DELTA DVP04AD-SL User Manual

2010-06-29
1-A4L1
DVP-1050130-02
………………………………………………………………… ENGLISH …………………………………………………………………
]
Thank you for choosing Delta’s DVP series PLC. The analog input module of DVP04AD-SL series can read/write the data of analog input module by using instructions FROM/TO via DVP SV/EH2-L MPU program. The analog input module receives 16bit digital data of 4 groups from PLC MPU and converts it into 4 points analog input signal either in voltage or in current. Users can select input from voltage or current via wiring. Voltage input range is -10V~10VDC (resolution is 312.5μV). Current input range is -20mA ~ 20mA (resolution is 625nA).
a This instruction sheet provides only information on the electrical specification,
general functions, installation and wiring. For detailed program design and applicable instructions, please refer to “DVP-ES2 Operation Manual: Modules”. For details of the optional peripheral, please refer to the instruction sheet enclosed in the package.
a This is an OPEN TYPE I/O module and therefore should be installed in an enclosure
free of airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required for operating the enclosure) in case danger and damage on the device may occur.
a DO NOT connect the input AC power supply to any of the I/O terminals; otherwise
serious damage may occur. Check all the wiring again before switching on the power. Make sure the ground terminal is correctly grounded in order to prevent electromagnetic interference.
a Tightening torque for I/O terminal block is 1.95 kg-cm (1.7 in-lbs) and please uses
60/75°C copper conductors only.
Product Profile & Dimension
1
234
90 [3.543]
6
7
8
9
DVP-04AD
5
63.4 [2.496]
10
3 [0.118]
1. I/O module connection port 6. Mounting hole of the I/O module
2. Status indicator
(POWER, RUN and ERROR)
3. Model name 8. Mounting slot (35mm)
4. I/O terminals 9. I/O module clip
5. Mounting slot clip 10. DC power input
5
60 [2.362]
Unit: mm [inch
7. I/O module connection port
I/O Terminal Layout
I2+V2+FGV1-I1+V1+ V3-
CH1 Ch2 Ch3 Ch4
FGV2- V4-I4 +V4+FG FG
DVP04AD-SL (4AI)
I3+V3+
- 1 -
33.1 [1.303]
[ Figure 1 ]
External Wiring
y Active-type
Volta ge input
U
IN
Current input
U
IN
Te rmi nal of power module
+
-
Shielded cable*1
+
-
Shielded cable*1
Grounding
*4 System grounding
(100 or less)
CH1
V1+
250
I1+
*5
VI1-
FE
CH4
V4+
*2
*3
VI4-
24V
250
I4+
FE
0V
y Passive-type
Voltage input
+
U
IN
-
Shielded cable*1
Current input
-
+
Shielded cable*1
Terminal of
power module
Note 1: When performing analog input, please isolate other power wirings.
Note 2: When the A/D module is connected to current signals, make sure you short-circuit “V+” and
“I+” terminals.
Note 3: If the noise is too significant, please connect FE to the grounding terminal.
Note 4: Please connect the
point and ground the system contact or connect it to the cover of power distribution cabinet.
Note 5: If the ripples at the loaded input terminal are too significant that causes noise interference on
the wiring, connect the wiring to 0.1 ~ 0.47μF 25V capacitor.
Grounding
*4 System grounding
(100 or less)
CH1
V1+
250
I1+
*5
VI1-
FE
CH4
V4+
*2
250
I4+ VI4-
FE
*3
0V
24V
terminal on both the power module and A/D module to the system earth
1M
1M
1M
1M
DC/DC
Converter
1M
1M
1M
1M
DC/DC
Convert er
AG
CH1
AG
CH4
+15V
AG
-15V
[ Fig ure 2 ]
AG
CH1
AG
CH4
+15V
AG
-15V
[ Fig ure 3 ]
Electrical Specifications
Analog / Digital module Voltage input Current input
Power supply voltage
Analog input channel 4 channels / each module
Range of analog input ±10V ±5V ±20mA 0 ~ 20mA 4 ~ 20mA
Range of digital conversion
24VDC (-15% ~ +20%) / 3.5W
DVPPS01(PS02): input 100-240VAC, output 24VDC/1A(PS02: 2A)
±32,000 ±32,000 ±32,000 0 ~ 32,000 0 ~ 32,000
- 2 -
Analog / Digital module Voltage input Current input
Hardware Resolution
Input impedance < 0.5
Overall accuracy
Response time 250μs / each channel
Max. output current 1K ~ 2M
Tolerance carried impedance
Digital data format 2’s complement of 16 bits, 15 significant bits
Isolation method
Series connection to DVP-PLC MPU
Operation/storage temperature
Vibration/shock immunity
16 bits 16 bits 16 bits 15 bits 15 bits
±0.3% when in full scale (25°C, 77°F)
±0.5% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F)
0Ω~500
Optical coupler isolation between digital circuits and analog circuits. No isolation among analog channels.
