Burkert 8631 User Manual

On-off valve with
TOP
Control
Quickstart
Installation and Operation
ON/OFF
GENERAL NOTES
These instructions explain with the aid of an example the commissioning of a single-acting on-off valve. A detailed description of the device, including the external connection of the terminals and the data bit configuration and LED displays, can be found in the operating instructions for the TOP
Control
instructions for the process valves on the accompanying CD.
ON/OFF Type 8631, as well as in the operating
Safety notes
• Keep to standard engineering rules in planning the use of and operating the device!
• Installation and intervention for maintenance work are only allowed by qualified personnel using suitable tools!
• Observe the current regulations on accident prevention and safety for electrical devices during operation and mainte-nance of the device!
• Before interfering with the system, always switch off the voltage!
• Note that in systems under pressure, piping and valves may not be loosened!
• Take suitable precautions to prevent inadvertent operation or damage by unauthorized action!
• After interruption of the electrical or pneumatic supply, make sure the process is restarted in a well-defined, controlled manner!
GENERAL NOTES DEVICE
EXERCISE CAUTION ON HANDLING!
This device contains electronic components that are sensitive to electrostatic discharge (ESD). Contact to electrostatically charged persons or objects will endanger these components. In the worst case, they will be immediately destroyed or will fail after commissioning. Observe the requirements of EN 100 015 - 1 in order to minimize the possibility of, or avoid, damage from instantaneous electrostatic discharge. Also take care not to touch components that are under supply voltage.
ATTENTION
ELECTROSTATICALLY SENSITIVE
COMPONENTS / MODULES
Intended use
instructions together with the conditions of use and permitted data that are specified in the data sheet Type 8631, in order that the device will function perfectly and remain operable for a long time. On non-observance of these notes and unauthorized interference with the device, we will refuse all liability and the warranty on device and accessories will become void! The device serves exclusively to actuate pneumatically operated process valves. Any other use or use exceeding the specific scope is considered to be will not be liable for any damage resulting therefrom. The risk will be borne by the user.
non-intended use
. Bürkert
9
o
When connecting units with EEx-i approval, always follow the operation instructions in detail!
Notes for use in the Ex-area
Please comply with the following:
• In the case of installation and operation in areas that have a risk of explosion, the respective national regulations. In Germany, this is VDE 0165.
• When making electrical connections to the inherently safe circuit, the information given in the corresponding conformity certificates.
• Always follow the information contained in the ATEX approval.
Notes for devices with EEx-i-approval
• Take suitable measures to avoid an electrostatic discharge from the plastic parts of the housing (see EN 100 015 - 1).
• No component should be connected to the inputs and outputs of the circuit board whose electrical data is outside the limits determined for intrinsically safe operation quoted in the data sheet of the positioner.
• Work out on the device with the housing open should not be carried in very damp or aggressive atmospheres. Take precautions to exclude unintentional mechanical damage to the circuit boards or their components. Limit the period during which the unit is opened to that which is absolutely necessary.
Electrical data (EEx-i-approval)
Connections: 2 x M16 cable connector with screw terminals
Power supply:
Sensor see Manufacturer's Declaration form
Valve see Qualification Test Certificate
Safety requirements
The maximum permissible voltages and the associated maximum permissible short-circuit currents for the corresponding gas group may be taken from Table A1 in the standard DIN EN 50020, 1994 Edition.
In order that the maximum permissible temperature at the solenoid coil of the valve installed is not exceeded, the following limits to the applied power for use in the corresponding temperature class must be observed:
Temperature
class
T6
T5
2)
Ambient temperature for compl. TopControl 8631
(temperature inside the device is higher by max. 5°C )
for cable cross-sections 0,14 ... 1,5 mm²
2)
[°C]
1)
1)
Max. permissible
power [W]
Fa. Pepperl & Fuchs
PTB 01 ATEX 2173
1)
see detailed operating instructions
Max. permissible ambient
temperature
+50 0,4
+45 0,5
+40 0,7
+35 0,8
+50 0,8
+45 1,0
+40 1,1
DEVICES WITH EEx-i-APPROVALDEVICES WITH EEx-i-APPROVAL
The control head must not be exposed directly to sunshine or strong light sources: this would cause additional warming!
Functional data
Resistance at 20°C (R20): 510 Ohm
Minimum terminal voltage: 11,7 V
Minimum current: 23 mA
The maximum voltage and current values are determined by the permissible electrical operating equipment.
TECHNICAL DATA
Technical Data
Operating conditions
Ambient temperature -10... +50°C
Protection class IP 65 nach EN 60529
Electrical data
Voltage supply (see nameplate)
24 V DC ± 10 % 110 / 230 V AC
Protection class 3 to VDE 0580
Pneumatic data
Control medium Quality classes
- Dust content max. particle size 40 µm
to DIN ISO 8573-1
max. particle density 10 mg/m
- Water content max. pressure dew point -20 °C
- Oil content max. 25 mg/m
Temperature range of compressed air
-10 ... +50 °C
Pressure range 3 ... 7 bar
3)
Attention: do not use insustrial DC.
