Baldor ID15H201-E, ID15H202-W, ID15H201-W, ID15H202-E, ID15H203-E Installation & Operating Manual

...
0 (0)
ADJUSTABLE SPEED DRIVE
SERIES 15H
Inverter Control
Installation & Operating Manual
2/01 MN715
Table of Contents
Quick Start Guide 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quick Start Checklist 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quick Start Procedure 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 2
General Information 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CE Compliance 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Limited W arranty 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Notice 2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 3
Receiving & Installation 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Receiving & Inspection 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Physical Installation 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Installation 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Through the Wall Mounting 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Keypad Installation 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Remote Keypad Installation 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Installation 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Grounding 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Line Impedance 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Line Reactors 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load Reactors 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Main Circuit 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Disconnect 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protective Devices 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wire Size and Protection Devices 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Line Connections 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reduced Input Voltage Derating 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
380-400VAC Operation 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Phase Installation 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single Phase Input Power Considerations 3-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single Phase Control Derating 3-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size A, B and B2 Single Phase Power Installation 3-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size C2 Single Phase Power Installation 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size C and D Single Phase Power Installation 3-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size D2 Single Phase Power Installation 3-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size E Single Phase Power Installation 3-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size F Single Phase Power Installation 3-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Brake Connections 3-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Connections 3-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
M-Contactor 3-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Dynamic Brake Hardware 3-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents iMN715
Selection of Operating Mode 3-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Inputs and Outputs 3-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Serial Operating Mode 3-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Keypad Operating Mode 3-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard Run 3 Wire Operating Mode 3-27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15 Speed 2-Wire Operating Mode 3-28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan Pump 2 Wire Operating Mode 3-29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan Pump 3 Wire Operating Mode 3-30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Speed Analog 2 Wire Operating Mode 3-31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Speed Analog 3 Wire Operating Mode 3-32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electronic Pot 2 Wire Operating Mode 3-33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electronic Pot 3 Wire Operating Mode 3-34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Process Operating Mode 3-35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External Trip Input 3-36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Opto-Isolated Inputs 3-36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Opto-Isolated Outputs 3-37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay Outputs 3-38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pre-Operation Checklist 3-39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Up Procedure 3-39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 4
Programming and Operation 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Mode 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting Display Contrast 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Screens 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Mode 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Blocks Access for Programming 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing Parameter Values when Security Code Not Used 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reset Parameters to Factory Settings 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initialize New Software EEPROM 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation Examples 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating the Control from the Keypad 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessing the Keypad JOG Command 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Speed Adjustment using Local Speed Reference 4-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Speed Adjustment Using Arrow Keys 4-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Security System Changes 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing Parameter Values with a Security Code in Use 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Security System Access Timeout Parameter Change 4-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Definitions 4-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii Table of Contents MN715
Troubleshooting 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
No Keypad Display - Display Contrast Adjustment 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Access Diagnostic Information 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initialize New Software EEPROM 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Access the Fault Log 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Clear the Fault Log 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initialize New Software EEPROM 5-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Base ID 5-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Noise Considerations 5-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay and Contactor Coils 5-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wires between Controls and Motors 5-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Drive Situations 5-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Enclosures 5-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Motor Considerations 5-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Signal Wires 5-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 6
Specifications and Product Data 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications: 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Conditions: 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Keypad Display: 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Specifications: 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Inputs: 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Outputs: 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Digital Inputs: 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Digital Outputs: 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic Indications: 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ratings 6-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal Tightening Torque Specifications 6-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continued on next page
Table of Contents iiiMN715
Mounting Dimensions 6-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size A Control 6-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size A Control – Through–Wall Mounting 6-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size B Control 6-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size B Control – Through–Wall Mounting 6-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size B2 Control 6-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size C Control 6-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size C2 Control 6-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size C2 Control – Through–Wall Mounting 6-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size D Control 6-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size D2 Control 6-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size D2 Control – Through–Wall Mounting 6-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size E Control 6-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size E Control – Through–Wall Mounting 6-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size F Control 6-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size F Control – Through–Wall Mounting 6-27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size G Control 6-29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size G2 Control 6-30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size G+ Control 6-31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Size H Control 6-32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dynamic Braking (DB) Hardware A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RGA Assemblies A-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RBA Assemblies A-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RTA Assemblies A-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix B B-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Values B-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix C C-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Keypad Mounting Template C-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iv Table of Contents MN715
Section 1 Quick Start Guide
Overview If you are an experienced user of Baldor controls, you are probably already familiar with
the keypad programming and keypad operation methods. If so, this quick start guide has been prepared for you. This procedure will help get your system up and running in the keypad mode quickly and will allow motor and control operation to be verified. This procedure assumes that the Control, Motor and Dynamic Brake hardware are correctly installed (see Section 3 for procedures) and that you have an understanding of the keypad programming & operation procedures. It is not necessary to wire the terminal strip to operate in the Keypad mode (Section 3 describes terminal strip wiring procedures). The quick start procedure is as follows:
1. Read the Safety Notice and Precautions in section 2 of this manual.
2. Mount the control. Refer to Section 3, “Physical Location” procedure.
3. Connect AC power. Refer to Section 3 “AC Line Connections”.
4. Connect the motor. Refer to Section 3, Motor Connections”.
5. Install Dynamic brake hardware, if required. Refer to Section 3, Optional Dynamic Brake Hardware.
6. Plug in the keypad. Refer to Section 3, “Keypad Installation” procedure.
Quick Start Checklist Check of electrical items.
1. Verify AC line voltage at source matches control rating.
2. Inspect all power connections for accuracy, workmanship and tightness as well as compliance to codes.
3. Verify control and motor are grounded to each other and the control is connected to earth ground.
4. Check all signal wiring for accuracy.
5. Be certain all brake coils, contactors and relay coils have noise suppression. This should be an R-C filter for AC coils and reverse polarity diodes for DC coils. MOV type transient suppression is not adequate.
