Yaskawa GPD506-P5 User Manual

Product Transition Guide
GPD 506/P5 to P7
PL.P7.06.TransitionP5
Product Transition Guide GPD506/P5 to P7
NOTICE
The information contained within this document is the proprietary property of Yaskawa Electric America, Inc., and may not be copied, reproduced or transmitted to other parties without the expressed written authorization of Yaskawa Electric America, Inc. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly improving its high-quality products, the information contained in this document is subject to change without notice. Every precaution has been taken in the preparation of this document. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
Contents
Product Transition Guide
GPD506/P5 to P7
FEATURE OVERVIEW ........................................................................................5
BENEFITS OF THE NEW P7 WHEN COMPARED TO GPD506/P5...................5
NEW/ADDITIONAL P7 PARAMETER FUNCTIONS NOT PRESENT IN THE GPD506/P5 ...................... 5
P7 DIGITAL INPUTS (ADDITIONAL FUNCTIONS)............................................................................. 6
P7 DIGITAL INPUTS (ADDITIONAL FUNCTIONS)............................................................................. 6
P7 ANALOG INPUT (ADDITIONAL FUNCTIONS).............................................................................. 6
P7 DIGITAL OUTPUT RELAY (ADDITIONAL FUNCTIONS).................................................................6
NALOG OUTPUTS (ADDITIONAL FUNCTIONS)......................................................................... 6
P7 A P7 S
ERIAL COMMUNICATIONS .................................................................................................... 7
P7 START-UP, INSTALLATION & MAINTENANCE IMPROVEMENTS.................................................... 7
P7 ADDITIONAL HARDWARE PROTECTION ...................................................................................7
REASONS TO CONTINUE GPD506/P5 ........................................................................................ 7
GPD506/P5 TO P7 SPECIFICATION DIFFERENCES........................................9
DIGITAL OPERATOR COMPARISON .............................................................. 12
GPD506/P5 TO P7 TERMINAL COMPARISON................................................13
NETWORK COMMUNICATIONS ......................................................................17
DETAILS ON NEW P7 FEATURES & FUNCTIONS .........................................18
APPENDIX 1 ......................................................................................................19
RATINGS AND HEAT LOSS COMPARISON ................................................................................... 19
NEC HP RATINGS FOR 240V NORMAL DUTY MODELS .............................................................. 21
NEC HP RATINGS FOR 480V NORMAL DUTY MODELS .............................................................. 22
HEAT LOSS DATA.................................................................................................................... 23
APPENDIX 2 ......................................................................................................25
M
ECHANICAL DIMENSIONS .......................................................................................................25
ANEL CUT-OUT FOR EXTERNAL HEATSINK MOUNTING ..............................................................27
P
MOUNTING HOLE DATA............................................................................................................ 28
APPENDIX 3 – PARAMETER CROSS REFERENCE.......................................29
Product Transition Guide GPD506/P5 to P7
Page Intentionally Left Blank
Product Transition Guide
GPD506/P5 to P7
Feature Overview
This document details differences between the GPD506/P5 and P7 product to assist in product transition and new product introduction.
GPD506/P5 Drive
The GPD 506/P5 inverter is intended for fan and pump applications in Building and Industrial Automation. It is available in constant and variable torque ratings, 3/4 to 500 horsepower.
P7 Drive
The P7 drive is an ideal choice for industrial applications, such as centrifugal fans and pumps. The P7 drive is provided in Normal Duty ratings with 110% overload capability. V/f control mode, network communication options, and an array of input/output choices are available.
New/Additional P7 Parameter Functions not Present in the GPD506/P5
Benefits of the New P7 When Compared to GPD506/P5
New Motor preheat function with adjustable current setting to prevent condensation in motor, (b2-09)
P7 is flash memory upgradeable Accel/Decel range now adjustable from 0.1 to 6000 sec.
(GPD506/P5 max. range is 3600) Critical frequency rejection: 3 selectable, adjustable
bands, d3-03—Jump frequency 3 (additional) (GPD506/P5 only has two)
New Wait To Run Timer function allowing output of drive to delay start after a Run command (b1-11)
Torque boost with adjustable filter time for better torque compensation response (C4-02)
Power loss ride-thru time settable to 25 sec. (GPD506/P5 is 2 sec. Max.)
Auto restart now has maximum restart time after fault if fault condition doesn’t clear during the first try
New "Up/Down" floating point control capability Primary resistance auto-tuning Customizable monitor display Run permissive input
New PI Snooze function available in conjunction with Sleep mode (b5-21)
Adjustable Undervoltage Detection level (L2-05) not available in GPD506/P5
Speed search function with new Speed Estimation mode and Bi-directional search mode (b3-01)
New Setpoint PI features include: Two feedback capability, Output Limit, Offset
adjustment, Primary delay, Output gain, Output reverse, Setpoint accel/decel, Setpoint display scaling, Selectable sleep input source, Snooze function, Setpoint boost, Fdbk square root function with output monitor. (b5-06, b5-07, b5-08, b5-10, b5-11, b5-17 thru 30)
Separately adjustable e-stop times (C1-09) Accel/decel rate switchover via output frequency (C1-
11) 14 more V/f presets than GPD506/P5 for a total of 15
V/f preset patterns (E1-03) Mid frequency and voltage V/f points on the custom
V/f pattern (E1-11,12) Trim speed control function (d4-02)
New/Additional P7 Parameter Functions not Present in the GPD506/P5
Product Transition Guide GPD506/P5 to P7
Motor thermistor input with temperature filter and selectable fault ,alarm settings (L1-02 to L1-
05) Intelligent stall prevention on
accel/decel with decel time 1 or 2 selections (L3-01,4,5)
Extended 0.5 to 600.0 sec. auto­restart time between attempts vs.
10.0 secs for GPD506/P5 (L5-03)
Hunting prevention function (n1­01,2)
DC Injection braking (b1-03) Run command can be accepted
while the drive is being programmed (b1-08) High slip braking function (n3-01,2,3,4) Selectable power-up monitor (o1-01,2) Keypad display contrast adjustment (o1-05) Two independent programmable over and under torque
detection levels
P7 Digital Inputs (Additional Functions)
One more digital input for a total of seven More versatile PNP/NPN sinking/sourcing 24 VDC
control logic Transmitter/option power supply 29 more programmable functions for digital inputs than
GPD506/P5. 59 total : Motor Preheat MOP increase/decrease function Forward and reverse jog input Trim control increase and decrease functions 15 additional external fault action settings such as Fast-
stop, Alarm only, Coast to stop with selectable N.O or N.C. for each fault action.
PI integral hold and PI cancel functions Speed search 3 Serial Communication test mode High slip braking input Jog 2
P7 Digital Inputs (Additional Functions)
Drive enable, with selectable accept run command or cycle run command function
P7 Analog Input (Additional Functions)
A convenient PCB switch now changes analog input A2 between current and voltage, cutting PCB jumper for mA signal is no longer required.
Adjustable analog input signal filter for added stability Terminal A2 is selectable for : Frequency bias Motor thermister PI differential Analog input filter Main and Aux frequency reference is selectable
between terminals A1 and A2
P7 Digital Output Relay (Additional Functions)
27 possible programmable functions for the digital outputs, seven more than the GPD506/P5.
One additional relay output, M3 and M4 relays DC bus under voltage output Reset command active output Reverse direction output Drive enable output OH frequency reduction output Restart Enabled
P7 Analog Outputs (Additional Functions)
Additional AM analog monitor output with bias and gain settings.
Analog monitors now selectable between 0-10V and 4­20ma, GPD506/P5 only 0-10V
18 programmable selections for the analog outputs, 14 more than the GPD506/P5.
Frequency reference monitor Terminal A1 or A2 monitor Motor SEC current monitor SFS output monitor PI- feedback, input, output and setpoint monitors PI feedback 2 monitor Output Voltage
P7 Serial Communications
Built-in RS-485/422 modbus serial communications Optional communication interface: Devicenet, Profibus,
and others Serial communications loss detection timeout function Drive Wizard upload/download and monitoring
/graphing software
Product Transition Guide
GPD506/P5 to P7
P7 Start-up, Installation & Maintenance Improvements
Control terminal board: Quick disconnect Enhanced digital keypad, 5 Line x 16 Character LCD
(Std) 6 new languages can be displayed on the keypad.
GPD506/P5 has only English (A1-00) User password protection for 32 customizable user
parameters (A1-04) A2-01 thru A2-32—User access level provides 32 user
selectable parameters. Parameter copy function to another P7 using standard
digital operator (o3-01) Improved fault storage, last 10 faults Quick disconnect I/O blocks for easy wiring Logged cooling fan hours for scheduled maintenance Modular cooling fan for easy replacement Automatic cooling fan run control to extend fan life
P7 Additional Hardware Protection
Adjustable heat-sink overheat pre-alarm level (L8-02) Selectable ground fault detection (L8-09) Selectable cooling fan operation with off delay (L8-
10,11) Automatic ambient temperature compensation to
protect the drive in environments exceeding its rating (L8-12)
Adjustable OH frequency reference reduction (L8-19) Adjustable motor overload time constant (L1-02)
Product Transition Guide GPD506/P5 to P7
Page left intentionally blank
Product Transition Guide
GPD506/P5 to P7 Specification Differences
GPD506/P5 to P7
Feature
Item Yaskawa GPD506/P5 Yaskawa P7
or Function Performance Features
HP Range
Note: The voltage rating in the “Item” column is generalized. Refer to the Service Conditions section for rated input voltage requirements.
