York D2CE, D2CG User Manual

4 (1)

®

Technical Guide

SINGLE PACKAGE

GAS / ELECTRIC UNITS AND

SINGLE PACKAGE AIR CONDITIONERS

D2CE / D2CG 300 CONSTANT VOLUME 25 NOMINAL TONS

8.5 EER

SUNLINE 2000 ™

036-21359-001-B-0302

DESCRIPTION

Sunline™ 2000 series convertible package rooftop models have two independent refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.

Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factorymounted options and field-installed accessories to make them suitable for almost every application.

All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging.

Every unit is completely piped, wired, charged and tested at the factory to simplify field installation and to provide years of dependable operation. Powder paint cabinets provide an exceptionally durable finish with the 750 hour salt spray process per ASTM-B117 test standard.

All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory.

All models are available with five different outdoor air damper options:

Single enthalpy economizer

Differential (dual) enthalpy economizer

Single enthalpy economizer with power exhaust

Differential (dual) enthalpy economizer with power exhaust

Motorized outdoor air damper

A fixed outdoor air intake assembly is shipped in the return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

036-21359-001-B-0302

All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high speed drive accessory is available for applications with a higher CFM and/or static pressure requirement.

All compressors include internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch. The unit control circuit includes two 75 VA transformers, two 24-volt circuit breakers and a relay board with two compressor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls.

All 208/230 and 460-volt models are ETL approved. All 208/230 and 575-volt models are CGA approved.

All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9- year warranty.

All gas heat models are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.

The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.

All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches.

The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.

All internal factory wiring is color coded and numbered for ease in servicing and troubleshooting.

FACTORY-INSTALLED OPTIONS

ECONOMIZERS

Interlocked outdoor and return air dampers are positioned by a fully modulating, spring return damper actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. As the outdoor air intake dampers open, the return air dampers close. The changeover from compressor to economizer cooling is determined by one or two solid state enthalpy controls.

On single enthalpy, an outdoor air sensor determines when the outdoor air is cool and dry enough to provide “free” cooling. On differential enthalpy, one sensor monitors the outdoor air while a second sensor monitors the return air. Whenever the outdoor air is cooler and drier than the return air, the unit will switch to economizer operation. For either option, the first compressor stage can provide additional cooling during economizer operation if the room thermostat calls for second stage.

The dampers and controls are installed and wired at the factory. Only the accessory rain hood needs to be assembled and installed in the field.

These economizer options can be used on all duct configurations.

POWER EXHAUST

Both the single and differential economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.

The exhaust fan, motor and controls are installed and wired at the factory. Only the back-draft damper assembly needs to be field installed and the accessory rain hoods need to be assembled and installed in the field.

The power exhaust option can only be used on bottom duct configurations.

MOTORIZED OUTDOOR AIR INTAKE DAMPER

Interlocked outdoor and return air dampers are controlled by a 2-position, spring return damper actuator. The outdoor damper will open to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower shuts down.

The damper and controls are installed and wired at the factory. Only the accessory rain hood needs to be assembled in the field.

This damper option can be used on all duct configurations.

2

Unitary Products Group

036-21359-001-B-0302

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS

Includes a slide-in/plug-in damper assembly with fully modulating spring-return monitor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide “free” cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

Power exhaust is not available as a field installed option.

DUAL INPUT ELECTRONIC ENTHALPY

ECONOMIZERS

Includes a slide-in / plug-in damper assembly with fully modulating spring-return monitor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

This enthalpy system contains one sensor that monitors the outdoor air and one sensor that monitors the return air. The logic module compares these two values and modulates the dampers providing the maximum efficiency of economizer system.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

Power exhaust is not available as a field installed option.

MOTORIZED OUTDOOR AIR INTAKE DAMPER

Includes a slide-in/plug-in damper assembly with a 2-position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

Power exhaust is not available as a field installed option.

ROOF CURBS

Fourteen inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly. They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.

ANTI-RECYCLE TIMERS

Two solid state timers prevent the compressors from short-cycling. Once a compressor is de-energized, it will remain de-energized for approximately five minutes.

HIGH ALTITUDE NATURAL GAS

Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.

PROPANE

Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.

HIGH ALTITUDE PROPANE

Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.

SIDE DUCT FLANGES

One inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply/horizontal return or horizontal supply/bottom return. They cannot be used on units with power exhaust.