Check of Motors and Couplings
1. Verify freedom of motion of motor shaft.
2. Verify that the motor coupling is tight without backlash.
3. Verify the holding brakes if any, are properly adjusted to fully release and set to the desired torque value.
Quick Start Guide 1-1MN715
Section 1 General Information
Quick Start Procedure The following procedure will help get your system up and running in the keypad mode
quickly, and will allow you to prove the motor and control operation. This procedure assumes that the Control, Motor and Dynamic Brake hardware are correctly installed (see Section 3 for procedures) and that you have an understanding of the keypad programming & operation procedures.
Initial Conditions
Be sure the Control (Physical Installation & AC Line Connections), Motor and Dynamic Brake hardware are wired according to the procedures in Section 3 of this manual. Become familiar with the keypad programming and keypad operation of the control as described in Section 4 of this manual.
WARNING: Make sure that unexpected operation of the motor shaft during start
up will not cause injury to personnel or damage to equipment.
1. Verify that any enable inputs to J4-8 are open.
2. Turn power on. Be sure no faults are displayed on the keypad display.
3. Set the Level 1 Input block, Operating Mode to “Keypad”.
4. Be sure the Level 2 Protection block, Local Enable INP parameter is OFF and the Level 2 Protection block, External Trip parameter is OFF.
5. Set the Level 2 Output Limits block, “Operating Zone” parameter as desired (STD CONST TQ, STD VAR TQ, QUIET CONST TQ or QUIET VAR TQ).
6. Set the Level 2 Output Limits block, “MIN Output FREQ” parameter.
7. Set the Level 2 Output Limits block, “MAX Output FREQ” parameter .
Note: JP1 is in position 2–3 as shipped from the factory (<120Hz operation).
For operation with MAX Output FREQ >120Hz, change the position of JP1 to pins 1–2. Refer to Section 3 for jumper location.
8. If the desired peak current limit setting is different than is automatically set by the Operating Zone, set the Level 2 Output Limits block, PK Current Limit parameter as desired.
9. Enter the following motor data in the Level 2 Motor Data block parameters: Motor Voltage (input) Motor Rated Amps (FLA) Motor Rated Speed (base speed) Motor Rated Frequency Motor Mag Amps (no load current)
10. If External Dynamic Brake hardware is used, set the Level 2 Brake Adjust block, Resistor Ohms and Resistor Watts parameters.
11. Set the Level 1 V/HZ Boost block, V/HZ Profile parameter for the correct V/Hz ratio for your application.
12. If the load is a high initial starting torque type, the torque boost and Accel time may need to be increased. Set the Level 1 V/HZ Boost block, Torque Boost and the Level 1 Accel/Decel Rate block, ACCEL TIME #1 as required.
13. Select and program additional parameters to suit your application.
The control is now ready for use in keypad mode or the terminal strip may be wired and the programming changed for another operating mode.
1-2 Quick Start Guide MN715
Section 2 General Information
Overview The Baldor Series 15H control is a PWM inverter motor control. The control converts AC
line power to fixed DC power. The DC power is then pulse width modulated into synthesized three-phase AC line voltage for the motor. In this way, the control converts the fixed input frequency to variable output frequency to cause the motor to have variable speed operation.
The rated horsepower of the control is based on a NEMA design B four pole motor and 60Hz operation at nominal rated input voltage. If any other type of motor is used, or input voltage other than 230, 460 or 575 VAC is applied to the input terminals, the control should be sized to the motor using the rated current of the motor.
The Baldor Series 15H control may be used in many different applications. It may be programmed by the user to operate in four different operating zones; standard constant torque, standard variable torque, quiet constant torque or quiet variable torque. It can also be configured to function in a number of operating modes for custom operation.
It is the responsibility of the user to determine the optimum operating zone and operating mode for the application. These choices are programmed using the keypad as explained in the programming section of this manual.
CE Compliance A custom unit may be required, contact Baldor. Compliance to Directive 89/336/EEC is
the responsibility of the system integrator. A control, motor and all system components must have proper shielding grounding and filtering as described in MN1383. Please refer to MN1383 for installation techniques for CE compliance.
General Information 2-1MN715
Limited Warranty
For a period of two (2) years from the date of original purchase, BALDOR will repair or replace without charge controls and accessories which our examination proves to be defective in material or workmanship. This warranty is valid if the unit has not been tampered with by unauthorized persons, misused, abused, or improperly installed and has been used in accordance with the instructions and/or ratings supplied. This warranty is in lieu of any other warranty or guarantee expressed or implied. BALDOR shall not be held responsible for any expense (including installation and removal), inconvenience, or consequential damage, including injury to any person or property caused by items of our manufacture or sale. (Some states do not allow exclusion or limitation of incidental or consequential damages, so the above exclusion may not apply.) In any event, BALDOR’s total liability, under all circumstances, shall not exceed the full purchase price of the control. Claims for purchase price refunds, repairs, or replacements must be referred to BALDOR with all pertinent data as to the defect, the date purchased, the task performed by the control, and the problem encountered. No liability is assumed for expendable items such as fuses.
Goods may be returned only with written notification including a BALDOR Return Authorization Number and any return shipments must be prepaid.
2-2 General Information MN715
Safety Notice: This equipment contains voltages that may be as great as 1000 volts! Electrical shock
can cause serious or fatal injury. Only qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
This equipment may be connected to other machines that have rotating parts or parts that are driven by this equipment. Improper use can cause serious or fatal injury. Only qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
PRECAUTIONS:
WARNING: Do not touch any circuit board, power device or electrical
connection before you first ensure that power has been disconnected and there is no high voltage present from this equipment or other equipment to which it is connected. Electrical shock can cause serious or fatal injury. Only qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
WARNING: Be sure that you are completely familiar with the safe operation of
this equipment. This equipment may be connected to other machines that have rotating parts or parts that are controlled by this equipment. Improper use can cause serious or fatal injury. Only qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
WARNING: Do not use motor overload relays with an automatic reset feature.