500VDC between digital circuits and Ground
500VDC between analog circuits and Ground
500VDC between analog circuits and digital circuits
500VDC between 24VDC and Ground
Connectable to the left side of MPU, numbered from 100 to 107 according to the position of module from the closest to farthest to MPU.
Operation: 0°C~55°C (temp.), 50~95% (humidity), Pollution degree2 Storage: -25°C~70°C (temp.), 5~95% (humidity)
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)
Control Register
CR# Attrib. Register name Explanation
#0 O R
#1 O R
#2 X R/W
#3 X R/W
#4 X R/W
#5 X R/W
#6 X R/W
#7 X R/W
Model name
Firmware version
CH1 input mode setting
CH2 input mode setting
CH3 input mode setting
CH4 input mode setting
History mode
History command
Set up by the system:
DVP04AD-SL model code = H’4400
Display the current firmware version in hex.
Input mode: Default = H’0000.
Take CH1 for example:
Mode 0 (H’0000): Voltage input (±10V)
Mode 1 (H’0001): Current input (±20mA)
Mode 2 (H’0002): Current input (0~+20mA)
Mode 3 (H’0003): Current input (+4~+20mA)
Mode 4 (H’0004): Voltage input (±5V)
Mode 5 (H’0005): Voltage input (0V~+5V)
Mode 6 (H’0006): Voltage input (1V~+5V)
Mode -1 (H’FFFF): Channel 1 unavailable
b15 ~ b12 b11 ~ b8 b7 ~ b4 b3 ~ b0
CH4 CH3 CH2 CH1
Only average values are recorded.
Default = H’0000. Take CH1 for example:
K0: Disable (Default). K1: Single. K2: Auto.
K3: Rising Edge Triggered
K4: Falling Edge Triggered
Refer to table of history command for detail. Default = H’0000
- 3 -
CR# Attrib. Register name Explanation
#8 X R/W
#9 X R/W
#10 X R/W
#11 X R/W
#12 X R
#13 X R
#14 X R
#15 X R
#16 X R
#17 X R
#18 X R
#19 X R
#20 X R/W
#21 X
#22 X
#23 X
#24 X
#25 X
#26 X
#27 X
#28 X R/W
#29 X R/W
#30 X R/W
#31 X R/W
#34 X R/W
#35 X R/W
#36 X R/W
#37 X R/W
#38 X
#39 X
#40 X
#41 X
#42 X R/W
#43 X R
#44 X R
CH1 sampling range
CH2 sampling range
CH3 sampling range
CH4 sampling range
CH1 average input value
CH2 average input value
CH3 average input value
CH4 average input value
CH1 present input value
CH2 present input value
CH3 present input value
CH4 present input value
Set value of CH1 upper bound
R/W
Set value of CH2 upper bound
R/W
Set value of CH3 upper bound
R/W
Set value of CH4 upper bound
R/W
Set value of CH1 lower bound
R/W
Set value of CH2 lower bound
R/W
Set value of CH3 lower bound
R/W
Set value of CH4 lower bound
Adjusted Offset value of CH1
Adjusted Offset value of CH2
Adjusted Offset value of CH3
Adjusted Offset value of CH4
Adjusted Gain value of CH1
Adjusted Gain value of CH2
Adjusted Gain value of CH3
Adjusted Gain value of CH4
R/W
CH1 Edge value
R/W
CH2 Edge value
R/W
CH3 Edge value
R/W
CH4 Edge value
Function: Return to default setting
Error status
History status
Set sampling range in CH1 ~ CH4:
Range = K1 ~ K20
Default = K10
Average value of input signals at CH1 ~ CH4
Present value of input signals at CH1 ~ CH4
Set value of CH1~CH4 upper bound.
Default = K32767.
Set value of CH1~CH4 lower bound.
Default = K-32768.
Set the adjusted Offset value of CH1 ~ CH4. Default = K0
Definition of Offset in DVP04AD-SL:
The corresponding voltage (current) input value when the digital input value = 0.
Set the adjusted Gain value in CH1 ~ CH4. Default = K16,000
Definition of Gain in DVP04AD-SL:
The corresponding voltage (current) input value when the digital input value = 16,000.
Default = K0
b0 ~ b3: reset CH1 ~ CH4
b4 ~ b15: reserved
Default = H’0000. Give CH1 setting for example: When b0 is set to 1, all settings are reset to default setting.
Register for storing all error status. Refer to table of error status for more information. Default = H’0000.
Refer to table of history status for detail.
Default = K1
- 4 -
CR# Attrib. Register name Explanation
#46 X R
#47 X R
#48 X R
#49 X R
#100 ~ #199
Symbols: O means latched. X means not latched.
CR#7 History command. See the table below.
CR#43: Error status value. See the table below.
