Bosch D7050DH Installation Manual

Page 1
Installation Instructions
EN
Multiplex Photoelectric Duct Smoke Detector
Page 2
D7050DH | Installation Instructions | 1.0 Description
Notices
Figure 1: D7050DH
These instructions cover the installation of the D7050DH Multiplex Photoelectric Duct Smoke Detector on a D7024 or a DS9400M 24 VDC Fire Alarm Control Panel (FACP) with a D7039 or DS9431 Multiplex Expansion Module installed. The D7024 and DS9400M requires ROM version 2.0 or greater.
Install, test, and maintain the D7050DH according to these instructions, NFPA 72, local codes, and authority having jurisdiction (AHJ).
Follow the procedures in these instructions to avoid personal injury and damage to the equipment. Failure to follow these instructions can result in the D7050DH not operating properly. Bosch is not responsible for improperly installed, tested, or maintained devices.
The D7050DH complies with Part 15 of the Federal Communications Commission (FCC) Rules and with the RSS-210 of Industry and Science Canada. D7050DH operation is subject to the following two conditions:
1. It does not cause harmful interference.
2. It must accept any interference it receives,
including interference that might cause undesirable operation.
1.0 Description
The D7050DH (Figure 1) is Underwriters Laboratories, Inc. (UL) Listed and requires a D343 Duct Detector Housing. Use this detector with the D7024 or a DS9400M that includes a D7039 or DS9431 Multiplex Expansion Module.
An LED indicator on the head flashes every 3 to 8 sec to ensure the D7050DH has power and the smoke sampling circuitry functions. This LED flashes at least once each second during an alarm confirming individual detector alarms. The D7050DH automatically resets after the alarm condition clears.
2.0 Installation
For installation details, refer to the D7024 FACP Operation and Installation Guide (P/N: 31499), the D9400M Reference Guide (P/N: 44578), the D7039 Installation Guide (P/N: 38685), or the DS9431 Installation Instructions (P/N: 41381).
1
4 in.
(10.2 cm)
1.5 in.
(3.8 cm)
2
5
6
1 - Side view 2 - Top view 3 - Alarm/Test LED
Table 1: Maximum Wire Length Allowed for
each Multiplex Bus
Wire Gauge
18 AWG (1.02 mm) 3800 ft (1170 m) 16 AWG (1.29 mm) 5950 ft (1810 m) 14 AWG (1.63 mm) 5950 ft (1810 m) 12 AWG (2.05 mm) 5950 ft (1810 m)
Table 2: Maximum Number of Detectors
Allowed for each Multiplex Bus
With Remote Test 40 With Remote LED 50 Without Annunciator 70
4 - Magnetic test locator 5 - Calibration voltage pins 6 - Tamper screw hole
Maximum 50 for each
Bus Loop
3
4
Do not use shielded cable.
Do not exceed the maximum line resistance
of 50.
2 Bosch Security Systems, Inc. | 9/06 | 49325E
Page 3
.
3.0 Wiring the D343
You can wire the D343 in series as shown in Figure 2.
Figure 2: Wiring the D343 Duct Housing
1
(-)
(+)
BBR
Y
O
LRE
E
R
KND
L
N
Tampe r Disable
14 13 12 11 10 9
B
G
L
R
U
N
1
Reset Disable
2 3 4 5 6 7 8
2
BBR
Y
O
LRE
E
R
KND
L
N
Tamper Disable
14 13 12 11 10 9
B
G
L
R
U
N
Reset Disable
1 - Input output module for the D7039 or DS9431 2 - Multiplex bus connections
4.0 Setting the Address
Set the D7050DH address before connecting to the control panel and applying power. The address number is the same as the input point or zone number.
D7050DH | Installation Instructions | 3.0 Wiring the D343
The A address range works on the D7039 Multiplex Expansion Module with the D7024 FACP. The B address range works on the DS9431 Multiplex Expansion Module with the DS9400M FACP.
Figure 3 shows the A address range set at 095, allowing
1
the D7039 to work with the D7024 FACP.
2 3 4 5 6 7 8
5.0 Mounting
1. Remove the tamper screw located in the recess
on the top of the dust cover.
2. Remove the dust cover.
3. Mount and wire the duct housing according to the
D343 Installation Instructions (P/N: 48199).
4. Mount the D7050DH to the base by turning it
clockwise until it clicks into place (Figure 4).
Figure 4: Mounting the D7050DH on the Base
1
Set the D7050DH’s address using a flat-blade screwdriver to position the rotary switches (Figure 3) located on the back. Note that the switches click when turned.