These are dangerous since the process may injure someone if a sudden or unexpected automatic restart occurs. If manual reset relays are not available, disable the automatic restart feature using external control wiring.
WARNING: This unit has an automatic restart feature that will start the motor
whenever input power is applied and a RUN (FWD or REV) command is issued and maintained. If an automatic restart of the motor could cause injury to personnel, the automatic restart feature should be disabled by changing the Restart Auto/Man parameter to MANUAL.
WARNING: Be sure the system is properly grounded before applying power.
Do not apply AC power before you ensure that grounds are connected. Electrical shock can cause serious or fatal injury.
WARNING: Do not remove cover for at least five (5) minutes after AC power is
disconnected to allow capacitors to discharge. Electrical shock can cause serious or fatal injury.
WARNING: Improper operation of control may cause violent motion of the
motor shaft and driven equipment. Be certain that unexpected motor shaft movement will not cause injury to personnel or damage to equipment. Peak torque of several times the rated motor torque can occur during control failure.
WARNING: Motor circuit may have high voltage present whenever AC power is
applied, even when motor is not rotating. Electrical shock can cause serious or fatal injury.
Continued on next page.
General Information 2-3MN715
Section 1 General Information
WARNING: Dynamic brake resistors may generate enough heat to ignite
combustible materials. Keep all combustible materials and flammable vapors away from brake resistors.
Caution: Suitable for use on a circuit capable of delivering not more than the
RMS symmetrical short circuit amperes listed here at rated voltage. Horsepower RMS Symmetrical Amperes 1–50 5,000 51–200 10,000 201–400 18,000 401–600 30,000 601–900 42,000
Caution: Do not supply any power on the External Trip (motor thermostat)
leads at J4-16 or J4-17 as the control may be damaged. Use a dry contact type that requires no external power to operate.
Caution: Disconnect motor leads (T1, T2 and T3) from control before you
perform a Megger test on the motor. Failure to disconnect motor from the control will result in extensive damage to the control. The control is tested at the factory for high voltage / leakage resistance as part of Underwriter Laboratory requirements.
Caution: Do not connect AC power to the Motor terminals T1, T2 and T3.
Connecting AC power to these terminals may result in damage to the control.
Caution: Baldor recommends not using “Grounded Leg Delta” transformer
power leads that may create ground loops and provide unstable power to the motor controller. Instead, we recommend using a four wire Wye.
Caution: If the DB hardware mounting is in any position other than vertical,
the DB hardware must be derated by 35% of its rated capacity.
2-4 General Information MN715
Section 3 Receiving & Installation
Receiving & Inspection When you receive your control, there are several things you should do immediately.
1. Observe the condition of the shipping container and report any damage immediately to the commercial carrier that delivered your control.
2. Verify that the control you received is the same as listed on your purchase order.
3. If the control is to be stored for several weeks before use, be sure that it is stored in a location that conforms to published storage specifications. (Refer to Section 6 of this manual).
Physical Installation The mounting location of the control is important. It should be installed in an area that is
protected from direct sunlight, corrosives, harmful gases or liquids, dust, metallic particles, and vibration.
Several other factors should be carefully evaluated when selecting a location for installation:
1. For effective cooling and maintenance, the control should be mounted on a smooth, non-flammable vertical surface. Table 3-1 lists the Watts Loss ratings for enclosure sizing.
2. At least two inches clearance must be provided on all sides for airflow.
3. Front access must be provided to allow the control cover to be opened or removed for service and to allow viewing of the Keypad Display.
4. Altitude derating. Up to 3300 feet (1000 meters), no derating required. Above 3300 feet, derate peak output current by 2% for each 1000 feet above 3300 feet.
5. Temperature derating. Up to 40°C, no derating required. Above 40°C, derate peak output current by 2% per °C above 40°C. Maximum ambient is 55°C.
Table 3-1 Series 15H Watts Loss Ratings
Enclosure Size 230VAC 460VAC 575VAC
2.5kHz PWM 8.0kHz PWM 2.5kHz PWM 8.0kHz PWM 2.5kHz PWM 8.0kHz PWM
A, B and B2 14 Watts/
Amp
C, C2, D, D2, E and F 12 Watts/
Amp
G 15 Watts/
H 15 Watts/
17 Watts/
Amp
15 Watts/
Amp
17 Watts/
Amp
15 Watts/
Amp
Amp
Amp
26 Watts/
Amp
23Watts/
Amp
18 Watts/
Amp
19Watts/
Amp
19Watts/
Amp
28 Watts/
Amp
29 Watts/
Amp
Receiving & Installation 3-1MN715
Section 1 General Information
Control Installation The control must be securely fastened to the mounting surface at the mounting holes.
Shock Mounting
If the control will be subjected to levels of shock greater than 1G or vibration greater than
0.5G at 10 to 60Hz, the control should be shock mounted.
Through the Wall Mounting
Control sizes A, B, B2, C2, D2, E and F are designed for panel or through the wall installation. To mount a control through the wall, a Through the Wall mounting kit must be purchased (except for B2, C2 and D2 sizes). These kits are:
Kit No.
KT0000A00 Size A control through the wall mounting kit. KT0001A00 Size B control through the wall mounting kit. V0083991 Size E control through the wall mounting kit. V0084001 Size F control through the wall mounting kit.
Refer to Section 6 of this manual for drawings and dimensions of the through the wall mounting kits.
