Bosch B820 Installation Manual

3.2 | Wire the B820 to the control panel
When you wire a B820 to a control panel, use the control panel SDI2 terminals labeled R, Y, G, B (PWR, A, B, COM). Connect them to the module terminals labeled PWR, A, B, COM. Refer to Figure 3.3.
Figure 3.3: Wiring to the control panel (GV4 Series control panel shown)
CAUTION!
Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage.
2 | SDI2 address settings
The address switch determines the address for the B820 module. The control panel uses the address for communications. Use a slotted screwdriver to set the address switch. Set the address for the module to 1 prior to installing it in the EN4200 housing. Figure
2.1 shows the address switches setting for address 1.
NOTICE!
The module reads the address switch setting only during power up. If you change the switch after you apply power to the module, you must cycle the power to the module in order for the new setting to be enabled.
Figure 2.1: Address switch
After you set the address switch for the proper address, install the module in the EN4200 housing, and then wire the module to the control panel.
3.1 | Install the B820 into the EN4200 housing
Installing the module into the housing:
1. Use a slotted screwdriver to press the housing release tab and separate the housing. Refer to Figure 3.1.
2. Remove the backing from the Velcro piece found in the product packaging to reveal the Velcro adhesive.
3. Place the Velcro’s adhesive side onto the back of the module.
4. Remove the remaining backing to use to secure the module in the housing.
5. Insert the B820 module into the EN4200 housing, connecting the B820’s serial data port to the EN4200’s serial data port. Refer to Figure 3.2.
6. Gently apply pressure to the B820 module to snap it into the housing clips and to apply the Velcro adhesive to the housing.
Figure 3.1: Opening the EN4200 housing
Figure 3.2: Installing the B820 in the EN4200 housing
1 2 3
Callout ― Description
1 ― Housing clips to secure the module
2 ― B820 serial data port
3 ― EN4200 serial data port
3 | Installation
The B820 SDI2 Inovonics Interface Module allows a control panel to interface with an Inovonics EN4200 EchoStream Serial Receiver through the SDI2 bus.
Callout ― Description
1 ― SDI2 Terminal strip (to control panel)
2 ― Serial data port (to Inovonics receiver)
3 ― Address switch
4 ― Heartbeat LED (blue)
5 ― TX (transmit) LED (green)
6 ― RX (receive) LED (green)
Figure 1.1: Module overview
1 | Overview
5
1
6
PWR A B COM
2
3
4
RX
TX
© 2016 Bosch Security Systems, Inc.
F.01U.265.460 | 06 | 2016.08
en Installation Guide
SDI2 Inovonics Interface Module
B820
Bosch Security Systems, Inc.
130 Perinton Parkway Fairport, NY 14450 USA
www.boschsecurity.com
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Ring 5 85630 Grasbrunn Germany
Flash Pattern
Function
Flashes once every 1 second
Normal state. Indicates normal operation state.
3 quick fl ashes every 1 second
Communication error state. Indicates (the module is in a “no communication state”) resulting in an SDI2 communication error.
ON steady LED trouble state. Module
is not powered (for OFF Steady only), or some other trouble condition prohibits the module from controlling the heartbeat LED.
OFF steady
Copyright
This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/.
In the following example, the version 1.4.3 shows as LED fl ashes: [3 second pause] *___****___*** [3 second pause, then normal operation].
Figure 5.1: Firmware LED fl ash patterns
7 | Specifi cations
Dimensions 3.2 in x 2.8 in x 0.60 in
(82.5 mm x 70 mm x
15.25 mm)
Voltage (operating)
12 V nominal
Current (maximum)
110 mA total for B820 module and the EN4200
Operating temperature
+32°F to +122°F (0°C to +50°C)
Relative humidity
5% to 93% at +90°F (+32°C) non-condensing
Terminal wire size
12 AWG to 22 AWG (2 mm to 0.65 mm)
SDI2 wiring Maximum distance -
Wire size: 600 ft (183 m) - 22 AWG (0.65 mm) 1000 ft (305 m) ­18 AWG (1.02 mm) (Unshielded wire only)
Compatibility B9512G/B9512G-E
B8512G/B8512G-E B6512 B5512/B5512E B4512/B4512E B3512/B3512E D9412GV4 D7412GV4 (Each control panel supports one B820.)
6 | Certifi cations
Region
US UL 365 - Police Station
Connected Burglar Alarm Units and Systems
UL 609 - Local Burglar Alarm Units and Systems
UL 636 - Holdup Alarm Units and Systems
UL 985 - Household Fire Warning System Units
UL 1023 - Household Burglar Alarm System Units
UL 1076 - Proprietary Burglar Alarm Units and Systems
UL 1610 - Central Station Burglar Alarm Units
CSFM - California Offi ce of The State Fire Marshall
FCC Part 15 Class B
Canada CAN/ULC S303 - Local Burglar
Alarm Units and Systems
CAN/ULC S304 - Signal Receiving Centre and Premise
ICES-003 - Information Technology Equipment (ITE)
ULC-ORD C1023 - Household Burglar Alarm System Units
ULC-ORD C1076 - Proprietary Burglar Alarm Units and System
5 | Show the fi rmware version
To show the fi rmware version using an LED fl ash pattern:
-
Remove the cover to the EN4200 housing.
Refer to
Section 3.1.
- If you removed the cover previously, press and release the tamper switch spring. The heartbeat LED stays OFF for 3 seconds before indicating the fi rmware version. The LED pulses the major, minor, and micro digits of the fi rmware version, with a 1 second pause after each digit.
4 | LED descriptions
The B820 module includes three LEDs: TX (transmit) LED to indicate data transmission, RX (receive) LED to indicate data receipt, and Heartbeat LED to indicate the status of the SDI2 connection. Refer to Tables 4.1 and 4.2.
Table 4.2: Heartbeat LED descriptions
Flash pattern Function
TX (transmit) ON steady
Occurs when transmitting data to the receiver.
RX (receive) ON steady
Occurs when receiving data from the receiver.
RX (receive) 3 quick fl ashes
Occurs when a wireless device is detected.
Table 4.1: TX and RX LED descriptions
3.3 | Mount the EN4200 housing
Refer to the EN4200 EchoStream Serial Receiver Installation Instructions for
mounting instructions.
Loading...