Bosch D7050TH Installation Manual

Installation Instructions
EN
Multiplex Photoelectric Smoke Detectors
D7050/D7050TH | Installation Instructions | 1.0 Description
Notices
These instructions cover the installation of the D7050/D7050TH Multiplex Photoelectric Smoke Detectors on a D7024 or DS9400M 24 VDC Fire Alarm Control Panel (FACP) with a D7039 or DS9431 Multiplex Expansion Module installed. The D7024 and DS9400M FACPs require ROM version 2.0 or greater.
Install, test, and maintain the D7050/D7050TH according to these instructions, NFPA 72, local codes, and the Authority Having Jurisdiction (AHJ).
Follow the procedures in these instructions to avoid personal injury and damage to
This device complies with Part 15 of the Federal Communications Commission (FCC) Rules and with RSS-210 of Industry and Science Canada. Operation is subject to the following conditions:
This device does not cause harmful interference.
This device must accept any interference received,
equipment. Failure to follow the procedures can cause the D7050-D7050TH to not operate properly. Bosch is not responsible for improperly installed, tested, or maintained devices.
including interference that might cause undesirable operation.
1.0 Description
The D7050/D7050TH are Underwriters Laboratories, Inc. (UL) Listed, open-area multiplex photoelectric smoke detectors. The D7050TH includes a built-in +135°F ± 5°F (+57°C ± 2.7°C) heat detector. Both detectors can be used with the D7024 or DS9400M FACP containing a D7039 or DS9431 Module.
Each detector uses a D7050-B6 or MXB2W detector base.
For commercial and industrial installations, space the D7050/D7050TH 30 ft (9.2 m) according to NFPA 72.
Wall-mounted smoke detectors must be at least 4 in. (10.2 cm) and no more than 12
An LED indicator flashes every 3 to 8 sec confirming the detector has power and the smoke sampling circuitry functions. The LED flashes at least once each second in an alarm allowing you to easily confirm individual detector alarms. The detector automatically resets after the alarm condition clears.
Refer to Figure 1 for the D7050/D7050TH’s dimensions and components.
Figure 1: D7050/D7050TH Side and Top Views
in. (30.5 cm) below the ceiling.
4 in.
(10.2 cm)
1.5 in.
(3.8 cm)
1 - Side view 2 - Top view 3 - Alarm/Test LED 4 - Magnetic test locator 5 - Calibration voltage pins 6 - Tamper screw hole
1
2
3
4
5
6
2 Bosch Security Systems, Inc. | 9/06 | 47458E
.
2.0 Installation
D7050/D7050TH | Installation Instructions | 2.0 Installation
3.0 Wiring the D7050-B6 Base
Do not use shielded cable.
For multiplex bus wiring requirements, refer to the
D7024 Operation and Installation Guide (P/N: 31799), the DS9400M Reference Guide (P/N: 44578), the D7039 Installation Guide (P/N: 38685), or the DS9431 Installation Instructions (P/N: 41381).
Do not exceed a maximum line resistance
of 50 .
You can wire the D7050-B6 Base in series or T-tap (refer to Figure 2).
Figure 2: Wiring the D7050-B6 Base
1
(-)
(+)
1
2
R2
+1
3-
R2
+1
3-
3
R2
+1
3-
R2
+1
3-
R2
+1
3-
R2
+1
3-
R2
+1
3-
R2
+1
3-
1 - Input-output module for the D7039 or DS9431 2 - Series connection 3 - T-tap connection
You can replace the dust cover during construction periods, but it must be removed once the alarm system is enabled.
Bosch Security Systems, Inc. | 9/06 | 47458E 3
Loading...
+ 5 hidden pages