Yaskawa GPD 506-P5 User Manual

Yaskawa Electric
America
Unit Troubleshooting Manual
Section Three:
Fault Codes & Appendix
(0.4 ~ 160kW)
PP.P5G5.03.Troubleshoot
Page 1
Rev. 06/11/2003
Section Three:
Fault Codes
REMOTE
SEQ
REF
OC
FOUT IOUT
FREF
MONTR
F/R
V/F
VMTR
FLA
PID
DIGITAL OPERATOR JVOP-131U
DSPL
LOCAL
REMOTE
RUN
kWout
ACCEL
DECEL
FGAIN
FBIAS
kWsav PRGM
ENTER
STOP
RESET
GPD 515/G5
GPD 505/P5 GPD 506/P5
PP.P5G5.03.Troubleshoot
Page 2
Rev. 06/11/2003
Fault Codes
The GPD 506/P5 and GPD 515/G5 inverters can store up to (4) faults.
The GPD 515/G5 inverter has a fault trace that saves the drive status at the time of the fault, and a fault history indicating elapsed time of the stored faults.
The fault codes can be grouped into (3) categories:
Major Fault - Motor coasts to a stop, the fault is displayed on the
digital operator, and the fault relay is activated.
Minor Fault - Operation continues and the fault flashes on the
digital operator. The fault relay does not activate.
Parameter Setting Error - Inverter can’t run. The fault is
displayed on the digital operator, and the fault relay is not activated.
A complete list of fault codes may be found in the appendix.
PP.P5G5.03.Troubleshoot
Page 3
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
UV1
DC Bus Undervolt
Possible Cause(s): Single phase condition on the input, low input voltage at L1, L2, and L3.
Corrective Action: Check the three phase input voltage, verify L2-05 for 515/G5 units.
UV2
CTL PS Undervolt
Possible Cause(s): External load connected pulling down the inverter power supplies.
Corrective Action: Repair or replace the power/gate drive board.
505
Uu1
Uu2
Undervoltage of the main circuit when running.
230V Units - trip point 190V DC or less.
460V Units - trip point 380V DC or less.
600V Units - trip point 546V DC or less.
Undervoltage of the control circuit when running.
230V Units - 30kW ~ 75kW, monitors the (-15V) power supply.
460V Units - 55kW ~ 160kW, monitors the (-15V) power supply.
PP.P5G5.03.Troubleshoot
Page 4
Rev. 06/11/2003
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
506 515
Fault Codes
operator, and the fault relay is activated.
505
UV3
MC Answerback
This fault only applies to 230V units 18kW ~ 75kW , 460V units 22kW ~ 160kW and
600V units 30kW ~ 160kW .
Possible Cause(s):
Corrective Action: Check the contactor, check the ribbon cable from the control board to the
gate drive board.
OV
DC Bus Overvolt
Possible Cause(s): High input voltage at L1, L2, and L3. The deceleration time is set too
short. Power factor correction capacitors are being used on the input to the inverter.
Corrective Action: Check the input circuit, verify the program parameters, add a braking
resistor, remove the power factor correction capacitors.
Uu3
Contacts on contactor are dirty, contactor does not function mechanically.
ou
The pre-charge contactor opened while the inverter is running.
Overvoltage of the main circuit when running.
230V Units - trip point 400V DC or more.
460V Units - trip point 800V DC or more.
600V Units - trip point 1050V DC or more.
PP.P5G5.03.Troubleshoot
Page 5
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
OC
Over current
505
oc
Possible Cause(s): Shorted inverter output phase to phase, shorted motor, locked rotor.
Corrective Action: Remove the motor and run the inverter without the motor. Check the
motor for a phase to phase short. Check the inverter for a phase to phase short at the output.
Designed to protect the inverter.
Output current has exceeded OC level of the inverter rated value instantaneously.
OC – 200%
20P4 – 2015
40P4 – 4015
51P5 - 5160
OC – 180%
2018 – 2075
4018 – 4160
GF
Ground Fault
gf
Designed to protect the inverter.
Inverter output grounding current has exceeded 50% of the inverter rated current.
Possible Cause(s): Motor lead shorted to ground, DCCT defective.
Corrective Action: Remove the motor and run the inverter without the motor. Check the
motor for a phase to ground short. Check the output current with a clamp on meter to verify the DCCT reading.
PP.P5G5.03.Troubleshoot
Page 6
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
SC
Short Circuit
Possible Cause(s): Shorted inverter output phase to phase, shorted motor, locked rotor.
Corrective Action: Remove the motor and run the inverter without the motor. Check the
motor for a phase to phase short. Check the inverter for a phase to phase short at the output.
PUF
DC Bus Fuse Open
Possible Cause(s): Shorted output transistor, shorted main circuit component.
Corrective Action: Remove power from the inverter and disconnect the motor. Perform the
checks without/with power starting on page 10. Replace the shorted component(s), then replace the defective fuse.
505
sc
PUf
The inverter output is short-circuited.
