Bosch B450 Installation Guide

1 | Overview
The B450 Bus Communicator Interface Module (wired to a compatible control panel) is a four-wire powered SDI2, SDI, or Option bus device that provides two-way communication over commercial cellular networks using a plug-in communicator.
The B450 on-board rotary switch determines the bus address of the device. Conguration of the B450 is performed via USB or SMS. On SDI2 control panels conguration can also be done on the keypad or through Remote Programming Software (RPS).
2.1 | Set the B450 address
The B450 address switch determines the bus address of the device. Set the address switch per the control panel conguration. If multiple B450 devices reside on the same system, each B450 module must have a unique system address, and cannot share the same address value. Figure 2.1 shows the address switch settings for address 01. Refer to Table 2.1 for panel-specic settings.
NOTICE!
3
3
Remove power to the control panel prior to wiring a B450 module to the control panel using either the terminal strip wiring or interconnect cable to wire to the control panel. Do not use both.
2
2
1
Figure 1.1: Board overview
Callout ― Description
1 ― Tamper switch connector
2 ― Address switch
MODE 2-pin connector (for future use)
3 ―
4 ― Bus address label
5 ― USB connector
6 ― Heartbeat LED
7 ― RX LED (indicates packets received from the wireless network)
8 ― TX LED (indicates packets transmitted over the wireless net-
work)
9 ― Terminal strip (to control panel bus)
Interconnect wiring connectors (to control panel bus or other
10 ―
compatible modules)
2 | SDI2 address settings
The address switch determines the bus address for the B450 module. The control panel requires the address for communications. Use a slotted screwdriver to set the address
switch.
NOTICE!
The module reads the address switch setting only during power up. If you change the switch after you apply power to the module, you must cycle the power to the module in order for the new setting to be enabled.
Figure 2.1: Address switch set to address 1
Control Panels Switch
USB or SMS conguration setting
B5512/B4512/B3512/ D9412GV4/D7412GV4/ D7212GV4/ Solution 2000/3000
D9412GV4/D7412GV4/ D7212GV4 Solution 2000/3000
D9412GV4/D7412GV4/ D7212GV4/D9412GV3/ D7412GV3/D7212GV3 D9412GV2/D7412GV2/ D7212GV2 v7.06+
D9412GV4/D7412GV4/ D7212GV4 D9412GV3/D7412GV3/ D7212GV3
AMAX 2000/2100/3000/ 4000 CMS 6/8/40 Easy Series v3+
FPD-7024 v1.03+ 9 250 Option RPS or Reporting
1
For D9412GV4/D7412GV4/D7212GV4 congurations, SDI2 bus connection is the recommended conguration option, but SDI bus conguration is also supported.
Position
0 n/a Any Change
1 1 SDI2 Automation, RPS,
2 2 SDI2 Automation, RPS,
4 88 SDI
5 92 SDI
6 134 Option RPS or Reporting
Control Panel Address
Bus Type
Function
Conguration
or Reporting
or Reporting
1
RPS or Reporting
1
RPS or Reporting
3 | Installation
Perform the following steps to install the B450.
3.1 | Insert the module into the B450
Insert the communication module into the slot of the B450, depending on your communication module (one with a SIM card, or one without). Refer to Figure 3.1.2.
Figure 3.1.2: Inserting the communication module
Callout ― Description
1 ― SIM card
2 ― B44x cellular communication module (available separately)
3 ― B450
3.2 | Install the module
Mount the B450 into the enclosure’s 3-hole mounting pattern using the supplied mounting screws, and secure the antenna onto the enclosure. Mount the B450 into the interior side of the enclosure. Refer to Figure 3.2.
Figure 3.3: Installing the module
Callout ― Description
1 ― B450
2 ― Enclosure
3 ― Mounting screws (3)
B44x plug-in cellular communicator antenna (routed through
4 ―
any knock-out)
5 ― B44x plug-in cellular communicator antenna cable (connected
to the communication module)
3.3 | Wire to the control panel
When wiring a B450 to a control panel, you can use either the module’s terminal strip labeled with PWR, A, B, and COM or the module’s interconnect wiring connectors (wire included). Interconnect wiring parallels the PWR, A, B, and COM terminals on the terminal strip. Figure 1.1 indicates the location of both the terminal strip and the interconnect connect connectors on the module.
