Delta DVP Series, DVP04PT-S, DVP06PT-S Instruction Sheet

2018-07-20
5014002905-6P05
………………………………………………………………… ENGLISH …………………………………………………………………
Thank you for choosing Delta DVP series PLC. DVP04 /06PT-S is able to receive 4/6 points of RTDs and
convert them into 16-bit digital signals. Through F ROM/TO instructions in DVP Slim series MPU pr ogram,
the data can be read and written. There are many 16-bit control registers (CR) in modules. The power unit
is separate from it and is small in size and easy to install.
EN DVP04/06PT-S is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne
dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating
DVP04/06PT-S, or to prevent an accident from dam aging DVP04/06PT-S, the control cabinet in
which DVP04/06PT-S is installed should be equipped with a safeguard. For example, the control
cabinet in which DVP04/06PT-S is installed can be un locked with a special tool or key.
EN DO NOT connect AC power to any of I/O terminals, other wise serious damage may occur. Please
check all wiring again before DVP04/06 PT-S is powered up. After DVP04/06PT-S is disconnected,
Do NOT touch any terminals in a minute. Make sure th at the ground terminal
on
DVP04/06PT-S is correctly grounded in order to prevent electromagnetic interfer ence.
FR DVP04/06PT-S est un module OUVERT. Il doit être installé que dans une enceinte protectrice
(boitier, armoire, etc.) saine, dépourvue de poussière , d’humidité, de vibrations et hors d’atteinte
des chocs électriques. La protection do it éviter que les personnes non habilitées à la maintenance
puissent accéder à l’appareil (par exem ple, une clé ou un outil doivent être nécess aire pour ouvrir
a protection).
FR Ne pas appliquer la tension secteur sur les bornes d’entrées/Sorties, ou l’appareil D VP04/06PT-S
pourra être endommagé. Merci de vérifier encore une fois le câblage avant la mise sous tension du
DVP04/06PT-S. Lors de la déconnection de l’appareil, ne pas toucher les connecteurs dans la
minute suivante. Vérifier que la ter re est bien reliée au connecteur de terre
afin d’éviter toute
interférence électromagnétique.
Product Profile & Dimension
1
L+
L-CH
1 I-
L+
L-CH
2 I-
L+
C
L-
H
3
2
3
I-
L+
C
H
L-
4 I-
L+
C
L-
H
5 I-
L+
C L-
H
D VP- 06 PT
6 I-
60.00 3.40
5
4
3.0090.00
25.20
6
7
8
10
9
3
11
12
11
13
60.00
3.00
14
3.00
1. Status indicator (POWER, RUN and ERROR)
4. I/O terminals 5. I/O point indicator 6. Mounting holes
7. Specification label 8. I/O module connection port 9. I/O module clip
10. DIN rail (35mm) 11. I/O module clip
13. Power connection port
(DVP04PT-S)
Unit: mm
2. Model name 3. DIN rail clip
12. RS-485 communication port (DVP04PT-S)
14. I/O connection port
- 1 -
[ Figure 1 ]
I/O Terminal Layout
,
DVP04PT-S
CH1 Ch2 Ch3 Ch4
DVP06PT
CH1
CH2
L-L+FGL-L+
FGI- L+FGI-L-L+ FGI-L-I-
L-L+L-L+
CH3 CH4 CH5 CH6
I- L+I-L-L+ I-L-I-
L-L+ I- L+ I-L-
[ Figure 2 ]
External Wiring
Pt1000
2-Wire
Shielded cable*1
Pt100
3-Wir e
Note1: Use only the wires that are packed with the temperature sensor for analog input and separate from
other power line or any wire that ma y cause noise. Note2: 3-wire RTD sensor provides a compens ation loop that can be used to subtract the wire resistance while 2-wire RTD sensor has no mechanism to compensate. Use cables (3-wired) with the same length (less than 2 00 m) and wire resistance of less than 2 0 ohm. Note3: If there is noise, please connect the shielded cables to the system earth point, and then ground the
system earth point or connect it to the distributio n box. Note4: Please keep wires as short as possib le when connecting the module to a devic e whose
temperature is going to be measured, and keep the power cable used as far away from the cable connected to a load as possible to prevent noise interference.
Note5: Please connect
ground, and then ground the system ground or connect the system ground to a distr ibution box.
