Bosch B450 Installation Guide

Bosch B450 Installation Guide

1 | Overview

The B450 Bus Communicator Interface Module (wired to a compatible control panel) is a four-wire powered SDI2, SDI, or Option bus device that provides two-way communication over commercial cellular networks using a plug-in communicator.

The B450 on-board rotary switch determines the bus address of the device. Configuration of the B450 is performed via USB or SMS. On SDI2 control panels configuration can also be done on the keypad or through Remote Programming Software (RPS).

Figure 1.1: Board overview

Callout ― Description

1 ― Tamper switch connector

2 ― Address switch

3 ― MODE 2-pin connector (for future use)

4 ― Bus address label

5 ― USB connector

6 ― Heartbeat LED

7 ― RX LED (indicates packets received from the wireless network)

8 ― TX LED (indicates packets transmitted over the wireless network)

9 ― Terminal strip (to control panel bus)

10 ― Interconnect wiring connectors (to control panel bus or other compatible modules)

2 | SDI2 address settings

The address switch determines the bus address for the B450 module. The control panel requires the address for communications. Use a slotted screwdriver to set the address

switch.

NOTICE!

The module reads the address switch setting only during power up. If you change the switch after you apply power to the module, you must cycle the power to the module in order for the new setting to be enabled.

2.1 | Set the B450 address

The B450 address switch determines the bus address of the device. Set the address switch per the control panel configuration. If multiple B450 devices reside on the same

system, each B450 module must have a unique system address, and cannot share the same address value. Figure 2.1 shows the address switch settings for address 01. Refer to Table 2.1 for panel-specific settings.

Figure 2.1: Address switch set to address 1

Control Panels

Switch

Control

Bus

Function

 

Position

Panel

Type

 

 

 

Address

 

 

 

 

 

 

 

USB or SMS

0

n/a

Any

Change

configuration setting

 

 

 

Configuration

 

 

 

 

 

B5512/B4512/B3512/

1

1

SDI2

Automation, RPS,

D9412GV4/D7412GV4/

 

 

 

or Reporting

D7212GV4/

 

 

 

 

Solution 2000/3000

 

 

 

 

 

 

 

 

 

D9412GV4/D7412GV4/

2

2

SDI2

Automation, RPS,

D7212GV4

 

 

 

or Reporting

Solution 2000/3000

 

 

 

 

 

 

 

 

 

D9412GV4/D7412GV4/

4

88

SDI1

RPS or Reporting

D7212GV4/D9412GV3/

 

 

 

 

D7412GV3/D7212GV3

 

 

 

 

D9412GV2/D7412GV2/

 

 

 

 

D7212GV2 v7.06+

 

 

 

 

 

 

 

 

 

D9412GV4/D7412GV4/

5

92

SDI1

RPS or Reporting

D7212GV4

 

 

 

 

D9412GV3/D7412GV3/

 

 

 

 

D7212GV3

 

 

 

 

 

 

 

 

 

AMAX 2000/2100/3000/

6

134

Option

RPS or Reporting

4000

 

 

 

 

CMS 6/8/40

 

 

 

 

Easy Series v3+

 

 

 

 

 

 

 

 

 

FPD-7024 v1.03+

9

250

Option

RPS or Reporting

 

 

 

 

 

1For D9412GV4/D7412GV4/D7212GV4 configurations, SDI2 bus connection is the recommended configuration option, but SDI bus configuration is also supported.

3 | Installation

Perform the following steps to install the B450.

3.1 | Insert the module into the B450

Insert the communication module into the slot of the B450, depending on your communication module (one with a SIM card, or one without). Refer to Figure 3.1.2.

3

3

2

2

1

Figure 3.1.2: Inserting the communication module

Callout ― Description

1 ― SIM card

2 ― B44x cellular communication module (available separately)

3 ― B450

3.2 | Install the module

Mount the B450 into the enclosure’s 3-hole mounting pattern using the supplied mounting screws, and secure the antenna onto the enclosure. Mount the B450 into the interior side of the enclosure. Refer to Figure 3.2.

Figure 3.3: Installing the module

Callout ― Description

1 ― B450

2 ― Enclosure

3 ― Mounting screws (3)

4 ― B44x plug-in cellular communicator antenna (routed through any knock-out)

5 ― B44x plug-in cellular communicator antenna cable (connected to the communication module)

3.3 | Wire to the control panel

When wiring a B450 to a control panel, you can use either the module’s terminal strip labeled with PWR, A, B, and COM or the module’s interconnect wiring connectors (wire included).

Interconnect wiring parallels the PWR, A, B, and COM terminals on the terminal strip. Figure 1.1 indicates the location of both the terminal strip and the interconnect connect connectors on the module.

NOTICE!

UL requires that for security installations, the B450 module be installed in a UL Listed enclosure with a tamper.

