Yaskawa GPD 506-P5 User Manual

Yaskawa Electric
America
Unit Troubleshooting Manual
Section Three:
Fault Codes & Appendix
(0.4 ~ 160kW)
PP.P5G5.03.Troubleshoot
Page 1
Rev. 06/11/2003
Section Three:
Fault Codes
REMOTE
SEQ
REF
OC
FOUT IOUT
FREF
MONTR
F/R
V/F
VMTR
FLA
PID
DIGITAL OPERATOR JVOP-131U
DSPL
LOCAL
REMOTE
RUN
kWout
ACCEL
DECEL
FGAIN
FBIAS
kWsav PRGM
ENTER
STOP
RESET
GPD 515/G5
GPD 505/P5 GPD 506/P5
PP.P5G5.03.Troubleshoot
Page 2
Rev. 06/11/2003
Fault Codes
The GPD 506/P5 and GPD 515/G5 inverters can store up to (4) faults.
The GPD 515/G5 inverter has a fault trace that saves the drive status at the time of the fault, and a fault history indicating elapsed time of the stored faults.
The fault codes can be grouped into (3) categories:
Major Fault - Motor coasts to a stop, the fault is displayed on the
digital operator, and the fault relay is activated.
Minor Fault - Operation continues and the fault flashes on the
digital operator. The fault relay does not activate.
Parameter Setting Error - Inverter can’t run. The fault is
displayed on the digital operator, and the fault relay is not activated.
A complete list of fault codes may be found in the appendix.
PP.P5G5.03.Troubleshoot
Page 3
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
UV1
DC Bus Undervolt
Possible Cause(s): Single phase condition on the input, low input voltage at L1, L2, and L3.
Corrective Action: Check the three phase input voltage, verify L2-05 for 515/G5 units.
UV2
CTL PS Undervolt
Possible Cause(s): External load connected pulling down the inverter power supplies.
Corrective Action: Repair or replace the power/gate drive board.
505
Uu1
Uu2
Undervoltage of the main circuit when running.
230V Units - trip point 190V DC or less.
460V Units - trip point 380V DC or less.
600V Units - trip point 546V DC or less.
Undervoltage of the control circuit when running.
230V Units - 30kW ~ 75kW, monitors the (-15V) power supply.
460V Units - 55kW ~ 160kW, monitors the (-15V) power supply.
PP.P5G5.03.Troubleshoot
Page 4
Rev. 06/11/2003
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
506 515
Fault Codes
operator, and the fault relay is activated.
505
UV3
MC Answerback
This fault only applies to 230V units 18kW ~ 75kW , 460V units 22kW ~ 160kW and
600V units 30kW ~ 160kW .
Possible Cause(s):
Corrective Action: Check the contactor, check the ribbon cable from the control board to the
gate drive board.
OV
DC Bus Overvolt
Possible Cause(s): High input voltage at L1, L2, and L3. The deceleration time is set too
short. Power factor correction capacitors are being used on the input to the inverter.
Corrective Action: Check the input circuit, verify the program parameters, add a braking
resistor, remove the power factor correction capacitors.
Uu3
Contacts on contactor are dirty, contactor does not function mechanically.
ou
The pre-charge contactor opened while the inverter is running.
Overvoltage of the main circuit when running.
230V Units - trip point 400V DC or more.
460V Units - trip point 800V DC or more.
600V Units - trip point 1050V DC or more.
PP.P5G5.03.Troubleshoot
Page 5
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
OC
Over current
505
oc
Possible Cause(s): Shorted inverter output phase to phase, shorted motor, locked rotor.
Corrective Action: Remove the motor and run the inverter without the motor. Check the
motor for a phase to phase short. Check the inverter for a phase to phase short at the output.
Designed to protect the inverter.
Output current has exceeded OC level of the inverter rated value instantaneously.
OC – 200%
20P4 – 2015
40P4 – 4015
51P5 - 5160
OC – 180%
2018 – 2075
4018 – 4160
GF
Ground Fault
gf
Designed to protect the inverter.
Inverter output grounding current has exceeded 50% of the inverter rated current.
Possible Cause(s): Motor lead shorted to ground, DCCT defective.
Corrective Action: Remove the motor and run the inverter without the motor. Check the
motor for a phase to ground short. Check the output current with a clamp on meter to verify the DCCT reading.
PP.P5G5.03.Troubleshoot
Page 6
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
SC
Short Circuit
Possible Cause(s): Shorted inverter output phase to phase, shorted motor, locked rotor.
Corrective Action: Remove the motor and run the inverter without the motor. Check the
motor for a phase to phase short. Check the inverter for a phase to phase short at the output.
PUF
DC Bus Fuse Open
Possible Cause(s): Shorted output transistor, shorted main circuit component.
Corrective Action: Remove power from the inverter and disconnect the motor. Perform the
checks without/with power starting on page 10. Replace the shorted component(s), then replace the defective fuse.
505
sc
PUf
The inverter output is short-circuited.
Detects if the DC bus fuse has opened.
PP.P5G5.03.Troubleshoot
Page 7
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
OL1
Motor Overloaded
Possible Cause(s): Motor is overloaded.
Corrective Action: Verify the program settings, reduce the load on the motor.
OL2
Inv Overloaded
Possible Cause(s): Motor is overloaded.
Corrective Action: Verify the program settings, reduce the load on the motor.
505
ol1
ol2
Motor overload, designed to protect the motor.
Fully adjustable from parameter setting (n033 and n034 for 506/P5 and E1-02 and E2-01 for 515/G5)
A pre-alarm can be selected as a minor fault by using the multi-function outputs.
Inverter overload, designed to protect the inverter.
120 or150% of inverter rated current for 1 minute.
515 - 150% for 1 minute
505 and 506 - 120% or 150% depending on drive
capacity and setting parameter n116
PP.P5G5.03.Troubleshoot
Page 8
Rev. 06/11/2003
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
506 515
Fault Codes
operator, and the fault relay is activated.
505
OL3
Overtorque Det 1
Possible Cause(s): Motor is overloaded.
Corrective Action: Verify the program settings, reduce the load on the motor.
506 515
OL4
Overtorque Det 2
Possible Cause(s): Motor is overloaded.
Corrective Action: Verify the program settings, reduce the load on the motor.
ol3
505
N/A
Over torque detection function.
A customer programmable current detection. Response may be selected. A minor fault contact output can be programmed by using the multi-function outputs.
Over torque detection function (2).
A customer programmable current detection. Response may be selected. A minor fault contact output can be programmed by using the multi-function outputs.
PP.P5G5.03.Troubleshoot
Page 9
Rev. 06/11/2003
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
506 515
Fault Codes
operator, and the fault relay is activated.
505
PF
Input Pha Loss
Possible Cause(s): Open phase on the input of the inverter. Loose terminal screws at
terminals L1, L2, or L3. Program parameters set incorrectly (n083 for 506/P5, L8-05 for 515/G5)
Corrective Action: Tighten the terminal screws, check the input voltage, verify the program
settings.
506 515
LF
Output Pha Loss
Possible Cause(s): Open phase on the output of the inverter. Loose terminal screws at
terminals T1, T2, or T3. Program parameters set incorrectly.
Corrective Action: Tighten the terminal screws, check the output voltage, verify the
program settings.
sp1
505
spo
Inverter input power supply has an open phase.
Large imbalance of input voltage.
Inverter output has an open phase.
