Delta DVP04TC-H2 User Manual

2007-01-09
VX.XXXX
14 BITS
THERMOCOUPLESE:
(thermocouple)
Production plant (Taoyuan)
CH1
CH4
DC/ DC
24+0VSLD
L -
10 k
MUX
Cold-Juncti on
#
Parameter
○ R
http://www.delta.c om.tw/indus trialautomation /
5011652100-T2E0
Temperature Measurement Module
Instruction Sheet
Warning
9 Please read this instruction sheet carefully before use.
9 Switch off the power before wiring.
9 DVP04TC-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required to open the enclosure) in case danger and damages on the device may occur.
9 DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all
the wiring again before switching on the power.
9 DO NOT touch any terminal when the power is switched on.
9 Make sure the ground termnial
9 Keep the wire as short as possible between RTD and PLC and the power wire as far away as possible from I/O wire to
prevent interference.
is correctly grounded in order to prevent electromagnetic interference.
Introduction
1.1 Model Explanation & Peripherals
Thank you for choosing Delta’s DVP series. DVP04TC-H2 is able to receive 4 points of external thermocouple
temperature sensors (J-type, K-type, R-type, S-type, T-type) and convert them into 14-bit digital signals. Besides, through FROM/TO instructions in DVP-EH2 MPU program, DVP04TC-H2 is able to read and write the data in the module. There are 49 16-bit control registers (CR) in DVP04TC-H2.
The power unit and module of DVP04TC-H2 are separate, compact in size and easy to install.
DVP04TC-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F).
Nameplate Explanation
Delta PL C model na me
Power input specification
Analog I/O module specification
Barcode, serial No., Version
Model/Serial No. Explanation
DVP series
Points (input + output)
Model type
AD: Analog input DA: Analog output PT: Temperature measurement (PT-100) TC: Temperature measurement
H: For EH series MPU H2: F or EH2 se ries MP U
XA: Mixed analog I/O HC: High-speed counter input PU: Single-axis position control
1.2 Product Profile (Indicators, Terminal Block, I/O Terminals)
Unit: mm
1 DIN rail (35mm) 6 Terminals 2 Connection port for extension unit/module 7 Mounting hole 3 Model name 8 I/O terminals 4 POWER, ERROR, A/D indicator 9 Mounting port for extension unit/module 5 DIN rail clip
MODEL:
POWER INPUT:
RESOLUTION:
24Vdc 2.5W
TYPE J, K, R, S, T
04TC-H20T6 500001
MADE IN XXXXXX
Production No.
Production week Production year (2006)
Vers ion No . Model name
24V 0V
D - L + L - L +
D + SLD
CH1 CH 2 CH 3 CH4RS-485
SLD SLD SLD
L - L + L - L + L -
8
1.3 External Wiring
Thermocouple
Thermocouple
Termin al of power module
*1: The wiring used for analog input should adopts the connection cable or shielding cable of thermocouple temperature
sensor J-type or K-type and should be separated from other power cable or wirings that may cause interference. The screw torque of the terminal should be 1.95 kg-cm (1.7 in-lbs).
*2: Terminal SLD is the ground location for noise suppression.
*3: Please connect the
system contact or connect it to the cover of power distribution cabinet.
Note: DO NOT wire empty terminal Note: Use 60/75°C copper conductor only.
terminal on both the power module and DVP04TC-H2 to the system earth point and ground the
+
-
+
-
Ear th (100 or less)
.
Shielding cable *1
Shielding cable *1
*3
System grounding
L+
L+ L -
SLD
Compensation
*2
Converter
AG
5V
AG
+15V
-15V
Specifications
2.1. Functions
Temperature measurement
(04TC) module
Power supply voltage 24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Analog output channel 4 channels/module
Applicable sensor types
J-type, K-type, R-type, S-type, T-type thermocouple
J type: -100°C ~ 700°C
Range of input
temperature
K type: -100°C ~ 1,000°C
R type: -10°C ~ 1,700°C
S type: -10°C ~ 1,700°C
T type: -100°C ~ 350°C
J type: K-1,000 ~ K7,000
Range of digital conversion
K type: K-1,000 ~ K10,000
R type: K-100 ~ K17,000
S type: K-100 ~ K17,000
T type: K-1,000 ~ K3,500
Resolution 14 bits (0.1) 14 bits (0.18)
Overall accuracy
±0.5% when in full scale (25°C, 77°F)
±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Response time 200 ms × the number of channels
Isolation Isolation between digital area and analog area. No isolation among channels.
