Thank you for choosing Delta’s DVP series PLC. Delta releases DVP02LC-SL load cell
module of weight measurement function. DVP02LC-SL provides 24-bit resolution
applicable for 4-wire or 6-wire load cells with various eigenvalues. Therefore, the
response time can be adjusted in coordination with each other according to users’ needs.
On this basis, the market requirements on weight measurement can easily be met.
a This instruction sheet provides introductory information on electrical specifications,
general specifications, installation and wiring.
a This is an OPEN TYPE I/O module and therefore should be installed in an enclosure
free of airborne dust, humidity, electric shock and vibration. The enclosure should
prevent non-maintenance staff from operating the device (e.g. key or specific tools
are required to open the enclosure) in case danger and damage on the device may
occur.
a DO NOT connect the input AC power supply to any of the I/O terminals; otherwise
serious damage may occur. Check all the wiring again before switching on the power.
Make sure the ground terminal is correctly grounded in order to prevent
electromagnetic interference.
a The tightening torque for I/O terminal block is 1.95 kg-cm (1.7 in-lbs). Use 60/75°C
copper conductors only.
Product Profile & Dimensions
3 mm
DVP02LC
POWER
EXC+
RUN
EXC-
ERROR
SIG+
L.V
CH1
SIG-
SEN+
SEN-
NET
SHD
ZERO
MAX
MOTION
EXC+
90 mm
EXC-
SIG+
CH2
SIG-
NET
SEN+
ZERO
SEN-
MAX
SHD
MOTION
60 mm
33 mm
1. Mounting hole of the I/O module 2. DIN rail mounting slot (35mm)
3. I/O module connection port 4. I/O module clip
Status indicator
Note 1: Please connect the terminal on both the power module and Load Cell module to the system
earth point and ground the system contact or connect it to the cover of power distribution
cabinet.
Grounding
*1
System
grounding
(100 or less)
EXC+
EXCSIG+
SIG-
SEN+
SEN-
EXC+
EXCSIG+
SIG-
SEN+
SEN-
0V
24V
A+5V
AGND
A+5V
AGND
DC/DC
Converter
CH1
CH2
A+5V
AGND
[ Fig ure 2 ]
Electrical Specifications
Load cell module Voltage output
Rated power supply voltage/
power consumption
Voltage Boundary 18 to 31.2 VDC
Max. current consumption 125 mA
Input signal range ± 40 mVDC
Sensibility +5 VDC +/-10%
Internal resolution 24 bits
Communication port RS-232, RS-485
Applicable sensor type 4-wire or 6-wire strain gauge
Temperature coefficient span ≤ ± 50 ppm/K v. E
Temperature coefficient zero
point
Linearity error ≤ 0.02%
Response time 2, 10, 20, 40, 80 ms × channels
4 measuring ranges 0 to 1 mV/V, 0 to 2 mV/V, 0 to 4 mV/V, 0 to 6mV/V
Max. distance for connecting
to load cell
Max. current output 5 VDC * 300 mA
Permitted load cell resistance 40 to 4,010 Ω
Common mode rejection
(CMRR @50/60 Hz)
Dynamic value filter Setting range: K1 to K5
Average value filter Setting range: K1 to K100
Isolation method
24 VDC (-15 to +20%) / 3W
≤ ± 0.4 μV/K
100 M
≥100dB
500 VAC between digital circuits and Ground
500 VAC between analog circuits and Ground
500 VAC between analog circuits and digital circuits
- 2 -
Load cell module Voltage output
Series connection to
DVP-PLC MPU
Operation / storage
temperature
Vibration / shock immunity
Complying with DIN1319-1, the tolerance of measured value should be ≤ 0.05% under 20°C
+ 10K temperature range
When the corrected ambient temperature and the actual temperature have a difference of
more than 10°C, it is suggested that you re-correct it.
Connectable to the left side of MPU, numbered from 100 to
107 according to the position of module from the closest to
farthest to MPU.