The valid address range is from 009 to 255. Refer to the D7024 Operation and Installation Guide (P/N: 31499) or the DS9400M Reference Guide (P/N: 44578) for additional address limitations.
Figure 3: Setting the D7050DH Address
A
0
1
2
0
1
B
2
0
1
9 8 7
6
2
3
4
5
0
1
9 8 7
6
2
3
4
5
1 2 3
1 - Hundreds 2 - Tens 3 - Ones A = D7024 FACP, B = DS9400 FACP For example: 0 hundreds, 9 tens, 5 ones = Address 95 on
the D7024 FACP
R2
+1
3-
2
1 - Base contacts (three sets) 2 - Set detector contact here and rotate clockwise
The detector is keyed. Do not force the detector onto the base.
2
Bosch Security Systems, Inc. | 9/06 | 49325E 3
Page 4
D7050DH | Installation Instructions | 6.0 Programming
6.0 Programming
For multiplex programming, refer to the D7024 FACP Operation and Installation Guide (P/N: 31499) or the DS9400M Reference Guide (P/N: 44578).
7.0 Testing
Test detection devices immediately after installation. Test the D7050DH according to NFPA Chapter 7-1.6.2 (1999) or more often as required by local code.
7.1 Operational Testing
Notify all concerned parties before and after completing maintenance on or testing
1. Apply power to the system and check for alarms.
2. If a D7050DH is in alarm, shut down the system.
3. Remove the D7050DH and recheck for proper
4. When the system is free of alarms, check each
5. Test each D7050DH to ensure it causes a control
6. Alarm the D7050DH by doing one of the
7. When a D7050DH alarms, the red LED indicator
the fire alarm system.
wiring. If the problems persist, replace the affected D7050DH or exchange it with a known good detector. This determines if the problem is caused by the D7050DH.
D7050DH to ensure the red LED indicator on the head flashes. This confirms the detector is operating properly.
panel alarm.
following:
a. Place a magnet horizontally against the recess
in the duct cover, centering it over the “T” marked on the head to activate an internal reed switch.
b. Remove the duct cover and use a UL Listed
aerosol smoke detector tester such as the Home Safeguard Industries’ 25S to simulate an alarm. Follow the instructions included in the aerosol smoke detector tester.
on the head flashes at least once per second. Clear the alarm by initiating a system reset before proceeding to the next detector.
7.2 Sensitivity Testing
Calibration is important in determining a detector’s continued operation. Depending
Test the D7050DH’s sensitivity to meet NFPA 72 requirements by conducting a Magnet Test (refer to Section 7.3 Magnet Test). You can also test sensitivity by measuring the calibration voltage pins with D1005 Test Cable, D344-RL, or D344-RT (refer to Section 7.4 Voltage Measurement Test). Calibration can be quickly determined by visually inspecting the D7050DH’s LED (refer to Section 7.2.2 Visual Check). These tests confirm whether or not the detector is within its factory marked calibration range.
7.2.1 Sensitivity Test
The control panel constantly monitors the D7050DH. If the detector exceeds the limits of the sensitivity thresholds, the control panel reports the detector in question and generates a fault condition.
7.2.2 Visual Check
The D7050DH includes the Chamber Check Automatic Trouble Indication that allows it to automatically show if its calibration is out of the factory-listed range. You can meet the NFPA guidelines for sensitivity testing by visually inspecting the D7050DH and checking the Alarm LED flash rate.
If the calibration is out of range during power up or longer than 24 h, the Alarm LED double flashes. This LED single flashes when the detector is operating normally.
on local regulations, calibration testing might be required more than once a year. According to NFPA72, perform a Calibration Test at installation and every other year thereafter. Perform a Functional Test monthly.
Visually check all detectors before disconnecting the multiplex bus. Disconnecting the bus erases the calibration indication. If the detector was disconnected or the control panel lost power within the last 24 h, perform a Magnet Test or Voltage Measurement Test to confirm sensitivity.
4 Bosch Security Systems, Inc. | 9/06 | 49325E
Page 5
.
7.3 Magnet Test
To perform the Magnet Test, the control panel must be in the Fire Walk Test Mode.