Overload Rating
% for Minutes
PWM Carrier Frequency Max. Output Frequency Speed Range
Protective Features
240V 0.75 to 125HP (VT) 5 to 150HP (ND2) 480V 0.75 to 500HP (VT) 5 to 500HP (ND2)
600V 2 to 200HP (VT)
150% for 1 min (CT)
200% peak
120% for 1 min (VT)
180% peak
Range See Carrier Frequency Table See Carrier Frequency Table
Hz 400Hz 0 To 120Hz
V/f 40:1 40:1
Available w/GPD506/P5
Not Available in P7
110% for 1 min (ND2)
150% peak
Heat Sink Temperature Fault
Fault Action Coast, Ramp, Continue
Design Features
Keypad Design
Qty of keys 7 11
Copy Function No
--Coast, Ramp, Continue or
Continue with reduced speed
--OH Pre-alarm level setting
Language 1 7 (w/LCD)
Yes
Display
LCD display, alpha numeric, 16
char x 2 lines
LCD display, alpha numeric, 16
char x 5 lines, backlit
Product Transition Guide GPD506/P5 to P7
GPD506/P5 to P7 Specification Differences (continued)
Feature or Function
Item Yaskawa GPD506/P5 Yaskawa P7
Design Features (continued)
Network Communications
Diagnostics
Quick Disconnect I/O Terminals
Auto-Tuning
Synchronized Start PI / PID Control
Sleep Function In Open Loop Mode No Yes Automatic Restart Time Between
V/Hz Patterns Qty. 1 Preset, 1 Custom 15 Preset, 2 Custom Skip Frequencies Qty. 2 3 Custom Drive Software Embedded No Flash memory Parameter Upload/Download PC Software InverterWin Drive Wizard Software Accel/Decel Time Sec. 0.0 - 3600.0 sec 0.1 - 6000.0 sec.
DC Injection Function
Braking Function
Cooling Fan
Timer Function
Standard Modbus RTU via RS232
RS232 to RS485, DeviceNet,
Optional
Fault Storage Last 4 Faults
Type No
Rotating/Stationary No
Bi/Uni-Directional Uni-Directional Bi-Directional Speed Search
Method Current Current/Speed
Analog Input Signal
Filter
Two Feedback No Yes
Attempts
Analog Input Filter No Yes Closed Loop PID Control
Two Feedback No Yes
At Start/At Stop At Start/At Stop
DB Transistor
Special No
On/Off Control Power-up based Run Based
Service Disassembly required
Operating Hours Drive power-up hours logged Logged
On/Off Delay On/Off Delay (0-25.5 sec)
Lonworks, ApogeeFLN,
MetasysN2
No Yes
Not Adjustable 0.0 – 600.0 sec (selectable)
Built-in to 10HP (VT-230V) Built-in to 25HP (VT-460V)
Modbus RTU via built in
RS485/422
DeviceNet, Profibus-DP,
Lonworks,
Ethernet
Last 10 Faults with Elapsed Time,
Most Recent Fault with all
Operating Conditions
Yes (Phoenix)
With split front cover for easy
wiring
Primary
resistance auto-tuning
At Start/At Stop (adjustable)
+HSB during stop
Built-in to 25HP
High Slip Braking all models
(Faster stopping without options)
Modular/pluggable fan select
models
On Delay at start (0-600 sec)
On/Off Delay Timer ( 0-3000sec)
Page 10 of 48
Product Transition Guide
GPD506/P5 to P7
GPD506/P5 to P7 Specification Differences (continued)
Feature or Function
Item Yaskawa GPD506/P5 Yaskawa P7
Design Features (continued)
Common DC Bus Capable - No Yes DC Link or AC Choke
Harmonic Counter Measures
Unique Feature/Function - - HSB – High Slip Braking
-
-
230V: 30HP to 125HP (VT)
460V: 30 to 250HP (VT)
12 Pulse: 230V: 30HP and Above
460V: 30HP to 250HP
Inputs and Outputs
Total Qty. 6 7 (optically isolated) Digital Input Terminal NPN/PNP NPN Switchable NPN/PNP
Total Qty 2 3 Digital Output Terminal
Relay Output 1 x Form C, 1 x Form A, 2 x Form A, 1 x Form C
Analog Input
Analog Output
Qty. 2 2
Level Input 0-10V or 4-20mA 0-10 or 4-20mA
Scan Rate 5 msec 5 msec
Loss Detection Ramp or Continue Ramp, Coast or Continue
Qty. 1 2
Output Level 0-10V
Resolution 9 bit 10 bit plus sign
Service Conditions
Rated Input
-
Ambient Temperature
ºC
Storage Temperature ºC -10ºC ~ +60ºC -20ºC ~ +60ºC
NEMA 4X Optional N/A Enclosure Types
NEMA 3/3R Optional N/A
3-phase, 200-230Vac 3-phase, 380-460Vac
Tolerance +10 to –15%
3-phase,500-600Vac
Tolerance +10 to –10%
Frequency: 50/60 Hz +/- 5%
(IP21/NEMA1)
-10ºC ~ +40ºC
(IP00/Protected Chassis)
-10ºC ~ +45ºC
DC Link (Standard)
240V: 30HP to 150 HP
480V: 40 HP to 500 HP
12 Pulse: 240V: 30HP to 150HP 480V: 40HP to 500HP
0-10V or 4-20ma
With independent level selections
3-phase, 200-240Vac 3-phase, 380-480Vac
Tolerance +10 to –15%
Frequency: 50/60 Hz +/- 5%
Note: P7 Models 2037-2110 rated
for 200-230Vac.
-10ºC ~ +40ºC (IP21/NEMA1)
-10ºC ~ +45ºC
(IP00/Protected Chassis)
(Automatic OL protection curve
based on ambient temperature
setting of L8-12)
Page 11 of 48
Product Transition Guide
A
GPD506/P5 to P7
Digital Operator Comparison
Enhanced LCD operator with built-in copy function and parameter verify for P7
Optional LED operator available for P7
LCD contrast adjustment
Simplified parameter grouping for easier navigation and set-up
GPD506/P5 Operator New P7 Operator
LCD DISPLAY
Frequency Ref
-
=
Menu Display
-DRIVE- Rdy
Frequency Ref
U1-01= 60.00Hz
- - - - - - - - - - - - - - - - - - - - - - - - - - - - -
U1-02= 60.00Hz U1-03= 10.05A
-QUICK-
Accel Time 1
------------------------------
21.0secs
C1-01=
(0.0~6000.0)
“30.0 sec”
-Rdy-
P7 copy keypad is capable of uploading all of the parameter settings from the P7 drive memory.
o Upload of GPD506/P5 parameters to P7 not possible at this time o P7 Drives must have the same software version, model, and control mode to copy parameters.
A Quick Start menu is added to aid in simple start-ups.
The Quick Start menu consists of 64 parameters. The Advanced menu is the other menu choice.
Simplified Menu Structure in P7:
GPD506/P5 P7
-- Operation “DRIVE” Quick Start -- 16 Parameters Quick Setting “QUICK” Programming (All Parameters) Programming “ADV”
-- Modified Constants “VERIFY”
-- Auto-Tuning “A.TUNE”
--
Drive Mode Indicators
Dr ive ca n o pe rate when a driv e co mman d is inpu t
Displays monitor data, parameter data and settings
Read y Display
Data Display
1 line x 13 characters
3 li nes x 1 6 ch arac ter s
RUN & STOP Indicators
Present Setting (user adjusts)
llowed Setting Range
Factory Default
Keys
Page 12 of 48
GPD506/P5 to P7 Terminal Comparison
The factory default is 2-wire control as shown.
Type
Digital Input Signals
GPD506/P5 Terminal
GPD506/P5
Terminal
S1
S2
S3
S4
S5
S6
SC
Default Function & Description P7
Forward run/stop, Forward run when closed, and stop when open. Photo-coupler insulation Input: +24VDC 8mA
Reverse run/stop, Reverse run when closed, Stop when open. Multi-function contact input (n036) Photo-coupler insulation Input: +24VDC 8mA
External fault input, Fault when closed, normal state when open. Multi-function contact input (n037) Photo-coupler insulation Input: +24VDC 8mA
Fault reset input, Reset when closed. Multi-function contact input (n038) Photo-coupler insulation Input: +24VDC 8mA
Multi-step speed reference 1, Enabled when closed. Multi-function contact input (n039) Photo-coupler insulation Input: +24VDC 8mA
Multi-step speed reference 2, Enabled when closed. Multi-function contact input (n040) Photo-coupler insulation Input: +24VDC 8mA
Sequence input common terminal
Terminal
S1
S2
S3
S4
S5
S6
S7
SN
SC SP
(Designations similar to GPD506/P5)
Default Function P7 Description
Forward run/stop command
Reverse run/stop command
External fault input
Fault reset
Multi-step speed reference 1
Multi-step speed reference 2
Jog frequency reference Digital input common
Factory connected to SP Factory connected to SC
Product Transition Guide
GPD506/P5 to P7
P7 Terminal
Multi-function digital inputs.
Functions set by: H1-01 to H1-05. 24 VDC, 8mA Photo coupler isolation
Factory connected for internal supply sinking mode. Refer to P7 User Manual for other methods.
Page 13 of 48
Product Transition Guide
g
GPD506/P5 to P7
Type
Analog Input Signals
Digital Output Signals
Analog Output
GPD506/P5 Terminal
GPD506/P5
Terminal
FS
FV
FI
FC
E(G)
M1 M1
M2
MA MA MB MB
MC
nals
AM
Si
Default Function & Description P7
+15V Power supply output for analog command (Allowable current, 20mA max.)
Frequency reference input (voltage) 0 to +10V/100%, n043 = “FV=MSTR”: FV enabled n043 = “FI=MSTR”: FI enabled 0 to +10V (20kW)
Frequency reference input (current) 4 to 20mA/100% n043 = “FV=MSTR”: FV enabled n043 = “FI=MSTR”: FI enabled 4 to 20mA (250W)
Common terminal 0V
Connection to shield sheath of signal lead
During running (N.O. contact) Closed when running. Multi-function contact output (n042) Dry contact capacity: 250VAC 1A or less 30VDC 1A or less
Fault contact output (N.O./N.C. contact) Fault when closed between terminals MA and MC Fault when open between terminals MB and MC Multi-function contact output (n041) Dry contact capacity: 250VAC 1A or less 30VDC 1A or less
Frequency meter output 0 to +10V/100% frequency Multi-function analog monitor 1
(n052)
0 to +10V 2mA or less
Terminal
+V
A1
A2
AC
E(G)
M2
M3
M4
MC
FM
Page 14 of 48
(Designations similar to GPD506/P5)
Default Function P7 Description
+15Vdc power output
Analog input or speed command
Analog input or speed command
Analog common – Shield wire, optional ground
line connection point
During run (N.O. contact)
Remote/Auto Operation (N.O. contact)
Same function as GPD506/P5. Non­programmable
Output frequency
P7 Terminal
+15Vdc (Max. current: 20mA)
0 to +10Vdc=100% (20k ohm)
4 to 20mA=100%/(250 ohms) 0 to +10Vdc=100%/(20k ohm) Function set by H3-09.