Operation: 0 to 55°C (temp.), 50 to 95% (humidity), pollution
degree 2
Mode 0 (H’0000): 2 ms
Mode 1 (H’0001): 10 ms
Mode 2 (H’0002): 20 ms
Mode 3 (H’0003): 40 ms
Mode 4 (H’0004): 80 ms, default
Sum up CH1 average value and CH2
average value and equalize them.
Equation: (CH1 average value + CH2
average value)/2
Read present average value as tare weight
value
bit0: CH1; bit1: CH2; bit2 to bit15: reserved
Display present weight as Gross (K0) or Net
(K1). bit0 to bit3: CH1; bit4 to bit7: CH2; bit8
to bit15: reserved.
Take CH1 for example: bit3 to bit0 = 0000,
gross; bit3 to bit0 = 0001, net; bit3 to bit0 =
1111, channel disabled.
The user can write in the weight or read it by
commands.
Default: K0; Range: -K32,768 to K32,767.
Default: K10; Range: K1 to K100.
When the set value exceeds the range, it will
automatically be changed to K1 or K100.
Display average weight.
Display present weight.
Default: K5
Range: K1 to K500
- 3 -
CR# Add. Attrib.Register name Explanation
#18 H1012 O R/W CH1 standstill range
#19 H1013 O R/W CH2 standstill range
#20 H1014 O R/W CH1 decimal place
#21 H1015 O R/W CH2 decimal place
#22 H1016 O R/W
#23 H1017 O R/W
#24 H1018 O R/W
#25 H1019 O R/W
#26 H101A X R/W
#33 H1021 O R/W
#34 H1022 O R/W
CH1 unit of
measurement
CH1 unit of
measurement
CH2 unit of
measurement
CH2 unit of
measurement
Weight correction
command
CH1 weight base
point
CH2 weight base
point
#35 H1023 O R CH1 max. weight
#36 H1024 O R CH2 max. weight
#37 H1025 O R/W
#38 H1026 O R/W
#39 H1027 O R/W
#40 H1028 O R/W
#41 H1029 X R/W
Upper limit for CH1
zero point check
Upper limit for CH2
zero point check
Lower limit for CH1
zero point check
Lower limit for CH2
zero point check
Saving set value
(H’5678)
Default: K10
Range: K1 to K10,000
Default: K2
Range: K1 to K4
Enter max. 4 ASCII words.
CR#22, CR#24: High word
CR#23, CR#25: Low word
For the user to correct the weight.
Default: H’0000
H’0001: CH1 Reset to zero command
H’0002: CH1 Weight base point command
H’0003: CH2 Reset to zero command
H’0004: CH2 Weight base point command
For CR#33 to CR#34 default = K1,000;
Range: K-32,768 to K32,767
Steps for correction: Take CH1 for example
1: Place no weights on the load cell
2: Set up CR#26 command = “H’0001”
3: Place standard weights on load cell
4: Write the weight of the weights on the plate
into CR#33.
5: Set up CR#26 command = “H’0002”
Set up the max. weight. When the measured
value exceeds the set value, error codes will
be recorded.
Reference for reset to zero. When the weight
is within this range, the status code will be set
to “zero bit”, indicating the current zero
weight status.
Default: K10
Range: K-32,768 to K32,767
Reference for reset to zero. When the weight
is within this range, the status code will be set
to “zero bit”, indicating the current zero
weight status.
Default: K-10
Range: K-32,768 to K32,767
Save the present set value and write all the
set values into the internal Flash for use next
time DVP02LC-SL is switched on.
H0: No action, Default
H’FFFF: Saving is successful
H’5678: Write to internal Flash
When H’5678 is written in, all set values will
be saved in Flash. When the saving is
completed, CR#41 will become H’FFFF. If the
value written in is not H’5678, it will
automatically return to H0, e.g. write K1 into
CR# to return to K0.