Keypad Installation
Procedure:
1. Refer to the Remote Keypad Installation procedure and mount the keypad.
2. Connect the keypad cable to the keypad connector of the main control board.
Description
3-2 Receiving & Installation MN715
Section 1 General Information
Optional Remote Keypad Installation The keypad may be remotely mounted using optional Baldor keypad
extension cable. Keypad assembly (white - DC00005A-01; gray - DC00005A-02) comes complete with the screws and gasket required to mount it to an enclosure. When the keypad is properly mounted to a NEMA Type 4X enclosure, it retains the Type 4X rating.
Tools Required:
Center punch, tap handle, screwdrivers (Phillips and straight) and crescent wrench.
8-32 tap and #29 drill bit (for tapped mounting holes) or #19 drill (for clearance mounting holes).
1
1-
RTV sealant.
(4) 8-32 nuts and lock washers.
Extended 8-32 screws (socket fillister) are required if the mounting surface is
Remote keypad mounting template. A tear out copy is provided at the end of
Mounting Instruction: For tapped mounting holes
1. Locate a flat 4 wide x 5.5 minimum high mounting surface. Material should
2. Place the template on the mounting surface or mark the holes as shown.
3. Accurately center punch the 4 mounting holes (marked A) and the large
4. Drill four #29 mounting holes (A). Thread each hole using an 8-32 tap.
5. Locate the 1-1/4″ knockout center (B) and punch using the manufacturers
6. Debur knockout and mounting holes making sure the panel stays clean and flat.
7. Apply RTV to the 4 holes marked (A).
8. Assemble the keypad to the panel. Use 8–32 screws, nuts and lock washers.
9. From the inside of the panel, apply RTV over each of the four mounting screws
Mounting Instructions: For clearance mounting holes
1. Locate a flat 4 wide x 5.5 minimum high mounting surface. Material should
2. Place the template on the mounting surface or mark the holes as shown on the
3. Accurately center punch the 4 mounting holes (marked A) and the large
4. Drill four #19 clearance holes (A).
5. Locate the 1-1/4″ knockout center (B) and punch using the manufacturers
6. Debur knockout and mounting holes making sure the panel stays clean and flat.
7. Apply RTV to the 4 holes marked (A).
8. Assemble the keypad to the panel. Use 8–32 screws, nuts and lock washers.
9. From the inside of the panel, apply RTV over each of the four mounting screws
/4″ standard knockout punch (1-11/16″ nominal diameter).
thicker than 12 gauge and is not tapped (clearance mounting holes). this manual for your convenience. (Photo copy or tear out.)
be sufficient thickness (14 gauge minimum).
knockout (marked B).
instructions.
and nuts. Cover a 3/4″ area around each screw while making sure to completely encapsulate the nut and washer.
be sufficient thickness (14 gauge minimum). template. knockout (marked B).
instructions.
and nuts. Cover a 3/4″ area around each screw while making sure to completely encapsulate the nut and washer.
Receiving & Installation 3-3MN715
Section 1 General Information
Electrical Installation To make electrical connections, use UL listed closed loop connectors that are of
appropriate size for wire gauge being used. Connectors are to be installed using crimp tool specified by the manufacturer of the connector. Only Class 1 wiring should be used.
Baldor Series H controls feature UL approved adjustable motor overload protection suitable for motors rated at no less than 50% of the output rating of the control. Other governing agencies such as NEC may require separate over-current protection. The installer of this equipment is responsible for complying with the National Electric Code and any applicable local codes which govern such practices as wiring protection, grounding, disconnects and other current protection.
System Grounding Baldor Controls are designed to be powered from standard three phase lines that are
electrically symmetrical with respect to ground. System grounding is an important step in the overall installation to prevent problems. The recommended grounding method is shown in Figure 3-1.
Figure 3-1 Recommended System Grounding
LOCAL
PROG
JOG
DISP
FWD
SHIFT
ENTER
REV
RESET
STOP
AC Main Supply
Safety
Ground
Note: A line reactor is recommended
and must be ordered separately.
L1
L2
L3 Earth
Four Wire
Wye Driven Earth Ground Rod
(Plant Ground)
Route all 4 wires L1, L2, L3 and Earth (Ground) together in conduit or cable.
Route all 4 wires T1, T2, T3 and Motor Ground together in conduit or cable.
Connect all wires (including motor ground) inside the motor terminal box.
Line Reactor
Series H
L1
L2 L3 T1 T2 T3
Note: A load reactor is recommended
and must be ordered separately.
Load
Reactor
Ground per NEC and Local codes.
3-4 Receiving & Installation MN715
Section 1 General Information
System Grounding Continued
Ungrounded Distribution System
With an ungrounded power distribution system it is possible to have a continuous current path to ground through the MOV devices. To avoid equipment damage, an isolation transformer with a grounded secondary is recommended. This provides three phase AC power that is symmetrical with respect to ground.
Input Power Conditioning
Baldor controls are designed for direct connection to standard three phase lines that are electrically symmetrical with respect to ground. Certain power line conditions must be avoided. An AC line reactor or an isolation transformer may be required for some power conditions.
If the feeder or branch circuit that provides power to the control has
permanently connected power factor correction capacitors, an input AC line reactor or an isolation transformer must be connected between the power factor correction capacitors and the control.
If the feeder or branch circuit that provides power to the control has power
factor correction capacitors that are switched on line and off line, the capacitors must not be switched while the control is connected to the AC power line. If the capacitors are switched on line while the control is still connected to the AC power line, additional protection is required. TVSS (Transient Voltage Surge Suppressor) of the proper rating must be installed between the AC line reactor or an isolation transformer and the AC input to the control.
Line Impedance The Baldor control requires a minimum line impedance. If the impedance of the incoming
power does not meet the requirement for the control, a 3 phase line reactor can be used to provide the needed impedance in most cases. Line reactors are optional and are available from Baldor.