BAROMETRIC RELIEF DAMPER

This damper accessory can be used to relieve internal air pressure on units with an economizer but no power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.

ECONOMIZER / POWER EXHAUST RAIN HOODS

A rain hood accessory must be used on units with an economizer, a motorized damper, or a combined economizer with power exhaust option. These accessories include all the hood panels, the necessary components and hardware for field assembly.

HIGH SPEED DRIVE

A smaller blower pulley and a shorter belt increase the speed of the supply air blower for applications with a higher CFM and/or static pressure requirement.

LOW AMBIENT CONTROLS TO 0°F

An autotransformer and a thermostat maintain stable system operation by reducing the speed of the condenser fan motor at low outdoor temperatures. The kit

Unitary Products Group

3

036-21359-001-B-0302

also includes a 1-phase motor to replace the unit's Provides coil guard and fastners. standard 3-phase condenser fan motor. Standard units

can operate down to 45°F.

COIL GUARD KIT

E L E C T R I C H E A T E R LOCA TI ON

L O N G L A S T(IONPGT I O N A L E L E CHT IRGIHC/EEFLFEICCTIRE INCC YU NSICT RS O) L L C O M P R E S S O R S

P O W D E R P A I N T F I N I S H

2 0GAUG E TUB UL A R

E CON OM I Z E R H O O D

A L U M I N I Z E D CSOTPEPEELR T U B E / A L U M I N U M F I N

H E A T E X C H A NCGOENRDSE N S E R C O I L S

LO WVOLTA G E R E L A Y B O A R D AN DTER M I A N L S T R I P

ELE C T R IC A L D I S C O N N E C T M O U N T I N G L O C A T I O N

( F ie ld in s t a lle d )

 

K N O C K O U T F O R

 

S I D E C O N T R O L W I R I N G E N T R Y

 

K N O C K O U T F O R

 

S I D E P O W E R W I R I N G E N T R Y

2 " D I S P O S A B L E

T E R M I N A L B L O C K

F I L T E R S

( F o r S in g le P o in t P o w e r S u p p

 

 

w it h E le c t r ic H e a t )

OU T D O O R A I R O P E N I N G

E L E C T R I C / E L E C T R I C U N I T S

 

F O R S L I D E - I N / P L U G - I N

B O T T O M P O W E R & C O N T R O L

I N T E R N A L E C O N O M I Z E R ( O P T I O N )

W I R I N G E N T R Y

 

S I D E A N D B O T T O M

K N O C K O U T S F O R S I D E

G A S S U P P L Y E N T R Y

S U P P L Y & R E T U R N A I R

H O L E F O R B O T T O M

G A S S U P P L Y E N T R Y

D U C T O P E N I N G S ( S I D E X S I D E )

 

1 "N PINTP T I

P O W E R V E N T O R M O T O R

W I T H P O S T P U R G E C Y C L E

C O N D E N S A T E B DE RL AT

I-ND R I V E

B L O W E R M O T O R

F U L L P E R I M E T E R 1 4 G U A G E B A S E

R A I L S W I T H L I F T I N G H O L E S

CAPACITY RATINGS - (ARI 360)*

 

 

 

 

 

MODEL

MBH

EER

IPLV

MODEL

MBH

EER

IPLV

 

 

 

 

 

 

 

COOLING WITH GAS HEAT

 

 

COOLING WITH ELECTRIC HEAT

 

 

 

 

 

 

 

 

 

 

 

D2CG300N240

290

8.5

8.3

D2CE300E018

290

8.5

8.6

 

 

 

 

 

 

 

 

D2CG300N320

290

8.5

8.3

D2CE300E036

290

8.5

8.6

 

 

 

 

 

 

 

 

COOLING ONLY

 

 

 

D2CE300E054

287

8.5

8.2

 

 

 

 

 

 

 

 

D2CE300

290

8.5

8.7

D2CE300E072

284

8.5

8.2

 

 

 

 

 

 

 

 

*. Outside the scope of ARI Standard 340/360.

EER=Energy Efficiency Rating at full load-the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).

IPLV - Integrated part load value. NOTE: All cooling is three stage.

 

 

GAS HEAT RATINGS

 

 

 

Note: All gas units are two-stage heating. First stage is 50% of total.

