2006-01-12
http://www.delta.com.tw/industr ialautoma tion/
5011627202-SXE2
Multi-function, Built-in Analog
DVP-SX
I/O, Multiple Commands PLC
Instruction Sheet
1
This Instruction Sheet only provides descriptions for electrical specifications, general specifications,
installation & wiring, troubleshooting and peripherals. Other detail infromation about programming and
commands is compatible with SA/SC/SX series; please see PLC Application Manual. For more information
about the optional peripherals , please see individual product manual.
This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity,
electric shock risk and vibration. Also, it is equipped with protective methods such as some special tools or
keys to open the enclosure, so as to avoid the hazard to users and the damage to the PLC.
Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the
PLC. Check all the wiring prior to power up. To avoid any electromagnetic noise, make sure the PLC is
properly grounded
2
. Do NOT touch terminals when power on.
2.1 Model Name Explanation and Peripherals
Thank you for choosing DELTA’s PLC DVP series.
TheDVP-SX series is a 10-point (4DI+2DO+2AI+2AO)
special main processing unit. Besides the same
commands and functions as DVP-SA/SX/SC series,
2-CH 12-bit analog voltage/current input and 2-CH
12-bit analog voltage/current output are all bipolar.
There is built-in 2-digit 7-segment display corresponds
to internal register directly to display PLC station or
user-defined code.
Model Name
Series Name
Points (6DI+2DO+2A I+2AO)
SX Series
R: Relay
T: Transistor
DC Power Input
Peripherals
◎ DVPHPP02: Handheld Programming panel
◎ WPLSoft: Windows Ladder Logic Programming Software
◎ DVPACAB115: 1.5M Cable (HPP PLC, included in DVPHPP02)
◎ DVPACAB215: 1.5M Cable (PC (DB9+DB25) PLC)
◎ DVPACAB230: 3.0M Cable (PC (DB9+DB25) PLC)
◎ DVPACAB2A30: 3.0M Cable (PC (DB9) PLC)
2.2 Product Profile and Outline
※ Battery replacement: Please change the battery within 3 minutes,
or the internal data of the PLC (including the program area, RTC
and latched registers) could be lost or destroyed.
Units: mm
WARNING
INTRODUCTION
Nameplate Explanation
Input Power Supply Spec.
Barcode and Serial Numbe r
PLC Model
Output Module Spec.
CPU Version
Serial Number
MODEL : DVP10SX11R
POWER IN PUT : 24 Vdc 6W
OUTPUT MODULE : 2.0A 250Vac 50/60Hz RES. LOA D
V1.00
DELTA ELECTRONICS INC.
Status indicator: POWER, RUN,
1
ERROR, BAT.LOW
RUN/STOP switch
2
2-digital 7-segment display
3
Digital I/O terminal
4
DIN rail clip
5
Analog I/O terminals
6
I/O point indicators
7
COM1 (RS-232) (Rx) indicator
8
COM2 (RS-485) (Tx) indicator
9
COM1 (RS-232) Communication
10
port (Slave)
Nameplate
11
Expansion port
12
Mounting hold of the expansion unit
13
DIN rail (35mm)
14
Expansion unit clip
15
COM2 (RS-485) Communication
16
port
DC Power input
17
10SX11R0T4020001
MADE IN XXXXXX
Production number
Production week
Production Year 2004
Production factory
Version type
Production model
2 pin removable terminal (standard accessory)
18
Power input cable (standard accessory)
19
Battery Cover
20
3
FUNCTION SPECIFICATIONS
Battery socket connection
21
Battery mount
22
Items Specifications Remarks
Control Method Stored program, cyclic scan system
I/O Processing Method
Execution Speed Basic commands (several us)
Program language Commands + Ladder Logic + SFC Including the Step commands
Program Capacity 7920 STEPS SRAM + Battery
Commands 32 Basic sequential commands (including STL/RET) 168 Application commands
X External input relay X0~X177, octal number system, 128 points Correspond to external input point
Y External output relay Y0~Y177, octal number system, 128 points
General M0~M511, 512 points (*1)
Auxiliary
M
T Timer
Relay (bit mode)
C Counter
S
T Current value of the timer T0~T255, 256 points
C Current value of the counter
D
Register (WORD data)
None File register 0~1599 (1600 points) (*4) Expansion register for storing data.