Control Size A, B, C, D, E B2, C2, D2, F, G, G2, G+, H Line Impedance Required 3% 1%
The input impedance of the power lines can be determined as follows:
Measure the line to line voltage at no load and at full rated load. Use these measured values to calculate impedance as follows:
%Impedance +
(Volts
No Load Speed
(Volts
* Volts
No Load Speed
Full Load Speed
)
)
100
Line Reactors Three phase line reactors are available from Baldor. The line reactor to order is based on
the full load current of the motor (FLA). If providing your own line reactor, use the following formula to calculate the minimum inductance required.
(V
0.03)
L +
L*L
(I 3Ǹ 377)
Where: L Minimum inductance in Henries.
V
L-L
0.03 Desired percentage of input impedance. I Input current rating of control. 377 Constant used with 60Hz power.
Input volts measured line to line.
Use 314 if input power is 50Hz.
Load Reactors Line reactors may be used at the control output to the motor. When used this way, they
are called Load Reactors. Load reactors serve several functions that include:
Protect the control from a short circuit at the motor. Limit the rate of rise of motor surge currents. Slowing the rate of change of power the control delivers to the motor.
Load reactors should be installed as close to the control as possible. Selection should be based on the motor nameplate FLA value.
Receiving & Installation 3-5MN715
AC Main Circuit
Power Disconnect A power disconnect should be installed between the input power service and the control
for a fail safe method to disconnect power. The control will remain in a powered-up condition until all input power is removed from the control and the internal bus voltage is depleted.
Protective Devices Recommended fuse sizes are based on the following:
115% of maximum continuous current for time delay. 150% of maximum continuous current for Fast or Very Fast action.
Note: These general size recommendations do not consider harmonic currents or
ambient temperatures greater than 40°C.
Be sure a suitable input power protection device is installed. Use the recommended circuit breaker or fuses listed in tables 3-2 through NO TAG (Wire Size and Protection Devices). Input and output wire size is based on the use of copper conductor wire rated at 75 °C. The table is specified for NEMA B motors.
Circuit Breaker: 1 phase, thermal magnetic.
Equal to GE type THQ or TEB for 230VAC 3 phase, thermal magnetic.
Equal to GE type THQ or TEB for 230VAC or Equal to GE type TED for 460VAC and 575VAC.
Fast Action Fuses: 230VAC, Buss KTN
460VAC, Buss KTS to 600A (KTU for 601 to 1200A) 575VAC, Buss FRS TO 600A (KTU for 601 to 1200A)
Very Fast Action: 230VAC, Buss JJN
460VAC, Buss JJS 575VAC, Buss JJS
Time Delay Fuses: 230VAC, Buss FRN
460VAC, Buss FRS to 600A (KTU for 601 to 1200A) 575VAC, Buss FRS to 600A (KLU for 601 to 1200A)
Wire Size and Protection Devices
Table 3-2 230VAC Controls (3 Phase) Wire Size and Protection Devices
Control Rating
Amps HP
3 0.75 7 5 4 14 2.5 4 1 7 6 5 14 2.5
7 2 15 12 9 14 2.5 10 3 15 15 12 14 2.5 16 5 20 25 20 12 3.31 22 7.5 30 35 30 10 5.26 28 10 40 45 35 8 8.37 42 15 60 70 60 6 13.3 54 20 70 80 70 6 13.3 68 25 90 100 90 4 21.2 80 30 100 125 110 3 26.7
104 40 150 175 150 1 42.4 130 50 175 200 175 1/0 53.5 145 60 200 225 200 2/0 67.4 192 75 250 300 250 4/0 107.0
Input Breaker
Input Breaker
(Amps)
Input Fuse (Amps) Wire Gauge
Fast Acting Time Delay AWG mm
2
Note: All wire sizes are based on 75°C copper wire. Higher temperature smaller gauge wire may be used per NEC
and local codes. Recommended fuses/breakers are based on 40°C ambient, maximum continuous control output current and no harmonic current.
3-6 Receiving & Installation MN715
T able 3-3 460VAC Controls (3 Phase) Wire Size and Protection Devices
Control Rating Input Breaker Input Fuse (Amps) Wire Gauge
Amps HP
2 0.75 3 2 2 14 2.5 2 1 3 3 2.5 14 2.5 4 2 7 5 4.5 14 2.5 5 3 7 8 6.3 14 2.5
8 5 15 12 10 14 2.5 11 7.5 15 17.5 15 14 2.5 14 10 20 20 17.5 12 3.31 21 15 30 30 25 10 5.26 27 20 40 40 35 10 5.26 34 25 50 50 45 8 8.37 40 30 50 60 50 8 8.37 52 40 70 80 70 6 13.3 65 50 90 100 90 4 21.2 77 60 100 125 100 3 26.7 96 75 125 150 125 2 33.6
124 100 175 200 175 1/0 53.5 156 125 200 250 200 2/0 67.4 180 150 225 300 250 3/0 85.0 240 200 300 350 300 (2) 2/0 (2) 67.4 302 250 400 450 400 (2) 4/0 (2) 107.0 361 300 450 600 450 (3) 2/0 (3) 67.4 414 350 500 650 500 (3) 3/0 (3) 85.0 477 400 600 750 600 (3) 4/0 (3) 107.0 515 450 650 800 700 (3) 250MCM (3) 127.0 590 500 750 900 800 (3) 300MCM (3) 152.0
(Amps)
Fast Acting Time Delay AWG mm
2
Note: All wire sizes are based on 75°C copper wire. Higher temperature smaller gauge wire may be used per NEC
and local codes. Recommended fuses/breakers are based on 40°C ambient, maximum continuous control output current and no harmonic current.