 

 

 

 

 

All models are 80% Steady State Efficiency (S.S.E.).

 

 

 

MBH Input

 

MBH Output

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

Stage

Stage 1

Stage

Stage 1

 

 

 

 

 

 

 

 

1&2

 

1&2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D2CG300N240

 

300

150

 

240

 

120

 

 

 

 

 

 

D2CG300N320

 

400

200

 

320

 

160

 

 

 

 

 

 

Unit

CFM

ESP

Blower

 

 

 

 

Sound Power (db 10-12 Watts)

 

 

Octave Band Centerline Frequency (Hz)

SWL

db(A)

Size

)

 

 

 

 

IWG

RPM

BHP

63

125

250

500

1,000

2,000

4,000

8,000

db(A)

@ 10 Ft.*

 

 

300

10,000

1.30

1,160

12.5

108

108

98

91

93

86

81

76

98

65

*. At a distance of 10 ft.from the blower.

NOTE: These values have been derived using a model of sound propagation, measuring the indoor ambient sound levels ten feet from the source. The dBA values provided are for reference only. Calculation of dBA values cover matters of system design and application. This constitutes an exception to any specifi-

cation or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.

4

Unitary Products Group

York D2CE, D2CG User Manual

036-21359-001-B-0302

COOLING CAPACITIES- 25 TON (DCE / DCG300)

Air On

 

 

 

 

 

Tem pera ture of Air on Con denser Coil

 

 

 

 

 

 

 

 

 

85? F

 

 

 

 

 

 

 

95? F

 

 

 

 

Evaporator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Coil

 

Total

Power

 

SensibleCapacity1, MBH

 

Total

Power

 

SensibleCapacity1, MBH

 

CFM

WB

Cap.1

Input2

 

En ter ing Dry Bulb, ? F

 

Cap.1

Input2

 

En ter ing Dry Bulb, ? F

 

? F

MBH

KW

86

83

80

77

74

71

68

MBH

KW

86

83

80

77

74

71

68

 

 

72

371

27.1

277

240

203

167

130

-

-

354

28.8

268

231

195

158

122

-

-

12,000

67

340

26.1

335

299

262

226

189

152

116

325

27.7

324

288

251

214

178

141

105

62

329

25.5

329

329

329

293

256

219

183

315

27.1

315

315

315

278

241

205

168

 

 

57

329

25.5

329

329

329

292

256

219

183

314

27.1

314

314

314

278

241

205

168

 

72

365

27.0

260

226

193

159

125

-

-

348

28.6

257

223

189

155

122

-

-

11,000

67

336

25.9

317

283

249

216

182

148

114

321

27.5

312

279

245

211

178

144

110

62

324

25.3

324

324

313

279

245

212

178

309

26.9

309

309

307

273

239

206

172

 

 

57

324

25.3

324

324

315

281

247

214

180

309

26.9

309

309

309

275

242

208

174

 

72

359

26.8

244

213

182

151

120

-

-

342

28.5

245

214

184

153

122

-

-

10,000

67

332

25.7

298

268

237

206

175

144

113

317

27.4

301

270

239

208

177

146

115

62

318

25.2

318

318

296

265

235

204

173

304

26.8

304

304

299

268

237

207

176

 

 

57

318

25.1

318

318

301

270

239

208

177

304

26.7

304

304

304

273

242

211

180

 

72

354

26.6

229

201

173

145

117

-

-

338

28.2

228

200

172

144

116

-

-

9,000

67

326

25.5

280

252

224

196

168

141

113

312

27.1

279

251

223

195

167

139

111

62

314

25.0

314

306

282

254

226

198

170

300

26.5

300

295

280

253

225

197

169

 

 

57

314

25.0

314

308

286

258

230

203

175

300

26.5

300

297

285

257

229

201

173

 

72

349

26.4

215

190

165

140

115

-

-

334

28.0

211

186

161

136

111

-

-

8,000

67

321

25.3

262

237

212

187

162

137

112

307

26.9

257

232

207

182

157

132

107

62

310

24.8

310

293

268

243

218

193

168

297

26.3

297

287

262

237

212

187

162

 

 

57

310

24.8

310

297

272

247

222

197

172

297

26.3

297

291

266

241

216

191

166

 