N
P For CJ, CALL commands P0~P255, 256 points The location point of CJ, CALL.
Pointer
I
K Decimal
H Hexadecimal H0000 ~ HFFFF (16-bit operation), H00000000 ~ HFFFFFFFF (32-bit operation)
Constant
Programming port COM1: RS-232, COM2: RS-485 (Master/Slave), They can be used at the same time.
Analog Volume / RTC MPU built-in bipolar 2-CH A/D, D/A, 12 bits, 2-digital 7-segment display, built-in RTC
Special Expansion Module Use the same modules (AD, DA, PT, TC, XA, RT) of SS series. (Max. 8 Expansion Unit points)
Latched
Relay
Special M1000~M1999, 1000 points (some are latched)
100ms
10ms
1ms T246~T249, 4 points Accumulative (*4)
16-bit count up
up/down
32bit high-speed
count up/down
Initial step point S0~S9, 10 points (*1)
Zero point reset S10~S19, 10 points (use with IST command) (*1)
Step
General S20~S511, 492 points (*1)
point
Latched S512~S895, 384 points (*3)
Alarm S896~S1023, 124 points (*3)
General D0~D199, 200 points (*1)
Data
register
For master control nested
loop
Latched
Special D1000~D1999, 1000 points
Index E0~E3, F0~F3, 8 points (*1)
External interrupt
Time interrupt
Hi-speed counter I010, I020, I030, I040, I050, I060; 6 points
Interrupt Service
Communication I150, 1 point
Batch processing method (when END command is
executed)
points
M512~M999, 488 points (*3)
M2000~M4095, 2096 points (*3)
T0~T199, 200 points (*1)
T192~T199 for Subroutine
T250~T255, 6 points Accumulative (*4)
T200~T239, 40 points (*2)
T240~T245, 6 points Accumulative (*4)
C0~C95, 96 points (*1)
C96~C199, 104 points (*3)
C200~C215, 16 points (*1) 32-bit count
C216~C234, 19 points (*3)
C235~C245, 1 phase 1 input, 9 points (*3)
C246~C250, 1 phase 2 inputs, 3 points (*3)
C251~C254, 2 phase 2 inputs, 3 points (*3)
C0~C199, 16-bit counter, 200 points
C200~C254, 32-bit counter, 50 points
D200~D999, 800 points (*3)
D2000~D4999, 3000 points (*3)
N0~N7, 8 points
I001 (X0), I101 (X1), I201 (X2), I301 (X3), I401 (X4), I501
(X5); 6 points (all are rising-edge trigger)
I6□□ (1ms), I7□□ (1ms), (□□=1~99ms)
K-32,768 ~ K32,767 (16-bit operation)
K-2,147,483,648 ~ K2,147,483,647 (32-bit operation)
points
points
points
points
points
I/O refresh command is available
Application Commands
(10~hundreds us)
Tot a l
256
Correspond to external output point
Tot a l
Contacts can switch to On/Off in
4096
program
When the timer that set by TMR
Tot a l
command reaches the preset
256
value, the T contact with the same
number will be On.
When the counter that set by CNT
Tot a l
(DCNT) command reaches the
250
preset value, the C contact with the
same number will be On.
Usage device of step ladder
Tot a l
diagram (SFC)
1024
Latched Range:
Start: D1214 (K512)
End: D1215 (K895)
When the timer reaches the preset
value, the contact of timer will be
On.
When the counter reaches the
preset value, the contact of counter
will be On.
Tot a l
Can be memory area for storing
5000
data. E and F can be used as the
special purpose of index indication.
Control point of master control
nested loop
The location pointer of interrupt
subroutine
*1: The non-latched area is fixed, and can’t be changed.
*2: The non-latched area can be changed to a latched area with parameter setting.
*3: The latched area can be changed to a non-latched area with parameter setting.
*4: The latched area is fixed, and can’t be changed.