Shielded cable* 1
on a power supply module and on the temperature module to a system
CH1
CH6
L+ L­ I -
AG
L+ L­ I-
AG
Electrical Specifications
Max. rated power consumption
Operation/storage
Vibration/shock resistance
Series connection to DVP-PLC MPU
2W
Operation: 0°C~55°C (temp.), 5~95% (hum idity), pollution degree 2 Storage: -25°C~70°C (temp.), 5~95% (humidity) International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC6113 1- 2 & IEC 68-2-27 (TEST Ea) The modules are numbered from 0 to 7 autom atically by their distance from MPU. No.0 is the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.
Functional Specifications
DVP04/06PT-S Celsius (°C) Fahrenheit (°F)
Analog input channel 4/6 channels per module
Sensors type
Current excitation 1.53mA / 204.8uA Temperature input range Please refer to the temperature/digital value characteristic curve. Digital conversion range Please refer to the temperature/digital va lue characteristic curve. Resolution 16 bits (0.1°C) 16 bits (0.1°F) Overall accuracy Response time DVP04PT-S: 200ms/channel; DVP06PT-S: 160/ms/channel
Isolation method (between digital and analog circuitry)
Digital data format 2’s complement of 16-bit Average function Yes (DVP04PT-S: CR#2 ~ CR#5 / DVP06PT-S: CR#2) Self diagnostic function Every channel has the upper/lower l imit detection function.
2-wire/3-wire Pt100 / Pt1000 3850 PP M/°C (DIN 43760 JIS C1604-1989) / Ni100 / Ni1000 / LG-Ni1000 / Cu100 / Cu50/ 0 ~300Ω/ 0~3000Ω
0.6% of full scale during 0 ~ 55°C (32 ~ 13 1°F)
There is no isolation between cha nnels. 500VDC between digital/analog circuits and G round 500VDC between analog circuits and dig ital circuits 500VDC between 24VDC and Ground
*2
*2
- 2 -
Supported, including ASCII/RTU mode. Default communication f ormat: 9600, 7, E, 1, ASCII; refer to CR#32 for details on the comm unication
RS-485 Communication Mode
Control Register
CR# Address Latched Attribute Register content Description
#0 H’4064 O R
#1 H’4065 X R/W CH1~CH4 Mode setting
H’4066
#2
--
#3 H’4067 O H’4067
#4 H’4068 O H’4068
#5 H’4069 O H’4069
#6 H’406A X R CH1 average degrees #7 H’406B X R CH2 average degrees #8 H’406C X R CH3 average degrees
#9 H’406D X R CH4 average degrees #10 -- X R CH5 average degrees #11 -- X R CH6 average degrees #12 H’4070 X R CH1 average degrees #13 H’4071 X R CH2 average degrees #14 H’4072 X R CH3 average degrees #15 H’4073 X R CH4 average degrees #16 -- X R CH5 average degrees #17 -- X R CH6 average degrees #18 H’4076 X R Present temp. of CH1 #19 H’4077 X R Present temp. of CH2 #20 H’4078 X R Present temp. of CH3 #21 H’4079 X R Present temp. of CH4
format. Note1: RS-485 cannot be used when connected to CPU series PLCs. Note2: Refer to Slim Type Special Module Communications in the appendix E of the DVP programming manual f or more details on RS-485 communication setups.
O R/W
Model name (Set up by the system)
DVP04PT-S: CH1 average number
DVP06PT-S: CH1~CH6 average number
DVP04PT-S: CH2 average number
DVP04PT-S: CH3 average number
DVP04PT-S: CH4 average number
DVP04PT-S model code= H’8A DVP06PT-S model code = H’CA
b15~12 b11~8 b7~4 b3~0
CH4 CH3 CH2 CH1 Take CH1 mode (b3,b2,b1,b0) for example.
1. (0,0,0,0): Pt100 (default)
2. (0,0,0,1): Ni100
3. (0,0,1,0): Pt1000
4. (0,0,1,1): Ni1000
5. (0,1,0,0): LG-Ni1000
6. (0,1,0,1): Cu100
7. (0,1,1,0): Cu50
8. (0,1,1,1): 0~300 Ω
9. (1,0,0,0): 0~3000 Ω
10. (1,1,1,1)The channel is
disabled. Mode 8 and 9 are only available for DVP04PT-S V4.16 or later and DVP06PT-S V4.12 or later.