72

318

25.2

186

167

148

129

110

-

-

304

26.8

177

158

138

119

100

-

-

6,000

67

290

24.0

226

206

187

168

149

130

111

277

25.5

213

194

175

156

137

118

99

62

282

23.7

277

258

240

221

201

192

163

270

25.2

262

243

225

206

187

167

148

 

 

57

282

23.7

281

262

243

224

205

186

167

270

25.2

266

247

228

209

190

171

152

Air On

 

 

 

 

 

Tem pera ture of Air on Con denser Coil

 

 

 

 

 

 

 

 

 

105? F

 

 

 

 

 

 

 

115? F

 

 

 

 

Evaporator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Coil

 

Total

Power

 

SensibleCapacity1, MBH

 

Total

Power

 

SensibleCapacity1, MBH

 

CFM

WB

Cap.1

Input2

 

En ter ing Dry Bulb, ? F

 

Cap.1

Input2

 

En ter ing Dry Bulb, ? F

 

? F

MBH

KW

86

83

80

77

74

71

68

MBH

KW

86

83

80

77

74

71

68

 

 

72

337

30.7

264

228

191

155

118

-

-

320

32.6

261

224

188

151

114

-

-

12,000

67

310

29.5

309

283

246

210

173

137

100

294

31.3

294

278

242

205

169

132

95

 

62

300

28.8

300

300

300

263

226

190

153

285

30.5

285

285

285

248

212

175

138

 

57

299

28.8

299

299

299

263

226

190

153

285

30.5

285

285

285

248

211

175

138

 

72

331

30.5

254

221

187

153

119

-

-

315

32.3

252

218

185

151

117

-

-

11,000

67

306

29.3

302

276

242

208

174

141

107

291

31.0

291

273

239

205

171

138

104

62

295

28.5

295

295

294

260

226

192

159

280

30.3

280

280

280

246

213

179

145

 

 

57

294

28.5

294

294

294

261

227

193

160

280

30.3

280

280

280

246

213

179

145

 

72

326

30.2

244

213

183

152

121

-

-

310

32.1

243

212

181

151

120

-

-

10,000

67

302

29.0

294

268

237

206

176

145

114

287

30.8

287

267

236

205

174

143

112

62

290

28.3

290

290

287

256

226

195

164

276

30.0

276

276

276

245

214

183

152

 

57

290

28.2

290

290

290

259

228

197

166

275

29.9

275

275

275

244

214

183

152

 

72

322

30.0

228

200

172

144

116

-

-

306

31.8

228

200

172

144

116

-

-

9,000

67

297

28.8

276

251

223

195

167

139

111

283

30.5

274

251

223

195

167

139

111

62

286

28.1

286

284

271

243

215

187

159

272

29.8

272

272

262

234

206

178

150

 

 

57

286

28.1

286

285

273

245

217

189

161

272

29.7

272

272

261

234

206

178

150

 

72

319

29.8

212

187

162

137

112

-

-

303

31.6

213

188

163

138

113

-

-

8,000

67

293

28.6

259

234

209

184

159

134

109

278

30.3

260

235

210

185

160

135

110

62

283

28.0

283

278

255

230

205

180

155

269

29.6

269

269

248

223

198

173

148

 

 

57

283

28.0

283

280

257

232

207

182

157

269

29.6

269

269

248

223

198

173

148

 

72

290

28.3

180

161

141

122

103

-

-

276

30.0

183

164

145

125

106

-

-

6,000

67

264

26.9

224

200

181

162

142

123

104

251

28.5

222

203

194

165

146

127

108

62

258

26.6

258

241

223

204

184

165

146

245

28.2

245

239

220

201

182

163

144

 

 

57

258

26.6

258

242

224

205

186

167

148

245

28.2

245

240

221

202

182

163

144

1These ca paci ties are gross rat ings. For net ca pac ity, de duct the heat of the sup ply air blower mo tor, MBH = 3.415 x KW. Ref er to the ap pro pri ate Blower Per form ance Ta ble for the KW of the sup ply air blower mo tor.

2These rat ings in clude the con denser fan mo tors (To tal 2.3 KW) and the com pres sor mo tors but not the sup ply air blower mo tor.

