Daikin EWAQ009ACV3, EWAQ010ACV3, EWAQ011ACV3, EWYQ009ACV3, EWYQ010ACV3 Installation manuals

...
Page 1
INSTALLATION MANUAL
packaged reversible air to water heatpumps
EWAQ009ACV3 EWAQ010ACV3 EWAQ011ACV3
EWYQ009ACV3 EWYQ010ACV3 EWYQ011ACV3
EWAQ009ACW1 EWAQ011ACW1 EWAQ013ACW1
EWYQ009ACW1 EWYQ011ACW1 EWYQ013ACW1
Page 2
D2D2
L1
L2
B1
B2
D2D2
L1
L2
1
B2
B2
D2
D2D2
EE
L1
L1
CC
HH
B1B1B1
L2
L2
AA
D1D1D1
1
B2B2B2
D2D2
D2
EE
L1
CC
L2
L2
AA
D1D1D1
L1
HH
B1
B1
1
2
1
2
W1V3
DCAC DCAC
2
Page 3
.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
ATITIKTIES-DEKLARACIJA
ATBILSTĪBAS-DEKLARĀCIJA
VYHLÁSENIE-ZHODY
CE -
CE -
CE -
CE - UYUMLULUK-BİLDİRİSİ
ZJAVA O SKLADNOSTI
VASTAVUSDEKLARATSIOON
ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ
CE - I
CE -
CE -
deklaruje na własną i wyłączną odpowiedzialność, że modele klimatyzatorów, których dotyczy niniejsza deklaracja:
m
IZJAVA-O-USKLAĐENOSTI
DEKLARACJA-ZGODNOŚCI
DECLARAŢIE-DE-CONFORMITATE
CE - MEGFELELŐSÉGI-NYILATKOZAT
CE -
CE -
CE -
15
16
17
18
19
20
21
22
23
24
25
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
.
.
.
.
*
.
. 07
*
.
.
.
.
Direktive z vsemi spremembami.
Direktiivid koos muudatustega.
Директиви, с техните изменения.
Direktyvose su papildymais.
Direktiver, med senere ændringer.
Direktiv, med företagna ändringar.
Direktiver, med foretatte endringer.
Direktiivejä, sellaisina kuin ne ovat muutettuina.
declară pe proprie răspundere că aparatele de aer condiţionat la care se referă această declaraţie:
z vso odgovornostjo izjavlja, da so modeli klimatskih naprav, na katere se izjava nanaša:
kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluvad kliimaseadmete mudelid:
декларира на своя отговорност, че моделите климатична инсталация, за които се отнася тази декларация:
visiška savo atsakomybe skelbia, kad oro kondicionavimo prietaisų modeliai, kuriems yra taikoma ši deklaracija:
ar pilnu atbildību apliecina, ka tālāk uzskaitīto modeĮu gaisa kondicionētāji, uz kuriem attiecas šī deklarācija:
vyhlasuje na vlastnú zodpovednosť, že tieto klimatizačné modely, na ktoré sa vzťahuje toto vyhlásenie:
tamamen kendi sorumluluğunda olmak üzere bu bildirinin ilgili olduğu klima modellerinin aşağıdaki gibi olduğunu beyan eder:
r
o
x
b
t
v
k
w
25
megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi
instrukcjami:
sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în
conformitate cu instrucţiunile noastre
skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите
инструкции:
atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade
s našim návodom:
ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
Directives, as amended.
Direktiven, gemäß Änderung.
Directives, telles que modifiées.
Richtlijnen, zoals geamendeerd.
.
.
.
i
.
.
.
*
.
.
Direktīvās un to papildinājumos.
Smernice, v platnom znení.
Değiştirilmiş halleriyle Yönetmelikler.
<B>
v platném znění.
Smjernice, kako je izmijenjeno.
irányelv(ek) és módosításaik rendelkezéseit.
z późniejszymi poprawkami.
и оценено
Directivelor, cu amendamentele respective.
съгласно
<A>
ir kaip teigiamai nuspręsta
<B>
<A>
Sertifikatą <C>
положително от
pagal
както е изложено в
Cертификата <C>
kaip nustatyta
21 Забележка *
22 Pastaba *
Directivas, según lo enmendado.
Direttive, come da modifica.
√‰ËÁÈÒv, fiˆ˜ ¤¯Ô˘Ó ÙÚÔÔÔÈËı›.
Directivas, conforme alteração em.
Директив со всеми поправками.
, pozytywną opinią
şi apreciat pozitiv
igazolta a megfelelést,
<A>
<A>
<B>
szerint.
alapján, a(z)
Świadectwem <C>
<A>
<C> tanúsítvány
a(z)
a(z)
zgodnie z dokumentacją
<B>
aşa cum este stabilit în
.
.
.
*
01
02
03
04
<A> DAIKIN.TCF.025C14/11-2008
<B> KEMA (NB0344)
<C> 2082543.0551-QUA/EMC
v
<B>
pozitīvajam
<C> Sertifikasına
<B>
a pozitívne zistené
sertifikātu <C>
<A>
un atbilstoši
<A>
kā norādīts
tarafından olumlu olarak
<B>
osvedčením <C>
‘da belirtildiği gibi ve
vērtējumam saskaņā ar
değerlendirildiği gibi.
súlade s
ako bolo uvedené v
<A>
göre
Not
23 Piezīmes *
24 Poznámka *
25
v
<B>
ja heaks
<A>
sertifikaadile <C>
Certificatul <C>
in odobreno s strani
<A>
järgi vastavalt
certifikatom <C>
<B>
în conformitate cu
<B>
de
kiidetud
kot je določeno v
nagu on näidatud dokumendis
skladu s
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
PROHLÁŠENÍ-O-SHODĚ
CE - ERKLÆRING OM-SAMSVAR
CE - ILMOITUS-YHDENMUKAISUUDESTA
CE -
заявляет, исключительно под свою ответственность, что модели кондиционеров воздуха, к которым относится настоящее заявление:
erklærer under eneansvar, at klimaanlægmodellerne, som denne deklaration vedrører:
u
q
CE - DECLARAÇÃO-DE-CONFORMIDADE СЕ - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ
CE - OPFYLDELSESERKLÆRING
CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE
CE - ¢H§ø™H ™YMMOPºø™H™
CE - DECLARACION-DE-CONFORMIDAD
CE - DICHIARAZIONE-DI-CONFORMITA
prohlašuje ve své plné odpovědnosti, že modely klimatizace, k nimž se toto prohlášení vztahuje:
izjavljuje pod isključivo vlastitom odgovornošću da su modeli klima uređaja na koje se ova izjava odnosi:
deklarerar i egenskap av huvudansvarig, att luftkonditioneringsmodellerna som berörs av denna deklaration innebär att:
erklærer et fullstendig ansvar for at de luftkondisjoneringsmodeller som berøres av denne deklarasjon innebærer at:
s
n
teljes felelőssége tudatában kijelenti, hogy a klímaberendezés modellek, melyekre e nyilatkozat vonatkozik:
ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat ilmastointilaitteiden mallit:
j
c
y
h
declaración:
referencia la
estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de
acordo com as nossas instruções:
соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим
инструкциям:
overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore
instrukser:
respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under
förutsättning att användning sker i överensstämmelse med våra instruktioner:
respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at
disse brukes i henhold til våre instrukser:
vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme
mukaisesti:
za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům:
u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama:
Machinery 98/37/EC
Low Voltage 2006/95/EC
Electromagnetic Compatibility 2004/108/EC *
ob upoštevanju določb:
vastavalt nõuetele:
следвайки клаузите на:
laikantis nuostatų, pateikiamų:
ievērojot prasības, kas noteiktas:
održiavajúc ustanovenia:
bunun koşullarına uygun olarak:
under iagttagelse af bestemmelserne i:
enligt villkoren i:
gitt i henhold til bestemmelsene i:
noudattaen määräyksiä:
za dodržení ustanovení předpisu:
prema odredbama:
követi a(z):
zgodnie z postanowieniami Dyrektyw:
în urma prevederilor:
Notă *
16 Megjegyzés *
17 Uwaga *
18
on
<B>
ja jotka
enligt
<B>
och godkänts av
<A>
enligt
11 Information *
e giudicato positivamente
<A>
delineato nel
mukaisesti.
<A>
Sertifikat <C>
og gjennom positiv
<A>
ifølge
<B>
Sertifikaatin <C>
hyväksynyt
Certifikatet <C>
som det fremkommer i
bedømmelse av
jotka on esitetty asiakirjassa
12 Merk *
13 Huom *
Certificado <C>
¶ИЫЩФФИЛЩИОfi <C>
e com o parecer
Î·È ÎÚ›ÓÂÙ·È ıÂÙÈο
<A>
<A>
Certificato <C>
de acordo com o
Û‡Ìʈӷ Ì ÙÔ
<B>
<B>
secondo il
<B>
positivo de
·fi ÙÔ
tal como estabelecido em
da
* fiˆ˜ ηıÔÚ›˙ÂÙ·È ÛÙÔ
™ËÌ›ˆÛË
06 Nota *
08 Nota
<B>
positiv
<B>
<C>
<C>
et évalué positivement par
Certificat <C>
<A>
Certificate
and judged positively by
Zertifikat
aufgeführt und von
<A>
<A>
conformément au
beurteilt gemäß
according to the
as set out in
wie in der
tel que défini dans
<B>
19 Opomba *
20 Märkus
v
<B>
a pozitivně zjištěno
i pozitivno ocijenjeno od
<A>
Certifikatu <C>
<A>
prema
osvědčením <C>
<B>
strane
jak bylo uvedeno v
kako je izloženo u
souladu s
14 Poznámka *
15 Napomena *
i
<B>
согласно
<B>
и в соответствии с
og positivt vurderet af
<A>
<A>
Certifikat <C>
положительным решением
henhold til
как указано в
Свидетельству <C>
som anført i
09 Примечание *
10 Bemærk *
y es valorado
de acuerdo con el
<A>
Certificaat <C>
en positief beoordeeld door
<B>
<A>
overeenkomstig
zoals vermeld in
<B>
como se establece en
Certificado <C>
positivamente por
Jiro Tomita
Director Quality Assurance
Ostend, 1st of April 2009
declares under its sole responsibility that the air conditioning models to which this declaration relates:
erklärt auf seine alleinige Verantwortung daß die Modelle der Klimageräte für die diese Erklärung bestimmt ist:
déclare sous sa seule responsabilité que les appareils d'air conditionné visés par la présente déclaration:
verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de airconditioning units waarop deze verklaring betrekking heeft:
declara baja su única responsabilidad que los modelos de aire acondicionado a los cuales hace
dichiara sotto sua responsabilità che i condizionatori modello a cui è riferita questa dichiarazione:
a
d
f
l
e
CE - DECLARATION-OF-CONFORMITY
CE - KONFORMITÄTSERKLÄRUNG
CE - DECLARATION-DE-CONFORMITE
CE - CONFORMITEITSVERKLARING
Daikin Europe N.V.
i
‰ЛПТУВИ МВ ·ФОПВИЫЩИО‹ ЩЛ˜ В˘ı‡УЛ fiЩИ Щ· МФУЩ¤П· ЩˆУ ОПИМ·ЩИЫЩИОТУ Ы˘ЫОВ˘ТУ ЫЩ· ФФ›· ·У·К¤ЪВЩ·И Л ·ЪФ‡Ы· ‰‹ПˆЫЛ:
declara sob sua exclusiva responsabilidade que os modelos de ar condicionado a que esta declaração se refere:
g
p
EWAQ009ACV3****, EWAQ010ACV3****, EWAQ011ACV3****, EWYQ009ACV3****, EWYQ010ACV3****, EWYQ011ACV3****,
EWAQ009ACW1****, EWAQ011ACW1****, EWAQ013ACW1****, EWYQ009ACW1****, EWYQ011ACW1****, EWYQ013ACW1****,
* = , , -, 1, 2, 3, ..., 9, A, B, C, ..., Z
are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our
instructions:
der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung,
daß sie gemäß unseren Anweisungen eingesetzt werden:
sont conformes à la/aux norme(s) ou autre(s) document(s) nor matif(s), pour autant qu'ils soient utilisés conformément à nos instructions:
conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig
onze instructies:
están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) nor mativo(s), siempre que sean utilizados de acuerdo con
nuestras instrucciones:
sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle
nostre istruzioni:
В›У·И Ы‡МКˆУ· МВ ЩФ(·) ·ОfiПФ˘ıФ(·) ЪfiЩ˘Ф(·) ‹ ¿ППФ ¤ББЪ·КФ(·) О·УФУИЫМТУ, ˘fi ЩЛУ ЪФ¸fiıВЫЛ fiЩИ ¯ЪЛЫИМФФИФ‡УЩ·И
Û‡Ìʈӷ Ì ÙȘ Ô‰ËÁ›Â˜ Ì·˜:
following the provisions of:
gemäß den Vorschriften der:
conformément aux stipulations des:
overeenkomstig de bepalingen van:
EN60335-2-40,
siguiendo las disposiciones de:
secondo le prescrizioni per:
Ì ًÚËÛË Ùˆv ‰È·Ù¿Íˆv Ùˆv:
de acordo com o previsto em:
в соответствии с положениями:
01 Note *
02 Hinweis *
03 Remarque *
04 Bemerk *
05 Nota
3PW33163-3D
Page 4
EWAQ009~011ACV3 EWAQ009~013ACW1 EWYQ009~011ACV3 EWYQ009~013ACW1
Packaged air-cooled water chillers and
packaged reversible air to water heatpumps
Installation manual
CONTENTS Page
Introduction ....................................................................................... 1
General information ................................................................................... 1
Scope of this manual ................................................................................. 1
Model identification.................................................................................... 2
Accessories....................................................................................... 2
Accessories supplied with the unit............................................................. 2
Safety considerations........................................................................ 2
Before installation.............................................................................. 3
Important information regarding the refrigerant used........................ 3
Selecting installation site................................................................... 4
Selecting a location in cold climates.......................................................... 4
Precautions on installation ................................................................4
Installation method for prevention of falling over........................................ 5
Installation servicing space........................................................................ 5
Typical application examples............................................................. 6
Application 1 .............................................................................................. 6
Application 2 .............................................................................................. 6
Overview of the unit .......................................................................... 7
Opening the unit ........................................................................................ 7
Main components ...................................................................................... 7
Water pipework.......................................................................................... 8
Charging water ........................................................................................ 10
Piping insulation....................................................................................... 10
Field wiring .............................................................................................. 11
Specifications of standard wiring components ........................................ 13
Installation of the digital controller ........................................................... 15
Start-up and configuration............................................................... 16
Pump operation configuration.................................................................. 16
Initial start-up at low outdoor ambient temperatures ............................... 16
Pre-operation checks............................................................................... 16
Powering up the unit ................................................................................ 17
Failure diagnosis at the moment of first installation................................. 17
Setting the pump speed........................................................................... 17
Field settings............................................................................................ 18
Field settings table................................................................................... 21
Test run and final check .................................................................. 22
Test run operation (manual)..................................................................... 22
Final check............................................................................................... 22
Maintenance.................................................................................... 22
Chiller unit................................................................................................ 22
Digital controller....................................................................................... 23
Troubleshooting............................................................................... 23
General guidelines................................................................................... 23
General symptoms................................................................................... 23
Error codes .............................................................................................. 24
Technical specifications................................................................... 25
General.................................................................................................... 25
Electrical specifications ........................................................................... 25
READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATION.
The English text is the original instruction. Other languages are translations of the original instructions.