M
Auxiliary
Relay
T
Timer
C
Counter
S
Step re lay
D
Register
File Register K0~K1599, Latched (fixed)
General Latched Special auxiliary relay Latched
M0~M511 M512~M999 M1000~M1999 M2000~M4095
Non-latched (fixed)
100 ms 10 ms 10ms 1 ms 100 ms
T0 ~T199 T200~T239 T240~T245 T246~T249 T250~T255
Non-latched (fixed) Non-latched (fixed) Accumulative Latched (fixed)
16-bit count up 32-bit count up/down 32-bit high-speed count up/down
C0~C95 C96~C199 C200~C215 C216~C234 C235~C245 C246~C255
Non-latched
(fixed)
For general Latched Special register Latched For general
S0~S9 S10~S19 S20~S511 S512~S895 S896~S1023
Non-latched (fixed)
Latched (default) Latched (default) Latched (default)
Start: D1208 (K96)
End: D1209 (K199)
It is fixed to be non-latched
General Latched Special registers Latched
D0~D199 D200~D999 D1000~D1999 D2000~D4999
Latched (default) Latched (default)
Start: D1200 (K512)
End: D1201 (K999)
Non-latched
(fixed)
Factory setting is latched. Factory setting is latched.
Start: D1216 (K200)
End: D1217 (K999)
Some are latched and can’t
be changed
Start: D1210 (K216)
End: D1211 (K234)
Factory setting is latched
Start: D1214(K512)
End: D1215(K895)
Some are latched and can’t
be changed.
Start: D1202 (K2000)
End: D1203 (K4095)
Start: D1212 (K235)
End: D1213 (K255)
It is fixed to be latched
Start: D1218 (K2000)
End: D1219 (K4999)
※ When switching between power On/Off or MPU RUN/STOP modes:
Memory Type
Non-latched Clear Unchanged
Latched Unchanged Unchanged Clear 0
Special M, Special D,
Index register
File register Unchanged 0
4
POWER
OffOn
Initial value Unchanged Unchanged
STOPRUN RUNSTOP
M1033=Off, clear
M103=On, unchanged
BUILT-IN ANALOG I/OAND 7-SEGMENT DISPLAY
Clear all M1031
non-latched area
Clear Unchanged 0
Clear all M1032
latched area
Factory
Setting
Initial
value
Built-in 2-CH 12-bit A/D and 2-CH 12-bit D/A are bipolar. It can read A/D converted digital value and get
designated analog output by reading special D or writing into special D. Refer following table for corresponding
special D.
Device No. Function
D1111
Present value of AD card
channel 0 (CH0)
Present value of AD card
channel 1 (CH1)
Average value of AD card
channel 0 (CH0)
Average value of AD card
channel 1 (CH1)
Conversion sampling time
(ms)
D1056
D1057
D1110
D1116 DA card channel 0 (CH0)
D1117 DA card channel 1 (CH1)
D1118
5
Model
Item
Power supply voltage
Fuse 2A / 250VAC
Power Consumption 5W 1W 1.5W 1.5W 2W
Insulation Resistance
Noise Immunity
Grounding
Environment
Vibration / Shock Resistance Standard: IEC1131-2, IEC 68-2-6 (TEST Fc) / IEC1131-2 & IEC 68-2-27 (TEST Ea)
Weight (approx.) (g) 158 128 154 /146 141 /136 162 /154
Approvals
Electrical Specification of Input Point Electrical Specification of Output Point
Input Type DC (SINK or SOURCE) Output Type Relay-R Transistor-T
Input Current 24VDC 5mA
Active Level
Responding
Time
Off→On, above16VDC
On→Off, below 14.4VDC
About 10ms (An
adjustment range of 0~20
ms could be selected
through D1020 and D1021)
6
Model Power
DI AI DI AI DO AO DO AO
DVP10SX11R 4 2 2 2 Relay
DVP10SX11T
24VDC
+20%
-15%
4 2
7
■ Built-in Display
2-digital
7-segment di splay
ELECTRICAL SPECIFICATIONS
DVP10SX11R/T DVP08SM11N DVP08SN11R/T DVP08SP11R/T DVP16SP11R/T
MPU: 24VDC (-15%~20%) (with DC input reverse polarity protection),
Expansion Unit: supplied by the MPU
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz~1GHz, 10V/m
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N
(All DVP units should be grounded directly to the ground pole).
Operation: 0℃~55℃ (Temperature), 50~95% (Humidity), Pollution degree 2;
Storage: -25℃~70℃ (Temperature), 5~95% (Humidity); D/A output operation: 0℃~50℃
(Temperature)
> 5 MΩ at 500 VDC (Between all inputs / outputs and earth)
Current
Specification
Voltage
Specification
Maximum
Loading
Responding
Time
MODEL NAME & I/O CONFIGURATION
Input Output
Point Type Point Type
DC24V/5 mA
Sink or
Source
INSTALLATION & WIRING
This built-in display corresponds to special D directly.