NOTICE!

Remove power to the control panel prior to wiring a B450 module to the control panel using either the terminal strip wiring or interconnect cable to wire to the control panel. Do not use both.

Figure 3.3: Using SDI2 terminal strip or SDI2 interconnect cable wiring (B5512 control panel shown).

Callout ― Description

1 ― Control panel (B5512 shown)

2 ― B450 module

3 ― Terminal wiring strip

4 ― Interconnect wiring (P/N: F01U079745) (included)

4 | Configuration

You can configure the B450 using one of the methods described in this section for your control panel type.

4.1 | Plug and play configuration

When installing under the following conditions, the B450 needs no further configuration to communicate:

––AES Encryption is not required.

––Low signal delay can be no more than 200 sec.

4.2| Configuring with SDI2 control panels

An SDI2-compatible control panel automatically configures a connected module.

1.Power off the compatible control panel.

2.Set the address switch to the correct address for the control panel (SDI2 control panels use address 1 or 2).

3.Connect the module to the control panel bus and apply power.

4.Program the control panel communication settings using RPS or the keypad.

4.3 | Configuring with SMS

The B450 supports configuration by SMS. You can send SMS via mobile phone to the B450. For more information, refer to the

B450 Installation and Operation Guide.

NOTICE!

Power up the B450 with the address switch set to the desired bus. When ready to program using SMS, turn the switch to position 0. When done

programming, turn the switch back. Failure to return the address switch to the previous setting will result in a troubled condition.

4.4 | Configuring with USB

The B450 supports configuration by USB. Before you can access the USB interface, you must install the RBUS1CP.inf file on the target PC or laptop. The RBUS1CP.inf file is available on the supplied CD-ROM.

NOTICE!

Power up the B450 with the address switch set to the desired bus. When ready to program using USB, turn the switch to position 0. When done

programming, turn the switch back. Failure to return the address switch to the previous setting will result in a trouble condition.

4.4.1 | Install a communication program

To use USB connection from a computer to the B450 to configure the B450, you must use a terminal emulator software program such as Tera Term, located on the included B450 CDROM.

4.4.2 | Connect via USB cable

Insert one end of the USB cable into the PC or laptop, and insert the other end into the B450 USB port.

NOTICE!

USB connection via the USB cable is only used for temporary configuration programming.

4.4.3 | Log into USB interface

Log into the USB interface and make your selections. For more information, refer to the B450 Installation and Operation Guide.

5 | LED descriptions

The B450 Module includes the following on-board LEDs to assist with troubleshooting issues (refer to Figure 1.1 for the location of the LEDs):

Heartbeat (system status). Refer to Table 5.1.

RX/TX communication. Refer to Table 5.2

Flash pattern

Function

Flashes once every 1 sec

Normal State: Indicates

 

normal operation state.

3 quick flashes every 1 sec

Communication Error

 

State: Indicates a bus

 

communication error with

 

the control panel.

On Steady

Trouble State: Indicates a

 

trouble condition exists.

 

Examine the other LEDs

 

to determine the trouble

 

condition.

Off

LED Trouble State: Module

 

is not powered, or there is a

 

failure in the module. Check

 

for proper installation.

Table 5.1: Heartbeat LED Descriptions

NOTICE!

When the tamper is shorted, the firmware version flashes, then the B450 LEDs are disabled to conserve power. To see the troubleshooting LEDs, open the tamper circuit or jumper.

Flash pattern

Function

RX (Receive) Flashing

Occurs when the module

 

receives a message from

 

over-the-air.

TX (Transmit) Flashing

Occurs when the module

 

receives a message to send

 

out over-the-air.

Table 5.2: RX/TX LEDs Description

6 | Show the firmware version

To review the firmware version using an LED flash pattern, tamper the B450.

Refer to Section 5 for flash patterns.

To tamper the B450, do one of the following:

––If the optional tamper switch is installed:

With the enclosure door open, close the tamper switch.

––If the optional tamper switch is NOT installed: Momentarily short the tamper pins (use a jumper or screwdriver).

When the tamper switch is activated (open to closed), the heartbeat LED stays OFF for 3 sec before indicating the firmware version. The LED pulses the major, minor, and micro digits of the firmware version, with a 1 sec pause after each digit. The following is an example: The version 1.4.3 would be shown as LED flashes:

Figure 6.1: Firmware LED flash patterns example

[3 second pause] *___****___*** [3 second pause, then normal operation].