PP.P5G5.03.Troubleshoot
Page 10
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
OS
Overspeed Det
Possible Cause(s): The load has changed considerably, the program settings may not be
set correctly.
Corrective Action: Check the load on the motor, verify the program settings (F1-08 PG
Overspeed Level, and F1-09 PG Overspeed Time).
506 515
PGO
PG open
Possible Cause(s): The Pulse Generator feedback wires may be broken or not properly
connected to the PG feedback option board.
Corrective Action: Check for a broken wire or a loose connection from the Pulse
Generator, verify the program settings.
505
N/A
505
N/A
The motor speed has exceeded the overspeed level when operating in the Closed Loop V/f or Closed Loop Flux Vector modes.
Feedback pulses are not received by the PG option board.
PP.P5G5.03.Troubleshoot
Page 11
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
RR
DynBrk Transistr
Possible Cause(s):
resistor.
Corrective Action: Replace defective transistor or resistor, monitor DC bus level.
RH
DynBrk Resistor
Possible Cause(s): Overhauling load, extended braking duty cycle, defective braking
resistor.
Corrective Action: Verify braking duty cycle, monitor DC bus voltage, replace resistor.
Shorted braking transistor, high DC bus voltage, defective braking
505
N/A
N/A
The braking transistor has failed.
230V Units - 0.4kW ~ 7.5kW
460V Units - 0.4kW ~ 15kW
The braking resistor temperature has exceeded the allowable value.
(Protects Yaskawa 3% duty cycle resistors only)
Can be selected as a minor fault by using the multi­function outputs.
PP.P5G5.03.Troubleshoot
Page 12
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
CF
Out of Control
Possible Cause(s): The regen torque limit value is set too low, load torque is excessively
large.
Corrective Action: Verify the program setting, L7-03 forward regen torque limit and L7-04
reverse regen torque limit, extend the deceleration time.
SVE
Zero Servo Fault
Possible Cause(s): Torque limit or zero servo gain set too low, load torque excessively
large, PG signal noise.
Corrective Action: Verify the program parameters B9-01 zero servo gain and torque limit
settings L7-01 ~ L7-02, check for noise on the PG signals.
505
N/A
N/A
The actual torque during deceleration has reached the regen torque limit for more than 3 seconds. (Open Loop Flux Vector mode only)
In the zero servo mode, the motor shaft has rotated 10,000 non-quadrature PG pulses from the home position.
PP.P5G5.03.Troubleshoot
Page 13
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
OH1
Heatsnk MAX Temp
Possible Cause(s): Cooling fan(s) are not working, high ambient temperature.
Corrective Action: Check for dirt build-up on the fans, reduce the ambient temperature
around the inverter.
OPR
Oper Disconnect
Possible Cause(s):
Corrective Action: Attach the digital operator, check the cable connected to the digital operator,
verify the program setting of parameter O2-06 for 515/G5 models and n112 for 506/P5 models.
The operator is not attached, broken operator cable.
505
oh2
op
The transistor cooling fin temperature exceeded the allowable value. 506/P5 (105 ° C), 515/G5 (105 ° C)
The inverter will stop if the digital operator is removed when the inverter is commanded to run through the digital operator.
PP.P5G5.03.Troubleshoot
Page 14
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
E-10
SI-F/G CPU down
Possible Cause(s): Defective option board, electrical noise effecting operation.
Corrective Action: Cycle power, replace the option board.
E-15
SI-F/G Com Err
Possible Cause(s): Connection is broken, master has stopped communicating.
Corrective Action: Check all connections, verify all user side software configurations.
E-10 and E-15 fault codes may only appear when using the OMRON specification (O2-09=3).
505
N/A
N/A
The CPU on the SI-F/G option board has stopped operating.
After initial communication has been established, the connection was then lost.
Response may be selected.
PP.P5G5.03.Troubleshoot
Page 15
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
BUS
SI-B Com Err
Possible Cause(s): Connection is broken, master has stopped communicating.
Corrective Action: Check all connections, verify all user side software configurations.
506 515
CE
Memobus Com Err
Possible Cause(s): Connection is broken, master has stopped communicating.
Corrective Action: Check all connections, verify all user side software configurations.
505
N/A
505
ce
After initial communication has been established, the connection was then lost.
Response may be selected.
Transmission error. Control data was not received normally when the power supply is turned on.
Response may be selected.
PP.P5G5.03.Troubleshoot
Page 16
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
EF3
External Fault3
Possible Cause(s): An external fault condition exists connected to terminal number 3.
Corrective Action: Check for an external condition, verify the program parameters.
EF4~8
External Fault
Possible Cause(s): An external fault condition exists connected to one of the terminals 4,
5, 6, 7, or 8.
Corrective Action: Check for an external condition, verify the program parameters.
505
ef3
ef4
~6
External fault at terminal number 3.
External fault at the multi-function inputs terminal number 4 ~ 8. 506 is the same as 505 and only has EF 4-6.
PP.P5G5.03.Troubleshoot
Page 17
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
EF0
External Fault
Possible Cause(s): An external fault condition exists.
Corrective Action: Check for an external condition, verify the program parameters.
506 515
EF2
External Fault
Possible Cause(s): An external fault condition exists at terminal S2.
Corrective Action: Check for an external condition at terminal S2, verify the program
parameters.
505
ef0
505
ef2
External fault from serial communication.
External fault at the multi-function input terminal number S2.
PP.P5G5.03.Troubleshoot
Page 18
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
DEV
Speed Deviation
Possible Cause(s): The load has changed considerably.
Corrective Action: Check the load on the motor, verify the program settings (F1-10 PG
Deviate Level, F1-11 PG Deviate Time. F1-04 PG Deviation Select.
ERR
EEPROM R/W Err
Possible Cause(s): Control board hardware failure.
Corrective Action: Cycle power, replace the control board.
505
N/A
N/A
The deviation of the speed reference and speed feedback has exceeded the regulation level.
A minor fault contact output can be programmed by using the multi-function outputs.
EEPROM internal data does not match the value in RAM when setting a parameter.
PP.P5G5.03.Troubleshoot
Page 19
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
CPF00
Com-Err(OP&INV)
Possible Cause(s): Digital operator cable not securely connected, digital operator
defective, control board defective.
Corrective Action: Check the operator cable, replace the digital operator, replace the
control board.
CPF01
Com-Err(OP&INV)
Possible Cause(s): Digital operator cable not securely connected, digital operator
defective, control board defective.
Corrective Action: Check the digital operator cable, replace the digital operator, replace
the control board.
505
cpf0
cpf1
Transmission between the inverter and the operator cannot be established 5 seconds after supplying power.
Communication fault between the inverter and the operator has occurred for more than 2 seconds.
PP.P5G5.03.Troubleshoot
Page 20
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
CPF02
BB Circuit Err
Possible Cause(s):
Corrective Action: Perform a factory initialization, cycle power, replace the control board.
506 515
CPF03
EEPROM Error
Possible Cause(s): Noise or spike on the control input terminals.
Corrective Action: Perform a factory initialization , cycle power, replace the control board.
Gate array hardware failure during power up.
505
N/A
505
cpf4
Baseblock circuit fault at power up.
EEPROM fault, check sum not valid. 506 digital operator will display CPF04.
PP.P5G5.03.Troubleshoot
Page 21
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
CPF04
Internal A/D Err
Possible Cause(s): Noise or spike on the control board input terminals.
Corrective Action: Perform a factory initialization , cycle power, replace the control board.