4)
At present not available
We reserve the right to make technical changes without notice.
3)
4)
3
FLUIDIC CONNECTION
Possible expansion steps
• Mechanical over travel switch
• AS interface
• DeviceNet
Various process valves from the Bürkert range can be combined with the TOP seat, diaphragm or ball valves are suitable.
Control
ON/OFF to suit different applications. Y-, flat-
FLUIDIC CONNECTION
Fixing the TOP
The fixing screw (connection between Top process valve) may only be tightened with a maximum torque of 1.2 Nm.
Control
ON/OFF
Control
and
Installation of the valve
• Installation in any orientation but preferably upright.
• Observe the flow direction of the fitting.
• Clean piping from contamination!
Connection of the control air
Screw for adjusting the lower proximity switch
Screw for adjusting the upper proximity switch
3
Electrical connection module
Pressure supply port (marked 1)
Pilot valve (3/2- or 5/2-way solenoid valve)
Exhaust air port (marked 3)
Control ports (connected in the factory)
• Before attaching the valve housing, make sure the piping is aligned.
• If the housing is to be welded on, make absolutely sure that the actuator is removed beforehand.
Chr.-Bürkert-Straße 13-17 Berlin Ph: (0 30) 67 97 17 - 0
Contact addresses / Kontaktadressen
Germany / Deutschland / Allemange
Bürkert Fluid Control System Sales Centre Chr.-Bürkert-Str. 13-17 D-74653 Ingelfingen Tel. + 49 (0) 7940 - 10 91 111 Fax + 49 (0) 7940 - 10 91 448
E-mail: info@de.buerkert.com
International
Contact addresses can be found on the internet at: Die Kontaktadressen finden Sie im Internet unter: Les adresses se trouvent sur internet sous : www.burkert.com Bürkert / Company / Locations
74653 Ingelfingen Dortmund Ph: (0 23 73) 96 81 - 0 Ph: (0 79 40) 10-111 Frankfurt Ph: (0 61 03) 94 14 - 0 Fax (0 79 40) 10-448 Hannover Ph: ( 05 11) 9 02 76 - 0 www.buerkert.com München Ph: (0 89) 82 92 28 - 0 info@de.buerkert.com Stuttgart P h: (07 11) 4 51 10 - 0
BÜRKERT INTERNATIONAL
A Ph. (01) 894 13 33 Fax (01) 894 13 00 AUS Ph. (02) 1300 888 868 Fax (02) 1300 888 076 B Ph. (03) 325 89 00 Fax (03) 325 61 61 BRA Ph. (011) 51 82 00 11 Fax (011) 51 82 88 99 CDN Ph. (905) 847 55 66 Fax (905) 847 90 06 CH Ph. (041) 785 66 66 Fax (041) 785 66 33 CN Ph. (21) 58 68 21 19 Fax (21) 58 68 21 20 CZ Ph. (543) 25 25 05 Fax (543) 25 25 06 DK Ph. (44) 50 75 00 Fax (44) 50 75 75 E Ph. (93) 477 79 80 Fax (93) 477 79 81 EST Ph. (372)644 06 98 Fax (372)631 3 7 5 9 F Ph. (0388) 58 91 11 Fa x (0388) 57 20 08 HKG Ph. 24 80 12 02 Fa x 24 18 19 45 I Ph. (02) 95 90 71 Fax (02) 95 90 72 51 IND Ph . (044)52 30 34 56 Fax (044)52 30 32 32 J Ph. (03) 53 05 36 10 Fax (03) 53 05 36 11 KOR Ph. (02) 34 62 55 92 Fa x (02) 34 62 55 94 N Ph. (63) 84 44 10 Fax (63) 84 44 55 NL Ph. (0346) 58 10 10 Fax (0346) 56 37 17 NZ Ph. (09) 622 28 40 Fax (09) 622 28 47 P Ph. (21)212 84 90 F ax (21)212 84 91 PL Ph. (022) 840 60 10 Fax (022) 840 60 11 RC Ph. (02) 26 53 78 68 Fax (02) 26 53 79 68 RP Ph. (02) 776 43 8 4 Fa x (02)776 43 82 S Ph. (040) 664 51 00 Fax (040) 664 51 01 SA Ph. (011)574 60 00 Fa x (011) 454 14 77 SF Ph. (09) 54 97 06 00 Fax (09) 503 12 75 SIN Ph. 68 44 22 33 Fax 68 44 35 32 TR Ph. (0232) 459 53 95 F ax (0232) 459 76 94 TT Ph. (04)643 50 08 F ax (04)643 70 10 UK Ph. (01453) 73 13 53 Fa x (01453) 73 13 43 USA Ph. (949) 223 31 00 Fax (949) 223 31 98
Operating Instructions 0507/07_EU-EN_00804480
ELECTRICAL CONNECTIONBRANCH OFFICES
Connections
Plug connector for
initiator / limit switch 1
Plug connector for
initiator / limit switch 2
LED
Initiator / limit switch 1 triggered
LED
Initiator / limit switch 2 triggered
24-V-Version
Inductive proximity switch Mechanical limit switch
Term i-
nal
12Valve actuati on GND
Valve actuacti on 0 V/ 24 V
Supply to initiators GND
3
common reference for
4
initiators GND n. c.