Detects if the DC bus fuse has opened.
PP.P5G5.03.Troubleshoot
Page 7
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
OL1
Motor Overloaded
Possible Cause(s): Motor is overloaded.
Corrective Action: Verify the program settings, reduce the load on the motor.
OL2
Inv Overloaded
Possible Cause(s): Motor is overloaded.
Corrective Action: Verify the program settings, reduce the load on the motor.
505
ol1
ol2
Motor overload, designed to protect the motor.
Fully adjustable from parameter setting (n033 and n034 for 506/P5 and E1-02 and E2-01 for 515/G5)
A pre-alarm can be selected as a minor fault by using the multi-function outputs.
Inverter overload, designed to protect the inverter.
120 or150% of inverter rated current for 1 minute.
515 - 150% for 1 minute
505 and 506 - 120% or 150% depending on drive
capacity and setting parameter n116
PP.P5G5.03.Troubleshoot
Page 8
Rev. 06/11/2003
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
506 515
Fault Codes
operator, and the fault relay is activated.
505
OL3
Overtorque Det 1
Possible Cause(s): Motor is overloaded.
Corrective Action: Verify the program settings, reduce the load on the motor.
506 515
OL4
Overtorque Det 2
Possible Cause(s): Motor is overloaded.
Corrective Action: Verify the program settings, reduce the load on the motor.
ol3
505
N/A
Over torque detection function.
A customer programmable current detection. Response may be selected. A minor fault contact output can be programmed by using the multi-function outputs.
Over torque detection function (2).
A customer programmable current detection. Response may be selected. A minor fault contact output can be programmed by using the multi-function outputs.
PP.P5G5.03.Troubleshoot
Page 9
Rev. 06/11/2003
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
506 515
Fault Codes
operator, and the fault relay is activated.
505
PF
Input Pha Loss
Possible Cause(s): Open phase on the input of the inverter. Loose terminal screws at
terminals L1, L2, or L3. Program parameters set incorrectly (n083 for 506/P5, L8-05 for 515/G5)
Corrective Action: Tighten the terminal screws, check the input voltage, verify the program
settings.
506 515
LF
Output Pha Loss
Possible Cause(s): Open phase on the output of the inverter. Loose terminal screws at
terminals T1, T2, or T3. Program parameters set incorrectly.
Corrective Action: Tighten the terminal screws, check the output voltage, verify the
program settings.
sp1
505
spo
Inverter input power supply has an open phase.
Large imbalance of input voltage.
Inverter output has an open phase.
PP.P5G5.03.Troubleshoot
Page 10
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
OS
Overspeed Det
Possible Cause(s): The load has changed considerably, the program settings may not be
set correctly.
Corrective Action: Check the load on the motor, verify the program settings (F1-08 PG
Overspeed Level, and F1-09 PG Overspeed Time).
506 515
PGO
PG open
Possible Cause(s): The Pulse Generator feedback wires may be broken or not properly
connected to the PG feedback option board.
Corrective Action: Check for a broken wire or a loose connection from the Pulse
Generator, verify the program settings.
505
N/A
505
N/A
The motor speed has exceeded the overspeed level when operating in the Closed Loop V/f or Closed Loop Flux Vector modes.
Feedback pulses are not received by the PG option board.
PP.P5G5.03.Troubleshoot
Page 11
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
RR
DynBrk Transistr
Possible Cause(s):
resistor.
Corrective Action: Replace defective transistor or resistor, monitor DC bus level.
RH
DynBrk Resistor
Possible Cause(s): Overhauling load, extended braking duty cycle, defective braking
resistor.
Corrective Action: Verify braking duty cycle, monitor DC bus voltage, replace resistor.
Shorted braking transistor, high DC bus voltage, defective braking
505
N/A
N/A
The braking transistor has failed.
230V Units - 0.4kW ~ 7.5kW
460V Units - 0.4kW ~ 15kW
The braking resistor temperature has exceeded the allowable value.
(Protects Yaskawa 3% duty cycle resistors only)
Can be selected as a minor fault by using the multi­function outputs.
PP.P5G5.03.Troubleshoot
Page 12
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
CF
Out of Control
Possible Cause(s): The regen torque limit value is set too low, load torque is excessively
large.
Corrective Action: Verify the program setting, L7-03 forward regen torque limit and L7-04
reverse regen torque limit, extend the deceleration time.
SVE
Zero Servo Fault
Possible Cause(s): Torque limit or zero servo gain set too low, load torque excessively
large, PG signal noise.
Corrective Action: Verify the program parameters B9-01 zero servo gain and torque limit
settings L7-01 ~ L7-02, check for noise on the PG signals.
505
N/A
N/A
The actual torque during deceleration has reached the regen torque limit for more than 3 seconds. (Open Loop Flux Vector mode only)
In the zero servo mode, the motor shaft has rotated 10,000 non-quadrature PG pulses from the home position.