 

NominalRating

 

AllSensibleCapacity

Unitary Products Group

5

036-21359-001-B-0302

BLOWER PERFORMANCE- 25 TON (DCE/DCG300)

DCE300- BOT TOM DUCT CON NEC TIONS (COOLINGAPPLICATIONS)

BLOWER

PULLEY

 

7500 CFM

 

 

8750 CFM

 

 

10000 CFM

 

 

11250 CFM

 

 

12500 CFM

 

SPEED

TURNS

ESP

OUTPUT

INPUT

ESP

OUTPUT

INPUT

ESP

OUTPUT

 

INPUT

ESP

OUTPUT

 

INPUT

ESP

OUTPUT

 

INPUT

(rpm)

OPEN:

(iwg)

(bhp)

(kW)

(iwg)

(bhp)

(kW)

(iwg)

(bhp)

 

(kW)

(iwg)

(bhp)

 

(kW)

(iwg)

(bhp)

 

(kW)

 

 

 

 

 

 

 

STANDARD DRIVE:

 

 

 

 

 

 

 

 

 

975

6.0*

1.4

5.9

4.9

1.0

7.3

6.0

0.5

8.8

 

7.2

-

-

 

-

-

-

 

-

1005

5.0

1.6

6.2

5.1

1.2

7.7

6.3

0.7

9.2

 

7.6

0.1

10.9

 

8.9

-

-

 

-

1040

4.0

1.8

6.6

5.4

1.4

8.1

6.7

0.9

9.7

 

8.0

0.3

11.4

 

9.4

-

-

 

-

1070

3.0

2.0

6.9

5.7

1.6

8.5

7.0

1.1

10.2

 

8.3

0.6

11.9

 

9.8

-

-

 

-

1100

2.0

2.1

7.3

6.0

1.8

8.9

7.3

1.3

10.6

 

8.7

0.8

12.4

 

10.2

0.2

14.3

 

11.7

1135

1.0

2.4

7.7

6.3

2.0

9.3

7.6

1.6

11.1

 

9.1

1.0

13.0

 

10.6

0.4

14.9

 

12.2

1165

0.0

2.6

8.0

6.6

2.2

9.7

8.0

1.8

11.6

 

9.5

1.3

13.5

 

11.0

0.7

15.5

 

12.7

 

 

 

 

 

 

 

ACCESSORY DRIVE:

 

 

 

 

 

 

 

 

 

1140

6.0

2.4

7.7

6.3

2.1

9.4

7.7

1.6

11.2

 

9.2

1.1

13.1

 

10.7

0.5

15.0

 

12.3

1180

5.0

2.7

8.2

6.7

2.3

9.9

8.1

1.9

11.8

 

9.7

1.4

13.7

 

11.2

0.8

15.8

 

12.9

1215

4.0

2.9

8.6

7.0

2.6

10.4

8.5

2.2

12.3

 

10.1

1.7

14.3

 

11.7

1.1

16.4

 

13.5

1255

3.0

3.2

9.1

7.4

2.9

11.0

9.0

2.5

12.9

 

10.6

2.0

15.0

 

12.3

1.4

17.2

 

14.1

1290

2.0

3.4

9.5

7.8

3.1

11.5

9.4

2.7

13.5

 

11.1

2.2

15.6

 

12.8

-

-

 

-

1330

1.0

3.7

10.0

8.2

3.4

12.0

9.9

3.0

14.1

 

11.6

2.6

16.4

 

13.4

-

-

 

-

1365

0.0

3.9

10.5

8.6

3.7

12.6

10.3

3.3

14.7

 

12.1

2.9

17.0

 

13.9

-

-

 

-

NOTES:

Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil. Refer to page 7 for additional static resistances.

ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.

* FACTORY SETTING

BLOWER PERFORMANCE - 25 TON (DCE/DCG300)

DCG300 - BOT TOM DUCT CON NEC TIONS (COOLINGAPPLICATIONS)

BLOWER

PULLEY

 

7500 CFM

 

 

8750 CFM

 

 

10000 CFM

 

 

11250 CFM

 

 

12500 CFM

 

SPEED

TURNS

ESP

OUTPUT

INPUT

ESP

OUTPUT

INPUT

ESP

OUTPUT

 

INPUT

ESP

OUTPUT

 

INPUT

ESP

OUTPUT

 

INPUT

(rpm)

OPEN:

(iwg)

(bhp)

(kW)

(iwg)

(bhp)

(kW)

(iwg)

(bhp)