506 515
CPF05
External A/D Err
Possible Cause(s): Noise or spike on the control board input terminals.
Corrective Action: Perform a factory initialization , cycle power, replace the control board.
505
cpf5
505
N/A
CPU internal A/D converter fault. 506 digital operator will display CPF05.
CPU external A/D converter fault.
PP.P5G5.03.Troubleshoot
Page 22
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
CPF06
Option Error
Possible Cause(s): An option board is not correctly connected to the control board, an option
board that is not made for the 515/G5 inverter is attached to the control board.
Corrective Action: Remove power to the inverter and connect the option board once more.
Perform a factory initialization , cycle power, replace the option board, replace the control board.
CPF20
Option A/D Error
Possible Cause(s): Defective AI-14B option board, external input is loading down the option
board.
Corrective Action: Remove all inputs to the option board. Perform a factory initialization ,
cycle power, replace the option board, replace the control board.
505
N/A
N/A
Option connection fault.
A/D converter fault on the (AI-14B) option board.
PP.P5G5.03.Troubleshoot
Page 23
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
CPF21
Option CPU down
Possible Cause(s): Noise or spike on the communication line, defective SI-B option board.
Corrective Action: Perform a factory initialization , cycle power, replace the option board,
replace the control board.
CPF22
Option Type Err
Possible Cause(s): Unrecognizable communication or network option board is connected to
the control board.
Corrective Action: Remove any option boards and cycle power, perform a factory initialization,
replace the option board, replace the control board.
505
N/A
N/A
The CPU on the SI-B option board has locked up.
DPRAM fault detected at power up.
PP.P5G5.03.Troubleshoot
Page 24
Rev. 06/11/2003
Fault Codes
Major Fault - Motor coasts to a stop, the fault is displayed on the digital
operator, and the fault relay is activated.
506 515
CPF23
Option DPRAM Err
Possible Cause(s): An option board is not correctly connected to the control board, an
option board that is not made for the 515/G5 inverter is attached to the control board.
Corrective Action: Remove power to the inverter and connect the option board once more.
Perform a factory initialization , cycle power, replace the option board, replace the control board.
505
N/A
DPRAM handshake timing between the 515/G5 and a network or communication option card has timed out.
PP.P5G5.03.Troubleshoot
Page 25
Rev. 06/11/2003
F
ault Codes
Minor Fault - Operation continues and the digital operator indication blink
The fault relay does not activate.
506 515
UV
DC Bus Undervolt
Possible Cause(s): Single phase condition on the input, low input voltage at L1, L2, and L3.
Corrective Action: Check the three phase input voltage, verify setting of L2-05 for GPD515/G5
OV
DC Bus Overvolt
Possible Cause(s): High input voltage at L1, L2, and L3. Power factor correction
capacitors are being used on the input to the inverter.
Corrective Action: Check the input circuit, verify the program parameters, add a braking
resistor, remove power factor correction capacitors.
505
Uu
ou
The main circuit or control circuit voltage has fallen below the under voltage trip point momentarily.
A minor fault contact output can be programmed by using the multi-function outputs. (GPD515/G5 only)
The DC bus voltage has exceeded the overvoltage trip point while the inverter output is off.
PP.P5G5.03.Troubleshoot
Page 26
Rev. 06/11/2003
F
ault Codes
Minor Fault - Operation continues and the digital operator indication blinks
The fault relay does not activate.
506 515
OH
N/A ?
Heatsnk Ovrtemp
Possible Cause(s): Cooling fan(s) are not working, high ambient temperature.
Corrective Action: Check for dirt build-up on the fans, reduce the ambient temperature
around the inverter.
OH2
Over Heat 2
Possible Cause(s): An external overheat condition exists connected to one of the multi-
function input terminals 3, 4, 5, 6, 7, or 8.
Corrective Action: Check for an external condition, verify the program parameters.
505
oh1
oh3
The transistor cooling fin temperature exceeded the allowable value. GPD 506/P5 (95 ° C), GPD515/G5 (95 ° C) Response may be selected.
Inverter overheat pre-alarm signal is input from the multi-function input terminals.
PP.P5G5.03.Troubleshoot
Page 27
Rev. 06/11/2003
F
ault Codes
Minor Fault - Operation continues and the digital operator indication blinks
The fault relay does not activate.
506 515
OL3
Overtorque Det 1
Possible Cause(s): Motor is overloaded.
Corrective Action: Verify the program settings, reduce the load on the motor.
506 515
OL4
Overtorque Det 2
Possible Cause(s): Motor is overloaded.
Corrective Action: Verify the program settings, reduce the load on the motor.
505
ol3
505
N/A
Over torque detection function.
A customer programmable current detection. Response may be selected. A minor fault contact output can be programmed by using the multi-function outputs.
Over torque detection function (2).
A customer programmable current detection. Response may be selected. A minor fault contact output can be programmed by using the multi-function outputs.
PP.P5G5.03.Troubleshoot
Page 28
Rev. 06/11/2003
F
ault Codes
Minor Fault - Operation continues and the digital operator indication blinks
The fault relay does not activate.
506 515
EF0
External Fault
Possible Cause(s): An external fault condition exists.
Corrective Action: Check for an external condition, verify the program parameters.
EF
External Fault
Possible Cause(s): An external forward and reverse command are input simultaneously.
Corrective Action: Check external sequence logic.
505
ef0
ef
External fault from serial communication.
Both the forward and the reverse run commands are input simultaneously for 500 ms or more.
PP.P5G5.03.Troubleshoot
Page 29
Rev. 06/11/2003
F
ault Codes
Minor Fault - Operation continues and the digital operator indication blinks
The fault relay does not activate.
506 515
EF3
External Fault3
Possible Cause(s):
Corrective Action: Check for an external condition, verify the program parameters.
EF4~8
External Fault
Possible Cause(s): An external fault condition exists connected to one of the terminals 4,
5, 6, 7, or 8.
Corrective Action: Check for an external condition, verify the program parameters.
An external fault condition exists connected to terminal number 3.
505
N/A
N/A
External fault at terminal number 3.
External fault at the multi-function inputs terminal number 4 ~ 8.
PP.P5G5.03.Troubleshoot
Page 30
Rev. 06/11/2003
F
ault Codes
Minor Fault - Operation continues and the digital operator indication blinks
The fault relay does not activate.
506 515
OS
Overspeed Det
Possible Cause(s): The load has changed considerably, the program settings are not set
correctly.
Corrective Action: Check the load on the motor, verify the program settings (F1-08 PG
Overspeed Level, and F1-09 PG Overspeed Time).
PGO
PG open
Possible Cause(s): The Pulse Generator feedback wires may be broken or not properly
connected to the PG feedback option board, torque limit set too low, motor shaft locked.
Corrective Action: Check for a broken wire or a loose connection from the Pulse
Generator, verify the program settings (F1-01 PPR, and F1-02 Feedback Loss Select), increase the torque limits.
505
N/A
N/A
The motor speed has exceeded the overspeed level when operating in the Closed Loop V/f or Closed Loop Flux Vector modes.
Feedback pulses are not received by the PG option board.
PP.P5G5.03.Troubleshoot
Page 31
Rev. 06/11/2003
F
ault Codes
Minor Fault - Operation continues and the digital operator indication blinks
The fault relay does not activate.
506 515
DEV
Speed Deviation
Possible Cause(s): The load has changed considerably.
