Transistor module: 20~30us. 
Basic Commands and Application Commands of the PLC: 
1.  The basic commands and the application commands of the MPU of this series are totally applicable to 
the DELTA DVP-PLC SA/SX/SC Series MPU.  Refer to the DELTA PLC Technique Application Manual 
for relevant basic commands and application commands. 
2.  The DVPHPP handheld programming panel and the WPLSoft (the Windows version) editing program of 
the ladder diagram are both good for use with the DELTA DVP-PLC.  Also, the PLC could connect with 
the DVP12SX MPU through specific transmission wire to execute the program transmission, the MPU 
control and the program monitoring. 
9
TROUBLESHOOTING 
Judge the errors by the indicators on the front panel.  When errors occurred on DVP PLC, please check: 
☼ “POWER” LED
There is a “POWER” LED at the front of the MPU. When the MPU is powered On, the green LED light will be on. 
If the indicator is not on when the MPU is powered up and with the input power being normal, it is an indication 
that the PLC is out of order. Please have this machine replaced or have it repaired at a dealer near you. 
☼ PLC “RUN” LED
Identify the status of the PLC. When the PLC is in operation, this light will be on, and users could thus use HPP 
or the editing program of the ladder diagram to give commands to make the PLC “RUN” or “STOP”.  
☼ “ERROR” LED
If incorrect programs are input to the MPU, or that the commands and the components exceed the allowable 
range, the indicator will blink. At this moment, the user should check both the error codes saved in the MPU data 
register D1004 and the Error Code Table below to correct the programs.  The address that the error occurs will 
be stored in data register D1137 (the address saved in D1137 is invalid in case of common loop error). 
When the ERROR LED is on (not blinking), users should make a judgment from the special relay M1008 of the 
MPU. If it is On, it indicates that the execution time of the program loop has exceeded the time-out setting (set by 
D1000). Please turn the PLC RUN/STOP switch to STOP, and find out the address of the time-out program by 
special data register D1008. ”WDT” instruction can be used to solve the problem. Once program modification is 
completed, user can re-download the program of PLC and the ERROR LED will be off. If the ERROR LED is still 
keep on, please turn off the power and check if there’s any noise or any conductive invader inside the PLC. 
☼ “BAT.LOW” LED
When the battery voltage is low, the “BAT.LOW” LED will be on, and the battery should be replaced as soon as 
possible; otherwise the user program and the data in latched area will be lost. (On the unplugged PLC, please 
change the battery within 3 minutes to retain the PLC’s internal user programs and data). Choose lithium battery 
TDRTL-2150/S. Please refer to the following table for battery life information. 
Battery life: 
Temperature((°C) 
0 25 50 70 
Life(Years)  9 8 6 5 
Precision of calendar timer: 
At 0°C/32°F, less than –117 seconds error per month. 
At 25°C/77°F, less than 52 seconds error per month. 
At 55°C/131°F, less than –132 seconds error per month. 
☼ “Input” LED
The On/Off signals of the input point could be displayed through the “Input” LED, or the status of the input point 
could be monitored through the device monitoring function of HPP.  
☼ “Output” LED
Output LED indicates if the output signals are On or Off. Please check the following items when the LED On/Off 
indication does not correspond to the commands: 1. Output contacts may be melted and stuck together due to a 
short circuit or current overload. 2. Check wiring and verify that the screws are tight.