York AHV18B, AHV24B, AHV30B, AHV36C, AHV42D Technical Manual

...
TECHNICAL GUIDE
SINGLE PIECE ECM AIR HANDLERS
FOR USE WITH SPLIT-SYSTEM AIR CONDITIONERS & HEAT PUMPS
MODELS: AHV18 THRU 60
Due to continuous product improvement, specifications are subject to change without notice.
Visit us on the web at:
www.york.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY
Standard 5-year limited parts warranty.
Extended 10-year limited pa rt s warranty when product is registered online within 90 days of purchase for replace­ment or closing for new home construction.
ISO 9001
Certified Quality
Management System
824755-YTG-C-0912
DESCRIPTION
The AHV Air Handler line offers the ultimate in comfort, sound and application flexibility. The air handler is shipped ready to be installed in upflow, horizontal left or right position, with minor adjustments. No special kits are required to install this deluxe product.
Air handlers are shipped with “Flex-coils” without a factory installed metering device. Flex coil models allow these coils to be used with R-22 or R-410A for added flexibility to meet refrig­erant choices. An orifice metering device or a R-410A TXV should be installed in the field to meet your system require­ments.
FEATURES
Thermostatic Expansion Valve - Provides the ultimate refrig­erant control required for today’s high efficient product. The UPG bolt-on TXV provides easy installation to convert the air handler to the required refrigerant, which is a true bolt-on design that does not require brazing to replace or install.
Rust-proof Plastic Drain Pans - The vertical and horizontal drain pans in these units are made of a fiberglass reinforced thermoset polymer that will not rust or compromise stability at high temperatures.
Insulated Cabinet - All air handler cabinets are thermally insu­lated with 3/4” foil faced insulation to prevent sweating.
Factory Sealed - Achieves 2% or less total airflow leakage rate at duct leakage test conditions for system airflow verification.
Durable Finish Inside and Out - Air handler casings are made of pre-painted galvanized steel which provides a better paint to steel bond that resists corrosion and rust creep. All internal coil sheet metal parts are made of G60 galvanized or prepainted G30 galvanized steel.
Filters - All models have internal filter racks provided for use with 1” thick standard size filters.
Electric Heat Kits - The 6HK series of field installed electric heat kits are available for installation friendly and easy service applications. These 6HK kits have heat capacities from 2 kW to 25 kW to meet the application requirements.
ECM Variable Sp eed Motor - Designed for efficient, quiet oper­ation with added indoor comfort control. With the use of a humidistat, the system will monitor the humidity in the home and automatically keep the desired humidity level in both winter and summer seasons. The ECM motor utilizes only 24% of the energy used by standard blower motors to reduce your overall heating and cooling costs.
The climate comfort system allows dealer to customize comfort settings based on regional location.
Communications - These models may be connected as part of a communications system using a 4-wire connection bus.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
824755-YTG-C-0912
J
D
Blower Compartment
Circuit Breaker
Panel
Drain Pan Connections for Horizontal Applications
Refrigerant Connections
Drain Connections
for Upflow
Applications
7-11/32”
B
A
K
C
1-1/2”
Top Outlet
Dimensions
Filter Access
18-9/32”
E
Bottom Inlet Dimensions
13”
F
DIMENSIONS & DUCT CONNECTION DIMENSIONS
Dimensions
Models
1
Dimensions
ABC
DEF
Wiring Knockouts
2
JK
Refrigerant
Connections
Line Size
Height Width Depth Power Control Liquid Vapor
AHV18B/AHV24B/AHV30B 46 17 1/2 AHV36C 52 21 21 1/2 17-13/32 20
21 1/2
AHV42D/AHV48D/AHV60D 57 24 1/2 26 20-29/32 23-1/2 7/8
1. All dimensions are in inches.
2. Actual size (conduit size).
16 1/2 13-29/32 16 1/2
7/8 (1/2)
1-3/8(1)
1-23/32 (1-1/4)
7/8 (1/2) 3/8
COIL TECHNICAL DATA
Models Application
AHV18B3XH21
AHV24B3XH21
AHV30B3XH21
AHV36C3XH21
AHV42D3XH21
AHV48D3XH21
AHV60D3XH21
Cooling /Heat
Cooling /Heat
Cooling /Heat
Cooling /Heat
Cooling /Heat
Cooling /Heat
Cooling /Heat
Pump
Pump
Pump
Pump
Pump
Pump
Pump
Refrig.
Conn. Types
Sweat 3.4 2 14 (2) 14 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 3.9 3 12 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 3.9 3 12 (2) 16 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 4.9 3 12 (2) 20 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 5.4 3 12 (2) 22 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 5.8 3 11 (2) 24 x 17.5 1 x 0.866 3/8 Enhanced
Sweat 6.8 3 12 (2) 28 x 17.5 1 x 0.866 3/8 Enhanced
Face Area
(Sq. Ft.)