Corrective Action: Check the load on the motor, verify the program settings (F1-10 PG
Deviate Level, F1-11 PG Deviate Time. F1-04 PG Deviation Select.
506 515
CE
Memobus Com Err
Possible Cause(s): Connection is broken, master has stopped communicating.
Corrective Action: Check all connections, verify all user side software configurations.
505
N/A
505
ce
The deviation of the speed reference and speed feedback has exceeded the regulation level.
A minor fault contact output can be programmed by using the multi-function outputs.
Transmission error. Control data was not received normally when the power supply is turned on.
Response may be selected.
PP.P5G5.03.Troubleshoot
Page 32
Rev. 06/11/2003
F
ault Codes
Minor Fault - Operation continues and the digital operator indication blinks
The fault relay does not activate.
506 515
BB
Base Block
Possible Cause(s):
terminals 3, 4, 5, 6, 7, or 8.
Corrective Action: Check for an external condition, verify the program parameters.
A baseblock command was accepted at the multi-function input
505
bb
External baseblock command is input from the multi­function input terminals.
A minor fault contact output can be programmed by using the multi-function outputs.
PP.P5G5.03.Troubleshoot
Page 33
Rev. 06/11/2003
Fault Codes
Parameter Setting Error - Inverter can’t run. The fault is displayed
on the digital operator, and the fault relay is not activated.
506 515
OPE01
kVA Selection
Possible Cause(s): The control board was replaced and the kVA parameter is set incorrectly.
Corrective Action: Enter the correct kVA setting (O2-4 for GPD515/G5) and (n115 for
GPD506/P5) by referring to the inverter model number.
OPE02
Limit
Possible Cause(s): Parameter set above the allowable range.
Corrective Action: Verify the program settings.
505
ope 1
ope 6
Inverter kVA setting error.
Constant data is out of range. 506 digital operator will display OPE06.
PP.P5G5.03.Troubleshoot
Page 34
Rev. 06/11/2003
Fault Codes
Parameter Setting Error - Inverter can’t run. The fault is displayed
on the digital operator, and the fault relay is not activated.
506 515
OPE03
Terminal
Possible Cause(s): Duplicate functions are selected, up/down commands or trim control
increase/decrease are not set simultaneously (GPD515/G5 only). Speed search from maximum frequency and speed search from set frequency are set simultaneously.
Corrective Action: Verify program settings 515/G5 (H1-01 ~ H1-06), 506/P5 (n035 ~ n039).
506 515
OPE05
Sequence Select
Possible Cause(s): Serial communication option board is not installed, option board is
installed incorrectly. The run command selection parameter B1-02 is set to 3 and option board is not installed.
Corrective Action: Verify that an option board is installed. Remove power to the inverter
and connect the option board once more.
505
ope 3
505
N/A
Multi-function input selection fault.
Run command is selected through serial communication at 2CN but option board is not installed.
PP.P5G5.03.Troubleshoot
Page 35
Rev. 06/11/2003
Fault Codes
Parameter Setting Error - Inverter can’t run. The fault is displayed
on the digital operator, and the fault relay is not activated.
506 515
OPE06
PG Opt Missing
Possible Cause(s):
selection parameter A1-02 is set to 1 or 3 without a feedback board installed.
Corrective Action: Verify that an option board is installed. Remove power to the inverter
and connect the option board once more.
OPE07
Analog Selection
Possible Cause(s): Duplicate functions are selected.
Corrective Action: Verify the set values of H3-09 (terminal 14 selection) and H3-05
(terminal 16 selection).
505
N/A
PG option board not correctly installed or missing. The control method
N/A
Closed Loop Flux Vector mode has been selected without a PG board installed.
The multi-function analog inputs terminals 14 and 16 are set for the same function.
PP.P5G5.03.Troubleshoot
Page 36
Rev. 06/11/2003
Fault Codes
Parameter Setting Error - Inverter can’t run. The fault is displayed
on the digital operator, and the fault relay is not activated.
506 515
OPE08
Terminal
Possible Cause(s):
present control mode.
Corrective Action: Check the “modified constants” area and verify the set values in
parameters H1-01~H1-06, H2-01~H2-03, H3-05, H3-09, H4-01 and H4-04.
506 515
OPE10
V/F Ptrn Setting
Possible Cause(s): The V/f parameter settings are not set correctly.
Corrective Action: Check parameters (E1-04 ~ E1-11) for the 515/G5 and parameters
(n012 ~ n018) for the 506/P5. A minimum frequency/voltage value may be set higher than the maximum frequency/voltage.
505
N/A
A multi-function selection has been chosen that is not offered in the
505
ope 5
Multi-function input or multi-function output data setting error.
V/F data setting fault. 506 digital operator will display OPE10.
PP.P5G5.03.Troubleshoot
Page 37
Rev. 06/11/2003
Fault Codes
Parameter Setting Error - Inverter can’t run. The fault is displayed
on the digital operator, and the fault relay is not activated.
506 515
OPE11
FC/ On-Dly
Possible Cause(s): Parameter setting incorrect.
Corrective Action: Check the program settings and correct the errors.
505
N/A
Carrier frequency data setting fault.
Upper limit (C6-01) >5KHz, and the lower limit (C6-02) <= 5KHz.
Carrier frequency proportional gain (C6-03) > 6 and (C6-01) < (C6-02).
506 515
CALL
Serial Com Call
Possible Cause(s): Connection not made properly, user software not configured to the
proper baud rate or configuration.
Corrective Action: Check all connections, verify all user side software configurations.
505
call
Serial communication transmission error. Communication has not yet been established.
PP.P5G5.03.Troubleshoot
Page 38
Rev. 06/11/2003
Fault Codes
Parameter Setting Error - Inverter can’t run. The fault is displayed
on the digital operator, and the fault relay is not activated.
506 515
CALL
SI-F/G ComCall
Possible Cause(s): Connection is broken, master has stopped communicating.
Corrective Action: Check all connections, verify all user side software configurations.
505
N/A
Serial communication transmission error. Communication has not yet been established.
PP.P5G5.03.Troubleshoot
Page 39
Rev. 06/11/2003
Appendix
In the appendix of this manual you will find the following information;
Fault code list
Terminal function diagram for the GPD 515/G5
Terminal function diagram for the GPD 506/P5
Procedure for power component replacement
Thermal compound specifications
Power module layout
Parts lists not found in the technical manuals
PP.P5G5.03.Troubleshoot
Page 40
Rev. 06/11/2003
Appendix
PP.P5G5.03.Troubleshoot
Page 41
Rev. 06/11/2003
Fault Codes
G5 G5 P5 Major Minor Parameter G5 MODBUS
Code Text Code Fault Fault Setting Error Register Data Page #
BB Base Block bb X 91
BUS SI-B Com Err N/A X 74 CALL Serial Com Call CALL X 96 CALL SI-F/G ComCall N/A X 97
CE Memobus Com Err CE X X 21 74,90
CF O ut of Control N/A X 25 71 CPF00 Com-Err (OP&INV) CPF0 X 78 CPF01 Com-Err (OP&INV) CPF1 X 78 CPF02 BB Circuit Err N/A X 79 CPF03 EEPROM Error CPF4 X 79 CPF04 Internal A/D Err CPF 5 X 80 CPF05 Internal A/D Err N/A X 80 CPF06 Option Error N/A X 81 CPF20 Option A/D Error N/A X 81 CPF21 Option CPU down N/A X 82 CPF22 Option Ty pe Err N/A X 82 CPF23 Option DPRAM Err N/A X 83
DEV Speed Deviation N/A X X 19 77,90 E-10 SI-F/G CPU down N/A X 24 73 E-15 SI-F/G Com Err N/A X 23 73
EF External Fault EF X 87
EF0 External Fault EF0 X X 76,87
N/A N/A EF2 X 76 EF3 External Fault 3 EF3 X X 11 75,88 EF4 External Fault 4 EF4 X X 12 75,88 EF5 External Fault 5 EF5 X X 13 75,88 EF6 External Fault 6 EF6 X X 14 75,88 EF7 External Fault 7 N/A X X 15 75,88 EF8 External Fault 8 N/A X X 16 75,88 ERR EEPROM R/W Err N/A X 1F 77
GF Ground Fault GF X 06 64 LF Output Pha Loss SPo X 1C 68
Note: When communicating with the GPD 515G5 using the internal MODBUS protocol, access register 0090H to obtain the present fault.