Form A Dry contacts capacity: 1 A max. at 250Vac 1 A max. at 30Vdc Multi-function digital output. Function set by H2-01.
Form A Dry contacts capacity: 1 A max. at 250Vac 1 A max. at 30Vdc Multi-function digital output. Function set by H2-02.
Form C Dry contacts capacity: 1 A max. at 250Vac 1 A max. at 30Vdc
0 to +10Vdc 10V=100% Output frequency (Max current 2mA). Function set by H4-01.
Product Transition Guide
Terminal Comparison
Type
GPD506/P5 Terminal
GPD506/P5
Terminal
AC
RS-485/422
Default Function & Description P7
Frequency meter output “AM” Common
– – – – –
P7 Terminal
(Designations similar to GPD506/P5)
Terminal
AM
AC
– –
– –
R+
R­S+ S-
IG
Default Function P7 Description
0 to +10Vdc or 10V=100% Drive output
Output current
Analog common – Modbus communication
Differential input, PHC isolation
Modbus communication Differential output, PHC isolation
Signal common
current (Max current 2mA) Drive's rated output current / Function set by H4-04.
Page 15 of 48
Product Transition Guide
Ω
Ω
Ω
A
(
)
(
)
)
(
)
(
) (0V)
(
A
y
A
Terminal Comparison
Multi-Function
Inputs
nalog Inputs
Input FI selectable
4~20mA
or
0~10V
Serial Port
0~ + 10V 4~20mA
L1 L2
GPD506/P5
L3 L11
L21 L31
S1 - Fixed S2
S3 S4
S5 S6
SC (Com
G
FS
+15V
Ω
FV
20k
Ω
250
RS-232
10-pin
FI
FC
Gate Drive
PWM
8 bit
/D
10 bit
Digital
Operator
0~10VAM
Com) AC
G
MA MB MC
M1 M2
Shorting Bar Standard:
Ω
2k
PP
CIMR-P7U23P7 to 2018 CIMR-P7U43P7 to 4018
R/L1
S/L2
T/L3
S1
S2 S3 (H1-01) S4 (H1-02) S5 (H1-03) S6 (H1-04) S7 (H1-05)
SN
SC
SP
E(G)
+V +15VDC, 20mA
A1 0-10VDC, 20 K A2 (H3-08)
4-20mA, 250 K [0 to +10VDC, 20K ] AC
R+
R-
S+
S-
T1 T2
IM
T3
Foward Run/Stop
Reverse Run/Stop
External Fault
Multi-Function
nalog Outputs
Fault Reset
Multi-step Speed Setting 1
Multi-step Speed Setting 2
Jog Frequency Reference
Multi-Function
Outputs
Rela
Power Supply
L1
L2
L3
PE
2k
Modbus
RS-485/422
3-Phase
50/60Hz
MCCB
Multi-function
Contact Inputs
(Factory Default)
External Frequency Reference
4 to 20mA
UX
Terminating Resistance
110
1+2+
P7
E7
Digital Outputs
250VAC/30VDC, 1A
S1-1
DC Reactor Standard: CIMR-P7U2022 to 2110 CIMR-P7U4030 to 4300
+
3
-
Multi-function
(H2-01)
(H2-02)
(H4-01) FM
(H4-04) AM
U/T1
V/T2
W/T3
MA
MB
MC
M1
M2
M3
M4
E(G)
AC
Motor
M
Fault Contact Digital Output
250VAC/30VDC, 1A
Digital Output 1
(Default: During RUN)
Digital Output 2
(Default: Remote/
Auto Operation)
Multi-function
Analog Outputs
0 to +10VDC, 2mA
+
+
-
-
IG
Page 16 of 48
Product Transition Guide
GPD506/P5 to P7
Network Communications
GPD506/P5 P7
Not Available DeviceNet Not Available EtherNet Not Available Profi-Bus
RS-232 PCB Port (2CN) RS-232 via Digital Operator Port
SI-K2/P RS-485 Modbus Communication Card Standard Built-in RS-485
Lon Works Lon Works2
Johnson Controls MetaSys N2 Not Applicable
Software Upload/Download Tool
2
Available as an option based on market demands
FLN Network for System 600/ Apogee Not Applicable
InverterWin DriveWizard
Network Communications Option Availability
Note: Communication option release schedule is subject to change. Yaskawa Marketing Communications will provide official notice of product availability.
Ethernet
Ethernet
MODBUS TCP/IP
MODBUS TCP/IP
Present
Present
Ready now, available at P7 launch
Ready now, available at P7 launch
P7 (CM058) available at P7 launch
P7 (CM058) available at P7 launch
Modbus - Plus, testing, available at P7 launch
Modbus - Plus, testing, available at P7 launch
Available at P7 launch
Available at P7 launch
Ready now, available at P7 launch
Ready now, available at P7 launch
Page 17 of 48
Product Transition Guide GPD506/P5 to P7
Details on New P7 Features & Functions
Note: This section details only a few of the new P7 features.
o New Auto Tuning
The P7 comes with a Motor Auto-tuning function to help to optimize the drive performance.
Feature GPD506/P5 P7
R1 Primary Resistance Tuning No Yes
R1 Primary Resistance Auto-tuning method is for motor terminal resistance. This method involves no motor shaft rotation.
o New High Slip Braking
The P7 incorporates a new braking function called High Slip Braking (HSB). By using a method that utilizes increased rotor slip, the drive will gain the capability of stopping up to 50% faster than without a braking resistor. All of this without the need of any external equipment or resistors!
Greater than 150% brake torque is possible.
Motor speed
Motor voltag e
DC-Bus voltage
Motor speed
Motor voltage
DC-Bus voltage
Page 18 of 48
Product Transition Guide
Appendix 1 Ratings and Heat Loss Comparison
Page 19 of 48
Product Transition Guide GPD506/P5 to P7
Page Intentionally Left Blank
Page 20 of 48
Product Transition Guide
Appendix 1 –Ratings and Heat Loss Comparison
NEC HP Ratings for 240V Normal Duty Models
GPD506/P5 230V Models P7 240V Models Variable Torque (n116=1) Normal Duty (C6-01=2)
NEC
HP
230V
Amps
NEC
GPD506/P5
Model
CIMR-P5U
Output
Amps
Fc
kHz
Overload%
VT
1 minute
P7
Model
CIMR-P7U
Output
Amps
Fc
kHz
Overload %
ND
1 minute
5 15.2
7.5 22 10 28 15 42 20 54 25 68 30 80 40 104 50 130 60 154 75 192
100 248 125 312 150 360 150 360
*Note: Optional NEMA1 kit required for NEMA1 rating. Input voltage rating is 230V on these models.
23P71 17.5 15 120 25P51 27 10 120 27P51 36 10 120 20111 54 10 120
20151 68 10 120 20181 80 15 120 20221 104 15 120
20301 130 10 120 20371* 160 10 120 20451* 192 10 120
20551* 248 8 120 20751* 312 8 120
- - - -
- - - -
23P71 16.8 10 107 25P51 23 15 120 27P51 31 15 102 20111 46.2 8 117 20151 59.4 10 117 20181 74.8 10 114 20221 88 10 116 20301 115 10 120
20371* 162 5 107
20451* 192 5 113 20551* 215 8 120
20751* 312 2 109
20901* 360 2 115 21100* 415 2 120
Page 21 of 48
Product Transition Guide Appendix 1 –Ratings and Heat Loss Comparison
NEC HP Ratings for 480V Normal Duty Models
GPD506/P5 460V Models P7 480V Models
Variable Torque (n116=1) Normal Duty (C6-02=2)
NEC
HP
Amps
460V
5.0 7.6
7.5 11 10 14 15 21 20 27 25 34 30 40 40 52 50 65 60 77 75 96
100 124 125 156 150 180
200 240
250 302 300 361 350 414 400 477 450 506 500 590
550 660
*Note: Optional NEMA1 kit required on these models for NEMA1 rating.
NEC
GPD506/P5
Model
CIMR-P5U
43P71 8.5 10 120 43P71 7.6 15 120
44P01 11.7 10 120 45P51 12.5 15 120 45P51 14.8 10 120 47P51 17 15 120 47P51 21 10 120 40111 28.6 10 120 40151 34 10 120 40151 34 10 109 40181 41 10 120 40181 40 10 117 40221 52 8 120 40301 65 5 120 40371 80 5 120 40371 77 8 117 40451 96 5 120 40451 96 8 114 40551 128 5 120 40551 125 5 108
40751* 180 5 120 40751* 156 5 115
41101* 240 5 120 41101* 240 5 108
41601* 302 5 120 41601* 304 5 120
41850 380 2.5 120 42200 506 2.5 120
43000 675 2.5 120
Output
Amps
Fc kHz
OL %
VT
1 minute
P7
Model
CIMR-P7U
44P01 8.7 15 120
40111 27 8 107
40301 67.2 8 107
40901* 180 8 120
41321* 260 5 120
41850 414 2 107
42200 506 2 118
43000 675 2 120
Output
Amps
Fc
kHz
Overload %
ND
1 minute
Page 22 of 48
Product Transition Guide
Appendix 1 –Ratings and Heat Loss Comparison
Heat Loss Data
Note: Ampacity ratings vary between GPD506/P5 and P7 models.
Refer to NEC Ratings tables in Appendix 1 for the appropriate GPD506/P5 to P7 cross-reference.