 

(kW)

(iwg)

(bhp)

 

(kW)

(iwg)

(bhp)

 

(kW)

 

 

 

 

 

 

 

STANDARD DRIVE:

 

 

 

 

 

 

 

 

 

975

6.0*

1.2

5.9

4.9

0.5

7.3

6.0

-

-

 

-

-

-

 

-

-

-

 

-

1005

5.0

1.4

6.2

5.1

0.7

7.7

6.3

-

-

 

-

-

-

 

-

-

-

 

-

1040

4.0

1.6

6.6

5.4

0.9

8.1

6.7

0.2

9.7

 

8.0

-

-

 

-

-

-

 

-

1070

3.0

1.8

6.9

5.7

1.1

8.5

7.0

0.4

10.2

 

8.3

-

-

 

-

-

-

 

-

1100

2.0

2.0

7.3

6.0

1.3

8.9

7.3

0.6

10.6

 

8.7

-

-

 

-

-

-

 

-

1135

1.0

2.2

7.7

6.3

1.6

9.3

7.6

0.8

11.1

 

9.1

-

-

 

-

-

-

 

-

1165

0.0

2.4

8.0

6.6

1.8

9.7

8.0

1.0

11.6

 

9.5

0.2

13.5

 

11.0

-

-

 

-

 

 

 

 

 

 

 

ACCESSORY DRIVE:

 

 

 

 

 

 

 

 

 

1140

6.0

2.2

7.7

6.3

1.6

9.4

7.7

0.9

11.2

 

9.2

-

-

 

-

-

-

 

-

1180

5.0

2.5

8.2

6.7

1.9

9.9

8.1

1.2

11.8

 

9.7

0.3

13.7

 

11.2

-

-

 

-

1215

4.0

2.7

8.6

7.0

2.1

10.4

8.5

1.4

12.3

 

10.1

0.6

14.3

 

11.7

-

-

 

-

1255

3.0

3.0

9.1

7.4

2.4

11.0

9.0

1.7

12.9

 

10.6

0.9

15.0

 

12.3

-

-

 

-

1290

2.0

3.2

9.5

7.8

2.7

11.5

9.4

2.0

13.5

 

11.1

1.2

15.6

 

12.8

-

-

 

-

1330

1.0

3.5

10.0

8.2

3.0

12.0

9.9

2.3

14.1

 

11.6

1.5

16.4

 

13.4

-

-

 

-

1365

0.0

3.7

10.5

8.6

3.2

12.6

10.3

2.6

14.7

 

12.1

1.8

17.0

 

13.9

-

-

 

-

NOTES:

Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil. Refer to page 7 for additional static resistances.

ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.

* FACTORY SETTING

6

Unitary Products Group

036-21359-001-B-0302

ELECTRICAL DATA - Units With Elec tric Heat

 

 

ELECTRIC HEATER OPTION

MINIMUM

MAXIMUM

MODEL

POWER

CIRCUIT

OVERCURRENT

 

 

 

 

D2CE

SUPPLY

MODEL

kW(1)

STAGES

AMPS

AMPACITY

DEVICE (1)

 

 

 

 

 

 

 

 

 

 

(AMPS)

(AMPS)

300A25

208-3-60

E018

13.5

1

37.5

139.5

175

300A25

208-3-60

E036

27.0

2

75.1

142.1

175

300A25

208-3-60

E054

40.6

2

112.6

189.0

200

300A25

208-3-60

E072

54.1

2

150.1

198.4

225

300A25

230-3-60

E018

18.0

1

43.3

139.5

175

300A25

230-3-60

E036

36.0

2

86.6

156.5

175

300A25

230-3-60

E054

54.0

2

129.9

178.2

200

300A25

230-3-60

E072

72.0

2

173.2

221.5

250

300A46

460-3-60

E018

18.0

1

21.7

68.3

80

300A46

460-3-60

E036

36.0

2

43.3

78.3

80

300A46

460-3-60

E054

54.0

2

65.0

89.1

100

300A46

460-3-60

E072

72.0

2

86.6

110.7

125

300A58

575-3-60

E018

18.0

1

17.3

56.1

70

300A58

575-3-60

E036

36.0

2

34.6

62.6

70

300A58

575-3-60

E054

54.0

2

52.0

71.2

80

300A58

575-3-60

E072

72.0

2

69.3

88.5

100

1

 