NOTICE!
UL requires that for security installations, the B450 module be installed in a UL Listed enclosure with a tamper.
Figure 3.3: Using SDI2 terminal strip or SDI2 interconnect cable
wiring (B5512 control panel shown).
Callout ― Description
1 ― Control panel (B5512 shown)
2 ― B450 module
3 ― Terminal wiring strip
Interconnect wiring (P/N: F01U079745) (included)
4 ―
4 |
Conguration
You can congure the B450 using one of the methods described in this section for your control panel type.
4.1 |
When installing under the following conditions, the B450 needs no further conguration to communicate:
AES Encryption is not required. Low signal delay can be no more than 200 sec.
4.2 |
Conguring with SDI2 control panels
An SDI2-compatible control panel automatically congures a
connected module.
1. Power off the compatible control panel.
2. Set the address switch to the correct address for the control panel (SDI2 control panels use address 1 or 2).
3. Connect the module to the control panel bus and apply power.
4. Program the control panel communication settings using RPS or the keypad.
4.3 |
Conguring with SMS
The B450 supports conguration by SMS. You can send SMS via mobile phone to the B450. For more information, refer to the
B450 Installation and Operation Guide.
NOTICE!
Power up the B450 with the address switch set to the desired bus. When ready to program using SMS, turn the switch to position 0. When done programming, turn the switch back. Failure to return the address switch to the previous setting will result in a troubled condition.
4.4 |
Conguring with USB
The B450 supports conguration by USB. Before you can access the USB interface, you must install the RBUS1CP.inf le on the target PC or laptop. The RBUS1CP.inf le is available on the supplied CD-ROM.
NOTICE!
Power up the B450 with the address switch set to the desired bus. When ready to program using USB, turn the switch to position 0. When done programming, turn the switch back. Failure to return the address switch to the previous setting will result in a trouble condition.
4.4.1 |
Install a communication program
To use USB connection from a computer to the B450 to congure the B450, you must use a terminal emulator software program such as Tera Term, located on the included B450 CD­ROM.
4.4.2 |
Connect via USB cable
Insert one end of the USB cable into the PC or laptop, and insert the other end into the B450 USB port.
NOTICE!
USB connection via the USB cable is only used for temporary conguration programming.
4.4.3 |
Log into USB interface
Log into the USB interface and make your selections. For more information, refer to the B450 Installation and Operation Guide.
5 |
LED descriptions
The B450 Module includes the following on-board LEDs to assist with troubleshooting issues (refer to Figure 1.1 for the location of the LEDs): – Heartbeat (system status). Refer to Table 5.1. – RX/TX communication. Refer to Table 5.2
Flash pattern Function
Flashes once every 1 sec Normal State: Indicates
normal operation state.
3 quick ashes every 1 sec Communication Error
State: Indicates a bus communication error with the control panel.
On Steady Trouble State: Indicates a
trouble condition exists. Examine the other LEDs to determine the trouble condition.
Off LED Trouble State: Module
is not powered, or there is a failure in the module. Check for proper installation.
Table 5.1: Heartbeat LED Descriptions
NOTICE!
When the tamper is shorted, the rmware version ashes, then the B450 LEDs are disabled to conserve power. To see the troubleshooting LEDs, open the tamper circuit or jumper.
Flash pattern Function
RX (Receive) Flashing Occurs when the module
receives a message from over-the-air.
TX (Transmit) Flashing Occurs when the module
receives a message to send out over-the-air.
Table 5.2: RX/TX LEDs Description
6 | Show the rmware version
To review the rmware version using an LED ash pattern, tamper the B450. Refer to Section 5 for ash patterns. To tamper the B450, do one of the following:
If the optional tamper switch is installed:
With the enclosure door open, close the tamper switch.
If the optional tamper switch is NOT installed:
Momentarily short the tamper pins (use a jumper or
screwdriver). When the tamper switch is activated (open to closed), the heartbeat LED stays OFF for 3 sec before indicating the rmware version. The LED pulses the major, minor, and micro digits of the rmware version, with a 1 sec pause after each digit. The following is an example: The version 1.4.3 would be shown as LED ashes:
Figure 6.1: Firmware LED ash patterns example [3 second pause] *___****___*** [3 second pause, then
normal operation].