Rows
Deep
Fins
Per In.
Coil Size
Tube
Geometry
Tube
Dia.
Fin
Type
3/4
2 Johnson Controls Unitary Products
COOLING CAPACITY
Models
AHV18B
AHV24B
AHV30B
AHV36C
For notes see Page 4.
1
Rated CFM
610
850
585
795
985
585
795
985
730
855
1000
1190
Entering Air
2
Dry/Wet Bulb (°F)
824755-YTG-C-0912
MBH@ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG)
35/107.9 40/118.9 45/130.7 50/143.3
85/72 37.9 33.7 28.3 23.3 80/67 31.8 27 22.5 17.6 75/62 26.4 21.5 16.7 11.6 70/57 20.7 18.4 15.8 13.5 85/72 49.7 43.2 36.9 28.4 80/67 42.1 35.1 28.8 22.5 75/62 33.7 28 21.4 14.7 70/57 26.5 23.8 20.3 16.9 85/72 38.7 34.4 30.1 24.7 80/67 33.6 28.9 23.9 18.9 75/62 27.2 22.7 17.8 12.8 70/57 21.2 18.6 16.2 13.7 85/72 50.8 45.2 38.4 32.0 80/67 43.7 36.8 31 24.0 75/62 35.7 29.5 23.1 16.1 70/57 27.9 24.5 21 17.6 85/72 64.9 54 45.6 37.8 80/67 52.3 44.6 36.9 28.4 75/62 42.2 35.2 26.8 19.3 70/57 33.6 29.6 25.4 21.4 85/72 38.7 34.4 30.1 24.7 80/67 33.6 28.9 23.9 18.9 75/62 27.2 22.7 17.8 12.8 70/57 21.2 18.6 16.2 13.7 85/72 50.8 45.2 38.4 32.0 80/67 43.7 36.8 31 24.0 75/62 35.7 29.5 23.1 16.1 70/57 27.9 24.5 21 17.6 85/72 64.9 54 45.6 37.8 80/67 52.3 44.6 36.9 28.4 75/62 42.2 35.2 26.8 19.3 70/57 33.6 29.6 25.4 21.4 85/72 49.3 45.2 38.3 31.4 80/67 43 37.3 31 24.0 75/62 34.7 28.8 22.8 16.2 70/57 26.8 23.4 20.4 16.9 85/72 59.1 51 44.1 36.5 80/67 49.3 42.4 35.4 27.6 75/62 39.9 33.1 26.1 18.2 70/57 31.1 26.9 23.5 19.7 85/72 65.2 59.5 51.2 41.3 80/67 56.4 48.3 39.9 31.3 75/62 45.8 38.1 29.7 20.8 70/57 35.7 31.2 26.9 22.6 85/72 67.5 65.9 59.8 48.7 80/67 64.9 56.7 46.2 35.7 75/62 53.5 43.2 34.1 24.0 70/57 41.4 36.6 31.5 26.2