INTRODUCTION

General information

Thank you for purchasing this Daikin inverter chiller. This unit is designed for outdoor installation and used for both
heating and cooling applications. The unit is designed to be combined with fan coil units or air handling units for air conditioning purposes.
Heat pump and cooling only versions
This chiller range consists of 2 main versions: a heat pump (EWYQ) version and a cooling only (EWAQ) version, available in 6 standard sizes:
V3: 9, 10, and 11 kW (single phase)
W1: 9, 11, and 13 kW (3 phase)
Options
Remote alarm kit EKRP1HB
Heater tape option OP10
Both versions are also available with a heater tape option (OP10) for protecting internal water pipework at cold outdoor temperatures.
Connection to a benefit kWh rate power supply
This equipment allows for connection to benefit kWh rate power supply delivery systems. Full control of the unit will remain possible only in case the benefit kWh rate power supply is of the type that power supply is not interrupted. Refer to "Connection to a benefit
kWh rate power supply" on page 14 for more details.
Installation manual
1

Scope of this manual

This manual describes the procedures for unpacking, installing and connecting all EWA/YQ models, as well as instructions for maintenance and troubleshooting of the unit.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 5
Model identification

SAFETY CONSIDERATIONS

EW A Q 009 AC V3 P -H-
P = Pump included H = OPHP
Nominal voltage V3: 1~ 230 V 50 Hz W1: 3N~ 400 V 50 Hz
Major/minor change
Indication of heating/cooling capacity (kW)
R410A refrigerant
A = cooling only, Y = heating and cooling
European water chiller
(a) OPHP = High ESP pump. (b) Please see "Technical specifications" on page 25 for exact values.

ACCESSORIES

Accessories supplied with the unit

12
1x 1x 2x 1x
67
1x 1x
1 Installation manual 2 Operation manual 3 Wiring diagram sticker (inside unit cover doors 1 and 2) 4 User interface kit
(digital remote controller, 4 fixing screws and 2 plugs)
5 Main switch handle 6 Protection cap 7 Protection cap (only for W1 models)
341x5
Option heater tape
(a)
included
(b)
The precautions listed here are divided into the following two types. Both cover very important topics, so be sure to follow them carefully.
WARNING
If the warning is not observed, it may cause serious casualties.
CAUTION
If the caution is not observed, it may cause injury or damage to the equipment.
Warning
For use of units in applications with temperature alarm settings it is advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded. The unit may stop for several minutes during normal operation for "defrosting of the unit" or when in "thermostat-stop" operation.
Ask your dealer or qualified personnel to carry out installation work Do not install the machine by yourself.
Improper installation may result in water leakage, electric shocks or fire.
Perform installation work in accordance with this installation manual.
Improper installation may lead to water leakage, electric shocks or fire.
Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in water leakage, electric shocks, fire, or the unit falling.
Install the unit on a foundation that can withstand its weight.
Insufficient strength may result in the fall of equipment and
causing injury.
Carry out the specified installation work in consideration of strong winds, typhoons, or earthquakes.
Improper installation work may result in accidents due to fall of equipment.
Make certain that all electrical work is carried out by qualified personnel according to the local laws and regulations and this installation manual, using a separate circuit.
Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire.
Make sure that all wiring is secure, using the specified wires and ensuring that external forces do not act on the terminal connections or wires.
Incomplete connection or fixing may cause a fire.
When wiring the power supply, form the wires so that the frontside panel can be securely fastened.
If the frontside panel is not in place, overheat of the terminals, electric shocks or a fire may be caused.
After completing the installation work, check to make sure that there is no leakage of refrigerant gas.
Before touching electric terminal parts, turn off power switch.
Live parts can be easily touched by accident.
Never leave the unit unattended during installation or servicing when the service panel is removed.
Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.
.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
2
Page 6
Caution
Earth the unit. Earthing resistance should be according to national regulations Do not connect the earth wire to gas or water pipes,
lightning conductor or telephone earth wire. Incomplete earthing may cause electric shocks.
Gas pipe.
Ignition or explosion may occur if the gas leaks.
Water pipe.
Hard vinyl tubes are not effective earths.
Lightning conductor or telephone earth wire.
Electric potential may rise abnormally if struck by a lightning bolt.
Be sure to install an earth leakage circuit breaker. Failure to install an earth leakage circuit breaker may cause
electric shocks and fire.
Install the power wire at least 1 meter away from televisions or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient to eliminate the noise.)
Do not rinse the unit. This may cause electric shocks or fire.
Do not install the unit in places such as the following:
Where there is mist of mineral oil, oil spray or vapour.
Plastic parts may deteriorate, and cause them to fall out or water to leak.
Where corrosive gas, such as sulphurous acid gas, is
produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
Where there is machinery which emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
Where flammable gases may leak, where carbon fiber or
ignitable dust is suspended in the air or where volatile flammables, such as thinner or gasoline, are handled. Such gases may cause a fire.
Where the air contains high levels of salt such as that near
the ocean.
Where voltage fluctuates a lot, such as that in factories.
In vehicles or vessels.
Where acidic or alkaline vapour is present.