 

 

 

NOMINALVOLTAGE

VOLTAGE

KWCAP.MULTIPLIER

 

208

208

1.00

 

240

230

0.92

 

480

460

0.92

 

600

575

0.92

PHYSICAL DATA

BASIC UNITS

MODELS

DCE/DCG/DCV

300

EVAPORATOR

BLOWER

EVAPORATOR

COIL

CONDENSER

FAN

(Two Per Unit)

CONDENSER

COIL

COMPRESSOR

(Qty. Per Unit)

AIR

FILTERS

CHARGE

CEN TRIFU GAL BLOWER (Dia. x Wd. in.)

18 x 15

FAN MO TOR HP

 

15

ROWS DEEP

 

4

FINS PER INCH

 

13.5

FACE AREA (Sq. Ft.)

 

25.0

PRO PEL LER DIA. (in.)

(Each)

30

FAN MO TOR HP

(Each)

1

NOM. CFM TO TAL

(Each)

7200

ROWS DEEP

 

3

FINS PER INCH

 

15

FACE AREA (Sq. Ft.)

 

43.3

12.5 TON, SCROLL, HER METIC,

2

TAN DEM (2 STAGE, 50% ea.)

 

QUAN TITY PER UNIT (16" X 20" X 2")

2

QUAN TITY PER UNIT (16" X 25" X 2")

4

QUAN TITY PER UNIT (14" X 20" X 2")

3

TO TAL FACE AREA (sq. ft.)

21.4

REFRIGERANT

SYS TEM NO. 1

20/8

22 (lbs./oz.)

 

 

 

 

SYS TEM NO. 2

20/0

OPERATING WEIGHTS

 

MODEL SIZE (MBH)

 

300

 

DCE (Cool ing only)

 

2730

 

DCV (Cool ing only)

 

2795

Ba sic Unit

DCG (Gas / Elec tric)

N240

2930

N320

2970

 

 

 

DCV (Gas / Elec tric)

N240

2995

 

N320

3035

 

 

 

Economizer

 

160

 

Econo mizer with

 

245

 

Power Ex haust

 

 

 

 

Options MotorizedDamper

 

150

 

 

18 KW

25

 

Elec tric Heater

36 KW

30

 

(Elec/Elec only)

54 KW

35

 

 

72 KW

40

 

Roof Curb

 

185

 

BarometricDamper

 

45

Accesso-

Economizer/MotorizedDamper

55

Rain Hood

 

ries

Econo mizer/Power Ex haust Rain

90

 

 

Hood

 

 

 

 

 

Wood Skid

 

220

Unitary Products Group

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036-21359-001-B-0302

 

BLOWER MOTOR AND DRIVE DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOTOR1

 

 

ADJUSTABLEMOTORPULLEY

 

FIXED BLOWER PUL LEY

 

BELT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(NOTCHED)

 

 

 

 

MODEL

 

DRIVE

RANGE

 

 

 

 

 

 

 

 

 

OUT-

PITCH

 

 

 

 

 

OUTSIDE

PITCH

 

 

 

PITCH

 

 

 

 

 

SIZE

 

FRAME

EFF.

 

 

DESIG-

 

SIDE

BORE

 

DESIG-

BORE

DESIG-

 

QTY.

 

 

 

 

 

 

 

(RPM)

 

HP

(%)

 

 

NATION

 

DIA.

DIA.

(IN.)

 

NATION

 

DIA.

 

 

DIA.

 

(IN.)

NATION

LENGTH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(IN.)

 

 

(IN.)

 

 

(IN.)

 

(IN.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(IN.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stan-

 

975/1165

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1B5V110

11.3

 

11.1

 

1-7/16

5VX860

86.0

 

1

 

 

 

 

 

dard

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1LVP58B70

 

 

 

6.2-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25 TON

 

High

 

 

 

15

254T

91

 

 

7.5

1 5/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

7.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed

1140/1365

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1B5V94

9.7

 

9.5

 

1-7/16

5VX840

84.0

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Access

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1All mo tors have a nomi nal speed of 1800 RPM, a 1.15 serv ice fac tor and a solid base. They can op er ate to the limit of their serv ice fac tor be cause they are lo cated in the mov ing air, upstream

 