PP.P5G5.03.Troubleshoot
Page 13
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
OH1
Heatsnk MAX Temp
Possible Cause(s): Cooling fan(s) are not working, high ambient temperature.
Corrective Action: Check for dirt build-up on the fans, reduce the ambient temperature
around the inverter.
OPR
Oper Disconnect
Possible Cause(s):
Corrective Action: Attach the digital operator, check the cable connected to the digital operator,
verify the program setting of parameter O2-06 for 515/G5 models and n112 for 506/P5 models.
The operator is not attached, broken operator cable.
505
oh2
op
The transistor cooling fin temperature exceeded the allowable value. 506/P5 (105 ° C), 515/G5 (105 ° C)
The inverter will stop if the digital operator is removed when the inverter is commanded to run through the digital operator.
PP.P5G5.03.Troubleshoot
Page 14
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
E-10
SI-F/G CPU down
Possible Cause(s): Defective option board, electrical noise effecting operation.
Corrective Action: Cycle power, replace the option board.
E-15
SI-F/G Com Err
Possible Cause(s): Connection is broken, master has stopped communicating.
Corrective Action: Check all connections, verify all user side software configurations.
E-10 and E-15 fault codes may only appear when using the OMRON specification (O2-09=3).
505
N/A
N/A
The CPU on the SI-F/G option board has stopped operating.
After initial communication has been established, the connection was then lost.
Response may be selected.
PP.P5G5.03.Troubleshoot
Page 15
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
BUS
SI-B Com Err
Possible Cause(s): Connection is broken, master has stopped communicating.
Corrective Action: Check all connections, verify all user side software configurations.
506 515
CE
Memobus Com Err
Possible Cause(s): Connection is broken, master has stopped communicating.
Corrective Action: Check all connections, verify all user side software configurations.
505
N/A
505
ce
After initial communication has been established, the connection was then lost.
Response may be selected.
Transmission error. Control data was not received normally when the power supply is turned on.
Response may be selected.
PP.P5G5.03.Troubleshoot
Page 16
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
EF3
External Fault3
Possible Cause(s): An external fault condition exists connected to terminal number 3.
Corrective Action: Check for an external condition, verify the program parameters.
EF4~8
External Fault
Possible Cause(s): An external fault condition exists connected to one of the terminals 4,
5, 6, 7, or 8.
Corrective Action: Check for an external condition, verify the program parameters.
505
ef3
ef4
~6
External fault at terminal number 3.
External fault at the multi-function inputs terminal number 4 ~ 8. 506 is the same as 505 and only has EF 4-6.
PP.P5G5.03.Troubleshoot
Page 17
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
EF0
External Fault
Possible Cause(s): An external fault condition exists.
Corrective Action: Check for an external condition, verify the program parameters.
506 515
EF2
External Fault
Possible Cause(s): An external fault condition exists at terminal S2.
Corrective Action: Check for an external condition at terminal S2, verify the program
parameters.
505
ef0
505
ef2
External fault from serial communication.
External fault at the multi-function input terminal number S2.
PP.P5G5.03.Troubleshoot
Page 18
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
DEV
Speed Deviation
Possible Cause(s): The load has changed considerably.
Corrective Action: Check the load on the motor, verify the program settings (F1-10 PG
Deviate Level, F1-11 PG Deviate Time. F1-04 PG Deviation Select.
ERR
EEPROM R/W Err
Possible Cause(s): Control board hardware failure.
Corrective Action: Cycle power, replace the control board.
505
N/A
N/A
The deviation of the speed reference and speed feedback has exceeded the regulation level.
A minor fault contact output can be programmed by using the multi-function outputs.
EEPROM internal data does not match the value in RAM when setting a parameter.
PP.P5G5.03.Troubleshoot
Page 19
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
CPF00
Com-Err(OP&INV)
Possible Cause(s): Digital operator cable not securely connected, digital operator
defective, control board defective.
Corrective Action: Check the operator cable, replace the digital operator, replace the
control board.
CPF01
Com-Err(OP&INV)
Possible Cause(s): Digital operator cable not securely connected, digital operator
defective, control board defective.
Corrective Action: Check the digital operator cable, replace the digital operator, replace
the control board.
505
cpf0
cpf1
Transmission between the inverter and the operator cannot be established 5 seconds after supplying power.
Communication fault between the inverter and the operator has occurred for more than 2 seconds.
PP.P5G5.03.Troubleshoot
Page 20
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
CPF02
BB Circuit Err
Possible Cause(s):
Corrective Action: Perform a factory initialization, cycle power, replace the control board.
506 515
CPF03
EEPROM Error
Possible Cause(s): Noise or spike on the control input terminals.
Corrective Action: Perform a factory initialization , cycle power, replace the control board.
Gate array hardware failure during power up.
505
N/A
505
cpf4
Baseblock circuit fault at power up.
EEPROM fault, check sum not valid. 506 digital operator will display CPF04.
PP.P5G5.03.Troubleshoot
Page 21
Rev. 06/11/2003
Loading...
+ 46 hidden pages