BEFORE INSTALLATION

Installation
Be sure to confirm the model name and the serial no. of the outer (front) plates when attaching/detaching the plates to avoid mistakes.
When closing the service panels, take care that the tightening torque does not exceed 4.1 N•m.
In case ambient temperatures below 0°C are expected, countermeasures need to be taken to prevent the water in the unit from freezing. In such cases, we recommend to install the heater tape option OP10 or we advise to put glycol in the system. See "Protecting the water circuit against freezing" on
page 10. It is also allowed to drain the water from the system
when longer periods of standstill are expected.
Model
EWAQ and EWYQ units include optional special equipment (insulation, heater tape,...) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the units may experience problems with severe ice build up on the aircooled coil. In case such conditions are expected, the heater tape option OP10 must be installed instead.
Possible options
Model OP10
EWA/YQ_AC*P — EWA/YQ_AC*P-H- Factory mounted — EWA/YQ_AC*H Factory mounted EWA/YQ_AC*H-H- Factory mounted Factory mounted
(a) Heater tape option OP10 (b) High ESP pump
(a)
Handling
Due to relatively large dimensions and high weight, the handling of the unit is only to be done by means of lifting tools with slings. These slings can be fitted into specially for this purpose foreseen sleeves at the base frame.
To avoid injury, do not touch the air inlet or aluminium fins of the unit.
Do not use the grips in the fan grills to avoid damage.
OPHP
(b)
Installation manual
3
IMPORTANT INFORMATION REGARDING THE
REFRIGERANT USED
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type: R410A
(1)
GWP
value: 1975
(1)
GWP = global warming potential
The refrigerant quantity is indicated on the unit name plate
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 7

SELECTING INSTALLATION SITE

Make sure to provide for adequate measures in order to prevent that the unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
1 Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.
- Places which are well-ventilated.
- Places where the unit does not bother next-door neighbours.
- Safe places which can withstand the unit's weight and vibration and where the unit can be installed level.
- Places where there is no possibility of flammable gas or product leak.
- The equipment is not intended for use in a potentially explosive atmosphere.
- Places where servicing space can be well ensured.
- Places where the units' piping and wiring lengths come within the allowable ranges.
- Places where water leaking from the unit cannot cause damage to the location (e.g. in case of a blocked drain pipe).
- Places where the rain can be avoided as much as possible.
2 When installing the unit in a place exposed to strong wind, pay
special attention to the following. Strong winds of 5 m/sec or more blowing against the unit's air
outlet causes short circuit (suction of discharge air), and this may have the following consequences:
- Deterioration of the operational capacity.
-Frequent frost acceleration in heating operation.
- Disruption of operation due to rise of high pressure.
- When a strong wind blows continuously on the face of the unit, the fan can start rotating very fast until it breaks.
Refer to the figures for installation of this unit in a place where the wind direction can be foreseen.
Tu rn the air outlet side toward the building's wall, fence or screen.
5 If you install the unit on a frame, please install a waterproof plate
within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction.
6 When installing the unit in a place frequently exposed to snow,
pay special attention to elevate the foundation as high as possible.
7 If you install the unit on a building frame,
please install a waterproof plate (field supply)(within 150 mm of the underside of the unit). (See figure).

Selecting a location in cold climates

Refer to "Model" on page 3.
CAUTION
When operating the unit in a low outdoor ambient temperature, be sure to follow the instructions described below.
To prevent exposure to wind, install the unit with its suction side facing the wall.
Never install the unit at a site where the suction side may be exposed directly to wind.
To prevent exposure to wind, install a baffle plate on the air discharge side of the unit.
In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit. If lateral snowfall is possible, make sure that the heat exchanger coil is not affected by the snow (if necessary construct a lateral canopy).
1 Construct a large canopy. 2 Construct a pedestal.
Install the unit high enough off the ground to prevent burying in snow.
Make sure there is enough room to do the installation
Set the outlet side at a right angle to the direction of the wind.
Strong wind
Blown air Strong wind
3 Prepare a water drainage channel around the foundation, to
drain waste water from around the unit.
4 If the water drainage of the unit is not easy, please build up the
unit on a foundation of concrete blocks, etc. (the height of the foundation should be maximum 150 mm).

PRECAUTIONS ON INSTALLATION

Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installation.
In accordance with the foundation drawing in the figure, fix the unit securely by means of the foundation bolts. (Prepare four sets of M12 foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their length are 20 mm from the foundation surface.
AC C
B
240 955 240
1435
A Discharge side B Bottom view (mm) C Drain hole
345
380
20
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
4
Page 8

Installation method for prevention of falling over

If it is necessary to prevent the unit from falling over, install as shown in the figure.
prepare all 4 wires as indicated in the drawing
unscrew the top plate at the 4 locations indicated A and B
put the screws through the nooses and screw them back tight
(B) In case of stacked installation
1. In case obstacles exist in front of the outlet side.
A
AA
B
C
A Location of the 2 fixation holes on the front side of the unit B Location of the 2 fixation holes on the rear side of the unit C Wires: field supply

Installation servicing space

The numerical figures used in the figures represent the dimensions in mm.
(Refer to "Precautions on installation" on page 4)
Precaution (A) In case of non-stacked installation (See figure 1)
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
Obstacle is present
In these cases, close the
1
bottom of the installation frame to prevent the discharged air from being bypassed
In these cases, only
2
2 units can be installed.
This situation is not allowed
100
1000
2. In case obstacles exist in front of the air inlet.
A
100
300
Do not stack more than one unit. About 100 mm is required as the dimension for laying the upper unit's
drain pipe. Get the portion A sealed so that air from the outlet does not bypass.
(C) In case of multiple-row installation (for roof top use, etc.)
1. In case of installing one unit per row.
100
2000
200
1000
2. In case of installing multiple units (2 units or more) in lateral connection per row.
NOTE
Installation manual
5
Minimum distance B1 in figure 1 mentions the space required for correct operation of the unit. Required space for servicing though is 300 mm.
L
A
3000
H
600
1500
Relation of dimensions of H, A and L are shown in the table below.
L A
LH
H<L Installation not allowed
0<L1/2H 250 1/2H<L 300
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 9

TYPICAL APPLICATION EXAMPLES

Application 2

The application examples given below are for illustration purposes only.

Application 1

Cooling and heating application (without room thermostat)
FCU1
M
RT1
DC
FCU2
M
RT2
7
FCU3
M
RT3
(field supply)
(field supply)
2 3 4 51
56
1 Reversible heat pump 7 Bypass valve 2 Plate heat exchanger FCU1..3 Fan coil unit 3 Expansion vessel 4 Pump DC Digital controller 5 Shut-off valve RT1..3 Room thermostat 6 Motorised valve (field supply)
The digital controller (DC) is installed indoors and allows the user to turn the unit (1) ON or OFF, to select between cooling and heating mode (only in case of a heat pump model) and to set the water temperature. When the unit is turned on, it will provide water at the set temperature to the fan coil units (FCU1..3).
Cooling and heating application with a room thermostat suitable for cooling/heating changeover connected to the unit.
T
62 3 4 51
7
FCU1
FCU2
FCU3
1 Reversible heat pump 7 Shut-off valve 2 Plate heat exchanger FCU1..3 Fan coil unit 3 Expansion vessel 4 Pump T Room thermostat or 5 Shut-off valve 6 Collector (field supply)
(field supply)
room thermostat with cooling/heating switch (field supply)
Pump operation and heating and cooling (cooling and heating
application with a room thermostat suitable for cooling/heating changeover connected to the unit)
According to the season, the customer will select cooling or heating on the room thermostat (T). This selection is not possible by operating the user interface.
When cooling/heating is requested by the room thermostat (T), the pump will start operating and the unit will switch to “cooling mode”/”heating mode”. The unit will start operating to achieve the target leaving cold/hot water temperature.
The ON/OFF setting of the heating/cooling operation is done by the room thermostat and cannot be done by the user interface on the unit.
Make sure to connect the thermostat wires to the correct terminals (see "Connection of the thermostat cable" on
page 13).
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
6
Page 10

OVERVIEW OF THE UNIT

O
t
R13T
t >
t >

Opening the unit

22
1
3
Door 1 gives acces to the compressor compartment and electrical parts Door 2 gives acces to the electrical parts of the hydraulic compartment Door 3 gives acces to the hydraulic compartment
Switch off all power supply — i.e. unit power supply — before removing doors 1 and 2.
Parts inside the unit can be hot.

Main components

Hydraulic compartment (door 3)
3. Heat exchanger
4. Expansion vessel (10 l)
5. Refrigerant liquid connection
6. Refrigerant gas connection
7. Shut-off valves
The shut-off valves on the water inlet connection and water outlet connection allow isolation of the unit water circuit side from the residential water circuit side. This facilitates draining and filter replacement of the unit.
8. Water inlet connection
9. Water outlet connection
10. Drain and fill valve
11. Water filter
The water filter removes dirt from the water to prevent damage to the pump or blockage of the evaporator. The water filter must be cleaned on a regular base. See "Maintenance" on page 22.
12. Manometer The manometer allows readout of the water pressure in the
water circuit.
13. Flow switch The flow switch checks the flow in the water circuit and protects
the heat exchanger against freezing and the pump against damage.
14. Pump The pump circulates the water in the water circuit.
15. Pressure relief valve The pressure relief valve prevents excessive water pressure in
the water circuit by opening at 3 bar and discharging some water.
15
14
7
9 8
7
11
2
10
5
13
1. Air purge valve
Remaining air in the water circuit will be automatically removed via the air purge valve.
2. Temperature sensors Three temperature sensors determine the water and refrigerant
temperature at various points in the water circuit.
1
12
4
2 3
6
2
Functional diagram of hydraulic compartment (door 3)
15 6
1 Manometer 8 Flow switch 2 Air purge valve 9 Drain/fill valve 3 Expansion vessel 10 Filter 4 Pressure relief valve 11 Shut-off valve water inlet with 5 Pump 6 Shut-off valve water
outlet
7 Heat exchanger
3
24
R11T R13T R14T
1178910
drain valve
Temperature sensors
Installation manual
7
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 11
Switch box main components (door 2)