PP.P5G5.03.Troubleshoot
Page 42
Rev. 06/11/2003
Fault Codes
G5 G5 P5 Major Minor Parameter G5 MODBUS
Code Text Code Fault Fault Setting Error Register Data Page #
OC Over current OC X 07 64
OH Heatsnk Overtemp OH1 X 85
OH1 Heatsnk MAX Temp OH2 X 0A 72 OH2 Over Heat 2 OH3 X 85
OL1 Motor Overloaded OL1 X 0B 66 OL2 Inv Overloaded OL2 X 0C 66 OL3 Overtorque Det 1 OL3 X X 0D 67,86 OL4 Overtorque Det 2 N/A X X 0E 67,86
OPE01 KVA Selection OPE1 X 92 OPE02 Limit OPE6 X 92 OPE03 Terminal OPE3 X 93 OPE05 Sequence Error N/A X 93 OPE06 PG Opt Missing N/A X 94 OPE07 Analog Selection N/A X 94 OPE08 Terminal N/A X 95 OPE10 V/F Ptrn Setting OPE5 X 95 OPE11 FC/ On-Dly N/A X 96
OPR Oper Disconnect OPr X 1E 72
OS Overspeed Det N/A X X 18 69,89
OV DC Bus Overvolt OU X X 08 63,84
PF Input Pha Loss SP1 X 1B 68
PGO PG Open N/A X X 1A 69,89
PUF DC Bus Fuse O pen PUF X 01 65
RH DynBrk Resistor N/A X 10 70
RR DynBrk Transistr N/A X 0F 70
SC Short Circuit SC X 05 65 SVE Zero Servo Fault N/A X 26 71
UV DC Bus Undervolt Uu X 84 UV1 DC Bus Undervolt UU1 X 02 62 UV2 CTL PS Undervolt UU2 X 03 62 UV3 MC Answerback UU3 X 04 63
Note: When communicating with the GPD 515/G5 using the internal MODBUS protocol, access register 0090H to obtain the present fault.
PP.P5G5.03.Troubleshoot
Page 43
Rev. 06/11/2003
GPD 515G5 MODBUS Register Data
The present fault may be obtained by accessing register 0090H. An example of an OL1 fault being read from a GPD515/G5 with the station address of 02 is shown below.
TRANSMIT
02 03 0090 0001 84 14
PLC
Station Address (H5-01)
Read
Register
Command
Fault
Code
Register
RECEIVE
Length of
(# of Register)
CRC High
02 03 02 000B BD 83
Station Address (H5-01)
Register Requested
# of Bytes
Fault (OL1)
CRC High
CRC
Low
CRC
Low
GPD
515/G5
PP.P5G5.03.Troubleshoot
Page 44
Rev. 06/11/2003
Terminal Functions of the GPD515/G5
Power Supply
2K
2K
B1
L1
L2
L3
Forward Run
1
2
Reverse Run
3
4
5
6
7
8
Digital Common
11
15 (+15V, 20mA)
13 Main Ref.(0±10V) 14 Main Ref.(4-20mA) 16 Aux. Ref.(0±10V) 17 Analog Common
33 (-15V, 20mA)
515/G5
Multi-function Inputs
B2
T1
T2
T3
0±10V 21
Common 22
0±10V 23
Multi-function
Analog Output
Multi-function
Analog Output
9
Multi-function Contact
10
Outputs 250Vac/30Vdc, 1A
18 19
Fault Contact 250Vac/30Vdc, 1A
20
25
Multi-function
26
Open Collector Outputs 48v, 50mA
27
IM
2mA maximum
* The braking circuit is factory installed in the following inverters;
230V 1/2 - 10HP
460V 1/2 - 20HP
** Input terminals 1-8 are level sensing type.
PP.P5G5.03.Troubleshoot
Page 45
Rev. 06/11/2003
Terminal functions of the GPD 506/P5
B1
B2
Power Supply
2K
L1
L2
L3
S1
S2
S3
S4
S5
S6
SC
2K
FS
FV
FI
FC
Braking resistor
506/P5
Forward Run
Common
Multi-function Inputs
Digital Common
Analog Supply (15v)
Main Ref. (0-10V)
Aux Ref. (4-20mA)*
Analog Common
0-10V
T1
T2
T3
AM
AC
MA
Multi-function output
MB
250Vac/30Vdc 1A
MC
M1
Multi-function output
M2
250Vac/30Vdc 1A
* Terminal FI is factory set as shown, but can be changed to a voltage input, with a program change and by cutting jumper J1 on the control board.
Multi-function
Output
2mA maximum
IM
PP.P5G5.03.Troubleshoot
Page 46
Rev. 06/11/2003
Power Component Replacement
Incorrect Method for Replacement of Circuit Board Mounted Components
Large board-mounted components (input diodes, output IGBT’s, and power modules) are not being correctly installed into small size inverters during repair. The components are being soldered to the power board, before being mounted to the heat sink.
POWER MODULE
HEAT SINK
POWER BOARD
AIR GAP
7MBR30NF060
PP.P5G5.03.Troubleshoot
Page 47
Rev. 06/11/2003
Power Component Replacement
Correct Method for Replacement of Circuit Board Mounted Components
When mounted correctly, the power module with thermal compound applied, will be in contact with the heatsink. The specifications for the thermal compound can be found on the following page.
POWER BOARD
POWER MODULE
HEAT SINK
7MBR30NF060
THERMAL
COMPOUND
PP.P5G5.03.Troubleshoot
Page 48
Rev. 06/11/2003
Power Component Replacement
Correct Method for Replacement of Circuit Board Mounted Components
The component must first be mounted to the heat sink. The power board should then be installed into the inverter, over the top of the components. Then the components should be soldered to the power board.
1. Mount components to heat sink (include thermal compound)
2. Install power board over components
3. Solder components to the power board
PP.P5G5.03.Troubleshoot
Page 49
Rev. 06/11/2003
Thermal Compound
In the chart below is a list of thermal compound specifications. The thermal
compound used on all power components in Yaskawa inverters is highlighted.