GPD506/
P5 Model
23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110 40P4 40P7 43P7 44P0 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300
GPD506/P5 (W)
Internal Heatsink Total
80 135 215
90 210 300 110 235 345 160 425 585 200 525 725 230 655 885 280 830 1110 500 1050 1550 700 1250 1950 750 1550 2300
1000 1950 2950 1300 2300 3600
-
- 50 10 60 65 20 85 65 80 145 80 120 200 85 135 220
120 240 360 150 305 455 180 390 570 195 465 660 260 620 880 315 705 1020 370 875 1245 415 970 1385 710 1110 1820 890 1430 2320
-
1160 1870 3030
-
1520 2670 4190 1510 3400 4910 2110 4740 6850 2910 6820 9730
P7
Model
23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110 40P4 40P7 43P7 44P0 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300
P7 (W)
Internal Heatsink Total
74 110 184
84 164 248 113 219 332 168 357 525 182 416 598 208 472 680 252 583 835 333 883 1216 421 1010 1431 499 1228 1727 619 1588 2207 844 1956 2800 964 2194 3158
1234 2733 3967
39 14 53
41 17 58
68 80 148
70 90 160
81 127 208 114 193 307 158 232 390 169 296 465 201 389 590 233 420 653 297 691 988 332 801 1133 386 901 1287 478 1204 1682 562 1285 1847 673 1614 2287 847 1889 2736
1005 2388 3393 1144 2791 3935 1328 2636 3964 1712 3797 5509 2482 5838 8320
Page 23 of 48
Product Transition Guide Appendix 1 – Ratings and Heat Loss Comparison
Page Intentionally Left Blank
Page 24 of 48
Product Transition Guide
Appendix 1 – Ratings and Heat Loss Comparison
Appendix 2
Mechanical Dimensions
Page 25 of 48
Product Transition Guide GPD506/P5 to P7
Page Intentionally Left Blank
Page 26 of 48
Product Transition Guide
Appendix 2 – Mechanical Dimensions
Panel Cut-out for External Heatsink Mounting
Note: Ampacity ratings vary between GPD506/P5 and P7 models.
Refer to NEC Ratings tables in Appendix 1 for the appropriate GPD506/P5 to P7 cross-reference.
GPD506/P5 Panel Cutout for
External Heatsink
Model GPD506/P5
(mm)
W H W H W H W H
23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300
138 271 5.43 10.67 180 298 7.09 11.73 180 298 7.09 11.73 200 377 7.87 14.84 200 377 7.87 14.84 308 404 12.13 15.91 308 404 12.13 15.91 403 627 15.87 24.69 403 627 15.87 24.69 445 756 17.52 29.76 445 756 17.52 29.76 555 894 21.85 35.20
- 138 271 5.43 10.67 180 298 7.09 11.73 180 298 7.09 11.73 200 377 7.87 14.84 200 377 7.87 14.84 308 404 12.13 15.91 308 404 12.13 15.91 309 571 12.17 22.48 309 571 12.17 22.48 309 571 12.17 22.48 440 761 17.32 29.96 440 761 17.32 29.96
555 894 21.85 35.20
- 555 894 21.85 35.20 875 1324 34.45 52.13 875 1324 34.45 52.13 873 1475 34.37 58.07
GPD506/P5 (in) Model P7 (mm) P7 (in)
-
-
P7 Panel Cutout for
External Heatsink
23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300
138 271 5.43 10.67 138 271 5.43 10.67 197 298 7.76 11.73 197 298 7.76 11.73 233 353 9.17 13.90 233 353 9.17 13.90 244 369 9.61 14.53 269 419 10.59 16.50 359 545 14.13 21.46 359 545 14.13 21.46 434 673 17.09 26.50 434 673 17.09 26.50 484 782 19.06 30.79 555 817 21.85 32.17 138 271 5.43 10.67 138 271 5.43 10.67 197 298 7.76 11.73 197 298 7.76 11.73 233 353 9.17 13.90 233 353 9.17 13.90 269 419 10.59 16.50 269 419 10.59 16.50 309 519 12.17 20.43 309 519 12.17 20.43 309 519 12.17 20.43 434 673 17.09 26.50 434 673 17.09 26.50 484 782 19.06 30.79 484 782 19.06 30.79 555 817 21.85 32.17
-
Page 27 of 48
Product Transition Guide Appendix 2 – Mechanical Dimensions
Mounting Hole Data
Note: Ampacity ratings vary between GPD506/P5 and P7 models. Refer to NEC Ratings tables in Appendix 1 for the appropriate GPD506/P5 to P7 cross-reference.
GPD506/P5 P7
Model Enclosure
23P71 25P51 27P51
20111 20151 20181 20221 20301 20371 20451 20551 20751 20900 21100
43P71 45P51 47P51
40111 40151 40181 40221 40301 40371 40451 40551 40751 40901 41101 41321 41601 41850 42200 43000
NEMA1 10.47 4.96 266 126 NEMA1 11.22 7.32 285 186 NEMA1 11.22 7.32 285 186 NEMA1 14.37 9.29 365 236 NEMA1 14.37 9.29 365 236 NEMA1 17.13 10.83 435 275 NEMA1 17.13 10.83 435 275 NEMA1 25.59 12.6 650 320 NEMA1 25.59 12.6 650 320 NEMA1 30.51 14.57 775 370 NEMA1 30.51 14.57 775 370
NEMA1 35.24 17.52 895 445 Open (IP00) - Open (IP00) -
NEMA1 10.47 4.96 266 126
NEMA1 10.22 7.32 260 186
NEMA1 10.22 7.32 260 186
NEMA1 14.37 9.29 365 236
NEMA1 14.37 9.29 365 236
NEMA1 17.13 10.83 435 275
NEMA1 17.13 10.83 435 275
NEMA1 24.02 10.83 610 275
NEMA1 24.02 10.83 610 275
NEMA1 24.02 10.83 610 275
NEMA1 31.3 13.78 795 350
NEMA1 31.3 13.78 795 350
NEMA1 -
NEMA1 35.24 17.52 895 445
NEMA1 35.24 17.52 895 445
NEMA1 35.24 17.52 895 445 Open (IP00) 55.12 29.53 1400 750 Open (IP00) 55.12 29.53 1400 750 Open (IP00) 61.02 29.53 1550 750
(in) (mm) (in) (mm)
H1 W1 H1 W1
Model Enclosure
23P71 25P51 27P51 20111 20151 20181 20221 20301 20371 20451 20551 20751 20901 21100
43P71 45P51 47P51 40111 40151 40181 40221 40301 40371 40451 40551 40751 40901 41101 41321
41601 41850 (1) 42200 (1) 43000 (1)
Note (1): 3 mounting holes top and 3 mounting holes bottom. Dimension is between each mounting hole.
NEMA1 10.47 4.96 266 126 NEMA1 10.47 4.96 266 126 NEMA1 11.22 7.32 285 186 NEMA1 11.22 7.32 285 186 NEMA1 13.19 8.5 335 216 NEMA1 13.19 8.5 335 216 NEMA1 15.16 7.68 385 195 NEMA1 17.13 8.66 435 220 NEMA1 22.64 9.84 575 250 NEMA1 22.64 9.84 575 250 NEMA1 27.56 12.8 700 325 NEMA1 27.56 12.8 700 325 NEMA1 32.28 14.57 820 370
Open (IP00) 33.56 17.52 852 445
NEMA1 10.47 4.96 266 126 NEMA1 10.47 4.96 266 126 NEMA1 11.22 7.32 285 186 NEMA1 11.22 7.32 285 186 NEMA1 13.19 8.5 335 216 NEMA1 13.19 8.5 335 216 NEMA1 17.13 8.66 435 220 NEMA1 17.13 8.66 435 220 NEMA1 21.06 10.24 535 260 NEMA1 21.06 10.24 535 260 NEMA1 21.06 10.24 535 260 NEMA1 27.56 12.8 700 325 NEMA1 27.56 12.8 700 325 NEMA1 32.28 14.57 820 370 NEMA1 32.28 14.57 820 370
NEMA1 33.66 17.52 855 445 Open (IP00) 50 10.63 1270 270 Open (IP00) 50 10.63 1270 270 Open (IP00) 56.7 14.37 1440 365
H1 W1 H1 W1
Page 28 of 48
Product Transition Guide Appendix 3 – Parameter Cross Reference
The following parameter list shows each GPD506/P5 parameter and the P7 equivalent. P7 parameters without a GPD506/P5 equivalent are omitted for brevity. For details on P7 parameters please refer to the P7 manual. Parameters are listed numerically by GPD506/P5.
Page 29 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
001
002
003
004
005 006
007
008
009
Parameter
Description or Selection
Name
Password
Run Signal Selection
Input voltage Set unit:0.1V and set ranges:150.0-733.1V
Stop method selection 0: Deceleration stop
Motor Rotation
Reverse inhibit 0: Reverse enabled
Remote/Local key 0: The function of the Remote/Local key is
Function selection of STOP key
Frequency Reference selection
0: Parameter n001 read/write and parameter n002 ~ n116 read only. (Operator's FREF and F/R is read/write. Others are read only, 1: The 1st function (n001 ~ n036)are read/write, others read only 2: The 2nd function (n001 ~ n053) are read/write, others read only 3: The 1st, 2nd, and 3rd functions (n001 ~ n116) are read/write
6: 2-wire initialization (Japanese spec.) 8: Initialization (2wire sequence) 9: Initialization (3wire sequence)
Value--Run Command-------Freq Reference
0: Operator---------------------Operator 1: Terminal block ------------Operator 2: Operator-------------------- Terminal block 3: Terminal block -------------Terminal block 4: Operator --------------------Communication 5: Terminal block -------------Communication 6: Communication-------------Transmission 7: Communication-------------Operator 8: Communication------------ Terminal block
1: Coast to stop 2: Coast to stop 1 with timer 3: Coast to stop 2 with timer
0: Rotation CCW from load side. 1: Rotation CW from load side
1: Reverse disabled
disabled. 1: The function of the Remote/Local key is enabled.
0: The STOP key is effective when run command is from the operator. 1: The STOP key is always enabled.
0: Frequency reference setting by the operator, the 'Enter' input is not required. 1: Frequency reference setting by the operator, the 'Enter' input is required.
Description or Selection
0: Operation Only 1: User Level (only available if A2 parameters have been set) 2: Advanced Level
0: No Initialize 1110: User Initialize (The user must first set their own parameter values and then store them using parameter o2-03.) 2220: 2-Wire Initialization 3330: 3-Wire Initialization
0: Operator - Digital preset speed U1-01 or d1-01 to d1-17. 1: Terminals - Analog input terminal A1 (or terminal A2 based on parameter H3 13). 2: Serial Com - Modbus RS-422/485 terminals R+, R-, S+, and S-. 3: Option PCB - Option board connected on 2CN.
0: Operator - RUN and STOP keys on Digital Operator. 1:Terminals - Contact closure on terminals S1 or S2. 2: Serial Com - Modbus RS-422/485 terminals R+, R-, S+, and S-. 3: Option PCB - Option board connected on 2CN.
Set to the nominal voltage of the incoming line. Sets the maximum and base voltage used by preset V/F patterns, adjusts the levels of drive protective features (i.e. overvoltage, braking resistor turn-on, stall prevention, etc.).