1. Hold a magnet horizontally against the recess in
2. Observe the LED. If the D7050DH is within the
3. If the D7050DH is not operating, it does not signal
If the control panel is not in this mode, it sends fire reports to the central station. Refer to your control panel’s reference guide for Fire Walk Test information.
the D343 cover for approximately 10 sec.
factory marked calibration range, it goes into alarm and the Alarm LED flashes at least once per second.
a. If the D7050DH is too sensitive, the Alarm
LED flashes six times rapidly (once every 0.5 sec) and the detector goes into alarm.
b. If the D7050DH is not sensitive enough, the
Alarm LED flashes four times slowly (once every 2 sec) and the detector goes into alarm.
an alarm. Return the detector for repair.
D7050DH | Installation Instructions | 8.0 Maintenance
8.0 Maintenance
Notify all concerned parties before and after completing maintenance on or testing
Clean the detector and base at least once each year using a vacuum or clean dry compressed air. Pay particular attention to the screens. You might need to clean more often in dusty areas or areas of heavy insect concentration.
1. Remove the D343’s cover.
2. Remove the D7050DH from the base and clean
3. Remove the D7050DH’s cover using a thin,
Figure 5: Removing the 7050DH Cover
the fire alarm system.
the base with a clean cloth and common window cleaner.
flat-blade screwdriver to pry the chamber from the cover. Insert the screwdriver into the cover slots and pry off the cover (Figure 5).
7.4 Voltage Measurement Test
1. Plug a D1005 Test Cable (optional) into the
calibration voltage pin.
2. Connect a digital voltmeter to the D1005.
3. Connect the voltmeter’s negative terminal to the
black wire on the D1005 and connect the positive terminal to the red wire. The white wire is not used.
4. If a D344-RL or D344-RT is installed, use the
voltage monitor jacks as described below:
a. The voltage measured by the voltmeter is half
the sensitivity (in %/ft obscuration) of the D7050DH.
b. Multiply the voltage by 2. The result must be
within the factory-marked calibration range printed on the label located on the bottom of the D7050DH.
c. If the D7050DH is outside the factory-marked
calibration range, remove it and clean it. Or replace it as described in Section 7.1 Operational Testing.
d. After cleaning, recheck the calibration voltage
measurement. If the D7050DH is still outside of the factory-marked calibration range, return it for recalibration to:
National Repair Center
130 Perinton Parkway
Fairport, New York 14450
1 2
2
3
4
2
1 - Flat blade screwdriver tip inserted into a cover
slot 2 - Cover slots (3) 3 - Chamber 4 - Cover
4. Remove the cover of the detector chamber. Gently
pull the chamber cover up and away from the chamber (Figure 6)
Figure 6: Removing the D7050 Chamber Cover
Bosch Security Systems, Inc. | 9/06 | 49325E 5
Page 6
D7050DH | Installation Instructions | 9.0 Specifications
5. With the chamber cover removed, clean te inside
of the cover with a vacuum or clean dry compressed air.
Do not clean the D7050DH components with water or any liquid cleaner.
6. Replace the chamber cover and ensure the hole for
the LED is properly aligned over the LED. Place the cover parallel to the chamber and gently snap the locking tabs into place.
7. Replace the D7050DH’s cover, lining up the holes
for the LED.
8. Return the D7050DH to its base and replace the
D343’s cover.
After cleaning, test the D7050DH for proper calibration. Refer to Section 7.0 Testing beginning on page 4.
Do not paint the D7050DH. Paint or other foreign matter covering the screens can stop or delay smoke from entering the detector.
9.0 Specifications
Table 3: column width table
Standby Current
Alarm Current
Minimum Operating Voltage
Power-Up Time
Installation Temperature
Relative Humidity
Required Accessories
Options
Refer to the D343 Installation Instructions (P/N: 48199), the DS9400M Reference Guide (P/N: 44578), and the DS6431 Installation Instructions
(P/N: 41381) Refer to the D343 Installation
Instructions (P/N: 48199), the DS9400M Reference Guide (P/N: 44578), and the DS6431 Installation Instructions
(P/N: 41381) 8 VDC peak
22 sec (maximum)
+32°F to +100°F (0°C to +38°C)
0% to 93% (non-condensing)
D343 Duct Housing and Sample Tube
D344-RT Remote Test D344-RL Remote LED SMK-TM Test Magnet
6 Bosch Security Systems, Inc. | 9/06 | 49325E
Page 7
D7050DH | Installation Instructions |
.
Notes
Bosch Security Systems, Inc. | 9/06 | 49325E 7
Page 8
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450-9199 Customer Service: (800) 289-0096 Technical Support: (888) 886-6189
© 2006 Bosch Security Systems, Inc. 49325E
Loading...