Water pipework

A B
A
K4M
A1P
B
3
10
S12M
12
1. Main PCB
The main PCB (Printed Circuit Board) controls the functioning of the unit.
2. Ter minal blocks
The terminal blocks allow easy connection of field wiring.
3. Cable tie mountings
The cable tie mountings allow to fix the field wiring with cable ties to the switch box to ensure strain relief.
4. PCB fuse FU1
5. DIP switch SS2
The DIP switch SS2 provides 4 toggle switches to configure certain installation parameters.
6. Pump fuse FU2 (in line fuse)
7. Pump relay K4M
8. Transformer TR1
9. A4P
Remote alarm input/output PCB (only for installations with remote alarm kit).
10. Conduit hole to pass through the main power supply cable to the
compressor module.
11. Conduit hole to pass through the thermistor cable and user
interface cable (and benefit kWh rate cable).
12. Conduit hole to pass through the installation power supply
wiring.
13. Conduit hole to pass through optional input/output PCB
connection wiring.
81467
TR1
5 9
A4P
3
13
2
3 11
In case of a power supply failure or pump operating failure, drain the system (as suggested in the figure below).
A
<A
When water is at standstill inside the system, freezing up is very likely to happen and damaging the system in the process.
Checking the water circuit
The units are equipped with a water inlet and water outlet for connection to a water circuit. This circuit must be provided by a licensed technician and must comply with all relevant European and national regulations.
The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion of the water piping.
Before continuing the installation of the unit, check the following points:
The maximum water pressure is 3 bar.
Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance. A drain valve is provided in the unit to drain the water from the
unit water system.
Air vents must be provided at all high points of the system. The vents should be located at points which are easily accessible for servicing. An automatic air purge is provided inside the unit. Check that this air purge valve is not tightened too much so that automatic release of air in the water circuit remains possible.
Ta ke care that the components installed in the field piping can withstand the water pressure.
NOTE
The electrical wiring diagram can be found on the inside of the switch box cover.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
8
Page 12
Checking the water volume and expansion vessel
40 l
pre-pressure
The unit is equipped with an expansion vessel of 10 litre which has a default pre-pressure of 1 bar.
To assure proper operation of the unit, the pre-pressure of the expansion vessel might need to be adjusted and the minimum and maximum water volume must be checked.
1 Check that the total water volume in the installation, excluding
the internal water volume of the unit, is 20 l minimum. Refer to
"Technical specifications" on page 25 to know the internal water
volume of the unit.
Operation range
Calculating the pre-pressure of the expansion vessel
The pre-pressure (Pg) to be set depends on the maximum installation height difference (H) and is calculated as below:
Pg=(H/10+0.3) bar
Checking the maximum allowed water volume
To determine the maximum allowed water volume in the entire circuit, proceed as follows:
1 Determine for the calculated pre-pressure (Pg) the
corresponding maximum water volume using the graph below.
2 Check that the total water volume in the entire water circuit is
lower than this value.
If this is not the case, the expansion vessel inside the unit is too small for the installation.
46
20 l
H2O
10
500
22 503525
A Outdoor temperature °C DB °C dry bulb LEWT Leaving evaporator water temperature LCWT Leaving condenser water temperature
–15
35
20 l
H2O
7
00
–5
40 l
In most applications this minimum water volume will have a satisfying result.
In critical processes or in rooms with a high heat load though, extra water volume might be required (40 l).
2 Using the table below, determine if the expansion vessel pre-
pressure requires adjustment.
3 Using the table and instructions below, determine if the total
water volume in the installation is below the maximum allowed water volume.
Installation height difference
(a)
7 m
>7 m
(a) Installation height difference: height difference (m) between the highest point of
the water circuit and the unit. If the unit is located at the highest point of the installation, the installation height is considered 0 m.
280 l (EWAQ) >280 l (EWYQ)
No pre-pressure adjustment required.
Actions required:
• pre-pressure must be increased, calculate according to "Calculating the
pre-pressure of the expansion vessel"
• check if the water volume is lower than maximum allowed water volume (use graph below)
Water volume
Actions required:
• pre-pressure must be decreased, calculate according to "Calculating the
pre-pressure of the expansion vessel"
• check if the water volume is lower than maximum allowed water volume (use graph below)
Expansion vessel of the unit too small for the installation.
2.5
2
1.5
1
pre-pressure [bar]
0.5
0.3
20
100
500
150 200 250 300 350 400 450
maximum water volume [l]
= pre-pressure = maximum water volume
Example 1
The unit is installed 5 m below the highest point in the water circuit. The total water volume in the water circuit is 100 l.
In this example, no action or adjustment is required.
Example 2
The unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 350 l.
Result:
Since 350 l is higher than 280 l, the pre-pressure must be decreased (see table above).
The required pre-pressure is: Pg = (H/10 + 0.3) bar = (0/10 + 0.3) bar = 0.3 bar
The corresponding maximum water volume can be read from the graph: approximately 410 l.
Since the total water volume (350 l) is below the maximum water volume (410 l), the expansion vessel suffices for the installation.
Setting the pre-pressure of the expansion vessel
When it is required to change the default pre-pressure of the expansion vessel (1 bar), keep in mind the following guidelines:
Use only dry nitrogen to set the expansion vessel pre-pressure.
Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system. Therefore, the pre-pressure should only be adjusted by a licensed installer.
Installation manual
9
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 13
Connecting the water circuit
Water connections must be made in accordance with the outlook diagram delivered with the unit, respecting the water in- and outlet.
Be careful not to deform the unit piping by using excessive force when connecting the piping. Deformation of the piping can cause the unit to malfunction.
If air, moisture or dust gets in the water circuit, problems may occur. Therefore, always take into account the following when connecting the water circuit:
Use clean pipes only.
Hold the pipe end downwards when removing burrs.
Cover the pipe end when inserting it through a wall so that no
dust and dirt enter.
Use a good thread sealant for the sealing of the connections. The sealing must be able to withstand the pressures and temperatures of the system.
When using non-brass metallic piping, make sure to insulate both materials from each other to prevent galvanic corrosion.
Because brass is a soft material, use appropriate tooling for connecting the water circuit. Inappropriate tooling will cause damage to the pipes.
The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion of the water piping.
Never use Zn-coated parts in the water circuit. Excessive corrosion of these parts may occur as copper piping is used in the unit's internal water circuit.
Protecting the water circuit against freezing
Frost can damage the unit. For this reason, in colder climates the water circuit can be protected by means of a heater tape option (OP10) or by adding glycol to the water.
In case of heater tape
Check that the unit has the option heater tape installed (factory mounted). Units with option heater tape have the possibility to install an extra heatertape to protect the waterpipe outside the unit against freezing. (Field supply, maximum 200 W, connections must be made on terminals 5/6 inside the switchbox).
For the heater tape to operate, power to the unit must be provided and the main isolator switch must be on. For this reason never disconnect power and never turn off the main isolator switch for a long time during cold periods!
In case of glycol
Depending on the expected lowest outdoor temperature, make sure the water system is filled with a weight concentration of glycol as mentioned in the table below.
Minimum
outdoor temperature
–5°C 10% 15% –10°C 25% 25% –15°C 35% 35%
Ethylene glycol Propylene glycol
Corrosion of the system due to presence of glycol
Uninhibited glycol will turn acidic under the influence of oxygen. This process is accelerated by presence of copper and at higher temperatures. The acidic uninhibited glycol attacks metal surfaces and forms galvanic corrosion cells that cause severe damage to the system.
It is therefore of extreme importance:
that the water treatment is correctly executed by a qualified water specialist;
that a glycol with corrosion inhibitors is selected to counteract acids formed by the oxidation of glycols;
that no automotive glycol is used because their corrosion inhibitors have a limited lifetime and contain silicates which can foul or plug the system;
that galvanized piping is not used in glycol systems since its presence may lead to the precipitation of certain components in the glycol’s corrosion inhibitor;
that it has to be made sure the glycol is compatible with the used materials in the system.
NOTE
Be aware of the hygroscopic property of glycol: it absorbs moisture from its environment.
Leaving the cap off the glycol container causes the concentration of water to increase. The glycol concentration is then lower than assumed. And in consequence, freezing can happen after all.
Preventive actions must be taken to ensure minimal exposure of the glycol to air.
Also refer to "Checks before initial start-up" on page 16.

Charging water

1 Connect the water supply to a drain and fill valve (see "Main
components" on page 7).
2 Make sure the automatic air purge valve is open (at least 2
turns).
3 Fill with water until the manometer indicates a pressure of
approximately 2.0 bar. Remove air in the circuit as much as possible using the air purge valves. Air present in the water circuit might cause malfunctioning.
NOTE
During filling, it might not be possible to remove all air in the system. Remaining air will be removed through the automatic air purge valves during first operating hours of the system. Additional filling with water afterwards might be required.
The water pressure indicated on the manometer will vary depending on the water temperature (higher pressure at higher water temperature).
However, at all times water pressure should remain above 0.3 bar to avoid air entering the circuit.
The unit might dispose some excessive water through the pressure relief valve.

Piping insulation

The complete water circuit, inclusive all piping, must be insulated to prevent condensation during cooling operation and reduction of the cooling and heating capacity as well as prevention of freezing of the outside water piping during winter time. The thickness of the sealing materials must be at least 13 mm with λ = 0.036 in order to prevent freezing on the outside water piping.
If the temperature is higher than 30°C and the humidity is higher than RH 80%, then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the surface of the sealing.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
10
Page 14