Vendor SHIN-ETSU SHIN-ETSU TOSHIBA CASTALL Description Material Appearance Model Number Thermal Conductivity Temperature Range
Thermal Compound Thermal Compound Thermal Compound Thermal Compound
Silicon Grease Silicon Grease Silicon Grease Silicon Grease
White Paste - - -
G746 KS609 YG6260 CASTALL800
1.6 x 10 ³ cal/cm•sec•°C 1.5 x 10 ³ cal/cm•sec•°C 2 x 10 ³ cal/cm•sec•°C 1.8 x 10 ³ cal/cm•sec•°C
-50° C ~ 150° C -55° C ~ 200° C -50° C ~ 150° C -55° C ~ 205° C
PP.P5G5.03.Troubleshoot
Page 50
Rev. 06/11/2003
Power Module Layout
The power module layout for 230V models 0.4kW ~ 5.5kW and
460V models 0.4kW ~ 4.0kW is shown below.
Pin # Description
P P1 N
1 2 3 4 5 6 7 8 9 10 11
R S T B U V W
P
P1
GU
R S T
B
GB
GU GV
N
GV
EU
EV
GW
EW
GW
1GU
2EU
3GV
4EV
5GW
6EW
7GU
8GV
9GW
10 GB
11 E
U V
W
E
PP.P5G5.03.Troubleshoot
Page 51
Rev. 06/11/2003
Power Module Layout
The power module layout for 230V model 7.5kW and 460V models
5.5kW and 7.5kW is shown below.
Pin # Description
1GW 2EW
1 2 4 5 7 8 10 11 12 13 14 15 16
B
P
N
W V U
P
GW
GV
GU
3 Not Used 4GV 5EV 6 Not Used 7GU 8EU
9 Not Used 10 GX 11 EX 12 GY 13 EY 14 GZ 15 EZ 16 GDB
GDB
B
N
EW
GZ GY
EZ
EY
EV
EU
GX
EX
W
V U
PP.P5G5.03.Troubleshoot
Page 52
Rev. 06/11/2003
Power Module Layout
The power module layout for 230V / 460V 11kW & 15kW models is shown below.
C1
C2E1
E2 C1
C2E1
G1 E1 G2 E2
G2 E2
E1 G1
E2
PP.P5G5.03.Troubleshoot
Page 53
Rev. 06/11/2003
Soft Charge Resistor
Part Numbers:
Inverter Model Inverter Model Mfg. Part YEA Code Resistor
Number Number Number Number Specifications Designation
(G5) (PC5)
230V 230V
CIMR- CIMR-
G5U20P4 P5U20P4 KNYS7W400K R010064 7W 40 OHM +/- 10% R2 G5U20P7 P5U20P7 G5U21P5 P5U21P5 KNYS7W220K R010072 7W 22 OHM +/- 10% R2 G5U22P2 P5U22P2 KNYS7W4R5K R010065 7W 4.5 OHM +/- 10% R14, R22 G5U23P7 P5U23P7 G5U25P5 P5U25P5 KNYS7W3R0K R010066 7W 3 OHM +/- 10% R79, R80 G5U27P5 P5U27P5 R80, R83 G5U2011 P5U2011 RGHS60LS2R2OHMJ R010062 2.2 OHM +/- 10% R1 G5U2015 P5U2015
460V 460V
G5U40P4 P5U40P4 G5U40P7 P5U40P7 KNYS10W800K R010067 10W 80 OHM +/- 10% R4 G5U41P5 P5U41P5 G5U42P2 P5U42P2 R12 G5U43P7 P5U43P7 KNYS10W500K R010068 10W 50 OHM +/- 10% R8, R12 G5U44P0 P5U44P0 R8, R12 G5U45P5 P5U45P5 KNYS10W4R0K R010069 10W 4 OHM +/- 10% R79, R82 G5U47P5 P5U47P5 G5U4011 P5U4011 RGHS80LS6R2OHMJ R010063 80W 6.2 OHM +/-10% R1 G5U4015 P5U4015
PP.P5G5.03.Troubleshoot
Page 54
Rev. 06/11/2003
Soft Charge Resistor
Part Numbers:
Inverter Model Inverter Model Mfg. Part YEA Code Resistor
Number Number Number Number Specifications Designation
230V 230V
CIMR- CIMR-
G5U2018 P5U2018 RGHS60LS2R20HMJ R010062 60W 2.2 OHM +/- 5% R1 G5U2022 P5U2022 G5U2030 P5U2030 G5U2037 P5U2037 SMR120W R007704 120W 1 OHM +/- 5% R1 G5U2045 P5U2045 G5U2055 P5U2055 G5U2075 P5U2075 SMRW220W R007705 220W 1 OHM +/- 5% R1
460V 460V
G5U4018 P5U4018 RGHS80LS6R2OHMJ R010063 80W 6.2 OHM +/-10% R1 G5U4022 P5U4022 G5U4030 P5U4030 G5U4037 P5U4037 RGHS100LS4R0OHMJ R010078 100W 4 OHM +/- 5% R1 G5U4045 P5U4045 G5U4055 P5U4055 G5U4075 P5U4075 SMRW220W R007705 220W 1 OHM +/- 5% R1 G5U4110 P5U4110 G5U4160 P5U4160 R1,R2
PP.P5G5.03.Troubleshoot
Page 55
Rev. 06/11/2003
Soft Charge Resistor
Part Numbers:
Inverter Mode l Inverter Mode l Mfg. Part YEA Code Resistor
Number Number Number Number Specifications Designation
600V 600V
CIMR- CI MR-
G5U51P5 P5U51P5 KNYS10W500K R010068 10W 500 OHM +/-5% R1 G5U52P2 P5U52P2 G5U53P7 P5U53P7 KNYS10W500K R010068 10W 500 OHM +/-5% R73, R74
G5U5P5 P5U5P5 KNYS10W4ROK RO10069 10W 40 OHM + /- 10% R80, R85 G5U57P5 P5U57P5 G5U5011 P5U5011 RGHS80LS6R20HMJ R0100063 80W 6.2 OHM +/ -5% G5U5015 P5U5015 G5U5018 P5U5018 SMR80WA4904 R007607 80W 4.3 OHM +/-10% G5U5022 P5U5022 G5U5030 P5U5030 G5U5037 P5U5037 G5U5045 P5U5045 SMR120WA 4905 R007608 120W 3 OHM + /- 10% R1 G5U5055 P5U5055 G5U5075 P5U5075 G5U5090 P5U5090 R1 G5U5110 P5U5110 SMR220W R007673 220W 3 OHM +/-5% G5U5160 P5U5160
R1
R1
R1,R2
PP.P5G5.03.Troubleshoot
Page 56
Rev. 06/11/2003
Soft Charge Contactor
Part Numbers:
Inverter Model Inverter Model Mfg. Part YEA Code Contactor
Number Number Number Number Specifications Designation
(G5) (PC5)
230V 230V
CIMR- CIMR-
G5U20P4 P5U20P4 G5U20P7 P5U20P7 VSB-24MC POR003011 G5U21P5 P5U21P5 G5U22P2 P5U22P2 HE1AN-DC24V POR003013 G5U23P7 P5U23P7 DC 24V MC1 G5U25P5 P5U25P5 HE2AN-DC24V POR003014 G5U27P5 P5U27P5
G5U2011 P5U2011 G7J-4A-B-DC24V POR003012 G5U2015 P5U2015
460V 460V
G5U40P4 P5U40P4 G5U40P7 P5U40P7 JC2AF-B-DC24V POR003015 G5U41P5 P5U41P5 G5U42P2 P5U42P2 G5U43P7 P5U43P7 DC 24V MC1 G5U44P0 P5U44P0 HE2AN-DC24V POR003014 G5U45P5 P5U45P5 G5U47P5 P5U47P5 HP-20GU MC003260
G5U4011 P5U4011 G7J-4A-B-DC24V POR003012 G5U4015 P5U4015
PP.P5G5.03.Troubleshoot
Page 57
Rev. 06/11/2003
Soft Charge Contactor