Johnson Controls Unitary Products 3
824755-YTG-C-0912
COOLING CAPACITY
Models
AHV42D
AHV48D
AHV60D
1. Actual capacity varies with the outdoor AC or HP that is used with the system.
2. Airflow is calculated for each system tonnage.
1
(Continued)
Rated CFM
820
1000
1180
1385
1000
1195
1385
1600
1190
1390
1565
1835
Entering Air
2
Dry/Wet Bulb (°F)
85/72 56.6 51.1 42.8 35.6 80/67 48.6 41.1 34.8 27.6 75/62 39.4 33 26 18.3 70/57 30.5 26.6 23.1 19.6 85/72 65.7 61 52.7 42.9 80/67 58 49.6 41.1 32.1 75/62 46.7 38.9 30.4 21.8 70/57 36.4 31.6 27.6 23.3 85/72 67.9 71.4 60.2 48.8 80/67 65.6 56.9 47.1 37.1 75/62 53.8 45.2 34.7 24.6 70/57 42.2 37.1 31.9 27.0 85/72 69.4 81 68 57.2 80/67 77.1 65.4 54.1 41.6 75/62 62.1 51 39.8 28.1 70/57 48.1 42.5 36.8 30.6 85/72 69 59.8 51.3 41.5 80/67 56.5 48.2 39.7 29.9 75/62 45.1 36.8 28.3 18.9 70/57 34.4 31 26.8 22.5 85/72 79.5 69.7 59.9 48.6 80/67 65.2 55.5 45.5 34.9 75/62 52.2 42.5 32.6 21.8 70/57 40.1 36.1 31.1 26.2 85/72 90 78.1 66 54.5 80/67 73.5 62.7 51.3 38.7 75/62 59.2 48.2 36.9 24.0 70/57 45.2 41 35.4 29.7 85/72 102.2 90 74.3 60.4 80/67 83.6 70.6 57.2 43.1 75/62 66.1 54 41.2 27.0 70/57 50.7 46.1 39.8 33.4 85/72 83.6 73.7 62.9 51.6 80/67 68.2 58.4 48.4 37.1 75/62 54.9 45.3 34.8 23.9 70/57 42.2 37.3 31.9 26.9 85/72 95.9 84.1 71.9 58.8 80/67 79.2 67.4 54.4 41.6 75/62 62.4 51.2 39.7 26.9 70/57 48 42.5 36.8 30.6 85/72 106.3 94.2 78.5 63.5 80/67 87.6 73.9 60.2 45.9 75/62 69.3 56.8 43.5 29.7 70/57 53.1 46.9 40.5 34.1 85/72 122.1 107.1 90.9 72.6 80/67 100.2 85.9 69.8 51.8 75/62 79.7 65.3 49.8 32.9 70/57 60.8 54.1 46.4 38.7
MBH@ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG)
35/107.9 40/118.9 45/130.7 50/143.3
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow (CFM)
Capacity Factor
4 Johnson Controls Unitary Products
80% 90% 100% 110% 120%
0.96 0.98 1.00 1.02 1.03
824755-YTG-C-0912
PHYSICAL & ELECTRICAL DATA - COOLING ONLY
MODELS
Models
Blower - Diameter x Width Motor
HP
Nominal RPM Voltage Full Load Amps @230V
18B 24B 30B 36C 42D 48D 60D
10 x 8 10 x 8 10 x 8 11 x 10 11 x 10 11 x 10 11 x 10
1/3 HP 1/3 HP 1/3 HP 1/2 HP 1/2 HP 3/4 HP 3/4 HP
1050 1050 1050 1050 1050 1050 1050
208/230 208/230 208/230 208/230 208/230 208/230 208/230
2.3 2.3 2.3 3.2 3.2 4.9 4.9
Type DISPOSABLE OR PERMANENT
1
Filter
Size
Permanent Type Kit Shipping /
Operating Weight (lbs.)
1. Field supplied.
16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 22 x 20 x 1
1PF0601BK 1PF0601BK 1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK 1PF0603BK
116/104 121/106 121/106 153/138 169/151 172/154 175/157
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH d ata from the table by the conversion factor in the following table.
DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR
208V 240V 0.75 220V 240V 0.84 230V 240V 0.92
ELECTRICAL DATA - COOLING ONLY
Models
Motor FLA
1
208V 230V 208V 230V
Minimum Circuit Ampacity
MOP
2
18B 24B
2.7 2.3 3.4 2.9 15 14
30B 36C
42D 48D
60D
1. FLA = Full Load Amps.
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
3. 75C, copper wire only. If wire other than non-plated, 75C ambient, copper wire is used, consult applicable tables of the NEC and local codes..
ELECTRICAL HEAT: MINIMUM FAN SPEED
Heater Kit Models
2,3
3.6 3.2 4.5 4.0 15 14
5.3 4.9 6.6 6.1 15 14
1
Nom. kW
@240V
AHV18B AHV24B AHV30B AHV36C AHV42D AHV48D AHV60D
Air Handler Models
6HK(0,1)6500206 2.4kW Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) 6HK(0,1)6500506 4.8kW Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) 6HK(0,1)6500806 7.7kW Med-Low (C) Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) 6HK(0,1)6501006
6HK06501025
9.6kW Med-Low (C) Low (D) Low (D) Low (D) Low (D) Low (D) Low (D)
6HK(1,2)6501306 12.5kW - Med-Low (C) Med-Low (C) Low (D) Low (D) Low (D) Low (D) 6HK(1,2)6501506
6HK06501525
6HK(1,2)6501806
6HK06501825
6HK(1,2)6502006
6HK16502025
6HK(1,2)6502506
6HK16502525
1. The referenced letter in this table is for the heat jumper tap.
2. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.
3. (1,2) - 1 = with circuit breaker, no breaker jumpe r bar OR 2 = with circuit breaker & breaker jumper bar.
14.4kW - Med-Low (C) Med-Low (C) Med-Low (C) Low (D) Low (D) Low (D)
17.3kW - - - Med-Low (C) Med-Low (C) Low (D) Low (D)
19.2kW - - - Med-High (B) Med-High (B) Low (D) Low (D)
24kW------Low (D)
Minimum Wire
Size (AWG)
3
Johnson Controls Unitary Products 5