Fire Alarm Systems | AL400UL PD4R Fire Power Supply and Charger
AL400UL PD4R Fire Power Supply and
Charger
www.boschsecurity.com
The Altronix AL400UL PD4R Fire Power Supply converts a 115 V, 60 Hz input to either 4 A of continuous supply current at 12 VDC or 3 A of continuous supply current at 24 VDC. The supply current is distributed through four fuse-protected, Class 2 Rated, power limited outputs.
Certifications and approvals
Region |
Certification |
|
|
|
|
USA |
UL |
ALVY: Access Control System Units (AN- |
|
|
SI/UL 294), APHV: Power Supplies, Bur- |
|
|
glar Alarm System (ANSI/UL 603) ,and |
|
|
UTRZ: Power-supply Units (UL 1481) |
|
|
|
Installation/configuration notes
Battery Considerations
The power supply accommodates up to two 12 VDC, 7 Ah standby batteries and automatically switches to battery power if AC input power fails. When batteries are not used, a loss of AC power results in a loss of output voltage. When batteries are used, they must be lead acid or gel type.
uFour fuse-protected, Class 2 Rated, power limited outputs
u12 VDC or 24 VDC selectable output
uOutputs are filtered and electronically regulated
uMain power input fuse rated at 3.5 A, 250 V
uShort circuit and thermal overload protection
Mounting Considerations
Mount indoors in areas protected from rain or moisture.
Wiring Considerations
Use 14 AWG (ISO 2.5 mm2) or larger wiring for all power connections (battery, DC output, AC input). Use 22 AWG to 18 AWG (ISO 0.34 mm2 to 0.75 mm2) wiring for power limited connections (AC fail, low battery reporting).
Notice
Maintain a minimum of 0.25 inch (0.64 cm) spacing between power limited wiring and wiring that is not power limited (AC input, battery wires).
Parts included
Quant. Component
1Power supply in red enclosure
2 | AL400UL PD4R Fire Power Supply and Charger
1Hardware pack
1Literature pack
Technical specifications
Mechanical Properties
Color: |
|
|
Red |
|
|
|
|
|
|
Dimensions (H x W x D): |
|
|
13 in. X 13.5 in. x x 3.25 in. |
|
|
|
|
|
(33 cm x 34.3 cm x 8.3 cm) |
|
|
|
|
|
Outputs |
|
|
|
|
|
|
|
||
Battery Charging: |
|
Maximum charge rate is 0.7 A |
||
|
|
|
|
|
Number: |
|
Four fused 12 VDC or 24 VDC selectable, |
||
|
|
power limited |
||
|
|
|
|
|
Ratings |
|
|
|
|
|
|
|
||
Fuses: |
|
3.5 A, 250 V |
||
|
|
|
|
|
Power: |
|
4 A at 12 VDC or 3 A at 24 VDC |
||
|
|
|
||
Power Requirements |
||||
|
|
|
||
Current Draw (input): |
|
1.45 A |
||
|
|
|
||
Voltage (supply): |
|
115 VAC, 60 Hz |
||
|
|
|
|
|
Supervision |
|
|
|
|
|
|
|||
AC Fail: |
|
Form C contacts rated for 1 A at 30 VDC. Relay |
||
|
|
normally energized when AC power is present. |
||
|
|
Fail condition report sent approximately 1 min |
||
|
|
after AC power loss. |
||
|
|
|
||
Battery Presence: |
|
Form C contacts rated for 1 A at 30 VDC. Relay |
||
|
|
normally energized when DC power is present. |
||
|
|
Fail condition report sent approximately 3 min |
||
|
|
after battery remains undetected. |
||
|
|
|
||
Low Battery: |
|
Form C contacts rated for 1 A at 30 VDC. Relay |
||
|
|
normally energized. Report sent when DC |
||
|
|
power drops to 10.5 VDC for 12 VDC setting or |
||
|
|
21 VDC for 24 VDC setting. |
||
|
|
|
|
|
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Ordering information
AL400UL PD4R Fire Power Supply and Charger
Converts a 115 V, 60 Hz input to either 4 A of continuous supply current at 12 VDC or 3 A of continuous supply current at 24 VDC
Order number AL400UL-PD4R