Receiving & Installation 3-7MN715
Table 3-4 575VAC Controls (3 Phase) Wire Size and Protection Devices
Control Rating Input Breaker Input Fuse (Amps) Wire Gauge
Amps HP
1.1 0.75 3 2 1.5 14 2.5
1.4 1 3 2.5 2 14 2.5
2.7 2 7 4 3.5 14 2.5
3.9 3 7 6 5 14 2.5
6.1 5 15 10 8 14 2.5
9.0 7.5 15 15 12 14 2.5 11 10 15 17.5 15 14 2.5 17 15 25 30 25 12 3.31 22 20 30 35 30 10 5.26 27 25 40 40 35 10 5.26 32 30 40 50 40 8 8.37 41 40 60 60 50 8 8.37 52 50 70 80 70 6 13.3 62 60 80 100 80 6 13.3 77 75 100 125 100 4 21.2 99 100 125 150 125 3 26.7
125 125 175 200 175 1/0 53.5 144 150 200 225 200 2/0 67.4 192 200 250 300 250 4/0 107.0 242 250 300 350 300 (2) 2/0 (2) 67.4 289 300 400 450 400 (2) 3/0 (2) 85.0 336 350 450 500 450 (3) 2/0 (3) 67.4 382 400 500 600 500 (3) 3/0 (3) 85.0 412 450 500 650 500 (3) 3/0 (3) 85.0 472 500 600 750 600 (3) 4/0 (3) 107.0
Note: All wire sizes are based on 75°C copper wire. Higher temperature smaller gauge wire may be used per NEC
and local codes. Recommended fuses/breakers are based on 40°C ambient, maximum continuous control output current and no harmonic current.
(Amps)
Fast Acting Time Delay AWG mm
2
3-8 Receiving & Installation MN715
Expansion Board
Motor Control Board
Figure 3-2 Series 15H Control
J4
J3
Keypad
Connector
3 2
JP1
1
JP2
123
123
122
JP3JP4
123
J4 Terminal Strip
44
See recommended Terminal Tightening Torques in Section 6.
Table 3-5 Control Board Jumpers
Analog GND
Analog Input 1
Pot Reference
Analog Input +2
Analog Input –2
Analog Out 1 Analog Out 2
Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8 Input 9
Opto In Common
Opto Out Common
Opto Out #1
Opto Out #2 Relay Out #1 Relay Out #2
1 2 3 4
5 6 7 8 9
10 11 12
J4-39 & 40 Jumper as shown to power the opto
13 14 15
inputs from the internal +24VDC supply.
Note: J4-18 and 41 are connected
together on the control circuit board.
16 17 18 19
20 21
22
39 40 41
42 43
44
+24VDC Opto In Power
Opto Out #1 Return Opto Out #2 Return
Relay Out #1 Return Relay Out #2 Return
Jumper Jumper Position Description of Jumper Position Setting
JP1
1–2 400 Hz Maximum Output Frequency. 2–3 120 Hz Maximum Output Frequency. (Factory Setting)
JP2
1–2 4–20mA Speed Command Signal. 2–3 0-5 or 0-10VDC Speed Command Signal. (Factory Setting)
JP3
1–2 Relay1 Normally Open (N.O.) contact. 2–3 Relay1 Normally Closed (N.C.) contact.
JP4
1–2 Relay2 Normally Open (N.O.) contact. 2–3 Relay2 Normally Closed (N.C.) contact.
Receiving & Installation 3-9MN715
AC Line Connections
Reduced Input Voltage Derating All power ratings stated in Section 6 are for the stated nominal AC input
voltages (230, 460 or 575VAC). The power rating of the control must be reduced when operating at a reduced input voltage. The amount of reduction is the ratio of the voltage change.
Examples:
A 10hp, 230VAC control operating at 208VAC has a reduced power rating of 9.04hp.
10HP
208VAC 230VAC
+ 9.04hp
Likewise, a 10hp, 460VAC control operating at 380VAC has a reduced power rating of
8.26hp. 10HP
380VAC 460VAC
+ 8.26hp
To obtain the full output rating of 10hp in either case requires a 15hp Control.
380-400VAC Operation Be sure all power to the control is disconnected before proceeding.
Size A, B, B2, C2 and D2 controls may be used directly with a 380-400VAC power source, control modification is not necessary.
Size C, D, E, F and G controls all require modification for operation on the reduced line voltage.
Tap change procedure (size C, D, E and F controls)
1. Be sure drive operation is terminated and secured.
2. Remove all power sources from the control. If power has been applied, wait at least 5 minutes for bus capacitors to discharge.
3. Remove or open the front cover and locate the control transformer (Figure 3-3).
4. Remove the wire from terminal 5.
5. Place the wire that was removed from terminal 5 onto terminal 4.
6. Install or close the front cover.
Figure 3-3 Control Transformer Identification
3-10 Receiving & Installation MN715
Section 1 General Information
Figure 3-4 Configuring the Control Transformer Terminal Block for 380 - 400VAC (Size G)
Control Transformer Tap Change Procedure (size G controls).
1. Be sure drive operation is terminated and control is disabled.
2. Remove all power sources from the control. If power has been applied, wait at least 5 minutes for bus capacitors to discharge.
3. Remove or open the front cover and locate the control transformer (Figure 3-4).
4. Remove the wires from the two right side terminals.
5. Place the wires on the center terminals as shown.
6. Install or close the front cover.
3 Phase Installation
Note 1
Note 3
Note 4
Note 3
* Circuit Breaker
A1 B1 C1
*Optional
Line
Reactor
A2 B2 C2
460VAC 380 - 400VAC
The AC power and motor connections are shown in Figure 3-5.
L1 L2 L3
L1 L2 L3
Baldor
Series 15H
Control
Figure 3-5 3 Phase AC Power Connections
Earth
Note 2
Alternate *
Fuse
Connection
L1 L2 L3
A1 B1 C1
* Optional components not provided with control.
