Bosch AL802-WAL Specsheet

Page 1
Fire Alarm Systems | AL802‑WAL NAC Power Extender (8 A)
AL802‑WAL NAC Power Extender (8 A)
www.boschsecurity.com
u Two (2) Class A or four (4) Class B outputs
u Input to Output Follower mode maintains
synchronization of NAC devices
supervision
The AL802‑WAL NAC Power Extender is a cost‑effective 8 A remote power supply and battery charger that can be connected to any 12 VDC or 24 VDC fire alarm control panel (FACP). Its primary application is to provide notification appliance circuit (NAC) expansion support that meets Americans with Disabilities Act (ADA) requirements. It can also be used to provide auxiliary power to support system accessories.
Functions
Battery Backup
There is a built‑in charger for sealed lead‑acid or gel‑type batteries. The enclosure has room for two 12 VDC, 12 Ah batteries. If AC fails, there is automatic switchover (with zero voltage drop on switchover) to standby battery.
Inputs
Power input is 115 VAC, 60 Hz, 1.45 A. There are two normally‑closed (NC) dry contact trigger inputs. The unit is equipped for two Class A or two Class B FACP inputs.
u LEDs indicate prior fault on one or more signaling
circuit outputs
u One auxiliary power output (1 A supply current)
with battery backup
NAC Loop Supervision
In non‑alarm conditions, independent loop supervision for Class A and/or Class B FACP NACs is provided. In the event of a loop trouble, the FACP is notified by the steered input (input 1 or input 2). In addition, there are common trouble output terminals (NC, C, NO) that are used to indicate general loop or system trouble. A common trouble input is provided for optional normally‑closed (NC) devices to report trouble to the FACP. Two FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four outputs. The unit also has Loop Output trouble memory indication to help identify troublesome sporadic problems.
Outputs
The AL802‑WAL delivers electronically regulated and filtered 12 V or 24 V power to Class B or Class A NAC loop circuits. Additionally, a separate 1.0 A auxiliary output for four‑wire smoke detectors is available. The 8 A maximum alarm current can be divided among the four outputs for powering NAC devices. Each output is rated at 2.5 A maximum. The outputs are Class 2 rated power limited outputs with auto reset thermal and short-circuit protection.
Page 2
2 | AL802‑WAL NAC Power Extender (8 A)
Output Programming
Each output can be independently programmed for Steady, Temporal Code 3, or Strobe synchronization. All outputs can be programmed for Input to Output Follower mode.
Paralleling Outputs
An individual output of 4 A can be obtained by paralleling two outputs.
Horn and Strobe Synchronization
The two-wire synchronization mode works with the Gentex Commander GOS Sync Mode 3, 4 and ST/HS series, the System Sensor SpectrAlert series of horns, strobes, and horn strobe combinations, and Cooper Wheelock horns, strobes, and horn strobe combinations to provide a means of synchronizing the temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn strobe combination over a two-wire circuit while leaving the strobes active.
Notice
The AL802‑WAL will synchronize only the horns, horn strobes and strobes that contain synchronization capability.
Technical specifications
Mechanical Properties
Dimensions: 15.5 in. high x 12 in. wide x 4.5 in. deep
(39.4 cm high x 30.5 cm wide x 11.4 cm deep)
Weight: 17 lbs (7.7 kg)
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Ordering information
AL802‑WAL NAC Power Extender (8 A)
8 A remote power supply/battery charger that can be connected to any 12 VDC or 24 VDC FACP
Order number AL802-WAL
Accessories
AL800LGK9E Logic Board
Replacement board used with the AL802‑WAL or AL1002WAL NAC Power Extenders; mounts in enclosure
Order number AL800LGK9E
Certifications and approvals
Altronix Corp. holds these Listings and Approvals:
NFPA Complies with NFPA 72
Region Certification
USA UL UOXX: Control Unit Accessories, System
FM AL802-WAL
CSFM see our website
(UL864)
Parts included
Quant. Component
1 NAC power extender
1 AL802 logic board (AL800LGK9E)
1 Enclosure (red)
1 Cam lock
1 Open‑frame transformer
1 Set of battery leads
1 Hardware pack
1 Literature – Installation Guide
Page 3
3 | AL802‑WAL NAC Power Extender (8 A)
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 203 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 latam.boschsecurity@bosch.com www.boschsecurity.com
© Bosch Security Systems 2015 | Data subject to change without notice 2694222731 | en, V5, 08. Jul 2015