Intrusion Alarm Systems | B440-C Conettix Plug-in Cellular Communicator
B440-C Conettix Plug-in Cellular
Communicator
www.boschsecurity.com
u Secure Conettix IP communication from compatible
Bosch panels to Bosch receivers using Verizon 3G
EVDO/CDMA
The cellular communicator enables 3G EVDO and
CDMA secure two-way IP communication over the
Verizon cellular networks. Typical applications are:
• Alarm reporting to a central station
• Remote panel programming through Remote
Programming Software
• Remote monitoring and control through a mobile
application
• Personal notification using SMS
The cellular communicator is built for a wide variety of
secure commercial and industrial applications. Flexible
end-to-end path supervision, 128-bit to 256-bit AES
encryption and anti-substitution features make cellular
communicator especially suited for use in high security
and fire monitoring applications.
Developed for the military, CDMA technology offers
long service life with resistance to hacking and
jamming. The cellular communicator’s dual technology
radio uses high speed 3G EVDO when available or
switches to CDMA if required.
Note: Cellular capability requires an appropriate data
plan from Bosch.
u Remote programming and monitoring of compatible
Bosch panels
u Personal SMS message and e-mail notification
options
u Direct configuration from Bosch Remote
Programming Software (RPS), eliminating the need
for separate configuration
u Simple LED status information and advanced keypad
diagnostics available
System overview
Callout ᅳ Description Callout ᅳ Description
1 ᅳ Cellular communicator 7 ᅳ Remote PC’s network
connection
2 ᅳ Compatible control panel 8 ᅳ Remote PC running RPS
3 ᅳ Antenna cable 9 ᅳ Personal SMS notification
4 ᅳ Magnetic base antenna 10 ᅳ Ethernet connection

2 | B440-C Conettix Plug-in Cellular Communicator
5 ᅳ Base station on wireless
carrier’s network
6 ᅳ IP network cloud
11 ᅳ Central montoring station
Functions
Conettix IP communication via Cellular
In addition to the security provided by the network
operator, the cellular communicator uses our Conettix
IP protocol that supports:
• Flexible polling intervals
• Resistance to Denial of Service attacks
• 128-bit to 256-bit AES encryption with Cypher Block
Chaining
• Anti-replay/anti-substitution keys
Easy Installation, troubleshooting, and maintenance
• No networking expertise required at field site (no
firewall or router settings)
• No PC or special tools required for installation and
troubleshooting
• Service plans and settings managed through RPS
• Diagnostic LEDs for on-site troubleshooting
LED Function
Blue (heartbeat) System status indicator
Red Unacceptable signal strength
Yellow Marginal signal strength
1 Green Good signal strength
2 Green Very good signal strength
Remote programming of Bosch control panels
The cellular communicator supports secure RPS
programming of compatible Bosch control panels.
Personal notification and control
The cellular communicator supports the Bosch Remote
Security Control mobile application and can be
configured for SMS personal notification reports to
mobile phones or e-mail addresses.
Certifications and approvals
Region Certification
USA Verizon Open Development Certified
Region Certification
USA UL UL 365 - Police Station Connected Bur-
UL UL 636 - Holdup Alarm Units and Sys-
UL UL 864 - Standard for Control Units and
UL UL 985 - Household Fire Warning Sys-
UL UL 1023 - Household Burglar Alarm Sys-
glar Alarm Units
tems
Accessories for Fire Alarm Systems
tem Units
tem Units
Region Certification
UL UL 1076 - Proprietary Burglar Alarm
UL UL 1610 - Central Station Burglar Alarm
CSFM see our website
FCC Part 15 Class B
FDNYCoA
FDNYCoA
FDNYCoA
Units and Systems
Units
6173
6174
6196
Installation/configuration notes
Mounting considerations
The module plugs into any compatible control panel,
available in a variety of enclosures.
Wiring considerations
The module connects to any compatible control panel
without tools or physical wiring for power. When used
with the B450 Conettix Plug-in Communicator
Interface, the B450 is wired to the control panel data
bus. The cellular module has a screw on SMA antenna
connection.
Cellular service considerations
The module is shipped pre-activated for Bosch Cellular
service on the Verizon cellular network. A valid service
contract is required prior to ordering.
Compatibilities
Control panels B9512G/B9512G-E, B8512G/B8512G-E
B6512
B6512/B5512/B4512/B3512, B5512E/
B4512E/B3512E control panel with firmware
v2.03 or higher (direct insertion)
The B440 is compatible with most Bosch control
panels when used with a B450 Conettix Plug-in
Communicator Interface. Refer to the B450
datasheet for complete control panel
compatibility listings.
Cellular EVDO rev A
CDMA2000
1xRTT
Cellular technology compatibility
Device Cellular networks
2G
(CDMA)
B440 * X X
B441 * X
B442 * X
3G
(CDMA)
GPRS
(GSM)
HSPA+
(GSM)

3 | B440-C Conettix Plug-in Cellular Communicator
Represented by:
Europe, Middle East, Africa: Germany: North America: Asia-Pacific:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
emea.securitysystems@bosch.com
emea.boschsecurity.com
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Ring 5
85630 Grasbrunn
Germany
www.boschsecurity.com
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
onlinehelp@us.bosch.com
www.boschsecurity.us
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
© Bosch Security Systems 2016 | Data subject to change without notice
23192484875 | en, V1, 29. Jul 2016
Device Cellular networks
2G
(CDMA)
3G
(CDMA)
GPRS
(GSM)
HSPA+
(GSM)
B443 * X X
*Check for availability in your region.
Parts included
Quantity Component
1 Cellular module
1 Antenna
1 Literature pack
Technical specifications
Electrical
Current
(operating)
Standby: 35 mA
Alarm: 150 mA
Voltage (operating) 12 VDC nominal
Radio Verizon CDMA dual band radio
850 MHz and 1900 MHz
Environmental
Environment Environmental Class III - Indoor
Relative humidity 5 – 93% at +32°C (+90°F) non-condensing
Operating
-10°C to +55°C (+14°F to +131°F)
temperature
Mechanical
Board dimensions 2 in x 3.68 in x 0.60 in (50 mm x 93.5 mm x
15.25 mm)
Antenna (included) • Magnetic base omni-directional
• 8.2 ft (2.5 m) cable with SMA connector
Ordering information
B440-C Conettix Plug-in Cellular Communicator
Dual technology 3G EVDO/CDMA cellular
communicator for secure two-way IP communication
on the Verizon Wireless network. Activate the module
by emailing at: installer.services@us.bosch.com, or by
calling Bosch Installer Services (800-289-0096).
Order number B440-C