Notes:
1. See Protective Devices described previously in this section.
2. Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3. Metal conduit should be used. Connect conduits so the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.
4. See Line/Load Reactors described previously in this section.
Note 1
See Recommended Tightening Torques in Section 6.
Receiving & Installation 3-11MN715
Table 3-6 and 3-7 list the wire size for the input AC power wires. Motor leads should be sized from the 3 phase tables.
Table 3-6 Single Phase Rating Wire Size and Protection Devices - 230 VAC Controls*
Control Rating
Amps HP
6.9 0.75 10 10 9 14 2.5
8.0 1 10 12 10 14 2.5 12 2 15 20 17.5 14 2.5 17 3 25 25 25 12 3.31 28 5 40 45 35 10 5.26 40 7.5 50 60 50 8 8.37 50 10 70 80 70 6 13.3 68 15 90 110 90 4 21.2 88 20 110 150 125 3 26.7
110 25 150 175 150 2 33.6 136 30 175 200 175 1/0 53.5 176 40 225 250 250 3/0 85.0 216 50 275 350 300 (2) 1/0 (2) 53.5
Input Breaker
Input Breaker
(Amps)
Input Fuse (Amps) Wire Gauge
Fast Acting Time Delay AWG mm
2
Table 3-7 Single Phase Rating Wire Size and Protection Devices - 460 VAC Controls*
Control Rating
Amps HP
3.5 0.75 5 5 5 14 2.5
4.0 1 5 6 5.6 14 2.5
6.0 2 7.5 10 8 14 2.5
8.5 3 12.5 15 12 14 2.5 14 5 17.5 20 20 12 3.31 20 7.5 25 30 25 10 5.26 25 10 40 40 30 10 5.26 34 15 45 50 45 8 8.37 44 20 60 70 60 8 8.37 55 25 70 80 70 6 13.3 68 30 90 100 90 4 21.2 88 40 110 150 125 3 26.7
108 50 150 175 150 2 33.6
Input Breaker
Input Breaker
(Amps)
Input Fuse (Amps) Wire Gauge
Fast Acting Time Delay AWG mm
2
*Note:All wire sizes are based on 75°C copper wire. Higher temperature smaller gauge wire may be used per NEC
and local codes. Recommended fuses/breakers are based on 40°C ambient, maximum continuous control output current and no harmonic current.
3-12 Receiving & Installation MN715
Section 1 General Information
Single Phase Input Power Considerations Single phase operation of G and H size controls is not possible.
Single phase AC input power can be used to power the control instead of three phase for control sizes A, B, B2, C, C2, D, D2, E and F. The specifications and control sizes are listed in Section 6 of this manual. If single phase power is to be used, the rated Horsepower of the control may have to be reduced (derated). In addition, power wiring and jumper changes are required. Single phase 3 wire connections are standard in the USA. However, single phase 2 wire connection is used in most of the world. Both connections types are shown.
Single phase rating wire size and protection devices are listed in Tables 3-6 and 3-7.
Single Phase Control Derating: Single phase power derating requires that the continuous and peak current ratings
of the control be reduced by the following percentages:
1. 1-2 hp 230 and 460VAC controls: No derating required.
2. 3-25 hp (Size B, B2 and C2) 230 and 460VAC controls: Derate hp by 40% of the nameplate rating.
3. 15 hp (Size C, D2) and Larger 230 and 460VAC controls: Derate hp by 50% of the nameplate rating.
Size A, B and B2 Single Phase Power Installation (See Figure 3-6).
Jumper Configuration
Size A, B and B2 controls, no jumper changes required.
Figure 3-6 Size A, B & B2 Single Phase 230/460VAC Power and Motor Connections
Note 1
Note 3
Note 4
* Circuit Breaker
*Optional
Line
Reactor
L1 L2
A1 B1
A2 B2
Earth
Note 2
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
L1 Neutral
* Circuit Breaker
A1
*Line
Reactor
A2
* Fuse
Connection
Note 1
* Optional components
not provided with control.
L1 L2
A1 B1
Note 3
L1 L2 L3
Baldor
Series 15H
Control
Notes:
1. See Protective Devices described previously in this section.
2. Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3. Metal conduit should be used. Connect conduits so the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.
4. See Line/Load Reactors described previously in this section.
See Recommended Tightening Torques in Section 6.
Receiving & Installation 3-13MN715
Size C2 Single Phase Power Installation
Jumper Configuration
Locate the Interface board, and place JP7 on pins 2 & 3 for single phase operation.
Figure 3-7 Jumper Configuration
Control Board
Bend plastic insulator upward to access the Interface Board.
Figure 3-8 Size C2 Single Phase 230/460VAC Power and Motor Connections
L1 L2
Note 1
Note 3
Note 4
Note 3
* Circuit Breaker
*Optional
Line
Reactor
A1 B1
A2 B2
L1 L2 L3
JP7
Interface Board
Baldor
Series 15H
Control
Earth
Note 2
JP7 Pins 1 & 2 = Three Phase Pins 2 & 3 = Single Phase
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
L1 Neutral
* Circuit Breaker
A1
*Line
Reactor
A2
* Fuse
Connection
Note 1
* Optional components
not provided with control.
L1 L2
A1 B1
Notes:
1. See Protective Devices described previously in this section.
2. Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3. Metal conduit should be used. Connect conduits so the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.
4. See Line/Load Reactors described previously in this section.
See Recommended Tightening Torques in Section 6.
3-14 Receiving & Installation MN715
Section 1 General Information
Size C and D Single Phase Power Installation
Jumper Configuration
Place JP2 on pins 1 & 2 for control single phase operation. Place JP3 in position B for single phase operation of cooling fan.
Figure 3-9 Jumper Configuration
Place JP2 on pins 1 & 2 for control single phase operation.
Place JP3 in position B for fan single phase operation.