Part Numbers:
Inverter Model Inverter Model Mfg. Part YEA Code 24V &
Number Number Number Number Specifications 24V Coil 230V Coil Designation
230V 230V
CIMR- CIMR-
G5U2018 P5U2018 HI-20ETCU-U MC003253 200V 35A X MC1 G5U2022 P5U2022 HI-25ETCU-U MC003333 200V 58A X MC1 G5U2030 P5U2030 HI-35E2T2CU-U MC003483 200V 70A X MC1 G5U2037 P5U2037 G5U2045 P5U2045 HI-35E2TCU MC003259 250V 200A X MC1 G5U2055 P5U2055 G5U2075 P5U2075 HI-100E2TCU MC003257 200V 190A X MC1
460V 460V
G5U4018 P5U4018 HP-20GU MC003260 DC 24V X MC1 G5U4022 P5U4022 HI-15E2TCU MC003274 220V 30A X MC1 G5U4030 P5U4030 G5U4037 P5U4037 HI-20ETCU MC003253 200V 35A X MC1 G5U4045 P5U4045 HI-25ETCU-U MC003333 200V 58A X MC1 G5U4055 P5U4055 HI-35E2T2CU-U MC003483 200V 70A X MC1 G5U4075 P5U4075 G5U4110 P5U4110 HI-35E2T2CU MC003259 200V 115A X MC1 G5U4160 P5U4160 HI-100E2TCU MC003257 200V 190A X MC1
PP.P5G5.03.Troubleshoot
Page 58
Rev. 06/11/2003
Soft Charge Contactor
Part Numbers:
Inverter Model Inverter Model Mfg. Part YEA Code 24V & Resistor
Numbe r Number Num be r Num be r S peci fica tion s 24V Co il 230V Coil Designation
600V 600V
CIMR- CIMR-
G5U51P5 P5U51P5 JC2AF-DC24V POR001074 DC24V A C250V 10A X MC1 G5U52P2 P5U52P2 G5U53P7 P5U53P7 HE2AN-DC24V POR003014 DC24V 20A 2 POLE X MC1
G5U5P5 P 5U5P5 HP-20GU MC003260 DC24V 20A 3A X MC1 G5U57P5 P5U57P5 G5U5011 P 5U5011 G5U5015 P 5U5015 HP-20GU MC003260 24VDC 20A X MC1 G5U5018 P 5U5018 G5U5022 P 5U5022 G5U5030 P 5U5030 G5U5037 P 5U5037 G5U5045 P 5U5045 HI-25ETCU-U MC003333 200V 58A X MC1 G5U5055 P 5U5055 G5U5075 P 5U5075 G5U5090 P 5U5090 S C-5N/UL MC003401 660V 100A X MC1 G5U5110 P 5U5110 S C-6N/UL MC003402 660V 125A X MC1 G5U5160 P 5U5160
PP.P5G5.03.Troubleshoot
Page 59
Rev. 06/11/2003
Part Numbers:
Braking Transistor
Inverter Model
Number
(G5)
230V
CIMR-
G5U20P4 P5U20P4 G5U20P7 P5U20P7 G5U21P5 P5U21P5 INSIDE POWE R MODULE PM1 G5U22P2 P5U22P2 (SEE OUTPUT TRANSISTOR PARTS LIST) G5U23P7 P5U23P7 G5U25P5 P5U25P5 G5U27P5 P5U27P5 TM1
G5U2011 P5U2011 N/A N/A G5U2015 P5U2015
460V 460V
G5U40P4 P5U40P4 G5U40P7 P5U40P7 G5U41P5 P5U41P5 PM1 G5U42P2 P5U42P2 INSIDE POWE R MODULE G5U43P7 P5U43P7 (SEE OUTPUT TRANSISTOR PARTS LIST) G5U44P0 P5U44P0 G5U45P5 P5U45P5 TM1 G5U47P5 P5U47P5
G5U4011 P5U4011 MG50Q1B S11 S TR001058 1200V 50A 1 IN 1 TRM 4 G5U4015 P5U4015
Inverter Model
Number
(PC5) 230V
CIMR-
Mfg. Part Number
YEA Cod e
Specifications
IGBT
Designation
Caution: It is crucial that you remember to apply a thermal compound to the mounting surface of the power module, to ensure proper heat transfer from the module to the inverter’s heat sink. Failure to do so may result in another component failure.
PP.P5G5.03.Troubleshoot
Page 60
Rev. 06/11/2003
Braking Transistor
Part Numbers:
Inverter Model Inverter Model YEA Code IGBT
Number Number Mfg. Part Number Number Specifications Designation
600V 600V
CIMR- CIMR-
G5U51P5 P5U51P5 G5U52P2 P5U52P2 G5U53P7 P5U53P7 PM1
G5U5P5 P5U5P 5 G5U57P5 P5U57P5 G5U5011 P5U5011 MG50Q1BS11 STR001222 1200V 50A TRM4 G5U5015 P5U5015 G5U5018 P5U5018 CM50E 3Y-24E STR001218 1200V 50A TRM4 G5U5022 P5U5022 G5U5030 P5U5030 G5U5037 P5U5037 G5U5045 P5U5045 G5U5055 P5U5055 G5U5075 P5U5075 G5U5090 P5U5090 G5U5110 P5U5110 G5U5160 P5U5160
(SEE OUTPUT TRANSISTOR PARTS LIST)
Caution: It is crucial that you remember to apply a thermal compound to the mounting surface of the power module, to ensure proper heat transfer from the module to the inverter’s heat sink. Failure to do so may result in another component failure.
INSIDE POWER MODULE
NOT INSTALLED IN THESE MODELS
PP.P5G5.03.Troubleshoot
Page 61
Rev. 06/11/2003
Snubber Diodes
Part Numbers:
Inverter Model Inverter Model YEA Code Diode
Number Number Mfg. Part Number Number Specifications Designa tion
230V 230V
CIMR- CIMR-
G5U2018 P5U2018 N/A G5U2022 P5U2022 G5U2030 P5U2030 MS0650D225P-1 SID000583 50A 2.2MFD SM1,3,5
G5U2037 P5U2037 MS0650D225P-1 SID000583 50A 2.2MFD SM1,3,5
G5U2045 P5U2045 MS0650D225P-1 SID000583 50A 2.2MFD SM11,31,51
G5U2055 P5U2055 MS0650D225P-1 SID000583 50A 2.2MFD SM11,31,51
G5U2075 P5U2075 MS0650D225P-1 SID000583 50A 2.2MFD SM111,121,311,321,511,521
460V 460V
G5U4018 P5U4018 G5U4022 P5U4022 G5U4030 P5U4030 N/A G5U4037 P5U4037 G5U4045 P5U4045 G5U4055 P5U4055 MS1250D225P SID000568 50A 2.2MFD SM1,3,5
G5U4075 P5U4075 MS1250D225P SID000568 50A 2.2MFD SM1,3,5
G5U4110 P5U4110 MS1250D225P SID000568 50A 2.2MFD SM11,12,31,32,51,52
G5U4160 P5U4160 MS1250D225P SID000568 50A 2.2MFD SM11,12,31,32,51,52
Caution: It is crucial that you remember to apply a thermal compound to the mounting surface of the transistor module, to ensure proper heat transfer from the module to the inverter heat sink. Failure to do so may result in another component failure.
