Bosch D7052 User Manual

D7052
Installation Instructions
EN
Multiplex Dual Input Module
D7052 | Installation Instructions |
Notices
Notices
Install, test, and maintain the D7052 according to these instructions, NFPA 72, local codes, and the Authority Having Jurisdiction (AHJ).
Follow the procedures in these instructions to avoid personal injury and damage to equipment. Failure to follow these instructions can cause the D7052 to not operate properly. Bosch is not responsible for improperly installed, tested, or maintained devices.
Test the FACP according to NFPA 72.
1.0 Description
The D7052 (Figure 1) is a general purpose module that connects to the multiplex bus of the control panel. It provides two supervised Class “B” input zones or one Class “A” input zone. Use a jumper pin setting for a Class “A” or Class “B” wiring configuration.
All operating power for the D7052 is drawn from the control panel. Rotary switches provide convenient address setting.
An on-board Status LED, visible through the faceplate, indicates normal operation and communication with the control panel. The LED flash rates are:
Fast: Approximately 4 sec indicating an alarm condition.
Medium: Approximately 8 sec indicating a normal operation.
Slow: Approximately 16 sec indicating a trouble condition.
The D7052 can be mounted in a standard double-gang or a 4 in. x 4 in. electrical box.
Figure 1: D7052 Features
1
2
4
0
0
A
1
9
2
8
0
7
1
B
2
0
1
1
9
2
8
2
3
7
6
5
5
3
4
6
4
5
3
1 - Status LED 2 - Class “A” and Class “B” jumper pins 3 - MUX bus loop terminals 4 - Zone input terminals 5 - Rotary address switches
2.0 Setting the Address
Set the D7052 address using a flat-blade screwdriver to position each rotary switch located on the front of the module (Figure 2). Note that the switches click when turned.
Figure 2: Setting the Address
A
0
1
2 0
1
B
2
1 2 3
1 - Hundreds 2 - Tens 3 - Ones
A = D7024 FACP, B = DS9400M FACP
For example: 0 hundreds, 9 tens, 5 ones = Address 095 on the
0
1
9 8 7
2
3
4
6
5
D7024 FACP
0
1
9 8 7
2
3
4
6
5
The valid address range is 9 to 255. Refer to the D7024 Operation and Installation Guide (P/N: 31499) or the DS9400M Reference Guide (P/N: 44578) for additional
address limitations.
The D7052 requires two program addresses. The address cannot be 8 or a multiple of 8, such as 16, 24, 32, and so on.
Bosch | 11/04 | 48709F2
D7052 | Installation Instructions | 3.0 Wiring
The A address range works on the D7039 Multiplex Expansion Module with the D7024 FACP. The B address range works on the DS9431 Multiplex Expansion Module with the DS9400M FACP.
Figure 2 on page 2 shows the input address set at 095. The second input address will be set to the next consecutive address, 096. Because the hundreds address is within the input address range, it works on the D7039 with the D7024 FACP.
3.0 Wiring
Remove all power before making electrical connections. Failure to do so can result in personal injury and damage to the equipment.
Use normally-open (NO) contacts for Underwriters Laboratories, Inc. (UL) Listed fire installations.
The wiring connections are made using the terminals on either side of the D7052 (refer to Figure 1 on page 2). All terminals can accommodate up to and including 12 AWG (2.3 mm) wire. Follow the wiring guidelines as specified by NFPA-70 and the local AHJ.
All wiring is power limited and supervised. Refer to Figure 3 and Figure 4 for the two types of wiring connections.
Ensure the D7052 is correctly configured for Class “A” or Class “B.” Refer to Figure 5 for jumper settings.
Figure 4: Class “B” Wiring Connections
2
1
3
4 5
4 5
A
0
1
2 0
1
2
B
1 - 2.21 kΩ end-of-line (EOL) resistor, UL Listed
(P/N: 25899) 2 - Input Zone 1 3 - Input Zone 2 4 - Zone in (+) 5 - Zone in (-)
Note: The maximum zone wire resistance = 100
Figure 5: Loop and Control Panel Wiring
Connections
1
2
3
Figure 3: Class “A” Wiring Connections
4
6
5 4
0
1
9
8
2 3
7
6
4
1
5
5
7
2 1 2
A
0
1
2 0
1
2
B
1 - Class “A” and Class “B” jumper pins 2 - Class “B” 3 - Class “A” 4 - MUX bus loop (+) 5 - MUX bus loop (-)
1 - Zone in (+) 2 - Zone in (-)
Note: The maximum zone wire resistance = 100
6 - To next device 7 - From previous device, the D7039, or the DS9431
3Bosch | 11/04 | 48709F