Note 1
Note 3
Note 4
Note 3
JP2 Pins 1 & 2 = Single Phase Pins 2 & 3 = Three Phase
Figure 3-10 Size C & D Single Phase 230/460VAC Power Connections
L1 L2
* Circuit Breaker
B1 C1
*Optional
Line
Reactor
B2 C2
L1 L2 L3
Baldor
Series 15H
Control
JP3
Position A = Three Phase Position B = Single Phase
JP2 1
JP3
A
B
Earth
Note 2
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
L1 Neutral
* Circuit Breaker
A1
*Line
Reactor
A2
* Fuse
Connection
Note 1
* Optional components
not provided with control.
L1 L2
A1 B1
Notes:
1. See Protective Devices described previously in this section.
2. Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3. Metal conduit should be used. Connect conduits so the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.
4. See Line/Load Reactors described previously in this section.
See Recommended Tightening Torques in Section 6.
Receiving & Installation 3-15MN715
Size D2 Single Phase Power Installation
Jumper Configuration
Locate the Interface board, and place J100 on pins 2 & 3 for single phase operation.
Figure 3-11 Jumper Configuration
Note 1
Note 3
Note 4
Note 3
J100 Pins 1 & 2 = Three Phase Pins 2 & 3 = Single Phase
1 2 3
J100
Figure 3-12 Size D2 Single Phase 230/460VAC Power and Motor Connections
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
* Circuit
Breaker
*Optional
Line
Reactor
L1 L2
A1 B1
A2 B2
L1 L2 L3
Baldor
Series H
Control
Earth
Note 2
L1 Neutral
* Circuit Breaker
A1
*Line
Reactor
A2
* Fuse
Connection
Note 1
* Optional components
Notes:
1. See Protective Devices described previously in this section.
2. Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3. Metal conduit should be used. Connect conduits so the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.
4. See Line/Load Reactors described previously in this section.
L1 L2
A1 B1
not provided with control.
See Recommended Tightening Torques in Section 6.
3-16 Receiving & Installation MN715
Size E Single Phase Power Installation
Place JP1 on the High Voltage Circuit Board across pins 1 and 2.
Figure 3-13 Jumper Configuration
Note 1
Note 3
Note 4
Note 3
* Circuit Breaker
*Optional
Line
Reactor
JP1
Pins 1 & 2 = Single Phase Pins 2 & 3 = Three Phase
1
JP1
Figure 3-14 Size E Single Phase 230/460VAC Power Connections
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
L1 L2
A1 B1
A2 B2
L1 L2 L3
Baldor
Series 15H
Control
Earth
L1 Neutral
* Circuit Breaker
A1
*Line
Reactor
A2
Notes:
1. See Protective Devices described previously in this section.
2. Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3. Metal conduit should be used. Connect conduits so the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.
4. See Line/Load Reactors described previously in this section.
L1 L2
* Fuse
Connection
Note 1
* Optional components
not provided with control.
A1 B1
See Recommended Tightening Torques in Section 6.
Receiving & Installation 3-17MN715
Size F Single Phase Power Installation
Place JP2 on the High Voltage Circuit Board across pins 1 and 2.
Figure 3-16 Size F Single Phase 230/460VAC Power Connections
Note 1
Note 3
Note 4
* Circuit Breaker
*Optional
Line
Reactor
L1 L2
B1 C1
B2 C2
Earth
Figure 3-15 Jumper Configuration
JP2
1
JP2
Pins 1 & 2 = Single Phase Pins 2 & 3 = Three Phase
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
L1 Neutral
Note 2
* Circuit Breaker
A1
*Line
Reactor
A2
L1 L2
* Fuse
Connection
Note 1
* Optional components
not provided with control.
A1 B1
Note 3
L1 L2 L3
Baldor
Series 15H
Control
Notes:
1. See Protective Devices described previously in this section.
2. Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3. Metal conduit should be used. Connect conduits so the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.
4. See Line/Load Reactors described previously in this section.
See Recommended Tightening Torques in Section 6.
3-18 Receiving & Installation MN715
Section 1 General Information
Motor Brake Connections For motors with spring set brakes, connect the brake power leads and the motor power
leads separately. Because the inverter has variable voltage output to the motor, the inverter may not supply enough power at low frequencies for proper brake operation. If using a motor with an internally connected brake, the brake power leads must be connected to a separate power source for proper brake operation.
Motor Connections Motor connections are shown in Figure 3-17.
Figure 3-17 Motor Connections
Notes:
1. Metal conduit should be used. Connect conduits so the use of Load
Baldor
Series 15H
Control
T1 T2 T3
Note 1
A1 B1 C1
Reactor or RC Device does not interrupt EMI/RFI shielding.
2. See Line/Load Reactors described previously in this section.
3. Use same gauge wire for Earth ground as for L1, L2 and L3.
Note 2
Note 1
*Optional
Load
Reactor
A2 B2 C2
T2 T3
T1
G
* Optional components not provided with control.
Note 3
See Recommended Tightening Torques in Section 6.
* AC Motor
M-Contactor If required by local codes or for safety reasons, an M-Contactor (motor circuit contactor)
may be installed. However, incorrect installation or failure of the M-contactor or wiring may damage the control. If an M-Contactor is installed, the control must be disabled for at least 20msec before the M-Contactor is opened or the control may be damaged. M-Contactor connections are shown in Figure 3-18.
Figure 3-18 M-Contactor Diagram
T1 T2 T3
MMM
M=Contacts of optional M-Contactor
T2 T3
T1
* Motor
To Power Source
(Rated Coil Voltage)
J4
*
M Enable
G
7
Note: Close “Enable”
8
after M contact closure.
9
* M-Contactor
See Recommended Tightening Torques in Section 6.
* Optional
RC Device
Electrocube
RG1781-3
Receiving & Installation 3-19MN715
Loading...
+ 101 hidden pages