Digital data format 13 significant bits out of 16 bits are available; in 2’s complement
Average function Yes; available for setting up in CR#2 ~ CR#5; range: K1 ~ K20
Self-diagnosis Upper and lower bound detection/channel
The voltage output is protected by short circuit. Please also be aware that being
Protection
short circuit for too long period of time may cause damage on internal circuit. The
current output can be open circuit.
ASCII/RTU mode.
Communication mode (RS-485)
Communication speed: 4,800/9,600/19,200/38,400/57,600 /115,200 bps
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1)
RS-485 cannot be used when connected to PLC MPU.
When connected to DVP-PLC MPU in series
The modules are numbered from 0 to 7 automatically by their distance from MPU.
No. 0 is the closest to MPU and No. 7 is the furthest. Maximum 8 modules are
allowed to connect to MPU and will not occupy any digital I/O points.
Celsius (°C) Fahrenheit (°F)
J type: -148°F ~ 1,292°F
K type: -148°F ~ 1,832°F
R type: -14°F ~ 3,092°F
S type: -14°F ~ 3,092°F
T type: -148°F ~ 662°F
J type: K-1,480 ~ K12,920
K type: K-1,480 ~ K18,320
R type: K-140 ~ K30,920
S type: K-140 ~ K30,920
T type: K-1,480 ~ K6,620
2.2. Others
Power Supply
Max. rated power consumption
Environment spec. Same as that of DVP-PLC MPU
24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 2.5W supplied by external power.
Environment
Control Register
RS-485
CR
address
#0 H’4096
#1 H’4097
#2 H’4098 #3 H’4099 #4 H’409A #5 H’409B
#6 H’409C ╳ R
#7 H’409D ╳ R
#8 H’409E ╳ R
#9 H’409F ╳ R
#10 H’40A0 ╳ R
#11 H’40A1 ╳ R
#12 H’40A2 ╳ R
#13 H’40A3 ╳ R
#14 H’40A4 ╳ R
#15 H’40A5 ╳ R
#16 H’40A6 ╳ R
#17 H’40A7 ╳ R
#18 Reserved
#19 H’40A9 ╳ R
#20 H’40AA ╳ R
#21 H’40AB ╳ R
#22 H’40AC ╳ R
#23 Reserved
#24 H’40AE #25 H’40AF #26 H’40B0 #27 H’40B1
#28 ~ #29 Reserved
#30 H’40B4 ╳ R Error status
#31 H’40B5
#32 H’40B6
#33 H’40B7
#34 H’40B8
#35 ~ #48 For system use
Symbols
: latched (when written in through RS-485 communication)
: non-latched R: Able to read data by FROM instruction or RS-485 communication W: Able to write data by TO instruction or RS-485 communication
Explanations:
1. CR#0: Model name. The user can read the model name from the program and see if the extension module
exists.