User can use it to display error code or station when
executing PLC LINK. It is great convenience for system
maintenance. Refer following table for corresponding
special D.
Device No. Function
M1196
M1197
M1198
D1196 Display content
1.5A/1 point
(5A/COM)
Below 250VAC,
30VDC
75VA (Inductive)
90 W (Resistive)
About 10 ms
-20~20mA
range(-1000~+1000)
-10~+10V
range(-2000~+2000)
Number system setting for display (Off:
Decimal, On: Hexadecimal)
The decimal point setting between the middle
and the right-most numbers
The decimal point setting after the right-most
number
-
0.3A/1 point @ 40℃; When the output of Y0
and Y1 is high-speed pulse, Y0 and Y1 =
30mA
30VDC
When the output of Y0 and
9W/1 point
Off→On 20us
On→Off 30us
2 2 Resistor
Y1 is high-speed pulse, Y0
and Y1 = 0.9W (Y0 = 32kHz,
Y1 = 10kHz)
Y0 and Y1 are specified
points for high-speed pulse
(range:-2000~+2000)
(range:-2000~+2000)
-20~20mA
-10~+10V
7.1 PLC Mounting Arrangements and Wiring Notes
Installation of the DIN rail
The DVP-PLC can be secured to a cabinet by using the DIN
rail that is 35mm high with a depth of 7.5mm. When
mounting the PLC on the DIN rail, be sure to use the end
bracket to stop any side-to-side motion of the PLC, thus to
reduce the chance of the wires being pulled loose. At the
bottom of the PLC is a small retaining clip. To secure the
PLC to the DIN rail, place it onto the rail and gently push up
the clip. To remove it, pull down the retaining clip and gently
pull the PLC away from the DIN rail. As shown on the right:
Wiring
22-16AWG
Notes:
1. Please use 22-16AWG (1.5mm) wiring (either single or multiple core) for I/O
When installing the DVP series
PLC, make sure that it is
installed in an enclosure with
sufficient space (as shown
below) to its surroundings so as
to allow heat dissipation.
D
DD
DVP
MP
D
D > 50 mm
wiring terminals. The specification for the terminals is as shown on the left.
PLC terminal screws should be tightened to between 1.95 kg-cm (1.7 in-lbs).
<1.5mm
2. I/O signal wires or power supply should not run through the same multi-wire
cable or conduit. Use Copper Conductor Only, 60/75 °C
7.2 Wiring Notes
Power Input Wiring
DVP-SX series input power supply is DC input. Please take a note of listed items when operating DVP-SX. Series.
1. Please make sure the power is at terminals 24VDC and 0V (power range is 20.4VDC~28.8VDC). When
voltage is lower than 20.4VDC, PLC will stop operating, all outputs will turn Off and ERROR LED will flash
continuously.
2. If the power-off time is less than 10ms, the PLC still operates unaffectedly. If the power-off time is too
long or the power voltage drops, the PLC will stop operating and all the outputs will be Off. Once the
power is restored, the PLC will return to operate automatically. (There are latched auxiliary relays and
registers inside of the PLC, please be aware when programming.)
DC Input Type
20.4V~28.8V
Safety Wiring
Since the PLC is in control of numerous devices, motion of either one device could affect the motion of other
devices, therefore the breakdown of either one device would consequently be detrimental to the whole auto
control system, and danger will thus be resulted. Please use the recommended wiring below for the power
input:
5
4
8
Guard
Limit
MC
NL
6
MC
2
3
MC
Input Point Wiring
The input signal of the input point is the DC power DC input. There are two types of DC type wiring: SINK and
SOURCE, defined as follows:
◎ There are two types of DC type wiring: SINK and SOURCE, defined as follows:
Sink = Current flows into the common terminal S/S Source = Current flows out of common terminal S/S
S/S
Sinking
X0
DC Type
(DC Signal IN)
SINK Mode
Loop Equivalent Circuit of Input Point Wiring Loop
+24V
24G
S/S
X0
7
24VDC
24V
0V
2A
DC/DC
S/S
5V
X0 X1 X2
Power supply for AC loads
1
Power Circuit Protection Fuse (3A)
Power On pilot indicator
Emergency stop
The machinery must provide a quick manual method
disconnecting all system power.