Field wiring

WARNING
Switch off the power supply before making any
All field wiring and components must be installed by a
The field wiring must be carried out in accordance
Be sure to use a dedicated power supply. Never use a
Be sure to establish an earth. Do not earth the unit to
Be sure to install an earth leakage protector (30 mA).
connections.
licensed electrician and must comply with relevant European and national regulations.
with the wiring diagram supplied with the unit and the instructions given below.
power supply shared by another appliance.
a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
Failure to do so may cause electrical shock.
Overview
The illustration below gives an overview of the required field wiring between several parts of the installation. Refer also to "Typical
application examples" on page 6.
C
I
2
B
1
4
D
T
Precautions on electrical wiring work
High voltage
To avoid electrical shock, make sure to disconnect the power supply 1 minute or more before servicing the electrical parts. Even after 1 minute, always measure the voltage at the terminals of main circuit capacitors or electrical parts and, before touching, make sure that those voltages are 50 V DC or less.
Use only copper wires.
Never squeeze bundled cables into a unit.
Fix cables so that cables do not make contact with the pipes
(especially on high pressure side).
Secure the electrical wiring with cable ties as shown in figure 2 so that it does not come in contact with the piping, particularly on the high-pressure side.
Make sure no external pressure is applied to the terminal connectors.
For W1 Make sure to connect power supply cables in normal phase. If
connected in reverse phase, the remote controller indicates "U1" and the equipment cannot operate. Change any two of the three power supply cables (L1, L2, L3) to correct phase.
As this unit is equipped with an inverter, installing a phase advancing capacitor not only will deteriorate power factor improvement effect, but also may cause capacitor abnormal heating accident due to high-frequency waves. Therefore, never install a phase advancing capacitor.
When installing the earth leakage circuit breaker make sure that it is compatible with the inverter (resistant to high frequency electrical noise) to avoid unnecessary opening of the earth leakage circuit breaker.
NOTE
The earth leakage circuit breaker must be a high­speed type breaker of 30 mA (<0.1 s).
Installation manual
11
A 3
A Single power supply for unit B Unit C User interface D Room thermostat (field supply, optional)
Required number of
AC/
conductors
Item Description
1 Power supply cable for unit AC 2+GND (V3)
2 User interface cable DC 2 100 mA 3 Benefit kWh rate power supply
cable (voltage free contact)
4 Room thermostat cable AC 3 or 4 100 mA
(a) Refer to nameplate on the unit (b) Minimum cable section 0.75 mm
DC
4+GND (W1)
DC 2 100 mA
2
Maximum running current
(a)
(b)
(b)
(b)
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit (on the inside of the switch box cover). The abbreviations used are listed below.
Door 1 compressor compartment and electrical parts
V3 models only
A1P.................. Main PCB
A2P.................. Inverter PCB
A3P.................. Noise filter PCB
A4P.................. PCB
BS1~BS4.........Push button switch
C1~C4 .............Capacitor
DS1..................DIP switch
E1HC............... Crankcase heater
F1U,F3U,F4U ..Fuse 6.3 A T 250 V
F6U.................. Fuse 5.0 A T 250 V
H1P~H7P ........Orange LED service monitor (A2P)
H2P: prepare, test = flickering
H2P: malfunction detection = light up
HAP (A1P)....... Green LED service monitor
K1R..................Magnetic relay (Y1S)
K4R..................Magnetic relay (E1HC)
K10R,K11R......Magnetic relay
L1R.................. Reactor
M1C................. Motor (compressor)
M1F .................Motor (upper fan)
M2F .................Motor (lower fan)
PS.................... Switching power supply
R1,R2 ..............Resistor
R1T.................. Thermistor (air)
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 15
R2T.................. Thermistor (discharge)
R3T.................. Thermistor (suction)
R4T.................. Thermistor (heat exchanger)
R5T.................. Thermistor (heat exchanger middle)
R6T.................. Thermistor (liquid)
R10T................ Thermistor (fin)
RC ...................Signal receiver circuit
S1NPH.............Pressure sensor
S1PH ...............High pressure switch
TC.................... Signal transmission circuit
V1R..................Power module
V2R,V3R..........Diode module
V1T.................. IGBT
X1M .................Power supply terminal strip
Y1E.................. Electronic expansion valve
Y1S.................. Solenoid valve (4-way valve)
Z1C~Z3C.........Noise filter (ferrite core)
Z1F~Z4F.......... Noise filter
W1 models only
A1P.................. PCB
A2P.................. Inverter PCB
A3P.................. Noise filter PCB
BS1~BS4.........Push button switch
C1~C4 .............Capacitor
DS1..................DIP switch
E1HC............... Crankcase heater
F1U,F2U.......... Fuse 31.5 A 500 V
F3U~F6U.........Fuse 6.3 A T 250 V
F7U.................. Fuse 5.0 A T 250 V
H1P~H7P ........Orange LED service monitor (A1P)
HAP (A1P)....... Green LED service monitor
HAP (A2P)....... Green LED service monitor
K1M,K2M......... Magnetic contactor
K1R (A1P) .......Magnetic relay (Y1S)
K1R (A2P) .......Magnetic relay
K2R (A1P) .......Magnetic relay (Y2S)
K3R (A1P) .......Magnetic relay (E1HC)
L1R~L3R .........Reactor
L4R.................. Reactor for outdoor fan motor
M1C................. Motor (compressor)
M1F .................Motor (upper fan)
M2F .................Motor (lower fan)
PS.................... Switching power supply
R1~R4 .............Resistor
R1T.................. Thermistor (air)
R2T.................. Thermistor (discharge)
R3T.................. Thermistor (suction)
R4T.................. Thermistor (heat exchanger)
R5T.................. Thermistor (heat exchanger middle)
R6T.................. Thermistor (liquid)
R7T.................. Thermistor (fin)
S1NPH.............Pressure sensor
S1PH ...............High pressure switch
V1R,V2R..........Power module
V3R..................Diode module
X1M .................Terminal strip
X6A,X77A........ Optional connectors
Y1E.................. Electronic expansion valve
Y1S.................. Solenoid valve (4-way valve)
Y3S.................. Solenoid valve
Z1C~Z9C.........Noise filter (ferrite core)
Z1F~Z4F.......... Noise filter
Door 2 electrical parts of the hydraulic compartment
A11P ................Main PCB
A12P ................User interface PCB
A4P ..................Remote alarm PCB (EKRP1HB)
E6H..................Expansion vessel heater
E7H..................Water piping heater
E8H..................Heatertape (field supply max. 200 W)
FU1 ..................Fuse 3.15 A T 250 V for PCB
FU2 ..................Fuse 5 A T 250 V
FuR,FuS...........Fuse 5 A 250 V for remote alarm PCB
K4M..................Pump relay
K9M..................Heaters relay
M1P..................Pump
PHC1 ...............Optocoupler input circuit
Q1DI.................Earth leakage protector
R11T ................Outlet water heat exchanger thermistor
R13T ................Refrigerant liquid side thermistor
R14T ................Inlet water thermistor
S1L...................Flow switch
S12M................Main switch
S2S ..................Benefit kWh rate power signal
S3S ..................Remote heating signal
S4S ..................Remote cooling signal
S5S ..................Remote ON/OFF signal
SS1,SS2 ..........DIP switch
TR1 ..................Transformer 24 V for PCB
V1S,V2S ..........Spark suppression 1, 2
X2M..................Terminal strips
X1Y,X2Y ...........Connector
When finishing cables inside the unit, make sure the cables do not touch the pump or refrigerant piping.
Field wiring guidelines
Do not operate the unit by shortcircuiting protection devices S1L and S12M.
Most field wiring on the unit is to be made on the terminal block or the main switch inside the switch box. To gain access to the terminal block or main switch, remove the switch box service panel (door 2).
Cable tie mountings are provided at the bottom of the switch box. Fix all cables using cable ties.
Secure the wiring in the order shown below.
Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely(see
figure 2).
Follow the electric wiring diagram for electrical wiring works (the electric wiring diagrams are located on the rear side of doors 1 and 2).
Form the wires and fix the cover firmly so that the cover may be fit in properly.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
12
Page 16
Precautions on wiring of power supply
For connection of the field wiring to the mainswitch, use the instruction as described below.
2
3
For other connections, use a round crimp-style terminal for connection to the power supply terminal board. In case it cannot be used due to unavoidable reasons, be sure to observe the following instruction (e.g. connection of the earth wire).
1 Round pressure terminal 2 Cut out section 3 Cup washer
123
- Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause overheating.)
- When connecting wires of the same gauge, connect them
according to the below figure.
1
NOTE
The earth leakage circuit breaker must be a high-speed type breaker of 30 mA (<0.1 s).
For V3 model: Equipment complying with EN/IEC 61000-3-12 (European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16 A and 75 A per phase.)
The wiring diagram can be found on the inside of the front plate of the unit.
Connection of the thermostat cable
Connection of the thermostat cable depends on the application. See also "Typical application examples" on page 6.
Thermostat requirements
Contact voltage: 230 V.
Procedure
1 Connect the thermostat cable to the appropriate terminals as
shown on the wiring diagram.
Heating/cooling thermostat Remote ON/OFF
Terminal block
HCthN
4
12
Terminal block
HCswN
4
12
Use the correct screwdriver to tighten the terminal screws. Small screwdrivers can damage the screw head and prevent appropriate tightening.
Over-tightening the terminal screws can damage the screws.
See the table below for tightening torques for the terminal
screws.
M4 (X1M) 1.2~1.8 M5 (X1M) 2.0~3.0 M5 (EARTH) 3.0~4.0
Tightening torque (N•m)
Attach an earth leakage circuit breaker and fuse to the power supply line.
In wiring, make certain that prescribed wires are used, carry out complete connections, and fix the wires so that outside forces are not applied to the terminals.
Specifications of standard wiring components
V3
1~ 50 Hz
230 V
L1 L3
1 2
3N~ 50 Hz
L2
W1
400 V
1 Earth leakage circuit
breaker
2 Fuse 3 Main switch
H C
2 Fix the cable with cable ties to the cable tie mountings to ensure
strain relief.
NOTE
When a room thermostat is connected to the unit, the heating and cooling schedule timers are never available. Other schedule timers are not affected. For more information on the schedule timers, refer to the operation manual.
When a room thermostat is connected to the unit, and the = button or o button is pressed, the centralised control indicator e will flash to indicate that the room thermostat has priority and controls on/off operation and change over operation.
S12M
3
L1 L3L2
X1MX1M
Minimum circuit amps (MCA) Recommended field fuse 32 A 20 A Wire type Size Wiring size must comply with the
Wire type of wiring between the units H05VV-U4G2.5
Installation manual
(b)
(a) Stated values are maximum values. (b) Only in protected pipes, use H07RN-F when protected pipes are not used.
(a)
V3 W1
28.2 13.5
H05VV-U3G H05VV-U5G
applicable local and national code
13
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 17
The following table summarizes the required configuration and thermostat wiring at the terminal block in the switch box. Pump operation is listed in the third column. The three last columns indicate whether the following functionality is available on the user interface (UI) or handled by the thermostat (T):
• space heating or cooling on/off (o)
• heating/cooling changeover (=)
• heating and cooling schedule timers (pr)
Pump
Thermostat Configuration
No thermostat wiring: on when unit is onUI UI UI
Terminal block
HCN
12
Thermostat with heating/cooling switch
Remote ON/OFF switch
wiring: on when
Terminal block
HCthN
12
H C
wiring: on when
Terminal block
HCswN
12
operation
4
heating request or cooling request by room
4
thermostat
remote on
4
th =
Thermostat contact
C =
Cooling contact
H =
Heating contact
N =
Neutral
sw =
Switch
oooo==== pppprr
TT—
T——
rr
Connection to a benefit kWh rate power supply
Electricity companies throughout the world work hard to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates,
Wärmepumpentarif in Germany and Austria, ... .
This equipment allows for connection to such benefit rate power supply delivery systems.
Consult with the electricity company acting as provider at the site where this equipment is to be installed to know whether it is appropriate to connect the equipment in one of the benefit kWh rate power supply delivery systems available, if any.
When the equipment is connected to such benefit kWh rate power supply, the electricity company is allowed to:
interrupt power supply to the equipment for certain periods of time;
demand that the equipment only consumes a limited amount of electricity during certain periods of time.
The unit is designed to receive an input signal by which the unit switches into forced off mode. At that moment, the unit compressor will not operate.
Warnings for a benefit kWh rate power supply like illustrated
below as type 1
If the benefit kWh rate power supply is of the type that power supply is not interrupted, then control of the heaters is still possible.
For the different possibilities of controlling heaters at moments that benefit kWh rate is active, refer to
"[D] Benefit kWh rate power supply" on page 20.
If heaters must be controlled at moments that the benefit kWh rate power supply is off, then these heaters have to be connected to a separate power supply.
During the period that the benefit kWh rate is active and power supply is continuous, then stand-by power consumption is possible (PCB, controller, pump, ...).
for a benefit kWh rate power supply like illustrated below as types 2 or 3
Benefit kWh rate power supplies that completely shut power supply are not allowed for OP10 models because of the heater tape that would not be powered.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
14
Page 18
Possible types of benefit kWh rate power supply
Possible connections and requirements to connect the equipment to such power supply are illustrated in the figure below:
[D-01]=1
LN
1 2
S2S
[D-01]=2
LN
1 2
S2S
Benefit kWh rate power supplies that completely shut power supply like illustrated above as types 2 and 3 are not allowed for this application because of the water freeze prevention that would not be powered.
When connecting the equipment to a benefit kWh rate power supply, change field settings [D-01] and both [D-01] and [D-00] in case the benefit kWh rate power supply is of the type that power supply is not interrupted (like illustrated above as type 1). Refer to
"[D] Benefit kWh rate power supply" on page 20 of
chapter "Field settings".
43
LN
1 2
1 2
3
3
S2S
LN
S2S
1 2
43
1 2
3
4
X2M17 18
A1P
X40A
LN
S2S
LN
S2S
43
43
EWAQ/EWYQ
1 Benefit kWh rate power supply box 2 Receiver controlling the signal of the electricity company 3 Power supply to unit 4 Voltage free contact
Allowed for all models
0
Not allowed for OP10 models, allowed for other models
X
When the unit is connected to a benefit kWh rate power supply, the voltage free contact of the receiver controlling the benefit kWh rate signal of the electricity company must be connected to clamps 17 and 18 of X2M (as illustrated in the figure above). When parameter [D-01]=1 at the moment that the benefit kWh rate signal is sent by the electricity company, that contact will open and
the unit will go in forced off mode When parameter [D-01]=2 at the moment that the benefit kWh rate signal is sent by the electricity company, that contact will close and
the unit will go in forced off mode
type 1
The benefit kWh rate power supply is of the type that power supply is not interrupted.
type 2 and 3
The benefit kWh rate power supply is of the type that power supply will be interrupted after elapse of time or is interrupted immediately.
(1)
.
(2)
.
NOTE
If the benefit kWh rate power supply is of the type that power supply is not interrupted, the unit will be forced to off.