0: Ramp to Stop 1: Coast to Stop 2: DC Injection to Stop 3: Coast with Timer (A new run command is ignored if received before the timer expires).
Determines the forward rotation of the motor, and if reverse operation is disabled. 0: Reverse Enabled 1: Reverse Disabled 2: Exchange Phase - Change direction of forward motor rotation. 3: ExchgPhs, Rev Dsbl - Change direction of forward motor rotation and disable reverse operation.
0: Disabled 1: Enabled
0: Disabled 1: Enabled
0: Disabled - Data/Enter key must be pressed to enter a frequency reference. 1: Enabled - Data/Enter key is not required. The frequency reference is adjusted by the up and down arrow keys on the Digital Operator without having to press the data/enter key.
Parameter
Name
Access Level Selection
Initialize Parameters
Frequency Reference Selection
Run Command Selection
Input Voltage Setting
Stopping Method Selection
Reverse Operation Selection
Local/Remote Key Function Selection
STOP Key Function Selection
Frequency Reference Setting Method Selection
Param.
No.
A1-01
A1-03
b1-01
b1-02
E1-01
b1-03
b1-04
o2-01
o2-02
o2-05
Page 30 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
010
011 012 013 014 015 016 017
018 019 020 021
022
Parameter
Description or Selection
Name
V/f pattern selection 1: Fixed V/f pattern
Max. output frequency Set unit: 0.1Hz and set range: 50.0-400.0Hz
Maximum voltage Set unit: 0.1V and set ranges: 0.1-733.1V
Base Frequency Set unit: 0.1Hz and set range: 0.2-400.0Hz
Mid Freq output Set unit: 0.1Hz and set range: 0.1-399.9Hz
Mid Freq. voltage Set unit: 0.1V and set ranges: 0.1-733.1V
Min output frequency Set unit: 0.1Hz and set range: 0.1-10.0Hz
Min output voltage Set unit: 0.1V and set ranges: 0.1-143.7V
Acceleration time 1 Set unit: 0.1sec (1sec in 1000sec or more)
Deceleration time 1 Set unit: 0.1sec (1sec in 1000sec or more)
Acceleration time 2 Set unit: 1sec and set range: 0-255sec
Deceleration time 2 Set unit: 1sec and set range: 0-255sec
S curve selection 0: No S curve
0: Adjustible V/f pattern (Constant n011-n017 can be set)
Set range: 0 to 3600sec
Set range: 0.to 3600sec
1 : 0.2sec 2 : 0.5sec 3 : 1.0sec
Description or Selection
There are 15 different preset V/F patterns to select from (E1-03 = 0 to E) with varying voltage profiles, base levels (base level = frequency at which maximum voltage is reached), and maximum frequencies. There are also settings for Custom V/F patterns that will use the settings of parameters E1-04 through E1-
13. E1-03 = F selects a custom V/F pattern with an upper voltage limit and E1-03 = FF selects a custom V/F pattern without an upper voltage limit. 0: 50 Hz 1: 60 Hz 2: 60Hz (50 Hz Base) 3: 72 Hz (60 Hz Base) 4: 50 Hz VT1 5: 50 Hz VT2 6: 60 Hz VT1 7: 60 Hz VT2 8: 50 Hz HST1 9: 50 Hz HST2 A: 60 Hz HST1 B: 60 Hz HST2 C: 90 Hz (60Hz Base) D: 120 Hz (60Hz Base) E: 180 Hz (60Hz Base) F: Custom V/F FF: Custom w/o limit
0.0 to 120.0
0 to 255.0 (240V), 0 to 510.0(480V) Maximum Output Voltage
Parameter
V/F Pattern Selection
Maximum Output Frequency
0.0 to 200.0
0.0 to 200.0
0 to 255.0 (240V, ) 0 to 510.0 (480V) Mid Output Voltage A
Base Frequency
Mid Output Frequency A
0.0 to 200.0
0 to 255.0 (240V), 0 to 510.0 (480V) Minimum Output Voltage
Minimum Output Frequency
Acceleration Time 1
0.0 to 6000.0
Deceleration Time 1
Acceleration Time 2
Deceleration Time 2
0.00 to 2.50
S-Curve Characteristic at Accel Start
S-Curve Characteristic at Accel End
Name
Param.
No.
E1-03
E1-04 E1-05 E1-06 E1-07 E1-08 E1-09 E1-10 C1-01 C1-02 C1-03 C1-04 C2-01
C2-02
Page 31 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
023
024 025
026
027
030
031
032
033
034
Parameter
Description or Selection
Name
Digital operator display mode
Freq Ref 1 Set unit: Set range by constant n023 setting:
Freq Ref 2 Set unit: Set range by constant n023 setting:
Freq Ref 3 Set unit: Set range by constant n023 setting:
Freq Ref 4 Set unit: Set range by constant n023 setting:
Jog Ref Set unit: Set range by constant n023 setting:
Output freq upper limit
Output freq lower limit
Rated motor current
Motor protection selection (OL1)
Set range: 0-4999 0: Hz with 0.1Hz 1: % speed with 0.1% 2-39: RPM. RPM =120 * freq ref(Hz) /n023 (N023 is a motor pole)
40-4999: n23 fourth digit = decimal point n23 1,2,3 digits = 100% freq set value (100% frequency = xxx*10 in case of 4xxx)
0-9999
0-9999
0-9999
0-9999
0-9999
Set unit: 1% and set range:0-109%
Set unit: 1% and set range:0-100%
Set unit: 0.1A (In 1000A or more, every 1A) Set range:10-200% of drive rated current
0: Disabled. 1: Standard motor (eight minutes) 2: Standard motor (five minutes) 3: Inverter rated motor (eight minutes) 4: Inverter rated motor (five minutes)
Description or Selection
Sets the units of the Freque ncy Refe rences (d 1- 01 to d1-17), the F requency Reference M o nitors (U1-01, U1-02 , U1 -05 ), and the Modbus communication frequency reference. 0: H z 1: % (100% = E1-04) 2 to 39: R PM (E nter the nu mb e r of mot o rpole s ). 40 to 39999: User display.
Example 1: o1-03 = 12 000, will result in fre qu ency refere nce fr om 0.0 to 20 0.0 ( 200.0 = Fmax ).
Example 2: o1-03 = 21 234, will result in fre qu ency refere nce from 0. 00 to 12.34 (1 2.34 = Fmax) .
Setting units are affected by o1-03
Frequency reference when multi-function input “Multi-step speed reference 1” is ON. Setting units are affected by o1-03.
Frequency reference when multi-function input “Multi-step speed reference 2” is ON. Setting units are affected by o1-03.
Frequency reference when multi-function input “Multi-step speed reference 1,2” is ON. Setting units are affected by o1-03.
Frequency reference when: “Jog frequency reference” is selected via multi-function input terminals. “Jog frequency reference” has priority over “multi-step speed reference 1 to 4”. d1-17 is also the reference for the JOG key on the Digital Operator, and the multi-function inputs “forward jog” and “reverse jog”. Setting units are affected by o1-03.
Determines maximum frequency reference, set as a percentage of maximum output frequency (E1-04). If the frequency reference is above this value, actual Drive speed will be limited to this value. This parameter applies to all frequency reference sources.
Determines minimum frequency reference, set as a percentage of maximum output frequency (E1-04). If frequency reference is below this value, actual Drive speed will be set to this value. This parameter applies to all frequency reference sources.
Set to the motor nameplate full load current in amperes (A). This value is automatically set during Auto-Tuning.
Sets the motor thermal overload protection (OL1) based on the cooling capacity of the motor. 0: Disabled 1: Standard Fan Cooled
Set the number desired at maximum output frequ enc y. 4 digit number Number of digits from the right of the decimal po int
0.00 to E1-04 Value
0.00 to E1-04 Value
0.00 to E1-04 Value
0.00 to E1-04 Value
0.00 to E1-04 Value
0.0 to 110.0
0.0 to 110.0
Parameter
Name
Digital Operator Display Selection
Frequency Reference 1
Frequency Reference 2
Frequency Reference 3
Frequency Reference 4
Jog Frequency Reference
Frequency Reference Upper Limit
Frequency Reference Lower Limit
Motor Rated Current
Motor Overload Protection Selection
Param.
No.
o1-03
d1-01 d1-02
d1-03
d1-04
d1-17
d2-01
d2-02
E2-01
L1-01
Page 32 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
035
036
037
Parameter
Name
Cooling fin overheat Stop method selection
Multi-function contact input 1 (terminal S2)
Multi-function contact input 2 (terminal S3)
Description or Selection
0: Deceleration stop (Decelerate by deceleration time 1) 1: Coast to stop 2: Deceleration stop (Decelerate by deceleration time 2) 3: Operation continues (The alarm is displayed, and drive runs at 80% of the freq ref)
0: REV command (2wire sequence selection) 1: FWD/REV Command (3wire sequence selection) 2: External fault. (N.O contact input) 3: External fault. (N.C contact input) 4: Fault reset 5: LOCAL/REMOTE switch (run and freq ref) 6: Communication/Control circuit terminal switch (run and freq ref) 7: Emergency stop (N.O. contact input) 8: Emergency stop (N.C contact input) 9: FV/FI terminal switch 10: Multistep speed set 1 11: Multistep speed set 2 12: Multistep speed set 3 13: Jog frequency select 14: Accel/decel time switch 15: External base block instruction (N.O.contact input) 16: External base block instruction (N.C contact input) 17: Speed search command from Max frequency 18: Speed search command from set frequency 19: Parameter set enable/disable 20: PID integral value reset 21: PID control disable 22: Timer start command 23: Inverter overheat (blinking display of OH3) 24: Sample/holding of analog reference 25: KEB instruction (N.O. contact) 26: KEB instruction (N.C. contact) 27: Decel/accel prohibit 28: PID input characteristic switchover
Set range: 2-28 (It is the same as constant n036)
Description or Selection
Drive Operation upon OH Pre Alarm Detection. 0: Ramp to Stop (Decel Time C1-02). 1: Coast to Stop 2: Fast-Stop (Decel Time = C1-09). 3: Alarm Only *0 to 2 is recognized as fault detection, and 3 is recognized as alarm. (For the fault detection, the fault contact operates.) 4: OH Alarm & Reduce (Continue operation and reduce output frequency by L8-19)
0 to 70 Selects the function of terminal S3. 0: 3-wire control FWD/REV selection for 3-wire sequence 1: Local/Remote Sel Hand/Auto Selection - Closed = Hand, Open = Auto 2: Option/Inv Sel Selects source of speed command and sequence Closed = Option Card, Open = b1-01 & b1­02 3: Multi-Step Ref 1 Closed = speed command from d1-02 or Terminal A2, Open = speed command determined by b1­01 4: Multi-Step Ref 2 Closed = speed command from d1-03 or d1-04 Open speed command determined by b1-01
Parameter
Name
Overheat Pre-Alarm Operation Selection
Param.