Circuit isolation device (System Power Disconnect)
Utilize the electromagnetic contactor and the relay to be
1
the isolation unit of the power circuit to prevent the
possible instability of the system when the power is
supplied on and off.
DVP PLC MPU (main processing unit)
Grounding
Power supply:
AC: 100~240VAC, 50/60Hz
DC: 24VDC
SINK
+5V
+24V OV
24VDC
X0
S/S
Sourcing
X1 X2S/S X0
Sink Type
Loop Equivalent Circuit of Input Point Wiring Loop
+24V
24VDC
DC Type
(DC Signal IN)
SOURCE Mode
24G
SOURCE
+5V
S/S
X0
24VDC
X1 X2S/S X0+24V OV
Source Type
Output Point Wiring
DVP-**-**-11-R
LED
LOAD
Y0
RY
C0
POWER
1. There are two kinds of DVP-SX Series PLC output modules:
Relay and Transistor. For relevant electrical specification,
please refer to the function specification.
2. Be careful with the connection of the common terminals when
wiring outputs. For example, when wiring DVP12SX11R,
output terminal Y0 uses one common terminal C0, Y1 uses C1,
as shown below:
C0Y0C1Y1
Action indication: When the output point is active, the
corresponding indicator at the front will be on.
3. Isolated circuit: The optical coupler is used to isolate signals
DVP-**-**-11-T
LED
RELAY OUTPUT
T
R
G
Y0
C0
TRANSISTOR OUTPUT
LOAD
< 0.3A
between PLC internal circuits and input modules.
Voltage input
-10V~+10V
Current input
-20mA~+20mA
AC drive, recorder,
scale valve...
AC drive, recorder,
scale valve...
terminal of
power module
8
Shielded*1
Shielded*1
voltage output
*5
class 3 grounding
(100
*3
-10V~+10V
shielding cable *1
current output
-20mA~20mA
shielding cable *4
or less)
CH0
CH1
*2
DC24V
V+
COM
V+
COM
I+
I+
CH0
CH1
250
250
V+
COM
V+
COM
24+
24-
100K
100K
AG
100K
100K
AG
Note 1: Please isolate analog input and other
CH0
power wiring.
Note 2: If input signal is in current, please short
out between V+ and I+ terminals.
Note 3: If the noise interference from loaded
CH1
input wiring terminal is significant,
please connect a capacitor with
0.1~0.47μF 25V for noise filtering.
Note 4: Please isolate analog output and other
I+
CH0
power wiring.
Note 5: If the noise interference from loaded
input wiring terminal is significant,
please connect a capacitor with
I+
CH1
0.1~0.47μF 25V for noise filtering.
Note 6: Please connect
terminal and
power module
analog output module
terminal to system earth point and
make system earth point be grounded
DC/DC
converter
+15V
AG
-15V
or connects to machine cover.
Warning: DO NOT wire to the No function
terminal
TRIAL RUN
☼ Power Indication
The “POWER” LED at the front of the MPU or the Expansion Units will be lit (in green) if the power is on. If the
indicator is not on when the MPU is powered up, it means that the 24V DC power supply of the PLC is
overloaded. It is thus necessary to remove the wiring on terminals +24V and 24G, and to use a 24VDC power
supply instead. If the ERROR LED is blinking swiftly, it suggests that the +24V power supply of the PLC is
insufficient.
☼ Low Voltage Indication
The “LOW V.” LED on the Expansion Unit is an indication that the input power voltage is insufficient, thus all
outputs of the expansion unit should be turned off.
☼ Low Battery Voltage Indication
There is also a “BAT.LOW” LED at the front of the MPU. When the LED is on, it indicates that the battery
voltage is insufficient. Please change the batter (within 3 minutes) as soon as possible; otherwise the user
programs and the data in latched area may be lost.
Preparation
1. Prior to applying power, please verify that the power lines and the input/output wiring are correct. And be
advised not to supply AC110V or AC220V into the I/O terminals, or it might short-circuit the wiring and
would cause direct damage to the PLC.
2. After using the peripheral devices to write the program into the MPU and that the ERROR LED of the MPU
is not on, it means that the program in use is legitimate, and it is now waiting for the user to give the RUN
command.
