INSTALLATION, OPERATION & MAINTENANCE
ROOF AND WALL MOUNTED PROFILE FANS
DIRECT DRIVE
MODELS VULK & VELK
CARNES COMPANY, 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 Phone: 608-845-6411 Fax: 608-845-6470 carnes@carnes.com www.carnes.com
INTRODUCTION
This manual is to be used as an aid in the proper installation, operation, and maintenance of the above Carnes fans.
This information is to be used as a general guide. Due to the variety and complexity of many installations it is the
responsibility of the purchaser to assure that qualified personnel handle these procedures.
RECEIVING, HANDLING, & STORAGE
1. Handle the fan with care. Avoid severe jarring or dropping of the unit.
2. Inspect the unit for damage upon delivery. If the unit has been damaged in transit it is the responsibility of the
recipient to file all freight claims.
3. Provide adequate, protected storage prior to installation.
FORM 1511, Page 1
MECHANICAL INSTALLATION CAUTIONS
1. Do not operate this fan in an environment where combustible or flammable materials, gasses, or fumes are
present unless it has been specifically designed and manufactured for use in that environment.
2. Turn the wheel by hand to check clearances. If necessary, adjust the wheel by moving the motor to center
the wheel over the inlet venturi and if necessary, raise or lower the wheel on the motor shaft.
3. Ensure that all fasteners and setscrews are tight.
ELECTRICAL INSTALLATION CAUTIONS
1. Be sure the supply voltage matches the motor nameplate voltage. On multiple voltage motors, check the
motor wiring to ensure that the motor has been wired for the correct voltage.
2. All fans must be grounded.
3. Keep all wiring clear of rotating components and moving parts such as gravity or motorized dampers.
4. Make sure power is locked OFF at the service entrance prior to wiring or otherwise approaching the fan.
5. A qualified electrician must do all electrical work in accordance with local and/or the National Electrical
Code (NEC).
FORM 1511
INSTALLATION OF ROOF TOP FANS
1. This fan is designed for exhaust applications only. Refer to the catalog V-104 for particular application details.
2. Any optional dampers should be mounted to allow free and unobstructed operation.
3. This fan requires a minimum of four (4) mounting fasteners, of the appropriate size and type in order to be
securely fastened to the roof curb. Be sure to use an approved sealant or gasket between the fan and curb to
prevent leaking and possible vibration.
INSTALLATION OF WALL MOUNTED FANS (VULK Only):
WALL OPENING PREPARATION
1. The wall opening must be sized according to the dimensions given in the Specification Sheet 11050 or on page 4 of
the Installation Instructions.
2. A mounting frame is supplied and must be attached to the wall on the side that the unit will be on.
3. Fasten the frame to the wall using a minimum size of 5/16” dia. thru-bolts, lag-bolts, expansion-bolts or other
appropriate heavy duty hardware for the type of wall construction at hand.
4. Push the supplied metal clips over the frame and line each of them up with one of the 4 unit mounting holes. Flat
side out.
WALL OPENING PREPARATION
1. Identify the Motor Compartment Vent Tube It is a short tube extending out of the motor compartment and passing
through the outer air shroud.
2. If a Damper is also being installed with this unit check its mounting position and wiring requirements (if motorized).
3. Apply a quality sealant around the frame in order to prevent water and air leaks between the wall and frame or
frame and unit.
4. Lift the unit into position on the wall with the Motor Compartment Vent Tube opening downward. This prevents
water from running into the motor compartment.