MS0650D225N-1 SID000582 50A 2.2MFD SM2,4,6
MS0650D225N-1 SID000582 50A 2.2MFD SM2,4,6
MS0650D225P-2 SID000585 50A 2.2 MFD SM12,32,52 MS0650D225N-1 SID000582 50A 2.2MFD SM21,41,61 MS0650D225N-2 SID000584 50A 2.2MFD SM22,42,62
MS0650D225P-2 SID000585 50A 2.2 MFD SM12,32,52 MS0650D225N-1 SID000582 50A 2.2MFD SM21,41,61 MS0650D225N-2 SID000584 50A 2.2MFD SM22,42,62
MS0650D225P-2 SID000585 50A 2.2 MFD SM112,122, 312,322,521,522 MS0650D225N-1 SID000582 50A 2.2MFD SM211,221,411,421,611,621 MS0650D225N-2 SID000584 50A 2.2MFD SM212,222,412,422,612,622
MS1250D225N SID000567 50A 2.2MFD SM2,4,6
MS1250D225N SID000567 50A 2.2MFD SM2,4,6
MS1250D225N SID000567 50A 2.2MFD SM21,22,41,42,61,62
MS1250D225N SID000567 50A 2.2MFD SM21,22,41,42,61,62
PP.P5G5.03.Troubleshoot
Page 62
Rev. 06/11/2003
Snubber Diodes
Part Numbers:
Inverter Mode l Inverter Mode l YEA Code Diode
Number Number Mfg. Part Number Number Specifications Designation
600V 600V
CIMR- CIMR-
G5U51P5 P5U51P5 G5U52P2 P5U52P2 G5U53P7 P5U53P7 G5U5P5 P5U5P5 G5U57P5 P5U57P5 G5U5011 P5U5011 G5U5015 P5U5015 G5U5018 P5U5018 G5U5022 P5U5022 G5U5030 P5U5030 G5U5037 P5U5037 G5U5045 P5U5045 G5U5055 P5U5055 ERG28-14 SID000506 1400V 30A D3, D5, D7 G5U5075 P5U5075 ERG78-14 SID000507 1400V 30A D2,D4, D6 G5U5090 P5U5090 MS145OD225N SID000622 1400V 50A 2.2MFD SM1, SM3, SM5 G5U5110 P5U5110 MS145OD225P SID000623 1400V 50A 2.2MFD SM2, SM4, SM6 G5U5160 P5U5160
Caution: It is crucial that you remember to apply a thermal compound to the mounting surface of the transistor module, to ensure proper heat transfer from the module to the inverter heat sink. Failure to do so may result in another component failure.
Not Required
PP.P5G5.03.Troubleshoot
Page 63
Rev. 06/11/2003
Snubber Resistors
Part Numbers:
Inverter Model Inverter Model YEA Code Resistor
Number Number Mfg. Part Number Number Specifications Designation
230V 230V
CIMR- CIMR-
G5U2018 P5U2018 N/A G5U2022 P5U2022 G5U2030 P5U2030 ERF-60WH100 R007497 60W 10 OHM +/- 5% R3~8 G5U2037 P5U2037 G5U2045 P5U2045 SMR90WA4748C R007157 90W 10 OHM +/- 5% (X2) R3~5 G5U2055 P5U2055 G5U2075 P5U2075 SMR90WA4748M R007697 90W 5 OHM +/- 5% (X2) R3~8
460V 460V
G5U4018 P5U4018 G5U4022 P5U4022 G5U4030 P5U4030 N/A G5U4037 P5U4037 G5U4045 P5U4045 G5U4055 P5U4055 ERF-60WH100 R007497 60W 10 OHM +/- 5% R5 ~ 10 G5U4075 P5U4075 G5U4110 P5U4110 SMR90WA4748C R007157 90W 10 OHM +/- 5% (X2) R7 ~ 9 G5U4160 P5U4160
PP.P5G5.03.Troubleshoot
Page 64
Rev. 06/11/2003
Snubber Resistors
Part Numbers:
Inverter Model Inverter Model YEA Code Resistor
Number Number Mfg. Part Number Number Specifications Designation
600V 600V
CIMR- CIMR-
G5U51P5 P5U51P5 G5U52P2 P5U52P2 G5U53P7 P5U53P7 G5U5P5 P5U5P5 G5U57P5 P5U57P5 G5U5011 P5U5011 G5U5015 P5U5015 G5U5018 P5U5018 G5U5022 P5U5022 G5U5030 P5U5030 G5U5037 P5U5037 G5U5045 P5U5045 G5U5055 P5U5055 ERF-60W R007621 60W 10 OHM +/ - 5% R7 - R12 G5U5075 P5U5075 G5U5090 P5U5090 R9 - R11 G5U5110 P5U5110 SMR90W R007672 90W 10 OHM +/- 5% G5U5160 P5U5160
Not Required
R12 - R14
PP.P5G5.03.Troubleshoot
Page 65
Rev. 06/11/2003
Snubber Capacitors
Part Numbers:
Inverter Model Inverter Model YEA Code Capacitor
Number Number Mfg. Part Number Number Specifications Designation
230V 230V
CIMR- CIMR-
G5U2018 P5U2018 MF-630MPD475K C006066 4.7 MFD +/- 10% C3~8 G5U2022 P5U2022 G5U2030 P5U2030 G5U2037 P5U2037 G5U2045 P5U2045 DE2110R472K2K C003017 2KV 4700PF C12~29 G5U2055 P5U2055 G5U2075 P5U2075 C17 ~ 52
460V 460V
G5U4018 P5U4018 C3 ~ 8 G5U4022 P5U4022 G5U4030 P5U4030 DMPPT3A335K C006097 1000V 3.3MFD G5U4037 P5U4037 C5 ~ 10 G5U4045 P5U4045 G5U4055 P5U4055 G5U4075 P5U4075 DE2110R472K2K C003017 2KV 4700PF C8 ~ 25 G5U4110 P5U4110 C15 ~ 50 G5U4160 P5U4160
PP.P5G5.03.Troubleshoot
Page 66
Rev. 06/11/2003
Snubber Capacitors
Part Numbers:
Inverter Mode l Inverter Model YEA Code Capacitor
Number Number Mfg. Part Number Number Specifications Designation
600V 600V
CIMR- CIMR-
G5U51P5 P5U51P5 G5U52P2 P5U52P2 G5U53P7 P5U53P7 G5U5P5 P5U5P5 G5U57P5 P5U57P5 G5U5011 P5U5011 C1NP3B335K-YA C006367 1250V 3.3UF +/-10% C3 - C5 G5U5015 P5U5015 G5U5018 P5U5018 C1NP3B225K-YA C006366 1250V 2.2UF +/-10% C7 - C9 G5U5022 P5U5022 G5U5030 P5U5030 C1NP3B225K-YA C006366 1250V 2.2UF +/-10% C9-C14 G5U5037 P5U5037 G5U5045 P5U5045 G5U5055 P5U5055 DE2110R472K2K C003017 2KV 4700PF C19 - C21 G5U5075 P5U5075 G5U5090 P5U5090 G5U5110 P5U5110 DE2110R472K2K C003017 2KV 4700PF C21 - C38 G5U5160 P5U5160
Not Required
PP.P5G5.03.Troubleshoot
Page 67
Rev. 06/11/2003
Loading...