Bosch AL400UL-PD4R Specsheet

Bosch AL400UL-PD4R Specsheet

Fire Alarm Systems | AL400UL PD4R Fire Power Supply and Charger

AL400UL PD4R Fire Power Supply and

Charger

www.boschsecurity.com

The Altronix AL400UL PD4R Fire Power Supply converts a 115 V, 60 Hz input to either 4 A of continuous supply current at 12 VDC or 3 A of continuous supply current at 24 VDC. The supply current is distributed through four fuse-protected, Class 2 Rated, power limited outputs.

Certifications and approvals

Region

Certification

 

 

 

USA

UL

ALVY: Access Control System Units (AN-

 

 

SI/UL 294), APHV: Power Supplies, Bur-

 

 

glar Alarm System (ANSI/UL 603) ,and

 

 

UTRZ: Power-supply Units (UL 1481)

 

 

 

Installation/configuration notes

Battery Considerations

The power supply accommodates up to two 12 VDC, 7 Ah standby batteries and automatically switches to battery power if AC input power fails. When batteries are not used, a loss of AC power results in a loss of output voltage. When batteries are used, they must be lead acid or gel type.

uFour fuse-protected, Class 2 Rated, power limited outputs

u12 VDC or 24 VDC selectable output

uOutputs are filtered and electronically regulated

uMain power input fuse rated at 3.5 A, 250 V

uShort circuit and thermal overload protection

Mounting Considerations

Mount indoors in areas protected from rain or moisture.

Wiring Considerations

Use 14 AWG (ISO 2.5 mm2) or larger wiring for all power connections (battery, DC output, AC input). Use 22 AWG to 18 AWG (ISO 0.34 mm2 to 0.75 mm2) wiring for power limited connections (AC fail, low battery reporting).

Notice

Maintain a minimum of 0.25 inch (0.64 cm) spacing between power limited wiring and wiring that is not power limited (AC input, battery wires).

Parts included

Quant. Component

1Power supply in red enclosure

2 | AL400UL PD4R Fire Power Supply and Charger

1Hardware pack

1Literature pack

Technical specifications

Mechanical Properties

Color:

 

 

Red

 

 

 

 

 

Dimensions (H x W x D):

 

 

13 in. X 13.5 in. x x 3.25 in.

 

 

 

 

(33 cm x 34.3 cm x 8.3 cm)

 

 

 

 

 

Outputs

 

 

 

 

 

 

Battery Charging:

 

Maximum charge rate is 0.7 A

 

 

 

 

Number:

 

Four fused 12 VDC or 24 VDC selectable,

 

 

power limited

 

 

 

 

 

Ratings

 

 

 

 

 

 

Fuses:

 

3.5 A, 250 V

 

 

 

 

Power:

 

4 A at 12 VDC or 3 A at 24 VDC

 

 

 

Power Requirements

 

 

 

Current Draw (input):

 

1.45 A

 

 

 

Voltage (supply):

 

115 VAC, 60 Hz

 

 

 

 

Supervision

 

 

 

 

 

AC Fail:

 

Form C contacts rated for 1 A at 30 VDC. Relay

 

 

normally energized when AC power is present.

 

 

Fail condition report sent approximately 1 min

 

 

after AC power loss.

 

 

 

Battery Presence:

 

Form C contacts rated for 1 A at 30 VDC. Relay

 

 

normally energized when DC power is present.

 

 

Fail condition report sent approximately 3 min

 

 

after battery remains undetected.

 

 

 

Low Battery:

 

Form C contacts rated for 1 A at 30 VDC. Relay

 

 

normally energized. Report sent when DC

 

 

power drops to 10.5 VDC for 12 VDC setting or

 

 

21 VDC for 24 VDC setting.

 

 

 

 

 

Trademarks

All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.

Ordering information

AL400UL PD4R Fire Power Supply and Charger

Converts a 115 V, 60 Hz input to either 4 A of continuous supply current at 12 VDC or 3 A of continuous supply current at 24 VDC

Order number AL400UL-PD4R