7 |
Certications
Region Certication
US
Canada
Europe
Australia
Brazil
FCC Part 15 Class B
NIST FIPS 197 AES Certication (IP Communications)
UL 365 – Police Station Connected Burglar Alarm Units and Systems
UL 636 – Hold Up Alarm Units and Systems
UL 864 – Control Units and Accessories for Fire Alarm Systems
UL 985 – Household Fire Warning System Units
UL 1023 – Household Burglar Alarm System Units
UL 1076 – Proprietary Burglar Alarm Units and Systems
UL 1610 – Central Station Burglar Alarm Units
SIA CP-01:2010 False Alarm Reduction
California State Fire Marshall (CSFM)
Fire Department of New York (FDNY) Certied
CAN/ULC S303 - Local Burglar Alarm Units and Systems
CAN/ULC S304 - Signal Receiving Centre and Premise Alarm Control Units
ULC - S545 - Residential Fire Warning System Control Units
ULC-ORD C1023 - Household Burglar Alarm System Units
ULC-ORD C1076 - Proprietary Burglar Alarm Units and Systems
ICES-003 - Digital Apparatus
CE - EMC Directive 2004/108/EC EN50130-4, EN61000-6-3, EN60950
A-Tick - Certied
ANATEL - 2708-14-1855
8 |
Specications
Dimensions (HxWxD)
Voltage (Operating)
Current (Maximum)
USB cable USB cable (Type A to A male-to-male) - not supplied It is
Data bus wire size 2 mm to 0.65 mm (12 AWG to 22 AWG)
Data bus wire length
Compatibility B5512/B4512/B3512 control panel
Relative humidity Up to 93% non-condensing
Temperature (operating)
1
Temporary loss of communication may be caused by static when using any-
one of the above enclosures.
8.1 |
B450 cellular interface compatibility
79 mm x 128 mm x 38 mm (3.11 in x 5.03 in x 1.50 in)
12 VDC nominal
Standby: B450 with B440/B441/B442/B443 = 75mA Alarm: B450 with B440/B441/B442/B443 = 180 mA
recommended to use Bosch cable B99 (F01U278853)
Maximum Distance – wire size: 22 AWG (0.65 mm) --> 12 m (40 ft) 18 AWG (1.0 mm) --> 30 m (100 ft) 16 AWG (1.3 mm) --> 48 m (158 ft) 12 AWG (2.0 mm) --> 122 m (400 ft) Using a separate UL listed power supply, such as the B520 Auxiliary Power Supply Module, connected to the B450 within the specication listed above, the wire distance can be extended up to 300 m (1000 ft)
D9412GV4/D7412GV4 (v1.00.oxx and up) control panel D9412GV3/D7412GV3/D7212GV3 control panel D9412GV2/D7412GV2/D7212GV2 control panel v7.06+ FPD-7024 (v1.03 and higher) control panel AMAX 2000/2100/3000/4000 control panel CMS 6/8/40 control panel Solution 2000/3000 Easy Series v3+
1
B10 enclosure
1
B11 enclosure
1
D8103 enclosure
1
D203 enclosure
0° to +49° C (+32° to 120° F)
Use the following table for cellular interface compatibilities.
Installed Bus
Function Option/SDI SDI2 Details
IP Event Report­ing
Remote Program (RPS or A-link)
Congure B450 from panel (RPS, A-link)
Personal Noti­cation via SMS or Email
Remote Security Control App
Y Y TCP protocols only sup-
ported on SDI2
Y Y Requires Bosch Cellular
service or other cellular network access
N Y GV4/B Series v2.03+
N Y Requires compatible con-
trol panel and cellular plan
N Y Requires Bosch Cellular
service or other cellular network access
Copyright
This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http://www.boschsecurity.com/datecodes/.
Conettix Plug-in Communicator Interface
B450
en Quick Start Guide
Bosch Security Systems, Inc.
130 Perinton Parkway Fairport, NY 14450 USA
www.boschsecurity.com
© 2014 Bosch Security Systems, Inc. F01U.300.696 | 09 | 2014.12
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Ring 5 85630 Grasbrunn Germany
Loading...