DVP04TC-H2 Description
Latched
R/W Thermocouple type
R/W CH1 average time
R/W CH2 average time
R/W CH3 average time
R/W CH4 average time
R/W OFFSET value of CH1
R/W OFFSET value of CH2
R/W OFFSET value of CH3
R/W OFFSET value of CH4
R/W
R/W
R/W Returning to default setting
Register content
Model name
Average °C temp. measured at CH1 Average °C temp. measured at CH2 Average °C temp. measured at CH3 Average °C temp. measured at CH4 Average °F temp. measured at CH1 Average °F temp. measured at CH2 Average °F temp. measured at CH3 Average °F temp. measured at CH4 Present °C temp. measured at CH1 Present °C temp. measured at CH2 Present °C temp. measured at CH3 Present °C temp. measured at CH4
Present °F temp. measured at CH1 Present °F temp. measured at CH2 Present °F temp. measured at CH3 Present °F temp. measured at CH4
Communication address setting
Communication speed (baud rate) setting
R Firmware version
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Set up by the system. DVP04TC-H2 model code = H’6403
Reserved CH4 CH3 CH2 CH1
Take the setting of CH1 for example:
1. When (b2, b1, b0) is set as (0,0,0), choose J-type
2. When (b2, b1, b0) is set as (0,0,1), choose K-type
3. When (b2, b1, b0) is set as (0,1,0), choose R-type
4. When (b2, b1, b0) is set as (0,1,1), choose S-type
5. When (b2, b1, b0) is set as (1,0,0), choose T-type
Range of settings in CH1 ~ CH4: K1 ~ K20 Default = K10
Average Celsius temperature measured at CH1 ~ CH4. Unit: 0.1°C
Average Fahrenheit temperature measured at CH1 ~ CH4 Unit: 0.1°F
Present Celsius temperature measured at CH1 ~ CH4 Unit: 0.1°C
Present Fahrenheit temperature measured at CH1 ~ CH4 Unit: 0.1°F
Adjustable OFFSET settings at CH1 ~ CH4. Range: -1,000 ~ +1,000 Default = K0 Unit: 0.1°C
Register for storing all error status. See the table of error status for more information.
For setting RS-485 communication address. Range: 01 ~ 255 Default = K1
For setting up communication speed: 4,800/9,600/19,200/38,400/57,600/115,200 bps ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1) RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1) Default: H’0002 b0: 4,800 bps b1: 9,600 bps (default) b2: 19,200 bps b3: 38,400 bps b4: 57,600 bps b5: 115,200 bps b6 ~ b13: reserved b14: High/low bit exchange of CRC checksum (only valid in RTU mode) b15: Switch between ASCII/RTU modes; 0 = ASCII mode (default)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
ERR LED CH4 CH3 CH2 CH1
Take the setting of CH1 for example:
1. b0 is reserved.
2. b1 is reserved.
3. When b2 is set as 1, all the settings will return to default settings. ERR LED definition: default of b12 ~ b15 = 1111
1. b12 corresponds to CH1. When b12 = 1 or the scale exceeds the range, ERR LED will flash.
2. b13 corresponds to CH2. When b13 = 1 or the scale exceeds the range, ERR LED will flash.
3. b14 corresponds to CH3. When b14 = 1 or the scale exceeds the range, ERR LED will flash.
4. b15 corresponds to CH4. When b15 = 1 or the scale exceeds the range, ERR LED will flash.
Displaying the current firmware version in hex; e.g. version 1.0A is indicated as H’010A
2. CR#1: The working mode of the 4 channels in the sensors selected by the temperature measurement module.
F)
(+1,292
Digital output
temperature input
(-1,832 F)
Digital output
temper ature input
F)
(+3,092
Digital output
temperature input
F)
(+662
Digital output
temperature input
M1000
END
D
P
X0
79
D
X0
DTO
D10
Remarks
Lower 16-bit
CR #5
CR #6
CR #7
CR #8
CR #9
CR #10
Designated device
Designated CR
Designated device
16-bit instruction wh en n=6
32-bit instruction when n=3
There are 2 modes (J-type and K-type) for each channel which can be set up separately. For example, if the
user needs to set up CH1: mode 0 (b2 ~ b0 = 100); CH2: mode 1 (b5 ~ b3 = 001); CH3: mode 0 (b8 ~ b6 =
000) and CH4: mode 1 (b11 ~ b9 = 001), CR#1 has to be set as H0208 and the higher bits (b12 ~ b15) have
to be reserved. The default value = H’0000.
3. CR#2 ~ CR#5: The times to average the temperatures measured at CH1 ~ CH4. Range: K1 ~ K20. Default =
K10. Please note that when PLC MPU writes in the average time by TO/DTO instruction, please use the
rising/falling edge contact detection instructions (LDP/LDF…) in case you may not obtain the correct average
temperature.