- 4 -
CR# Add. Attrib.Register name Explanation
#43 H102B X R/W CH1 filter percentage
#44 H102C X R/W CH2 filter percentage
#45 H102D X R/W
#46 H102E X R/W
#50 H1032 X R Status code
#51 H1033 X R Error code
#52 H1034 O R/W RS-232 node address
#53 H1035 O R/W
#54 H1036 O R/W RS-485 node address
#55 H1037 O R/W
Symbols: O means latched. X means not latched.
R means can read data. W means can write data.
c Error Code Table for CR#51:
bit Content Error bit Content Error
b0 K1 (H’0001)
b2 K4 (H’0004)
b4 K16 (H’0010)
b6 ~ b15 K64 (H’0040) Reserved
Note: Every error status is decided by its corresponding bit, so there might be more than
2 error statuses occurring at the same time. 0 refers to no error; 1 refers to error
occurring.
CR#
#12 H100C X R
#13 H100D X R
#14 H100E X R
#15 H100F X R
#16 H1010 O R/W
#17 H1011 O R/W
#18 H1012 O R/W
#19 H1013 O R/W
#20 H1014 O R/W
#21 H1015 O R/W
#22 H1016 O R/W
#23 H1017 O R/W
#24 H1018 O R/W
#25 H1019 O R/W
#26 H101A X R/W
#33 H1021 O R/W
#34 H1022 O R/W
#35 H1023 O R
#36 H1024 O R
#37 H1025 O R/W
#38 H1026 O R/W
#39 H1027 O R/W
#40 H1028 O R/W
#41 H1029 X R/W
#43 H102B X R/W
#44 H102C X R/W
#45 H102D X R/W
#46 H102E X R/W
#12 H100C X R
#13 H100D X R
#14 H100E X R
#15 H100F X R
#16 H1010 O R/W
#17 H1011 O R/W
#18 H1012 O R/W
#19 H1013 O R/W
#20 H1014 O R/W
#21 H1015 O R/W
#22 H1016 O R/W
#23 H1017 O R/W
#24 H1018 O R/W
#25 H1019 O R/W
#26 H101A X R/W
#33 H1021 O R/W
#34 H1022 O R/W
#35 H1023 O R
#36 H1024 O R
#37 H1025 O R/W
#38 H1026 O R/W
#39 H1027 O R/W
#40 H1028 O R/W
#41 H1029 X R/W
#43 H102B X R/W
#44 H102C X R/W
#45 H102D X R/W
#46 H102E X R/W
Delta’nın DVP serisi PLC’lerini seçtiğiniz için teşekkürler. Delta, load cell ile ağırlık
ölçümü için DVP02LC-SL modülünü sunar. DVP02LC-SL, 4-telli ve 6-telli özgün değerli
yük hücreleri (load cell) için uygulanabilir 24-bit çözünürlük sağlar. Buna bağlı olarak,
cevap zamanı (response time) kullanıcı ihtiyaçlarına göre herbiri ile koordinasyon
halinde çalışma için ayarlanabilir. Bu temelde, ağırlık ölçümünde pazar ihtiyaçları
rahatça karşılanabilir.
a Bu bilgi dökümanı ürünün elektriksel özellikleri, genel özellikleri, kurulumu ve
bağlantısı ile ilgili bilgiler sağlar.
a Bu ürün AÇIK TİP I/O modülü olduğu için toz, nem, elektrik şoku ve titreşimden uzak
yerlere kurulumu yapılmalıdır. Ürünün zarar görmemesi ve tehlike durumları
oluşmaması için yetkili olmayan kişilerin ürüne müdahale etmesini önleyecek
koruyucu önlemler alınmalıdır. (Örneğin ürünün bulunduğu panoya kilit konulması
gibi).
a Ürünün I/O terminallerine AC besleme bağlamayınız; aksi halde ciddi zararlar
meydana gelebilir. Ürüne enerji vermeden önce tüm bağlantıların doğru olduğunu
tekrar kontrol ediniz. Elektromanyetik gürültüyü önlemek için toprak terminalinin
düzgün topraklandığından emin olunuz.
a I/O terminal bloğu sıkma torku 1.95 kg-cm (1.7 in-lbs) olmalı ve sadece 60/75°C bakır
iletkenler kullanılmalıdır.