5
Binary output
6
initiator 2 (NO) n.c.
7
Binary output
8
initiator 1 /NO) Supply to initiators +24 V
9
LED
Supply for initiators / limit switches
Valve actuation GND Valve actuation 0 V/ 24 V
Supply to limit switches GND Common reference for limit switc hes GND Output limit switch 2 (NC) Output limit switch 2 (NO)
Output limit switch 1 (NC) Output limit switch 1 (NO)
Supply to limit switches +24 V
9 8 7 6 5 4 3 2 1
LED valve on
ELECTRICAL CONNECTION
Connections
110 / 230-V-Version
Terminal Mechanical limit switch
12Valve actuation N
Valve actuation L 1
Supply to limit switches
3
Output common pole
4
Output limit switch 2 (NC)
5
Output limit switch 2 (NO)
6
Output limit switch 1 (NC)
7
Output limit switch1 (NO)
8
Supply to limit switches
9
Adjustments on commissioning
To adjust the initiators / proximity switches or limit switches:
• open the housing of the TOP
• adjust the initiators using the setscrews (see illustration: Connection of the control air).
Turn clockwise: movement upward
Control
ON/OFF and
Turn anticlockwise: movement downward
BUS COMMUNICATION
Bus drive via AS interface
Intitiator 1 data bit D3
Valve 1 data bit D0
Initiator 2 data bit D2
Control ports connection 2
Bus connector M 12
4
3
Pin 1: Bus + Pin 3: Bus -
2
1
Watchdog function yes No. of valves /
power consumption 1 x 1 W
Power reduction yes, after ca. 30 ms Bus connection - via M 12 plug
(Pin 1 = Bus +, Pin 3 = Bus -)
- via screw terminals and PG bushing
pressurized when valve 1 = 1
BUS COMMUNICATION BUS COMMUNICATION BUS COMMUNICATION
Bus drive via AS interface Bus drive via AS interface
Status displayProgramming data
LED 1 Bus
Standard Device
IO code: D hex (1 output, 3 inputs) ID code: F hex (ext. ID-Codes 1 and 2 = F) Profile: S - D. F. F Certification: yes, Cert.-no. 32901 (to V.2.11)
Device for A/B-Slave addressing
IO code: D hex (1 output, 3 inputs) ID code: A hex (ext. ID-Codes 1 = 7 hex and 2 = E hex)
1
Profile: S - D. A. E Certification: yes, Cert.-no. 47601 (to V.2.11)
Observe bit configuration!
Data bit configuration
Parameter bit configuration
D3 D2 D1 D0
Input initiator 1
P3 P2 P1 P0
not connected
Input initiator 2
Input diagnosis
Output valve 1
(green)
off off POWER OFF
off on no data traffic (watchdog expired
on off ok
flashes on slave adress = 0
off flashes Overload of sensor supply
Standard addressing
LED (yellow) initiator 1
LED (yellow) initiator 2
A/B-Slave addressing
LED (yellow) valve on
LED 2 Bus (red)
LED (yellow) initiator 1
Status signalled
with slave address non-zero)
LED 2 Bus (red)
LED (green) valve on
LED 2 Bus (red)
LED 1 Bus (green)
LED (yellow) initiator 2
ASI + ASI -
n. c.
LED 1 Bus (yellow)
ASI + ASI -
BUS COMMUNICATION BUS COMMUNICATION BUS COMMUNICATION
Bus drive via DeviceNet
MNS LED = Module Network Status
LED for initiator 1
Plug connector for Initiator S1
LED for valve 1
Plug connector for valve
Power LED
DIP switches for address and data rate
Bus connection (circular plug connector M 12, 5-pole)
LED for initiator 2
Plug connector for initiator S2
Connection for bus and supply
Bus drive via DeviceNet
Settings of the DeviceNet address
MAC ID - Medium Access Control Identifier:
DIP1=off=0, DIP1=on=1
MAC ID=DIP 1*20+DIP2*21+...+DIP6*2
DIP 1
DIP 2 [21=2]
DIP 3
[22=4]
0
[2
=1]
off off off off off off 0
on off off off off off 1
off on off off off off 2
... ... ... ... ... ... ...
off on on on on on 62
on on on on on on 63
DIP 4 [23=8]
5
DIP 5
[24=16]
DIP 6
[25=32]
MAC ID
Bus drive via DeviceNet
Setting the network data rate
DIP 7 DIP 8 Network
off off 125 kBaud
on off 250 kBaud
off on 500 kBaud
on on not a llowed
data rate
Adaption to the data rate of the network