Installation of the digital controller

The unit is equipped with a digital controller offering a user-friendly way to set up, use and maintain the unit. Before operating the controller, follow this installation procedure.
Wiring specifications
Wire specification Val ue
Type 2 wire
Section
Maximum length 500 m
NOTE
The wiring for connection is not included.
0.75-1.25 mm
2
Mounting
The digital controller, delivered in a kit, has to be mounted indoors.
1 Remove the front part of the digital controller.
Insert a slotted screwdriver into the slots (1) in the rear part of the digital controller, and remove the front part of the digital controller.
2 Fasten the digital controller on a flat
surface.
NOTE
Be careful not to distort the shape of the lower part of the digital controller by over tightening the mounting screws.
1
(1) When the signal is released again, the voltage free contact will close and
the unit will restart operation. It is therefore important to leave the auto restart function enabled. Refer to "[3] Auto restart" on page 19.
(2) When the signal is released again, the voltage free contact will open and
the unit will restart operation. It is therefore important to leave the auto restart function enabled. Refer to "[3] Auto restart" on page 19.
Installation manual
15
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 19
3 Wire the unit.

START-UP AND CONFIGURATION

6
16a
16a
16
1
16
1
2
P1P2
P1P2
3
4 5
1 Unit 2 Rear part of the digital controller 3 Front part of the digital controller 4 Wired from the rear 5 Wired from the top 6 Notch the part for the wiring to pass through with nippers, etc.
Connect the terminals on top of the front part of the digital controller and the terminals inside the unit (P1 to 16, P2 to 16a).
NOTE
When wiring, run the wiring away from the power supply wiring in order to avoid receiving electric noise (external noise).
Peel the shield for the part that has to pass through the inside of the digital controller case ( l ).
4 Reattach the upper part of the digital controller.
The unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and user expertise.
It is important that all information in this chapter is read sequentially by the installer and that the system is configured as applicable.
Pump operation configuration
NOTE
To set the pump speed, refer to "Setting the pump
speed" on page 17.

Initial start-up at low outdoor ambient temperatures

During initial start-up and when water temperature is low, it is important that the water is heated gradually. Failure to do so may result in cracking of concrete floors due to rapid temperature change. Please contact the responsible cast concrete building contractor for further details.
To do so, the lowest leaving water set temperature can be decreased to a value between 25°C and 37°C by adjusting the field setting [9-01] (heating set point lower limit). Refer to "Field settings" on
page 18.

Pre-operation checks

Checks before initial start-up
Switch off the power supply before making any connections.
Be careful not to pinch the wiring when attaching.
First begin fitting from the clips at the bottom.
After the installation of the unit, check the following before switching on the circuit breaker:
1 Field wiring
Make sure that the field wiring has been carried out according to the instructions and guidelines as described in the chapter
"Field wiring" on page 11, according to the wiring diagrams and
according to European and national regulations.
1
2 Fuses or protection devices
Check that the fuses or the locally installed protection devices are of the size and type specified in the chapter "Technical
specifications" on page 25. Make sure that neither a fuse nor a
protection device has been bypassed.
3 Earth wiring
Make sure that the earth wires have been connected properly and that the earth terminals are tightened.
4 Internal wiring
Visually check the switch box on loose connections or damaged electrical components.
5 Fixation
Check that the unit is properly fixed, to avoid abnormal noises and vibrations when starting up the unit.
6 Damaged equipment
Check the inside of the unit on damaged components or squeezed pipes.
7 Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a refrigerant leak, call your local dealer.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
16
Page 20
8 Power supply voltage
Check the power supply voltage on the local supply panel. The voltage must correspond to the voltage on the identification label of the unit.
9 Air purge valve
Make sure the air purge valve is open (at least 2 turns).
10 Pressure relief valve
Check if the unit is completely filled with water by operating the pressure relief valve. It should purge water instead of air.
11 Shut-off valves
Make sure that the shut-off valves are fully open.
In case of possible reversal of phases after a momentary black out of power and the power goes on and off while the product is operating, install a reversed phase protection circuit on site. Such situation is not unimaginable when using generators. Running the product in reversed phase can break the compressor and other parts.
For a missing phase in case of W1 units, "E7" or "U2" will be
displayed on the remote controller of the indoor unit. Operation will be impossible with either one of these phenomena. If this happens, turn off the power, re-check the wiring and switch the position of two of the three electrical wires. (If operation is not possible, do not under any circumstances force the electromagnetic contactor on.)
Operating the system with closed valves will damage the pump!
12 Protection against freezing
Make sure that in colder climates (ambient temperature can become lower than 0°C) the unit is protected against freezing by means of a heater tape or by adding glycol to the water.
Also refer to "Protecting the water circuit against freezing" on
page 10.
13 Mainswitch handle
Mount the mainswitch handle and fasten screw in order to power up the unit.
14 Protection cap(s)
Protection cap(s) must be mounted on the right side of the mainswitch after connection of the field wiring.

Powering up the unit

1 Switch on the main switch on the unit. 2 When power supply to the unit is turned on, "88" is displayed on
the user interface during its initialisation, which might take up to 30 seconds. During this process the user interface cannot be operated.
Failure diagnosis at the moment of first installation
In case nothing is displayed on the remote controller (the current set temperature does not display), check for any of the following abnormalities before you can diagnose possible malfunction codes.
Disconnection or wiring error (between power supply and
unit, between unit and remote controller).
The fuse on the outdoor unit PCB may have run out.
If the remote controller shows "E3", "E4" or "L8" as an error code,
there is a possibility that either the stop valves are closed, or that air inlet or air outlet are blocked.
If the error code "U2" is displayed on the remote controller, check for voltage imbalance.
If the error code "L4" is displayed on the remote controller, it is possible that air inlet or air outlet are blocked.
The reversed phase protection detector of this product only works during the initialisation stage after a power reset. The reversed phase protection detector is designed to stop the product in case of an abnormality when the product is started up.
When the reversed phase protection circuit forced the unit to
stop, check if all phases are existing. If this is the case, shut off the power supply to the unit and replace two of three phases. Turn on power again and start the unit.
Reversed phase detection is not performed while the product
is operating.

Setting the pump speed

The pump speed can be selected on the pump (see "Main
components" on page 7).
The default setting is high speed (I). If the water flow in the system is too high (e.g., noise of running water in the installation) the speed can be set to low speed (II).
NOTE
The available external static pressure (ESP, expressed in kPa) in function of the water flow (l/min) is shown in the graph below.
The speed dial on the pump indicates 3 speed settings. However, only 2 speed settings exist: low speed and high speed. The indicated medium speed setting on the speed dial is equal to low speed.
70
65
60
55
50
45
40
35
ESP [kPa]
30
25
20
15
10
5
0
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58
[l/min]
II
II
I
I
Installation manual
17
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 21