Ürün Profili & Ölçüler
İngilizce bölümde Şekil 1 [Figure 1]’e bakınız. Birim = mm
1. I/O modülü montaj yuvası2. DIN ray montaj slotu (35mm)
3. I/O modül bağlantı portu 4. I/O modül klip
Durum indikatör
5.
(POWER, RUN, ERROR ve L.V)
7. I/O terminaller 8. RS-232 port
9. Montaj slot klipsi 10. RS-485 port
11. DC besleme girişi
Fonksiyon durum göstergesi
6.
(NET, ZERO, MAX, MOTION)
I/O Terminal Yerleşimi
İngilizce bölümde “terminal layout” şekline bakınız.
Harici Bağlantı
İngilizce bölümde Şekil 2 [Figure 2]’ye bakınız.
Not 1: Power modülü ve load cell modülü terminallerini sistemin toprak ucunda
birleştirdikten sonra topraklamayı güç dağıtım panelinin kasasına bağlayarak yapınız.
Elektriksel Özellikler
Load cell modülü Volt aj çıkışı
Besleme voltajı /Güç
tüketimi aralığı
Volt aj sınırları18 to 31.2 VDC
Max. akım tüketimi 125 mA
Giriş sinyal aralığı ±40 mVDC
Hassasiyet +5 VDC +/-10%
Dahili çözünürlük 24 bits
24 VDC (-15 to +20%) / 3W
- 14 -
Load cell modülü Volt aj çıkışı
Haberleşme portu RS-232, RS-485
Uygulanabilir sensör
tipi
Sıcaklık span Katsayısı ≤ ± 50 ppm/K v. E
Sıcaklık zero point
Katsayısı
Linearite hatası
Cevap Zamanı2, 10, 20, 40, 80 ms × kanal
4 ölçme aralığı0 to 1 mV/V, 0 to 2 mV/V, 0 to 4 mV/V, 0 to 6mV/V
Load cell bağlantısı için
maksimum mesafe
Max. Akım çıkışı5 VDC * 300 mA
Müsade edilen load cell
direnci
Ortak mod reddetme
(CMRR @50/60 Hz)
Dinamik değer filtresi
Ortalama değer filtresi
İzolasyon metodu
DVP-PLC MPU’ya seri
bağlantı
Çalışma/Saklama
Sıcaklığı
Titreşim / Şok
Bağışıklığı
DIN1319-1 ile uyumlu, ölçüm değeri toleransı 20°C + 10K sıcaklık aralığında ≤ 0.05 %
olmalıdır.
Düzeltilmiş sıcaklık ortamı ve gerçek sıcaklık arasında 10°C’den fazla fark varsa, tekrar
düzeltilmesi önerilir.
4-telli veya 6-telli gerinim ölçer
≤ ± 0.4 μV/K
≤ 0.02%
100m
40 to 4,010 Ω
≥ 100dB
Ayar aralığı: K1 to K5
Ayar aralığı: K1 to K100
Dijital devreler ve Ground arası 500 VAC
Analog devreler ve ground arası 500 VAC
Analog devreler ve dijital devreler arası 500 VAC
MPU’nun sol kenarına bağlanabilir, MPU’ya uzaklığına göre
yakından uzağa doğru 100 – 107 arası adreslenir.
Çalışma: 0 to 55°C (sıcaklık), 50 to 95% (rutubet), kirlenme derece 2
Saklama: -25 to ~70°C (sıcaklık), 5 to 95% (rutubet)
Kullanıcılar ağırlığı yazabilir veya komutlar ile
okuyabilir.
Var sa yılan: K0; Aralık: -K32,768 ~ K32,767.
Var sa yılan: K10; Aralık: K1 ~ K100.
Set değeri aralığı aştığı zaman, otomatik
olarak K1 ve K100 olarak değişir.
Ortalama ağırlığı gösterir.
Mevcut ağırlığı gösterir.