 

of any heat ing de vice.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATIC RESISTANCES*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW (CFM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION

 

7500

 

8750

 

10000

 

11250

 

12500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ESP

 

 

ESP

 

ESP

 

ESP

 

 

ESP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(IWG)

 

(IWG)

 

(IWG)

 

(IWG)

 

 

(IWG)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEDUCTIONS: (SUBTRACT VALUES

BELOW

FROM UNIT'S AVAILABLE ESP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALLOWANCE FOR WET COIL:

 

0.10

 

0.10

 

0.10

 

 

0.10

 

0.10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER (RETURN DUCT):

0.06

 

0.09

 

0.11

 

 

0.14

 

0.18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18kW ELECTRIC HEAT:

 

 

 

0.31

 

0.43

 

0.56

 

 

0.71

 

0.87

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36kW ELECTRIC HEAT:

 

 

 

0.38

 

0.52

 

0.68

 

 

0.87

 

1.07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54kW ELECTRIC HEAT:

 

 

 

0.62

 

0.84

 

1.10

 

 

1.39

 

1.72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72kW ELECTRIC HEAT:

 

 

 

0.68

 

0.93

 

1.21

 

 

1.54

 

1.90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADDITIONS: (ADD VALUES BELOW TO UNIT'S AVAILABLE ESP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HORIZONTAL (SIDE) SUPPLY DUCT:

0.31

 

0.26

 

0.27

 

 

0.31

 

0.41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HORIZONTAL (SIDE) RETURN DUCT:

0.05

 

0.05

 

0.05

 

 

0.05

 

0.05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER EXHAUST PERFORMANCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOTOR

 

 

 

 

 

 

STATIC RE SIS TANCE OF RE TURN DUCT WORK, IWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

 

 

 

0.3

 

 

 

 

 

 

0.4

 

 

 

0.5

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

SPEED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

KW

CFM

 

 

KW

 

CFM

 

KW

 

CFM

 

KW

 

CFM

 

 

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH*

5250

 

0.83

4500

 

 

0.85

 

4200

 

0.88

 

 

3750

 

 

0.93

 

 

3000

 

0.99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MEDIUM

4900

 

0.77

3900

 

 

0.79

 

3500

 

0.82

 

 

2900

 

 

0.85

 

 

-

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

 

4400

 

0.72

3700

 

 

0.74

 

3000

 

0.78

 

 

-

 

 

-

 

 

-

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*FactorySetting

Power Ex haust mo tor is a 3/4 HP, PSC type with sleeve bear ings, a 48 frame and in her ent protection.

ELECTRICAL DATA- Cool ing Only Units and Units With Gas Heat

ELECTRICAL DATA - Cooling Only Units & Units With Gas Heat

 

 

COMPRESSORS

COND. FAN

 

SUPPLY AIR

 

MINIMUM

 

MAXIMUM

MODEL NO.

POWER

(QTY. 2)

(#1 & #2)

 

 

BLOWER MOTOR

 

CIRCUIT

OVERCURRENT

 

 

 

 

 

 

 

SUPPLY

RLA

LRA

HP

FLA

 

HP

 

RLA

 

AMPACITY

 

DEVICE (1)

 

 

 

 

 

 

 

 

(ea.)

(ea.)

(ea.)

(ea.)

 

 

 

(AMPS)

 

(AMPS)

 

 

 

 

 

 

 

 

D2CE300

208/230-3-60

41.4

312

1

4.2

 

 

15

 

38.6

 

139.5

 

 

175

 

& D2CG300

460-3-60

20.0

150

1

2.1

 

 

15

 

19.3

 

68.3

 

 

80

 

 

575-3-60

16.4

108

1

2.0

 

 

15

 

15.4

 

56.1

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER SUP PLY

 

 

VOLTAGE

 

 

 

 

 

 

 

 

 

VOLTAGE

 

 

 

 

MIN.

 

MAX.

 

 

 

 

 

 

 

 

 

208/230-3-60

 

187

 

253

 

 

 

 

 

 

 

 

LIMITATIONS**

 

 

 

 

 

 

 

 

 

 

 

 

460-3-60

 

414

 

506

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

 

518

 

630

 

**Rated in ac cor dance with ARI Stan dard 110, utili za tion range “A”.

8

Unitary Products Group

Loading...
+ 16 hidden pages