4. CR#6 ~ CR#9: The average Celsius temperature measured at CH1 ~ CH4 obtained from the average time
settings in CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#6 ~ CR#9 will be
the average of the most recent 10 temperature signals in Celsius at CH1 ~ CH4.
5. CR#10 ~ CR#13: The average Fahrenheit temperature measured at CH1 ~ CH4 obtained from the average
time settings in CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#10 ~ CR#13
will be the average of the most recent 10 temperature signals in Fahrenheit at CH1 ~ CH4.
6. CR #14 ~ CR #17: Displaying the present temperature in Celsius at CH1 ~ CH4
7. CR#18, CR#23, CR#28 and CR#29 are reserved.
8. CR #19 ~ CR #22: Displaying the present temperature in Fahrenheit at CH1 ~ CH4
9. CR #24 ~ CR #27: The adjusted OFFSET value of CH1 ~ CH4. Range: -1,000 ~ +1,000. Unit: 0.1°C.
Temperature measured by the module – OFFSET value = Actual temperature displayed.
10. CR #30: Error status (see the table below)
Error status Content b15 ~ b8 b7 b6 b5 b4 b3 b2 b1 b0
Abnormal power supply
K1(H’1) 0 0 0 0 0 0 0 1 Scale exceeds the range or wiring to empty external contact
Incorrect mode setting
OFFSET/GAIN error
Hardware malfunction
Abnormal digital range
Incorrect average times setting
Instruction error
Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the same time.
0 = normal; 1 = error
K2(H’2) 0 0 0 0 0 0 1 0
K4(H’4) 0 0 0 0 0 1 0 0
K8(H’8) 0 0 0 0 1 0 0 0
K16(H’10)
K32(H’20)
K64(H’40)
K128(H’80)
reserved
0 0 0 1 0 0 0 0
0 0 1 0 0 0 0 0
0 1 0 0 0 0 0 0
1 0 0 0 0 0 0 0
11. CR#31: The setting of RS-485 communication address. Range: 01 ~ 255. Default = K1.
12. CR#32: The setting of RS-485 communication speed. b0: 4,800bps; b1: 9,600bps (default); b2: 19,200bps; b3:
38,400bps; b4: 57,600bps; b5: 115,200bps; b6 ~ b13: reserved; b14: high/low bit exchange of CRC checksum
(only valid in RTU mode); b15: switching between ASCII mode and RTU mode.
13. CR#33: b0 ~ b11: For returning the CR settings to default settings.
b12 ~ b15: ERR LED definition. Default: b12 ~ b15 = 1111.
14. CR#34: Firmware version of the model.
15. CR#35 ~ CR#48: Parameters for system use.
16. CR#0 ~ CR#34: The corresponding parameter address H’4096 ~ H’40B8 are for users to read/write data by
RS-485 communication. When using RS-485, the user has to separate the module with MPU first.
a. Communication baud rate: 4,800/9,600/19,200/38,400/57,600/115,200 bps.
b. Modbus ASCII/RTU communication protocol: ASCII data format (7-bit, Even bit, 1 stop bit (7, E, 1));
RTU data format (8-bit, Even bit, 1 stop bit (8, E, 1)).
c. Function: H’03 (read register data); H’06 (write 1 word datum into register); H’10 (write many word data
into register).
d. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written
by MPU through TO/DTO instruction.
Temperature/Digital Curve
Temperature measurement modes
J-type thermocouple
+7,000(12,92 0)
Measured
(-148
C
F)
-1,000(-1,480 )
+700-100
C
R & S-type thermocouple
+17,000(30,920)
Measured
+1,700-10
(-14
C
F)
-100(-140)
C
K-type thermocouple
+10,000(18,320)
T-type thermocouple
+3,500(6,620)
-100
(-148
Measured
+1,000-100
+350
C
Measured
C
C
-1,000(-1,4 80)
C
F)
-1,000(-1,480)
Trial Operation & Troubleshooting
LED Display
1. When the module is powered for the first time, POWER LED will be on and ERROR LED will be on for
0.5 second. After this, A/D LED will start to flash.