No.
L8-03
Terminal S2 is not programmable in P7 : P7 default setting for terminal S2:
Reverse run when closed, stopped when open.
Initialization parameter A1-03 programs terminals S1 and S2 for 2-Wire or 3-Wire run control.
Multi-Function Digital Input Terminal S3 Function Selection
-
H1-01
Page 33 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
(con’t)
037
Parameter
Name
Multi-function contact input 2 (terminal S3)
Description or Selection
Set range: 2-28
Description or Selection
6: Jog Freq Ref Closed = speed command from d1-17 Open = speed command determined by b1­01 7: Multi-Acc/Dec 1 Closed = Accel & Decel Ramps determined by C1-03 & C1-04, Open = Accel & Decel Ramps determined by C1-01 & C1-02 8: Ext BaseBlk N.O. Closed = Output transistors forced off, Open = Normal operation 9: Ext BaseBlk N.C. Closed = Normal Operation, Open = Output transistors forced off A: Acc/Dec RampHold Closed = Acceleration suspended and speed held, Open = Normal Operation C: Term A2 Enable Closed = Terminal A2 is active, Open = Terminal A2 is disabled F: Term Not Used Terminal has no effect 10: MOP Increase Closed = Speed Command Increases, Open = Speed Command Held. Must be set in conjunction with MOP Decrease and b1-02 must be set to 1. 11: MOP Decrease Closed = Speed Command Decreases, Open = Speed Command Held. Must be set in conjunction with MOP Increase and b1-02 must be set to 1. 12: Forward Jog Closed = drive runs forward at speed command entered into parameter d1-17. 13: Reverse Jog Closed = drive runs in reverse at speed command entered into parameter d1-17. 14: Fault Reset Closed = Resets the drive after the fault and the run command have been removed. 15: Fast-Stop N.O. Closed = Drive decelerates using C1-09, regardless of run command status. 17: Fast-Stop N.C. Closed = Normal operation Open = Drive decelerates using C1-09, regardless of run command status. Closed = Normal operation Open = Drive decelerates using C1-09, regardless of run command status. 18: Timer Function Input for independent timer, controlled by b4-01 and b4-02. Used in conjunction with a multi-function digital output. 19: PI Disable Turns off the PI controller, and PI setpoint becomes speed command. 1B: Program Lockout Closed =All parameter settings can be changed.
Parameter
Name
Multi-Function Digital Input Terminal S3 Function Selection
Param.
No.
H1-01
Page 34 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Parameter
Nxxx
Multi-function contact input 2
(con’t)
(terminal S3)
037
Name
Description or Selection
Set range: 2-28 (It is the same as constant n036)
Description or Selection
Open = Only speed command at U1-01 can be changed. 1C: TrimCtl Increase Closed = Increase motor speed by value in d4-02. Open = Return to normal speed command. Not effective when using d1-01 thru d1-04 as a speed command. Must be used in conjunction with Trim Ctrl Decrease. 1D: Trim Ctl Decrease Closed = Decrease motor speed by value in d4-02 Open = Return to normal speed command. Not effective when using d1-01 thru d1-04 as speed command. Must be used in conjunction with Trim Ctrl Increase. 1E: Ref Sample Hold Analog speed command is sampled then held at time of input closure. 20: External fault, Normally Open, Always Detected, Ramp To Stop 21: External fault, Normally Closed, Always Detected, Ramp To Stop 22: External fault, Normally Open, During Run, Ramp To Stop 23: External fault, Normally Closed, During Run, Ramp To Stop 24: External fault, Normally Open, Always Detected, Coast To Stop 25: External fault, Normally Closed, Always Detected, Coast To Stop 26: External fault, Normally Open, During Run, Coast To Stop 27: External fault, Normally Closed, During Run, Coast To Stop 28: External fault, Normally Open, Always Detected, Fast-Stop 29: External fault, Normally Open, Always Detected, Fast-Stop 2A: External fault, Normally Open, During Run, Fast-Stop 2B: External fault, Normally Closed, During Run, Fast-Stop 2C: External fault, Normally Open, Always Detected, Alarm Only 2D: External fault, Normally Closed, Always Detected, Alarm Only 2E: External fault, Normally Open, During Run, Alarm Only 2F: External fault, Normally Closed, During Run, Alarm Only 30: PI Integral Reset Resets the PI Integral component to zero when closed 31: PI Integral Hold Holds the PI integral value when closed 34: PI SFS Cancel (SFS= SoftStart, also called Accel/Decel, See Parameter b5-17) 35: PI Input Level Sel Inverts the PI error signal when closed 36: Option/Inv Sel 2 Selects source of speed command and sequence Closed = b1-01 & b1-02, Open = Option Card
Parameter
Name
Multi-Function Digital Input Terminal S3 Function Selection
Param.
No.
H1-01
Page 35 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Parameter
Nxxx
Multi-function
(con’t)
contact input 2
037
(terminal S3)
Multi-function contact input 3
038
(terminal S4)
Multi-function contact input 4
039
(terminal S5)
Multi-function contact input 5
040
(terminal S6)
Name
Description or Selection
Set range: 2-28 (It is the same as constant n036)
Set range: 2-28 (It is the same as constant n036)
Set range: 2-28 (It is the same as constant n036)
Set range: 2-29
Description or Selection
60: Motor Preheat Applies current to create heat to avoid condensation Closed = Apply amount of current as set in parameter b2-09 61: Speed Search 1 When closed as a run command is given, drive does a speed search starting at maximum frequency (E1-
04). 62: Speed Search 2 When closed as a run command is given, drive does a speed search starting at speed command. 64: Speed Search 3 When opened, the Drive performs a baseblock (motor coasts). When closed, the Drive performs Speed Search from set frequency. 67: Com Test Mode - Used to test RS­485/422 interface. 68: High Slip Braking - Closed = Drive stops using High Slip Braking regardless of run command status. 69: Jog2 - Closed = Drive runs at speed command entered into parameter d1-17. Direction determined by fwd/rev input. 3-wire control Only. 6A: Drive Enable - Closed = Drive will accept run command. Open = Drive will not run. If running, drive will stop per b1-03. Run Command must be cycled 6B: Com/Inv Sel - Selects source of Speed Command and Sequence. Closed = Serial Communication (R+,R­,S+,S-), Open = b1-01 & b1-02 6C: Com/Inv Sel 2 - Selects source of Speed Command and Sequence. Closed = b1-01 & b1-02, Open = Serial Communication (R+,R-,S+,S-) 6D: Auto Mode Sel - Hand/Auto Selection
- Closed = Auto, Open = Hand 6E: Hand Mode Sel - Hand/Auto Selection
- Closed = Hand, Open = Auto 70: Drv Enbl. Same as 6A except a run command is accepted
Same selections as H1-01
Same selections as H1-01
Same selections as H1-01
0-70
0-70
0-70
Parameter
Name
Multi-Function Digital Input Terminal S3 Function Selection
Multi-Function Digital Input Terminal S4 Function Selection
Multi-Function Digital Input Terminal S5 Function Selection
Multi-Function Digital Input Terminal S6 Function Selection
Param.
No.
H1-01
H1-02
H1-03
H1-04
Page 36 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
Multi-function
041
contact output 1 (terminal MA-MB-MC)
Parameter
Name
Description or Selection
0: Fault 1: During run. 2: Frequency agree 3: At set frequency agree 4: Freq detect (output freq = set freq detection level) 5: Freq detect (output frequency = set freq detect level) 6: Overtorque detect. (N.O contact) 7: Overtorque detect. (N.C contact) 8: The base block. 9: Operation mode 10: Inverter drive ready 11: Timer function 12: Auto restart. (Fault retry) 13: OL pre-alarm (OL1,OL2) 14: Frequency reference loss 15: Closed from serial communication. 16: PID feedback loss 17: OH1 alarm
Description or Selection
Selects the function of terminals M1 to M4. 0: During RUN 1 = Closed when a run command is input or the drive is outputting voltage. 1: Zero Speed = Closed when drive output frequency is less than Fmin (E1-09) 2: Fref/Fout Agree 1 = Closed when drive output speed equals the speed command within the bandwidth of L4-02. 3: Fref/Set Agree 1 = Closed when the drive output speed and the speed command are equal to the value in L4-01 within the bandwidth of L4-02. 4: Freq Detect 1 = Closed when the drive output speed is less than or equal to the value in L4-01, with hysteresis determined by L4-02. 5: Freq Detect 2 = Closed when the drive output speed is greater than or equal to the value in L4-01, with hysteresis determined by L4-
02. 6: Inverter Ready = Closed when the drive is not in a fault state, and not in program mode. 7: DC Bus Undervolt = Closed when the DC bus voltage falls below the UV trip level (L2-05) 8: Base Blk 1 = Closed when the drive is not outputting voltage. 9: Operator Reference = Closed when the speed command is coming from the digital operator. A: Remote/Auto Oper = Closed when the run command is coming from the digital operator. B: Trq Det 1 N.O. - Closes when the output current exceeds the value set in parameter L6-02 for more time than is set in parameter L6-03. C: Loss of Ref - Closes when the drive has detected a loss of analog speed command. Speed command is considered lost when it drops 90% in
0.4 seconds. Parameter L4-05 determines drive reaction to a loss of speed command. E: Fault - Closes when the drive experiences a major fault. F: Not Used 10: Minor Fault - Closes when drive experiences a minor fault or alarm. 11: Reset Cmd Active - Closes when the drive receives a reset command from terminals or serial comms. 12: Timer Output - Output for independent timer, controlled by b4-01 and b4-02. Used in conjunction with a multi-function digital input. 17: Trq. Det 1 N.C. - Opens when the output current exceeds the value set in parameter L6-02 for more time than is set in parameter L6-03.