Number piece of readings used for the calculation of “average” temperature on CH1. Setting range: K1~K20. Default setting is K10. Number piece of readings used for the calculation of “average” temperature on CH1 ~ 6. Setting range: K1~K20. Default setting is K10. Number piece of readings used for the calculation of “average” temperature on CH2. Setting range: K1~K20. Default setting is K10. Number piece of readings used for the calculation of “average” temperature on CH3. Setting range: K1~K20. Default setting is K10. Number piece of readings used for the calculation of “average” temperature on CH4. Setting range: K1~K20. Default setting is K10.
DVP04PT-S: Average degrees for CH1 ~ 4 DVP06PT-S: Average degrees for CH1 ~ 6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),
0.1 Ω (0~3000 Ω)
DVP04PT-S: Average degrees for CH1 ~ 4 DVP06PT-S: Average degrees for CH1 ~ 6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),
0.1 Ω (0~3000 Ω)
DVP04PT-S: Present temperature of CH 1~4 DVP06PT-S: Present temperature of CH1~6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),
- 3 -
CR# Address Latched Attribute Register content Description
#22 -- X R Present temp. of CH5 #23 -- X R Present temp. of CH6 #24 H’407C X R Present temp. of CH1 #25 H’407D X R Present temp. of CH2 #26 H’407E X R Present temp. of CH3 #27 H’407F X R Present tem p. of CH4 #28 -- X R Present temp. of CH5 #29 -- X R Present temp. of CH6
#29 H’4081 X R/W
#30 H’4082 X R Error status
H’4083 O R/W
#31
-- X R/W
H’4084 O R/W
32
-- X R/W
H’4085 O R/W
#33
-- X R/W
#34 H’4086 O R Firmware version
#35 ~ #48 For system use Symbols: O means latched. X means not latched. R means can read data by using FROM instruction or RS-485. W means can write data by using TO instructi on or RS-485.
Added the RESET function is only for 04PT-S modules with firm ware V4.16 or later and not available
for 06PT-S. Connect the module power input to 24 VDC and write H’4352 into CR#0 and then turn the power off and on again; all parameters in m odules, including communication parameters are restored to factory defaults.
If you want to use Modbus address in decimal f ormat, you can transfer a hexadecim al register to
decimal format and then add one to ha ve it become a decimal Modbus regis ter address. For example transferring the address “H’4064” of CR#0 in hexadecimal format to decimal format, to have the result 16484 and then adding one to it, you ha ve 16485, the Modbus addres s in decimal format.
CR#32 communication format settings: for DVP04PT-S modules with f irmware V4.14 or previous
versions, b11~b8 data format selection is not available. For ASCII mode, the format is fix ed to 7, E, 1
DVP04PT-S: PID mode setup
DVP04PT-S: Communication address setup
DVP06PT-S: CH5~CH6 Mode setting
DVP04PT-S: Communication format setting
DVP06PT-S: CH5~CH6 Error LED indicator setting
DVP04PT-S: CH1~CH4 Reset to default setting And Error LED indicator setting
DVP06PT-S: CH1~CH4 Reset to default setting And CH1~CH4 Error LED indicator setting
0.1 Ω (0~3000 Ω)
DVP04PT-S: Present temperature of CH 1~4 DVP06PT-S: Present temperature of CH 1~6 Unit: 0.1°C, 0.01 Ω (0~300 Ω),
0.1 Ω (0~3000 Ω)
Set H’5678 as PID mode and other values as normal mode
Default value is H’0000. Data register stores the error
status. Refer to the error code chart
for details. Set up the RS-485 communication address; setting range: 01~254. Default: K1 CH5 mode: b0 ~ b3 CH6 mode: b4 ~ b7 See CR#1 for reference
For baud rate, the settings are 4,800/9,600/19,200/38,400/57,600/ 115,200 bps. Communication format: ASCII: 7,E,1 / 7,O,1 / 8,E,1 / 8,O,1 / 8,N,1
RTU: 8,E,1 / 8,O,1 / 8,N,1 Factory default : ASCII,9600,7,E,1
(CR#32=H’0002) Refer to CR#32 communication format settings at the end of this
table for more information.