2. When the power supply is normal, POWER LED will be on and ERROR LED should be off. When the
power supply is less than 19.5V, ERROR LED will keep being on until the power supply goes higher
than 19.5V.
3. When controlled by RS485, RS-485 LED on the module will flash after receiving the RS-485
instruction.
4. When the input or output value exceeds the upper bound or falls below the lower bound after
conversion, ERROR LED will flash.
Program Example
M1002
= H6403 D0
FROM K0
TO K0
FROM K0
FROM K0
FROM K0
FROM K0
Read the model name from K0 and see if it is DVP04TC-H2: H’6403
Set the average times in CH1 ~ CH4 as D10 ~ D13.
If D0 = H’6403, read the average temperature (°C) measured in CH1 ~ CH4 from CR#6 ~ CR#9 and store the
4 data in D20 ~ D23.
Read the average temperature (°F) measured in CH1 ~ CH4 from CR#10 ~ CR#13 and store the 4 data in
D24~ D27.
Read the average temperature (°C) measured in CH1 ~ CH4 from CR#14 ~ CR#17 and store the 4 data in
D30~ D33.
Read the average temperature (°F) measured in CH1 ~ CH4 from CR#19 ~ CR#22 and store the 4 data in
D34~ D37.
K0
K2
K6
K10
K14
K19
D0
D10
D20
D24
D30
D34
K1
K4
K4
K4
K4
K4
Relevant Instructions
API
API
78
Instruction Explanation
Instruction Explanation
Program Example
Program Example
FROM
: No. of special module (m1 = 0 ~ 7) : CR# in special module to be read
: Device for storing read data : Number of data to be read at a time
Read CR#24 of special module No. 0 into D0 and CR#25 into D1. Only 2 groups of data are read at a time (n = 2).
FROM K0 K24 D0 K2
TO
P
: No. of special module (m1 = 0 ~ 7) : CR# in special module to be written
: Data to be written into CR : Number of data to be written at a time
Use 32-bit instruction DTO to write the content in D11 and D10 into CR#7 and CR#6 of special module No. 0. Only 1 group of data is written in at a time (n = 1).
K0 K6
Operand rules
: The No. of special modules connected to PLC MPU. No. 0 is the module closest to te
1.
MPU. Maximum 8 modules are allowed to connected to a PLC MPU and they will not occupy
any I/O points.
2.
: CR#. CR (control register) is the 49 16-bit memories built in the special module,
numbered in decimal as #0 ~ #48. All operation status and settings of the special module are
contained in the CR.
3. FROM/TO instruction is for reading/writing 1 CR at a time. DFROM/DTO instruction is for
reading/writing 2 CRs at a time.
Hi gh er 16 -bit
CR #10 CR #9
4. Number of groups “n” to be transmitted: n = 2 in 16-bit instructions and n = 1 in 32-bit
instructions mean the same.
D0
D1 D2
D3 D4
D5
M1083 for switching instruction modes in EH2 series models
1. When M1083 = Off, during the execution of FROM/TO instruction, all external or internal
interruption subroutines will be forbidden. The interruptions are allowed only after FROM/TO
instruction finishes its execution. FROM/TO instruction can also be used in an interruption
subroutine.
2. When M1083 = On and an interruption signal occurs during the execution of FROM/TO
instruction, the interruption will be processed first (with a 100us delay) and the execution of
FROM/TO will be stopped. After the interruption subroutine finishes its execution, the
program will jump to the next instructio of FROM/TO. FROM/TO cannot be used in an
interruption subroutine.
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or
Read CR data in special modules
Write CR data into special module
K1
De sig na ted C R num ber
CR #5
CR #6
CR #7
CR #8 CR #9
CR #10
download the most updated version at http://www.delta.com.tw/industrialautomation
D0
D1 D2
D3 D4
D5
Designated CR
Loading...