Var sa yılan: K5
Aralık: K1 ~ K500
Var sa yılan: K10
Aralık: K1 ~ K1,000
Var sa yılan: K2
Aralık: K1 ~ K4
Maksimum 4 ASCII word girilir.
CR#22, CR#24: Yüksek word
CR#23, CR#25: Düşük word
Kullanıcıların ağırlığı düzeltmesi için.
Var sa yılan: H’0000
H’0001: CH1 Sıfır komutuna resetle
H’0002: CH1 Ağırlık taban noktası komutu
H’0003: CH2 Sıfır komutuna resetle
H’0004: CH2 Ağırlık taban noktası komutu
CR#33~CR#34 için Varsayılan = K1,000;
Aralık: K-32,768 ~ K32,767
Düzeltme adımları: CH1 örneği
1: Load cell üzerine hiçbir ağırlık koymayınız.
2: CR#26 komutunu “H’0001” ayarlayınız.
3: Load cell üzerine standart ağırlığı
yerleştiriniz
4: Tabaka üzerindeki ağırlığı ikinci ağırlık
değeri olarak CR#33 içine yazınız.
5: CR#26 komutunu “H’0002” ayarlayınız
Maksimum ağırlık ayarı. Ölçüm değeri set
değerini aştığı zaman, hata kodları
kaydedilecek.
Sıfıra resetlemek için referans. Ağırlık bu
aralığın için de olduğu zaman, durum (Status)
kodu mevcut ağırlık durumunu gösteren
“zero bitini” set edecek.
Var sa yılan: K10
Aralık: K-32,768 ~ K32,767
- 16 -
CR# Add. ÖzellikRegister adı Açıklama
#39 H1027 OR/W
#40 H1028 OR/W
#41 H1029 X R/W
#43 H102B X R/W CH1 filtre yüzdesi
#44 H102C X R/W CH2 filtre yüzdesi
#45 H102D X R/W
#46 H102E X R/W
#50 H1032 XR Status (durum) kodu
#51 H1033 XR Hata kodu
#52 H1034 OR/W RS-232 slave adresi
#53 H1035 O R/W
#54 H1036 O R/W RS-485 slave adresi
#55 H1037 O R/W
Not: Her hata durumu ona karşılık gelen bir bit ile tanımlanır. Aynı anda 2 veya daha fazla
hata meydana gelebilir. 0 hata olmadığını; 1 hata olduğunu gösterir.
CH1 sıfır noktası
kontrol alt limiti
CH2 sıfır noktası
kontrol alt limiti
Set değeri kaydetme
(H’5678)
CH1 filtre ortalama
değeri
CH2 filtre ortalama
değeri
RS-232 haberleşme
formatı
RS-485 haberleşme
formatı
Power supply
anormal
Sıfıra resetlemek için referans. Ağırlık bu
aralığın için de olduğu zaman, durum (status)
kodu mevcut ağırlık durumunu gösteren
“zero bitini” set edecek.
Var sa yılan: K-10
Aralık: K-32,768 ~ K32,767
Mevcut set değerini kaydeder ve
DVP02LC-SL daha sonra enerjilendiğinde
kullanabilmesi için tüm set değerlerini dahili
flash içine yazar.
H0: Çalışma yok, Varsayılan
H’FFFF: Kayıt başarılı
H’5678: Dahili Flash’a yazar.
H’5678 yazıldığı zaman, tüm set değerleri
Flash içine kaydedilecek. Kayıt tamamlandığı
zaman, CR#41 H’FFFF olacak. Eğer yazılan
değer H’5678 değilse, otomatik olarak H0’a
dönecek. Örneğin CR# içine K1 yazılırsa
K0’a dönecek.
Default: K2; Aralık: K1 ~ K5 (Birim: 10%)
Filtrelemeden sonra ortalama ağırlığı gösterir
Filtre aktif etme şart: ortalama zam an ≥ 30
b0 (H’0001): CH1 sıfır ağırlık (boş)
b1 (H’0002): CH2 sıfır ağırlık (boş)
b2 (H’0004): CH1 maksimum ağırlığı aşar