Bit Error Status Content Value Bit Error Status Content Value
b0 K1 (H’0001) Power supply error b1 K2 (H’0002) Hardware error
b2 K4 (H’0004) Mode setting error b3 ~ b7 Reserved
b8 K256 (H’0100) CH1 Conversion er ror b9 K512 (H’0200) CH2 Conversion error
b10 K1024 (H’0400) CH3 Conversion error b11 K2048 (H’0800) CH4 Conversion error
b12 K4096 (H’1000)
b14
CR#44: History status. See the table below.
Value
CH1 History timer
CH2 History timer
CH3 History timer
CH4 History timer
CH1 ~ CH4 history
R means can read data by using FROM instruction. W means can write data by using TO instruction. LSB (Least Significant Bit):1. Voltage input: 1
CMD History Command
H’1000 ~ H’1003 CH1 ~ CH4 start
H’2000 ~ H’2003 CH1 ~ CH4 stop
H’4000 ~ H’4003 Reset history buffers of CH1 ~ CH4
H’6000 ~ H’6003 Read histories of CH1 ~ CH4
Note: Please use pulse instruction for executing history commands
When the instruction is completed, the CR will be reset to 0.
CH1 Upper / lower bound error
K16384
(H’4000)
Note: Each error status is determined by the corresponding bit and there may be more than 2
errors occurring at the same time. 0 = normal; 1 = error.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Ch4 Ch3 Ch2 Ch1 Ch4 Ch3 Ch2 Ch1 Ch4 Ch3 Ch2 Ch1 Ch4 Ch3 Ch2 Ch1
0 Not Ready Not Full Empty Stop
1 Ready Full Not Empty Run
Note: History Command for reading will be executed only when a set of full 100 records are
ready. If there are less than 100 records, Not Ready will be indicated.
bit 8 ~ bit11 = 1: History buffer full. bit12 ~ bit15 = 1: History buffer ready.
CH3 Upper / lower bound error
Set history timer in CH1 ~ CH4:
Range = K1 ~ K32767
Default = K1
2. Current input: 1
b13 K8192 (H’2000)
b15
=10V/32,000=312.5μV
LSB
=20mA/32,000=625nA
LSB
K32768
(H’8000)
CH2 Upper / lower bound error
CH4 Upper / lower bound error
Adjust A/D Conversion Curve
Users can adjust the conversion curves according to the actual needs by changing the Offset value (CR#28 ~ CR#31) and Gain value (CR#34 ~ CR#37).
- 5 -
Gain: The corresponding voltage/current input value when the digital output value = 16,000.
Offset: The corresponding voltage/current input value when the digital output value = 0.
y Equation for voltage input Mode0: 0.3125mV = 20V/64,000 = 10V/32,000
VX
Y
16000
)(
V
10
)(
()
××= 32000
⎟ ⎠
OffsetGainOffset
Y=Digital output, X=Voltage input
y Equation for voltage input Mode4 / Mode5 / Mode6: 0.15625mV = 10V/64,000 =
5V/32,000
VX
Y
16000
)(
V
5
)(
()
××= 32000
⎟ ⎠
OffsetGainOffset
Y=Digital output, X=Voltage input
y Equation for current input Mode1 / Mode2: 0.625μA = 40mA/64,000 = 20mA/32,000
)(
16000
Y
mAX
20
)(
mA
××= 32000
()
OffsetGainOffset
⎟ ⎠
Y=Digital output, X=Current input
y Equation for current input Mode3: 0.5μA = 16mA/32,000
Adopt the Equation of current input Mode3, substitute Gain for 19200 (12mA) and Offset for 6400 (4mA)
⎛ ⎜
⎜ ⎝
20
+32384 +32000
+16000
mAX
)()(mA
16000
Y
y Mode 0: y Mode 1:
Digital output
()
××=
⎟ ⎠
640019200640032000
Y=Digital output, X=Current input
+32384 +32000
Digital output
+16000
-10V 0
Offset
-16000
-32000
-32384
5V
Gain
Voltage input
10V
-20mA 0
Offset
-16000
-32000
-32384
10mA
Gain
Current input
Mode 0 of CR#2 ~ CR#5 -10V ~ +10VGain = 5V (16,000)Offset = 0V (0)
Mode 1 of CR#2 ~ CR#5 20mA ~ +20mAGain = 10mA (16,000)Offset = 0V (0)
Range of digital conversion -32,000 ~ +32,000
Max./Min. range of digital conversion
y Mode 2: y Mode 3:
Digital output
+32384 +32000
+16000
-384
0
Offset
-32,384 ~ +32,384
Gain
20mA
10mA
Curren t input
+32384 +32000
Digital output
+16000
Offset
Gain
4mA
Current input
0
-384
- 6 -
20mA
20mA12mA
Loading...
+ 15 hidden pages