7 | Certifications

Region

Certification

 

 

US

FCC Part 15 Class B

 

NIST FIPS 197 AES Certification (IP Communications)

 

 

 

UL 365 – Police Station Connected Burglar Alarm Units and

 

Systems

 

 

 

UL 636 – Hold Up Alarm Units and Systems

 

 

 

UL 864 – Control Units and Accessories for Fire Alarm Systems

 

 

 

UL 985 – Household Fire Warning System Units

 

 

 

UL 1023 – Household Burglar Alarm System Units

 

 

 

UL 1076 – Proprietary Burglar Alarm Units and Systems

 

 

 

UL 1610 – Central Station Burglar Alarm Units

 

 

 

SIA CP-01:2010 False Alarm Reduction

 

 

 

California State Fire Marshall (CSFM)

 

 

 

Fire Department of New York (FDNY) Certified

 

 

Canada

CAN/ULC S303 - Local Burglar Alarm Units and Systems

 

CAN/ULC S304 - Signal Receiving Centre and Premise Alarm

 

Control Units

 

 

 

ULC - S545 - Residential Fire Warning System Control Units

 

 

 

ULC-ORD C1023 - Household Burglar Alarm System Units

 

 

 

ULC-ORD C1076 - Proprietary Burglar Alarm Units and

 

Systems

 

 

 

ICES-003 - Digital Apparatus

 

 

Europe

CE - EMC Directive 2004/108/EC EN50130-4, EN61000-6-3,

 

EN60950

Australia

A-Tick - Certified

Brazil

ANATEL - 2708-14-1855

 

 

8 | Specifications

Dimensions

79 mm x 128 mm x 38 mm (3.11 in x 5.03 in x 1.50 in)

(HxWxD)

 

 

 

Voltage

12 VDC nominal

(Operating)

 

 

 

Current

Standby: B450 with B440/B441/B442/B443 = 75mA

(Maximum)

Alarm: B450 with B440/B441/B442/B443 = 180 mA

 

 

USB cable

USB cable (Type A to A male-to-male) - not supplied It is

 

recommended to use Bosch cable B99 (F01U278853)

 

 

Data bus wire size

2 mm to 0.65 mm (12 AWG to 22 AWG)

 

 

Data bus wire

Maximum Distance

length

– wire size: 22 AWG (0.65 mm) --> 12 m (40 ft)

 

18 AWG (1.0 mm) --> 30 m (100 ft)

 

16 AWG (1.3 mm) --> 48 m (158 ft)

 

12 AWG (2.0 mm) --> 122 m (400 ft)

 

Using a separate UL listed power supply, such as the

 

B520 Auxiliary Power Supply Module, connected to the

 

B450 within the specification listed above, the wire

 

distance can be extended up to 300 m (1000 ft)

 

 

Compatibility

B5512/B4512/B3512 control panel

 

D9412GV4/D7412GV4 (v1.00.oxx and up) control panel

 

D9412GV3/D7412GV3/D7212GV3 control panel

 

D9412GV2/D7412GV2/D7212GV2 control panel v7.06+

 

FPD-7024 (v1.03 and higher) control panel

 

AMAX 2000/2100/3000/4000 control panel

 

CMS 6/8/40 control panel

 

Solution 2000/3000

 

Easy Series v3+

 

1B10 enclosure

 

1B11 enclosure

 

1D8103 enclosure

 

1D203 enclosure

Relative humidity

Up to 93% non-condensing

 

 

Temperature

0° to +49° C (+32° to 120° F)

(operating)

 

 

 

1Temporary loss of communication may be caused by static when using anyone of the above enclosures.

8.1 | B450 cellular interface compatibility

Use the following table for cellular interface compatibilities.

 

 

Installed Bus

 

 

 

 

 

 

 

Function

Option/SDI

SDI2

Details

 

IP Event Report-

Y

Y

TCP protocols only sup-

 

ing

 

 

ported on SDI2

 

 

 

 

 

 

Remote Program

Y

Y

Requires Bosch Cellular

 

(RPS or A-link)

 

 

service or other cellular

 

 

 

 

network access

 

 

 

 

 

 

Configure B450

N

Y

GV4/B Series v2.03+

 

from panel

 

 

 

 

(RPS, A-link)

 

 

 

 

 

 

 

 

 

Personal Notifi-

N

Y

Requires compatible con-

 

cation via SMS

 

 

trol panel and cellular plan

 

or Email

 

 

 

 

 

 

 

 

 

Remote Security

N

Y

Requires Bosch Cellular

 

Control App

 

 

service or other cellular

 

 

 

 

network access

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copyright

This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.

Trademarks

All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.

Bosch Security Systems, Inc. product manufacturing dates

Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/.

Conettix Plug-in Communicator Interface

B450

en Quick Start Guide

Bosch Security Systems, Inc.

Bosch Sicherheitssysteme GmbH

130 Perinton Parkway

Robert-Bosch-Ring 5

Fairport, NY 14450

85630 Grasbrunn

USA

Germany

www.boschsecurity.com

 

© 2014 Bosch Security Systems, Inc.

F01U.300.696 | 09 | 2014.12

Loading...