b15~12 b11~9 b8~6 b5~3 b2~0
ERR
reserved CH6 CH5
LED b12~13 correspond to CH5~6, when bit is ON, the scale exceeds the range, and the Error LED indicator flashes.
b15~12 b11~9 b8~6 b5~3 b2~0
ERR
CH4 CH3 CH2 CH1
LED If b2~b0 are set to 100, all the setting values of CH1 will be reset to the defaults. To reset all channels to defaults, set b11~0 to H’924 (DVP04PT-S supports single and all channels reset; DVP06PT-S supports all channels reset only). b12~15 correspond to CH1~4, when bit is ON, the scale exceeds the range, and the Error LED indicator flashes.
Display version in hexadecim al. ex: H’010A = version 1.0A
- 4 -
(H’00XX) and for RTU mode, the format is fixed to 8, E, 1 (H’C0xx/H’80xx). For modules with firmware V4.15 or later, refer to the following table for setups. Note that the or iginal code H’C0XX/H’80XX will be seen as RTU, 8, E, 1 for modules with firm ware V4.15 or later.
b15 ~ b12 b11 ~ b8 b7 ~ b0
ASCII/RTU,
exchange low and high byte of
CRC check code
H'0 ASCII H'0 7,E,1*1 H'01 4800 bps
H'8
H'C
RTU,
do not exchange low and
high byte of CRC check
code RTU,
exchange low and high
byte of CRC check code
Note *1: This is only available for ASCII format.
Ex: Write H’C310 into CR#32 for a result of RTU, exc hange low and high byte of CRC check c ode, 8,N,1
and baud rate at 57600 bps.
CR#30 is the error code register.
Note: Each error code will have a corresponding bit and should be converted to 16-bit binar y numbers (Bit0~15). Two or more errors may happen at the same tim e. Refer to the chart below:
Bit number 0 1 2 3
Description
Bit number 4 5 6 7
Description
Bit number 8 9 10 11
Description
Bit number 12 13 14 15
Description
Power source
abnormal
Hardware
malfunction
CH1 Abnormal
conversion
CH5 Abnormal
conversion
Data form at Baud rate
Description
H'1 8,E,1 H'02 9600 bps
H'2 reserved H'04 19200 bps
H'3 8,N,1 H'08 38400 bps
H'4 7,O,1*1 H'10 57600 bps
H'5 8.O,1 H'20 115200 bps
The contact is
not connected to
anything.
Reserved
CH2 Abnormal
conversion
CH6 Abnormal
conversion
Reserved Reserved
average number
error
CH3 Abnormal
conversion
Instruction error
CH4 Abnormal
conversion
Reserved Reserved
Temperature/Digital Value Characteristic Curve
The mode of measuring Celsius (Fahr enheit) temperature:
Digital output
Max.
Min .
Sensor
Pt100 -180 ~ 800°C -292 ~ 1,472°F K-1,800 ~ K8,000 K-2,920 ~ K14,720
Ni100 -80 ~ 170°C -112 ~ 338°F K-800 ~ K1,700 K-1,120 ~ K3,380 Pt1000 -180 ~ 800°C -292 ~ 1,472°F K-1,800 ~ K8,0 00 K-2,920 ~ K14,720 Ni1000 -80 ~ 170°C -112 ~ 338°F K-800 ~ K1,700 K-1,120 ~ K3,380
LG-Ni1000 -60 ~ 200°C -76 ~ 392°F K-600 ~ K2, 000 K-760 ~ K3, 920
Cu100 -50 ~ 150°C -58 ~ 302°F K-500 ~ K1,500 K-580 ~ K3,020
Cu50 -50 ~ 150°C -58 ~ 302°F K-500 ~ K1,500 K-580 ~ K3,020 Sensor Input resistor range Digital value conversion range
0~300Ω 0Ω ~ 320Ω K0 ~ 32000 0~300Ω 0Ω ~ 320Ω
0~3000Ω 0Ω ~ 3200Ω K0 ~ 32000 0~3000Ω 0Ω ~ 3200Ω
Temperature range Digital value conversion range
°C (Min./Max.) °F (Min./Max.) °C (Min./Max.) °F (Min./Max.)
Min.
Max.
Temperature input
- 5 -
Loading...
+ 13 hidden pages