Bosch D7050TH Specsheet

Fire Alarm Systems | D7050 Addressable Photoelectric Smoke and Smoke Heat Detector Heads
D7050 Addressable Photoelectric Smoke and Smoke Heat Detector Heads
www.boschsecurity.com
u Connects to the multiplex bus of the FPD‑7024 or
D7024 Addressable FACP and the DS7400Xi Control Panel
The D7050 Photoelectric Smoke and Smoke Heat Detector Heads are UL Listed, open-area photoelectric smoke detectors designed for use with commercial fire protective signaling systems and household fire warning systems (see NFPA 72, the National Fire Alarm Code). They are compatible with the FPD‑7024 or D7024 Addressable Fire Alarm Control Panels (FACPs), the DS7400Xi Control Panel, and the G Series Control Panels. They detect large smoke particles by scattering light from a pulsed infrared source operating with a gated, high-speed, photodiode infrared sensor. The symmetry of the optical chamber allows 360° uniform smoke entry, but minimizes external light entry. Use both of these smoke detectors for detection circuits installed in areas where personnel are present. The D7050TH has an added fixed-temperature sensor. This expands the detector application to confined areas where a fire increases air temperature slowly and where there is a substantial increase in air temperature before the fire breaks confinement, such as furnace rooms, closets, and other confined areas.
u Superior dust immunity
u Exclusive Chamber Check self-diagnostics
u Automatic sensitivity test features
u Easy disassembly for cleaning
Functions
Detector Head and Base System
The D7050 Photoelectric Smoke and Smoke Heat Detector Heads are part of a compound system of detector head and base. The detector base installs over a back box and contains all the wiring. The detector head attaches to the base by aligning the head with the base and turning it clockwise. No tools are required for installation other than the hex key used to tighten the tamper screw. Each detector head requires a D7050-B6 detector base.
Chamber Check Self-diagnostics
The detector meets NFPA guidelines for sensitivity testing, because you can visually inspect the detector and check the flash rate of the LED. If the calibration is out of factory-listed range, the LED on the detector double flashes once every 3 sec to 8 sec. Follow the instructions provided with the detector to clean it. The detector also sends a dirty chamber report to the control panel.
LED Operation
When the detector is operating normally, the LED flashes once every 3 sec to 8 sec. In alarm, the detector flashes at least once per second.
2 | D7050 Addressable Photoelectric Smoke and Smoke Heat Detector Heads
Magnetic Test Feature
Test the detector's operation by placing the SMK-TM Test Magnet next to the detector's LED for three consecutive flashes. This causes the detector to send an alarm.
Certifications and approvals
Region Certification
USA UL UROX: Smoke-automatic Fire Detectors
FM D7050 Family
CSFM see our website
FDNY­CoA
Hong Kong HKFSD
(ANSI/UL 268) and UROX7: Smoke-au­tomatic Fire Detectors Certified for Can­ada (CAN/ULC-S529)
#6173
Installation/configuration notes
Compatible Products
The following products are compatible with the D7050 Smoke Detector and the D7050TH Smoke Heat Detector:
Category Product ID Product Description
Control Panels FPD‑7024 FACP
D7024 FACP
D7024-EXP FACP for export
G Series D9412G (or later), D7412G (or
Detector Bases D7050-B6 Two-wire base
Remote Annunciators
Interface Modules
1
The D7212G models are not UL Listed for commercial fire.
DRA-12/24 12/24 VDC remote annunciator
D8125MUX Multiplex bus interface module
later), and D7212G1 (or later)
Parts included
Quant. Component
1 Detector head
1 Literature pack
Technical specifications
Environmental Considerations
Radio Frequency Interference (RFI) Immunity:
Temperature (normal operating):
Note: The environment where these detectors are installed must be within the specified normal operating temperature limits.
No alarm or setup on critical frequencies in the range of 26 MHz to 950 MHz for field strengths less than 50 V/m
+32°F to +100°F (0°C to +38°C)
Mechanical Properties
Color: Off-white
Dimensions (diameter x D):
Material: High-impact, fire-retardant ABS plastic
4 in. x 1.3 in. (10.2 cm x 3.3 cm)
Power Requirements
Current (alarm): 0.55 mA maximum
Current (standby): 0.55 mA nominal
Power-up Time: 22 sec maximum
Voltage (minimum): 8 VDC peak from the multiplex bus
Ordering information
D7050 Addressable Photoelectric Smoke Detector Head
The D7050 detects large smoke particles by scattering light from a pulsed infrared source operating with a gated, high-speed, photodiode infrared sensor. The symmetry of the optical chamber allows 360° uniform smoke entry, but minimizes external light entry.
Order number D7050
D7050TH Addressable Photoelectric Smoke and Heat Detector Head
The D7050TH, in addition to an optical smoke chamber, has an added 135°F (57°C) fixed­temperature sensor that expands its application to confined areas where a fire increases air temperature slowly and where there is a substantial increase in air temperature before the fire breaks confinement.
Order number D7050TH
Accessories
DRA‑12/24 Remote Annunciator (12/24 VDC)
Designed to provide remote annunciation of alarms when connected to the D7050‑B6 Multiplex Detector Base
Order number DRA-12/24
DT‑2 Detector Removal Tool
Use the DT‑2 to remove, replace, or test the detector head
Order number DT-2