Field settings

The unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and user demand. Thereto, a number of so called field settings are available. These field settings are accessible and programmable through the user interface.
Each field setting is assigned a 3-digit number or code, for example [5-03], which is indicated on the user interface display. The first digit [5] indicates the 'first code' or field setting group. The second and third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given under "Field
settings table" on page 21. In this same list, we provided for 2
columns to register the date and value of altered field settings at variance with the default value.
A detailed description of each field setting is given under "Detailed
description" on page 18.
Procedure
To change one or more field settings, proceed as follows.
3
1
2
Detailed description
[0] User permission level
If required, certain user interface buttons can be made unavailable for the user.
Three permission levels are defined (see the table below). Switching between level 1 and level 2/3 is done by simultaneously pressing buttons pfi and pfj immediately followed by simultaneously pressing buttons s and ba, and keeping all 4 buttons pressed for at least 5 seconds (in normal mode). Note that no indication on the user interface is given. When level 2/3 is selected, the actual permission level — either level 2 or level 3 — is determined by the field setting [0-00].
Permission level
Button
On/off button
Operation changeover button
Sanitary water heating button
Sanitary temperature adjust buttons
Temperature adjust buttons
Time adjust buttons
Programming button
Schedule timer enable/ disable button
Quiet mode button
Weather dependent set point button
Inspection/test operation button
o
h/c
w
wbi wbj
bgi bgj
pf
i
pf
j
<
pr
s
ba
z
1 2 3
operable operable operable
operable operable operable
– Not available –
– Not available –
operable operable operable
operable
operable
operable operable
operable
operable
operable
1 Press the z button for a minimum of 5 seconds to enter FIELD
SET MODE. The $ icon (3) will be displayed. The current selected field setting code is indicated ; (2), with the set value displayed to the right - (1).
2 Press the bgi button to select the appropriate field
setting first code.
3 Press the bgj button to select the appropriate field
setting second code.
4 Press the pfi button and pfj button to change
the set value of the select field setting.
5 Save the new value by pressing the pr button.
6 Repeat step 2 through 4 to change other field settings as
required.
7 When finished, press the z button to exit FIELD SET MODE
NOTE
Changes made to a specific field setting are only
.
stored when the pr button is pressed. Navigating to a new field setting code or pressing the z button will discard the change made.
NOTE
Before shipping, the set values have been set as shown under "Field settings table" on page 21.
When exiting FIELD SET MODE, "88" may be displayed on the user interface LCD while the unit initialises itself.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
18
Page 22
[1] Weather dependent set point (heat pump models only)
The weather dependent set point field settings define the parameters for the weather dependent operation of the unit. When weather dependent operation is active the water temperature is determined automatically depending on the outdoor temperature: colder outdoor temperatures will result in warmer water and vice versa. During weather dependent operation, the user has the possibility to shift up or down the target water temperature by a maximum of 5°C. See the operation manual for more details on weather dependent operation.
[1-00] Low ambient temperature (Lo_A): low outdoor temperature.
[1-01] High ambient temperature (Hi_A): high outdoor temperature.
[1-02] Set point at low ambient temperature (Lo_Ti): the target outgoing water temperature when the outdoor temperature equals or drops below the low ambient temperature (Lo_A). Note that the Lo_Ti value should be higher than Hi_Ti, as for colder outdoor temperatures (i.e. Lo_A) warmer water is required.
[1-03] Set point at high ambient temperature (Hi_Ti): the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature (Hi_A). Note that the Hi_Ti value should be lower than Lo_Ti, as for warmer outdoor temperatures (i.e. Hi_A) less warm water suffices.
T
t
Lo_Ti
+ 05
Shift value
Hi_Ti
Lo_A Hi_A T
T
Target water temperature
t
T
Ambient (outdoor) temperature
A
= Shift value
00
– 05
A
[3] Auto restart
When power returns after a power supply failure, the auto restart function reapplies the user interface settings at the time of the power supply failure.
NOTE
It is therefore recommended to leave the auto restart function enabled.
Note that with the function disabled the schedule timer will not be activated when power returns to the unit after a power supply failure. Press the pr button to enable the schedule timer again.
[3-00] Status: defines whether the auto restart function is turned ON (0) or OFF (1).
[9] Cooling and heating set points
The purpose of this field setting is to prevent the user from selecting a wrong (i.e., too hot or too cold) leaving water temperature. Thereto the heating temperature set point range and the cooling temperature set point range available to the user can be configured.
In case of a floor cooling application, it is important to limit the minimum leaving water temperature at cooling operation (field setting of parameter [9-03]) to 16~18°C to prevent condensation on the floor.
[9-00] Heating set point upper limit: maximum leaving water temperature for heating operation.
[9-01] Heating set point lower limit: minimum leaving water temperature for heating operation.
[9-02] Cooling set point upper limit: maximum leaving water temperature for cooling operation.
[9-03] Cooling set point lower limit: minimum leaving water temperature for cooling operation.
[9-04] Overshoot setting: defines how much the water temperature may rise above the setpoint before the compressor stops. This function is only applicable in heating mode.
[A] Quiet mode
This field setting allows to select the desired quiet mode. Two quiet modes are available: quiet mode A and quiet mode B.
In quiet mode A, priority is given to the unit operating quietly under all circumstances. Fan and compressor speed (and thus performance) will be limited to a certain percentage of the speed at normal operation. In certain cases, this might result in reduced performance.
In quiet mode B, quiet operation might be overridden when higher performance is required. In certain cases, this might result in less quiet operation of the unit to meet the requested performance.
[A-00] Quiet mode type: defines whether quiet mode A (0) or quiet mode B (2) is selected.
[A-01] Parameter 01: do not change this setting. Leave it set to its default value.
Do not set other values than the ones mentioned.
[C] Alarm output logic of EKRP1HB
[C-01] Defines the logic of the alarm output on the EKRP1HB remote alarm input/output PCB.
If [C-01]=0, the alarm output will be powered when an alarm occurs (default).
If [C-01]=1, the alarm output will not be powered when an alarm occurs. This field setting allows for distinction between detection of an alarm and detection of a power failure to the unit.
No power supply
[C-01] Alarm No alarm
0 (default) Closed output Open output Open output 1 Open output Closed output Open output
to unit
NOTE
If the benefit kWh rate power supply is of the type that power supply is interrupted, then always allow the auto restart function.
Installation manual
19
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 23
[D] Benefit kWh rate power supply
If [D-01]=1 or 2 and the benefit kWh rate signal of the electricity company is received, following devices will be switched off:
[D-00] Compressor
0 (default) Forced off 1Forced off 2Forced off 3Forced off
NOTE
[D-00] settings 1, 2 and 3 are only meaningful if the benefit kWh rate power supply is of the type that power supply is not interrupted,
[D-01] Defines whether or not the unit is connected to a benefit kWh rate power supply.
If [D-01]=0, the unit is connected to a normal power supply (default value).
If [D-01]=1 or 2, the unit is connected to a benefit kWh rate power supply. In this case the wiring requires specific installation like explained in "Connection to a benefit kWh rate power
supply" on page 14.
When parameter [D-01]=1 at the moment that the benefit kWh rate signal is sent by the electricity company, that contact will open and the unit will go in forced off mode
(1)
. When parameter [D-01]=2 at the moment that the benefit kWh rate signal is sent by the electricity company, that contact will close and the unit will go in forced off mode
(2)
.
[E] Unit information readout
[E-00] Readout of the software version (example: 23)
[E-01] Readout of the EEPROM version (example: 23)
[E-02] Readout of the unit model identification (example: 11)
[E-03] Readout of the liquid refrigerant temperature
[E-04] Readout of the inlet water temperature
NOTE
[E-03] and [E-04] readouts are not permanently refreshed. Temperature readouts are updated after looping through the field setting first codes again only.
(1) When the signal is released again, the voltage free contact will close and
the unit will restart operation. It is therefore important to leave the auto restart function enabled. Refer to "[3] Auto restart" on page 19.
(2) When the signal is released again, the voltage free contact will open and
the unit will restart operation. It is therefore important to leave the auto restart function enabled. Refer to "[3] Auto restart" on page 19.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
20
Page 24

Field settings table

First
Second
code
code
Setting name
0 User permission level
00 User permission level 3 2/3 1
1 Weather dependent set point
00 Low ambient temperature (Lo_A) –10 –20~5 1 °C
01 High ambient temperature (Hi_A) 15 10~20 1 °C
02 Set point at low ambient temperature (Lo_TI) 40 25~55 1 °C
03 Set point at high ambient temperature (Hi_TI) 25 25~55 1 °C
2 Not available
3 Auto restart
00 Status 0 (ON) 0/1
4 Not available
5 Not available
6 Not available
7 Not available
8 Not available
9 Cooling and heating set point ranges
00 Heating set point upper limit 55 37~55 1 °C
01 Heating set point lower limit 15 15~37 1 °C
02 Cooling set point upper limit 22 18~22 1 °C
03 Cooling set point lower limit 5 5~18 1 °C
04 Overshoot setting 2 1~4 1 °C
A Quiet mode
00 Quiet mode type 0 0/2
01 Parameter 01 3———
C Alarm output logic of EKRP1HB
00 Not applicable. Do not change the default value! 0
01 Output logic of the EKRP1HB remote alarm
input/output PCB
D Benefit kWh rate power supply
00 Not available
01 Unit connection to benefit kWh rate power supply 0 (OFF) 0/1/2
02 Not applicable. Do not change the default value! 0
E Unit information readout
00 Software version Read
01 EEPROM version Read
02 Unit model identification Read
03 Liquid refrigerant temperature Read
04 Inlet water temperature Read
Installer setting at variance with default value
Default
value
0 0/1
only
only
only
only
only
Range Step UnitDate Value Date Val ue
———
———
———
——°C
——°C
Installation manual
21
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 25

TEST RUN AND FINAL CHECK

MAINTENANCE

The installer is obliged to verify correct operation of unit after installation.

Test run operation (manual)

If required, the installer can perform a manual test run operation at any time to check correct operation of cooling and heating.
Procedure
1 Push the z button 4 times so the t icon will be displayed.
2 Depending on the unit model, heating operation, cooling
operation or both must be tested as follows (when no action is performed, the user interface will return to normal mode after 10 seconds or by pressing the z button once):
•To test the heating operation push the h/c button so the h
icon is displayed. To start the test run operation press the y button.
•To test the cooling operation push the h/c button so the c
icon is displayed. To start the test run operation press the y button.
3 The test run operation will end automatically after 30 minutes or
when reaching the set temperature. The test run operation can be stopped manually by pressing the z button once. If there are misconnections or malfunctions, an error code will be displayed on the user interface. Otherwise, the user interface will return to normal operation.
4 To resolve the error codes, see "Error codes" on page 24.
NOTE
NOTE
To display the last resolved error code, push the z button 1 time. Push the z button again 4 times to return to normal mode.
It is not possible to perform a test run if a forced operation from the unit is in progress. Should forced operation be started during a test run, the test run will be aborted.

Final check

Before switching on the unit, read following recommendations:
When the complete installation and all necessary settings have been carried out, close all front panels of the unit and refit the unit cover.
The service panel of the switch box may only be opened by a licensed electrician for maintenance purposes.
NOTE
Note that during the first running period of the unit, required power input may be higher than stated on the nameplate of the unit. This phenomenon originates from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption.
In order to ensure optimal availability of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals.
Before carrying out any maintenance or repair activity, always switch off the circuit breaker on the supply panel, remove the fuses or open the protection devices of the unit.
Make sure that before starting any maintenance or repair activity, also the power supply to the unit is switched off.
Beware that some parts of the unit can be extremely hot.

Chiller unit

The described checks must be executed at least once a year by qualified personnel.
1 Water pressure
Check if the water pressure is above 0.3 bar. If necessary add water.
2 Water filter
Clean the water filter.
3 Water pressure relief valve
Check for correct operation of the pressure relief valve by turning the red knob on the valve counter-clockwise:
If you do not hear a clacking sound, contact your local dealer.
In case the water keeps running out of the unit, close both
the water inlet and outlet shut-off valves first and then contact your local dealer.
4 Pressure relief valve hose
Check that the pressure relief valve hose is positioned appropriately to drain the water.
5 Air heat exchanger
Remove dust and any other contaminant from the coil fins using a brush and a blower. Blow from the inside of the unit. Take care not to bend or damage the fins.
6 Fan motor
Clean the cooling ribs of the motor.
Check on abnormal noises. If the fan or motor are damaged,
contact your local Daikin dealer.
7 Unit switch box
Carry out a thorough visual inspection of the switch box and look for obvious defects such as loose connections or defective wiring.
8 In case of use of glycol
Document the glycol concentration and the pH-value in the system at least once a year.
A pH-value below 8.0 indicates that a signifcant portion of the inhibitor has been depleted and that more inhibitor needs to be added.
When the pH-value is below 7.0 then oxidation of the glycol occured, the system should be drained and flushed thoroughly before severe damage occurs.
Make sure that the disposal of the glycol solution is done in accordance with relevant local and national legislation.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
22
Page 26

Digital controller

General symptoms

The digital controller does not need maintenance. Remove dirt with a soft damp cloth.