3. Use HPP to execute the forced On/Off test of the output contact.
Operation & Test
If the “ERROR” LED of the MPU is not blinking, use RUN/STOP switch or the peripheral devices (HPP or
WPLSoft) to give the RUN command, and the RUN indicator will then be on. If the “RUN” LED is not on, it
indicates that there is no program inside the PLC.
HPP could be utilized to monitor the settings and the registered values of the timer (T), the counter (C) and the
data register (D) during operation, and moreover, to force the output contacts to conduct the On/Off action. If
the ERROR LED is on (but not blinking), it means that the setting of the user’s program has exceeded the
preset time-out limit. At this case, please turn the PLC RUN/STOP switch to STOP, and find out the address
of the time-out program by special data register D1008. ”WDT” instruction can be used to solve the problem.
PLC Input/Output Reaction Time
The total reaction time from the input signal to the output operation is calculated as follows:
Reaction Time = input delay time + program scan time + output delay time
Input delay time
Factory setting: 10 ms. Please refer to the usage of special
register D1020~1021.
Program scan time Please refer to the usage of special register D1010.
Output delay time Relay module: 10ms. Transistor module: 20~30us.
Basic Commands and Application Commands of the PLC:
1. The basic commands and the application commands of the MPU of this series are totally applicable to
the DELTA DVP-PLC SA/SX/SC Series MPU. Refer to the DELTA PLC Technique Application Manual
for relevant basic commands and application commands.
2. The DVPHPP handheld programming panel and the WPLSoft (the Windows version) editing program of
the ladder diagram are both good for use with the DELTA DVP-PLC. Also, the PLC could connect with
the DVP12SX MPU through specific transmission wire to execute the program transmission, the MPU
control and the program monitoring.
9
TROUBLESHOOTING
Judge the errors by the indicators on the front panel. When errors occurred on DVP PLC, please check:
☼ “POWER” LED
There is a “POWER” LED at the front of the MPU. When the MPU is powered On, the green LED light will be on.
If the indicator is not on when the MPU is powered up and with the input power being normal, it is an indication
that the PLC is out of order. Please have this machine replaced or have it repaired at a dealer near you.
☼ PLC “RUN” LED
Identify the status of the PLC. When the PLC is in operation, this light will be on, and users could thus use HPP
or the editing program of the ladder diagram to give commands to make the PLC “RUN” or “STOP”.
☼ “ERROR” LED
If incorrect programs are input to the MPU, or that the commands and the components exceed the allowable
range, the indicator will blink. At this moment, the user should check both the error codes saved in the MPU data
register D1004 and the Error Code Table below to correct the programs. The address that the error occurs will
be stored in data register D1137 (the address saved in D1137 is invalid in case of common loop error).
When the ERROR LED is on (not blinking), users should make a judgment from the special relay M1008 of the
MPU. If it is On, it indicates that the execution time of the program loop has exceeded the time-out setting (set by
D1000). Please turn the PLC RUN/STOP switch to STOP, and find out the address of the time-out program by
special data register D1008. ”WDT” instruction can be used to solve the problem. Once program modification is
completed, user can re-download the program of PLC and the ERROR LED will be off. If the ERROR LED is still
keep on, please turn off the power and check if there’s any noise or any conductive invader inside the PLC.
☼ “BAT.LOW” LED
When the battery voltage is low, the “BAT.LOW” LED will be on, and the battery should be replaced as soon as
possible; otherwise the user program and the data in latched area will be lost. (On the unplugged PLC, please
change the battery within 3 minutes to retain the PLC’s internal user programs and data). Choose lithium battery
TDRTL-2150/S. Please refer to the following table for battery life information.
Battery life:
Temperature((°C)
0 25 50 70
Life(Years) 9 8 6 5
Precision of calendar timer:
At 0°C/32°F, less than –117 seconds error per month.
At 25°C/77°F, less than 52 seconds error per month.
At 55°C/131°F, less than –132 seconds error per month.
☼ “Input” LED
The On/Off signals of the input point could be displayed through the “Input” LED, or the status of the input point
could be monitored through the device monitoring function of HPP.
☼ “Output” LED
Output LED indicates if the output signals are On or Off. Please check the following items when the LED On/Off
indication does not correspond to the commands: 1. Output contacts may be melted and stuck together due to a
short circuit or current overload. 2. Check wiring and verify that the screws are tight.