Parameter
Name
Terminal M3-M4 Function Selection
Param.
No.
H2-01
Page 37 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
Multi-function
(con’t)
contact output 1
041
(terminal MA-MB-MC)
Parameter
Name
Description or Selection
Description or Selection
1A: Reverse Dir - Closes when the drive is running in the reverse direction. 1E: Restart Enabled - Closes when the drive is performing an automatic restart. Automatic restart is configured by parameter L5-01. 1F: Overload (OL1) - Closes before a motor overload occurs. (90% of OL1 time) 20: OH Prealarm - Closes when the Drive’s heatsink temperature exceeds the setting of parameter L8-02. 38: Drive Enable - Closes when the drive enable input is active. 39: Waiting to Run - Closes during the time after a run command is issued, but the Drive is not running due to the time set in parameter b1-10. 3A: OH Freq Reduce 3B: Run Src Com/Opt
Parameter
Name
Param.
No.
H2-01
Page 38 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
042
044
045
046
047
048
049
050 051 052
Parameter
Description or Selection
Name
Multi-function contact output 2 (terminal M1-M2)
Terminal FI signal Level Selection
Frequency Reference Retention
Frequency Ref Loss selection
Frequency Ref when frequency reference is lost
Terminal FV gain Set unit: 1% and set range: 0 to 200%
Terminal FV bias Set unit: 1% and set range = -100 to +100%
Terminal FI gain Set unit: 1% and set range: 0 to 200%
Terminal FI bias Set unit: 1% and set range -100 to +100%
Analog output Select (terminal AM-AC)
It is the same as constant n041.
0: The FI terminal inputs 0-10V. (Jumper J1 is cut) 1: The FI terminal inputs 4-20mA.
1: The holding frequency reference is not memorized. 0: The holding frequency reference is memorized and stored in n024
0: No detection 1: Continue running at n047 setting
Set unit: 1% and set range: 0-100%
0: Output frequency (10V = Max frequency n011) 1: Output current (10V = rated current of inverter) 2: Output power (10V = inverter rated power) 3: DC bus voltage (10V = 1150VDC)
Description or Selection
Same selections as H2-01
Selects the signal level of terminal A2. 0: 0 to 10Vdc (switch S1-2 must be in the OFF position). 2: 4 to 20mA (switch S1-2 must be in the ON position)
This parameter is used to retain the held frequency reference in U1-01 (d1-01) when power is removed. This function is available when the multi-function inputs “accel/decel ramp hold” or “up/down” commands are selected (H1-XX = A or 10 and 11). 0: Disabled 1: Enabled
The frequency reference is considered lost when reference drops 90% or more of its current value in less than 400ms. 0: Normal Operation - Drive will run at the frequency reference. 1: Run at L4-06 PrevRef - Drive will run at the percentage set in L4-06 of the frequency reference level at the time frequency reference was lost.
0 to 100.0 If the frequency reference loss function is enabled (L4-05=1) and frequency reference is lost, the Drive will run at a reduced frequency reference determined by the following formula: Fref=Fref at time of loss * L4-06.
0.0 to1000.0 Sets the output level when 10V is input, as a percentage of the maximum output frequency (E1-04).
–100.0 to +100.0 Sets the output level when 0V is input, as a percentage of the maximum output frequency (E1-04).
0.0 to 1000.0 Sets the output level when 10V is input.
–100.0 to+100.0 Sets the output level when 0V is input.
Selects which monitor will be output on terminals FM and FC. 1: Frequency Ref (100% = max. output frequency)
2: Output Freq (100% = max. output frequency) 3: Output Current (100% = drive rated current) 6: Output Voltage (100% = 230V or 100% = 460V) 7: DC Bus Voltage (100% = 400V or 100% = 800V) 8: Output kWatts (100% = drive rated power) 15: Term A1 Level 16: Term A2 Level 18: Mot SEC Current (100% = Motor rated secondary current) 20: SFS Output (100% = max. output frequency) 24: PI Feedback
Parameter
Name
Terminal M3-M4 Function Selection
Terminal A2 Signal Level Selection
MOP Ref Memory
Frequency Reference Loss Detection Selection
Frequency Reference Level at Loss Frequency
Terminal A1 Gain Setting
Terminal A1 Bias Setting
Terminal A2 Gain Setting Terminal A2 Bias Setting
Terminal FM Monitor Selection
Param.
No.
H2-02
H3-08
d4-01
L4-05
L4-06
H3-02
H3-03
H3-10 H3-11 H4-01
Page 39 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
(cont)
052
053
054
Parameter
Description or Selection
Name
Analog output Select (terminal AM-AC)
Analog output gain Set unit: 0.01 and set range: 0.01-2.00
Carrier frequency 1, 2, 4 ~ 6: carrier freq = set value * 2.5 Khz
3: Carrier frequency =8kHz 7, 8, 9: The output freq of 2.5kHz or less is proportional to the carrier frequency. (7: 12*fout ,8: 24*fout, 9:36*fout) 10: Carrier frequency =7kHz (Only 400V 45kW)
Description or Selection
31: Not Used 36: PI Input 37: PI Output (100% = max. output frequency) 38: PI Setpoint 51: Auto Mode Fref (100% = max. output frequency) 52: Hand Mode Fref (100% = max. output frequency) 53: PI Feedback 2 NOTE: 100% = 10V DC output * FM gain setting (H4-02).
0.0 to 1000.0 Sets terminal FM output voltage (in percent of 10V) when selected monitor is at 100% output.
Carrier frequency sets the number of pulses per second of the output voltage waveform. 0: Low Noise (Carrier frequency is randomly moduled for lower audible noise) 1: Fc = 2.0 kHz 2: Fc = 5.0 kHz 3: Fc = 8.0 kHz 4: Fc = 10.0 kHz 5: Fc = 12.5 kHz 6: Fc = 15.0 kHz F: Program (Determined by the settings of C6-03 thru C6-05)
0.4 to 15.0 kHz Carrier Frequency Upper
Parameter
Name
Terminal FM Monitor Selection
Terminal FM Gain Setting
Carrier Frequency Selection
Limit
Param.
No.
H4-01
H4-02
C6-02
C6-03
Operation after
055
momentary power loss
Speed search operation level Set unit: 1%
056
Minimum base block time Set unit: 0.1sec
057
0: Not Provided. 1: Operation continues after power recovery within 2 sec 2: Operation continues while control power is on ( UV1, UV3 faults not are detected)
Set range: 0-200% (100%= rated current of inverter)
Set range: 0.5-10.0sec
Page 40 of 48
0.4 to 15.0 kHz Carrier Frequency Lower
Sets the relationship of output frequency to carrier frequency when C6-02 = F.
Enables and disables the momentary power loss function. 0: Disabled - Drive trips on (UV1) fault when power is lost. 1: Power Loss Ride Thru Time - Drive will restart if power returns within the time set in L2-02.* 2: CPU Power Active - Drive will restart if power returns prior to control power supply shut down.* * In order for a restart to occur, the run command must be maintained throughout the ride thru period.
0 to 200 Used only when b3-01 = 2 or 3. Sets the speed search operation current as a percentage of Drive rated current.
0.1 to 5.0sec Sets the minimum time to wait to allow the residual motor voltage to decay before the Drive output turns back on during power loss ride thru. After a power loss, if L2-03 is greater than L2-02, operation resumes after the time set in L2-03.
0 to 99
Limit Carrier Frequency
Proportional Gain
Momentary Power Loss Detection Selection
Speed Search Deactivation Current
Momentary Power Loss Minimum Base Block Time
C6-04 C6-05
L2-01
b3-02
L2-03
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
059
060
061
062 063 064
065
066
067
068
069
070
Parameter
Description or Selection
Name
Power ride through time
No. of Fault Retries Setting unit = 1 times
Fault contact during fault retry
Jump frequency 1 Set unit: 0.1Hz and set range: 0.0-400.0Hz
Jump frequency 2 Set unit: 0.1Hz and set range: 0.0-400.0Hz
Width of jump Set unit: 0.1Hz and set range: 0.0-25.5Hz
Elapsed timer 1 mode
Elapsed timer 1 (lower 4 digits)
Elapsed timer 1 (upper 4 digits)
DC injection braking current Set unit: 1%
DC braking time at stop Set unit:0.1sec and set range: 0.0-10.0sec
DC braking time at start Set unit: 0.1sec and set range: 0.0-10.0sec
Set unit: 0.1sec and set range: 0.0-2.0sec
Set range: 0-10 times (There is no fault retry at 0)
0: Fault contact output enabled while fault retry. 1: Fault contact output disabled while fault retry.
0: Operation time accumulates. 1: Operation time accumulates. (During Run)
Setting unit = 1 hour, range = 0 ~ 9999 hours 1 minute is stored in EEPROM, < 1day rounded up
Set unit: 1(For 10000 hours) and a set range: 0-27. * Initial value becomes 0 only when initialized during CPF4 occurrence.
Set range: 0-100% (100%= rated current of inverter)
Description or Selection
0.0 to 25.5sec Sets the power loss ride-thru time. This value is dependent on the capacity of the Drive. Only effective when L2-01 = 1.
0 to 10 Sets the counter for the number of times the Drive will perform an automatic restart on the following faults: GF, LF, OC, OV, PF, PUF, RH, RR, OL1, OL2, OL3, OL4, UV1. Auto restart will check to see if the fault has cleared every 5ms. When no fault is present, the Drive will attempt an auto restart. If the Drive faults after an auto restart attempt, the counter is incremented. When the drive operates without fault for 10 minutes, the counter will reset to the value set in L5-01
Determines if the fault contact activates during an automatic restart attempt. 0: No Fault Relay - fault contact will not activate during an automatic restart attempt. 1: Fault Relay Active - fault contact will activate during an automatic restart attempt.
0.0 to 200.0 These parameters allow programming of up to three prohibited frequency reference points for eliminating problems with resonant vibration of the motor / machine. This feature does not actually eliminate the selected frequency values, but will accelerate and decelerate the motor through the prohibited bandwidth.
Sets how time is accumulated for the elapsed operation timer U1-13. 0: Power-On Time - Time accumulates when the Drive is powered. 1: Running Time - Time accumulates only when the Drive is running.
0 to 65535 Sets the initial value of the elapsed operation timer U1-13.