TROUBLESHOOTING

This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit.

General guidelines

Before starting the troubleshooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring.
Before contacting your local dealer, read this chapter carefully, it will save you time and money.
When carrying out an inspection on the switch box of the unit, always make sure that the main switch of the unit is switched off.
When a safety device was activated, stop the unit and find out why the safety device was activated before resetting it. Under no circumstances safety devices may be bridged or changed to a value other than the factory setting. If the cause of the problem cannot be found, call your local dealer
If the pressure relief valve is not working correctly and is to be replaced, always reconnect the flexible hose attached to the pressure relief valve, to avoid water dripping out of the unit!
NOTE
For problems related to the optional remote alarm kit, refer to the troubleshooting in the installation manual of that kit.
.
Symptom 1: The unit is turned on (y LED is lit) but the unit is not heating or cooling as expected
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting is not correct.
The water flow is too low.
The water volume in the installation is too low.
Symptom 2: The unit is turned on but the compressor is not starting (heating)
POSSIBLE CAUSES CORRECTIVE ACTION
The benefit kWh rate power supply settings and electrical connections do not match.
The benefit kWh rate signal was sent by the electricity company.
Check the controller set point.
• Check that all shut off valves of the water circuit are completely open.
• Check if the water filter needs cleaning.
• Make sure there is no air in the system (purge air).
• Check on the manometer that there is sufficient water pressure. The water pressure must be >0.3 bar (water is cold), >>0.3 bar (water is hot).
• Check that the pump speed setting is on the highest speed.
• Make sure that the expansion vessel is not broken.
• Check that the resistance in the water circuit is not too high for the pump (refer to "Setting the pump
speed" on page 17).
Make sure that the water volume in the installation is above the minimum required value (refer to "Checking
the water volume and expansion vessel pre-pressure" on page 9).
If [D-01]=1 or 2, the wiring requires specific installation like illustrated in
"Connection to a benefit kWh rate power supply" on page 14. Other
correctly installed configurations are possible, but are to be specific for the type of benefit kWh rate power supply type at this specific site.
Wait for the power to return.
Symptom 3: Pump is making noise (cavitation)
POSSIBLE CAUSES CORRECTIVE ACTION There is air in the system. Purge air. Water pressure at pump inlet is too
low.
Symptom 4: The water pressure relief valve opens
POSSIBLE CAUSES CORRECTIVE ACTION The expansion vessel is broken. Replace the expansion vessel. The water volume in the installation
is too high.
• Check on the manometer that there is sufficient water pressure. The water pressure must be >0.3 bar (water is cold), >>0.3 bar (water is hot).
• Check that the manometer is not broken.
• Check that the expansion vessel is not broken.
• Check that the setting of the pre­pressure of the expansion vessel is correct (refer to "Setting the pre-
pressure of the expansion vessel" on page 9).
Make sure that the water volume in the installation is under the maximum allowed value (refer to
"Checking the water volume and expansion vessel pre-pressure" on page 9).
Installation manual
23
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 27
Symptom 5: The water pressure relief valve leaks
POSSIBLE CAUSES CORRECTIVE ACTION
Dirt is blocking the water pressure relief valve outlet.
Check for correct operation of the pressure relief valve by turning the red knob on the valve counter clockwise:
• If you do not hear a clacking sound, contact your local dealer.
•In case the water keeps running out of the unit, close both the water inlet and outlet shut-off valves first and then contact your local dealer.
Symptom 6: The user interface displays "nn
nn
" when pressing
certain buttons
POSSIBLE CAUSES CORRECTIVE ACTION
The current permission level is set to a level that prevents using the pressed button.
Change the "user permission level" field setting ([0-00], see "Field
settings" on page 18.

Error codes

When a safety device is activated, the user interface LED will be flashing, and an error code will be displayed.
A list of all errors and corrective actions can be found in the table below.
Reset the safety by turning the unit OFF and back ON.
Instruction to turn the unit OFF User interface mode (heating/cooling =) Push the y button
ON 1 time ON 1 time OFF OFF
In case this procedure for resetting the safety is not successful, contact your local dealer.
Error code
Failure cause Corrective action
80 Inlet water temperature
thermistor failure (inlet water thermistor broken)
81 Outlet water temperature
thermistor failure (outlet water temperature sensor broken)
89 Water heat exchanger freeze-up
failure (due to water flow too low) Water heat exchanger freeze-up
failure (due to refrigerant shortage)
7H Flow failure (water flow too low
or no water flow at all, minimum required water flow is 16 l/min)
Contact your local dealer.
Contact your local dealer.
Refer to error code 7H.
Contact your local dealer.
• Check that all shut off valves of the water circuit are completely open.
• Check if the water filter needs cleaning.
Check that the unit is operating within its operating range (refer to
specifications" on page 25
•Also refer to "Charging water" on
page 10.
• Make sure there is no air in the system (purge air).
• Check on the manometer that there is sufficient water pressure. The water pressure must be >0.3 bar (water is cold), >>0.3 bar (water is hot).
• Check that the pump speed setting is on the highest speed.
• Make sure that the expansion vessel is not broken.
• Check that the resistance in the water circuit is not too high for the pump (refer to "Setting the
pump speed" on page 17).
• Check that the pump fuse (FU2) and PCB fuse (FU1) are not blown.
"Technical
).
Error code
Failure cause Corrective action
8H Outlet water temperature of unit
too high (>65°C)
Check that the outlet water thermistor is giving the correct read out.
A1 Hydraulic PCB defective Contact your local dealer. A5 Too low (during cooling
operation) or too high (during
Contact your local dealer.
heating operation) refrigerant temperature (measured by R13T)
C0 Flow switch failure (flow switch
remains closed while pump is stopped)
C4 Heat exchanger thermistor
failure (heat exchanger
Check that the flow switch is not clogged with dirt.
Contact your local dealer.
temperature sensor broken)
E1 Compressor PCB defective Contact your local dealer. E3 Abnormal high pressure Check that the unit is operating
within its operating range (refer to "Technical specifications" on
page 25).
Contact your local dealer.
E4 Actuation of low pressure sensor Check that the unit is operating
within its operating range (refer to "Technical specifications" on
page 25).
Contact your local dealer.
E5 Overload activation of
compressor
Check that the unit is operating within its operating range (refer to "Technical specifications" on
page 25).
Contact your local dealer.
E7 Fan lock failure (fan is locked) Check if the fan is not obstructed
by dirt. If the fan is not obstructed, contact your local dealer.
E9 Malfunction of electronic
Contact your local dealer.
expansion valve
F3 Too high discharge temperature
(e.g. due to coil blockage)
Clean the coil. If the coil is clean, contact your local dealer.
H3 Malfunctioning HPS system Contact your local dealer. H9 Outdoor temperature thermistor
failure (outdoor thermistor is broken)
Contact your local dealer.
J1 Malfunction of pressure sensor Contact your local dealer. J3 Discharge pipe thermistor failure Contact your local dealer. J5 Suction pipe unit thermistor
failure
J6 Aircoil thermistor frost detection
failure
J7 Aircoil thermistor mean
temperature failure
Contact your local dealer.
Contact your local dealer.
Contact your local dealer.
J8 Liquid pipe unit thermistor failure Contact your local dealer. L4 Electric component failure Contact your local dealer. L5 Electric component failure Contact your local dealer. L8 Electric component failure Contact your local dealer. L9 Electric component failure Contact your local dealer. LC Electric component failure Contact your local dealer. P1 PCB failure Contact your local dealer. P4 Electric component failure Contact your local dealer. PJ Failure of capacity setting Contact your local dealer. U0 Refrigerant failure (due to
refrigerant leak)
U1 Power supply cables are
connected in the reverse phase instead of the normal phase.
Contact your local dealer.
Connect the power supply cables in normal phase. Change any two of the three power supply cables (L1, L2, L3) to correct phase.
U2 Main circuit voltage failure Contact your local dealer. U4 Communication failure Contact your local dealer. U5 Communication failure Contact your local dealer. U7 Communication failure Contact your local dealer. UA Communication failure Contact your local dealer.
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged reversible air to water heatpumps
4PW51587-1A
Installation manual
24
Page 28

TECHNICAL SPECIFICATIONS

General

EWAQ009 EWAQ010 EWAQ011 EWYQ009 EWYQ010 EWYQ011 EWAQ009 EWAQ011 EWAQ013 EWYQ009 EWYQ011 EWYQ013
V3 models (1~) W1 models (3N~)
Nominal capacity
• cooling
• heating
Refer to the Technical Data Refer to the Technical Data Refer to the Technical Data Refer to the Technical Data
Dimensions H x W x D 1418 x 1435 x 382 1418 x 1435 x 382 Weight
• machine weight
• operation weight
180 kg 180 kg 185 kg 185 kg
Connections
•water inlet/outlet
•water drain
•refrigerant liquid side
•refrigerant gas side
G 5/4" FBSP
(a)
G 5/4" FBSP
hose nipple hose nipple
Ø9.5 mm (3/8 inch) Ø9.5 mm (3/8 inch)
Ø15.9 mm (5/8 inch) Ø15.9 mm (5/8 inch)
(a)
Expansion vessel
•volume
• maximum working pressure (MWP)
10 l 10 l
3 bar 3 bar
Pump
•type
•no. of speed
Sound pressure level
• heating
• cooling
(b)
———51 dBA 51 dBA 51 dBA 51 dBA 51 dBA 52 dBA
51 dBA 51 dBA 51 dBA 51 dBA 51 dBA 51 dBA 51 dBA 51 dBA 52 dBA 51 dBA 51 dBA 52 dBA
water cooled water cooled
22
Internal water volume 4 l 4 l Pressure relief valve
water circuit
3 bar 3 bar
Operation range - water side
• heating
• cooling
+25~+50°C +25~+50°C
+5~+22°C +5~+22°C +5~+22°C +5~+22°C
Operation range - air side (RH: 85%)
• heating
• cooling
(a) FBSP = Female British Standard Pipe (b) At 1 m in front of the unit (free field condition)
–15~+35°C –15~+35°C
+10~+46°C +10~+46°C +10~+46°C +10~+46°C
Electrical specifications
Standard unit (power supply via unit)
•power supply
• nominal running current
V3 models (1~) W1 models (3N~)
230 V 50 Hz 1P 400 V 50 Hz 3P
5.8 A
Installation manual
25
EWAQ+EWYQ009~011ACV3 + EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
Page 29
NOTES NOTES
Page 30
4PW51587-1A
Copyright © Daikin
Loading...