0 to 100 Sets the DC injection braking current as a percentage of the Drive rated current.
0.00 to 10.00 Sets the time length of DC injection braking at stop in units of 0.01 seconds. NOTE: When b1-03 = 2, actual DC Injection time is calculated as follows: b2-04 * 10 * Output Frequency / E1-04. NOTE: When b1-03 = 0, this parameter determines the amount of time DC Injection is applied to the motor at the end of the decel ramp. NOTE: This should be set to a minimum of
0.50 seconds when using HSB. This will activate DC injection during the final portion of HSB and help ensure that the motor stops completely.
0.00 to 10.00 Sets the time of DC injection braking at start in units of 0.01 seconds.
Parameter
Name
Momentary Power Loss Ride-thru Time
Number of Auto Restart Attempts
Auto Restart Operation Selection
Jump Frequency 1 Jump Frequency 2
Jump Frequency Width
Cumulative Operation Time Selection
Cumulative Operation Time Setting
DC Injection Braking Current
DC Injection Braking Time at Stop
DC Injection Braking Time at Start
Param.
No.
L2-02
L5-01
L5-02
d3-01 d3-02 d3-04
o2-08
o2-07
b2-02
b2-04
b2-03
Page 41 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
Torque comp gain
071
Stall prevention during
072
deceleration
Stall prevention level
073
during acceleration
Stall prevention level
074
during run
Parameter
Name
Description or Selection
Set unit: 0.1 and set range: 0.0-3.0
0: Stall prevention function none at deceleration 1: The stall prevention is provided while decelerating.
Set unit: 1% Set range: 30-200% (100%= rated current of inverter) (Stall prevention disabled when set point =200%)
Set unit: 1% Set range: 30-200% (100%= rated current of inverter) (Stall prevention disabled when set point =200%)
Description or Selection
0.00 to 2.50 This parameter sets the gain for the Drive’s automatic torque boost function to match the Drive’s output voltage to the motor load. This parameter helps to produce better starting torque. It determines the amount of torque or voltage boost based upon motor current, motor resistance, and output frequency.
When using a braking resistor, use setting “0”. Setting “3” is used in specific applications.
0: Disabled - The Drive decelerates at the active deceleration rate. If the load is too large or the deceleration time is too short, an OV fault may occur. 1: General Purpose - The Drive decelerates at the active deceleration rate, but if the main circuit DC bus voltage reaches the stall prevention level (380/760Vdc), deceleration will stop. Deceleration will continue once the DC bus level drops below the stall prevention level. 2: Intelligent - The active deceleration rate is ignored and the Drive decelerates as fast as possible w/o hitting OV fault level. Range: C1-02 / 10. 3: Stall Prevention w/ Braking Resistor
Selects the stall prevention method used to prevent excessive current during acceleration. 0: Disabled - Motor accelerates at active acceleration rate. The motor may stall if load is too heavy or accel time is too short. 1: General Purpose - When output current exceeds L3-02 level, acceleration stops. Acceleration will continue when the output current level falls below the L3-02 level. 2: Intelligent - The active acceleration rate is ignored. Acceleration is completed in the shortest amount of time without exceeding the current value set in L3-02.
0 to 200 This function is enabled when L3-01 is “1” or “2”.Drive rated current is 100%. Decrease the set value if stalling or excessive current occurs with factory setting.
Selects the stall prevention method to use to prevent Drive faults during run. 0: Disabled - Drive runs a set frequency. A heavy load may cause the Drive to trip on an OC or OL fault. 1: Decel Time 1 - In order to avoid stalling during heavy loading, the Drive will decelerate at Decel time 1 (C1-02) if the output current exceeds the level set by L3-06. Once the current level drops below the L3-06 level, the Drive will accelerate back to its frequency reference at the active acceleration rate. 2: Decel Time 2 - Same as setting 1 except the Drive decelerates at Decel Time 2 (C1-04). When output frequency is 6Hz or less, stall prevention during running is disabled regardless of L3-05 setting.
Parameter
Name
Torque Compensation Gain
Stall Prevention Selection During Decel
Stall Prevention Selection During Accel
Stall Prevention Level During Accel
Stall Prevention Selection During Run
Param.
No.
C4-01
L3-04
L3-01
L3-02
L3-05
Page 42 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
075
076
077
078
079
080
Parameter
Description or Selection
Name
Set frequency detection level
Width of frequency agreement detection
Overtorque/ Undertorque Selection
Overtorque detection level
Overtorque detection time Set unit: 0.1sec and set range: 0.1-10.0sec
(timer function) ON Delay time
Set unit: 0.1Hz and set range: 0.0-400.0Hz
Set unit: 0.1Hz and set range: 0.0-25.5Hz
0: Overtorque/undertorque detection disabled. 1: Overtorque is detected during constant
speed operation and operation continues
after overtorque detection. 2: Overtorque is always detected and operation continues after overtorque detection. 3: Overtorque is detected during constant speed operation and inverter output is disabled after overtorque detection. 4: Overtorque is always detected and inverter output is disabled after overtorque detection. 5: Undertorque is detected during constant speed operation and operation continues after undertorque detection. 6: Undertorque is always detected and operation continues after undertorque detection. 7: Undertorque is detected during constant speed operation and inverter output is disabled after undertorque detection. 8: Undertorque is always detected and inverter output is disabled after undertorque detection.
Set unit: 1% Set range: 30-200% (100%= rated current of inverter)
Set unit: 0.1sec Set range: 0.0-25.5sec
Description or Selection
0.0 to 200.0 L4-01 and L4-02 are used in conjunction with the multi-function outputs, (H2-01and H2-02) as a setpoint and hysteresis for a contact closure.
0.0 to 20.0
Determines the drive's response to an overtorque / undertorque condition. Overtorque and Undertorque are determined by the settings in parameters L6-02 and L6-03. 0: Disabled 1: OL@SpdAgree - Alm (Overtorque Detection only active during Speed Agree and Operation continues after detection) 2: OL At RUN - Alm (Overtorque Detection is always active and operation continues after detection) 3: OL@SpdAgree - Flt (Overtorque Detection only active during Speed Agree and drive output will shut down on an OL3 fault.) 4: OL At RUN - Flt (Overtorque Detection is always active and drive output will shut down on an OL3 fault.) 5: UL@SpdAgree - Alm (Undertorque Detection is only active during Speed Agree and operation continues after detection.) 6: UL at RUN - Alm (Undertorque Detection is always active and operation continues after detection.) 7: UL @ SpdAgree - Flt (Undertorque Detection only active during Speed Agree and drive output will shut down on an OL3 fault.) 8: UL At RUN - Flt (Undertorque Detection is always active and drive output will shut down on an OL3 fault.)
0 to 300 Sets the overtorque/undertorque detection level as a percentage of Drive rated current.
0.0 to 10.0 Sets the length of time an Over/Under torque condition must exist before torque detection 1 recognized by the Drive.
0.0 to 3000.0 Used in conjunction with a multi-function digital input and a multi-function digital output programmed for the timer function. This sets the amount of time between when the digital input is closed, and the digital output is energized.
Parameter
Name
Speed Agreement Detection Level
Param.
No.
L4-01
Speed Agreement Detection Width
Torque Detection Selection 1
Torque Detection Level 1
L4-02
L6-01
L6-02
Torque Detection Time 1
Timer Function ON-Delay Time
L6-03
b4-01
Page 43 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Parameter
Nxxx
(timer function)
081
Off delay time
Braking resistor
082
Overheat protection
Input open-phase
083
detection level
(PID control)
084
PID control selection
(PID control)
086
Proportional gain
(PID control)
087
Integral time
(PID control)
089
Integration upper limit
PID Feedback loss
090
detection selection
PID Feedback loss
091
detection level
PID Feedback loss
092
detection time
PID output
093
reverse-characteristic
PID Sleep function
094
operation level
PID Sleep function
095
operation time
Energy Saving
096
Selection
Energy Save Voltage Lower
098
limit @ 60 Hz Energy Save Voltage Lower
099
limit @ 6 Hz
Name
Description or Selection
Set unit: 0.1sec Set range: 0.0-25.5sec
0: Braking resistor overheat protection disabled. 1: Braking resistor overheat protection enabled.
Set unit:1% and set range: 1-100% (Open-phase detection disabled at set point =100%)
0: PID control disabled. 1: PID control enabled. (D=Fdbk) 2: PID control enabled. (D=Fdfwd) 3: PID control enabled. (D=Fdbk, feedback=reverse)
Set unit: 0.1 Set range: 0.0-10.0
Set unit: 0.1sec Set range: 0.0-100.0sec
Set unit: 1% Set range: 0-109%
0: PID feedback loss disabled. 1: PID feedback loss enabled, no fault detected. 2: PID feedback loss enabled, fault detection enabled.
Set unit:1% Set range: 0-100%
Set unit: 0.1sec Set range: 0.0-25.5sec
0: Reverse-characteristic disabled 1: Reverse-characteristic enabled.
Set unit: 0.1Hz Set range: 0.0-400.0Hz
Set unit: 0.1sec Set range: 0.0-25.5sec
0: Energy saving disabled 1: Energy saving enabled
Set unit: 1% Set range: 0-120%
Set unit:1% Set range:0-25%
Description or Selection
0.0 to 3000.0 Used in conjunction with a multi-function digital input and a multi-function digital output programmed for the timer function. This sets the amount of time the output stays energized after the digital input is opened.
Selects the DB protection only when using 3% duty cycle heatsink mount Yaskawa braking resistor. This parameter does not enable or disable the DB function of the Drive. 0: Not Provided 1: Provided
Monitors the DC Bus current ripple and activates when one of the input phases is lost (PF).
This parameter enables / disables the closed loop (PI) controller. 0: Disabled 1: Enabled (commanded speed becomes PI setpoint) 3: Fref+PI
0.00 to25.00 Sets the proportional gain of the PID controller.
0.0 to 360.0 Sets the integral time for the PID controller. A setting of zero disables integral control.
0.0 to100.0 Sets the maximum output possible from the integrator. Set as a% of maximum frequency.
0: Disabled 1: Alarm 2: Fault
0 to 100 Sets the PID feedback loss detection level as a percentage of maximum frequency (E1-04).
0.0 to 25.5 Sets the PID feedback loss detection delay time in terms of seconds.
Determines whether the PID controller will be direct or reverse acting. 0: Normal Output (direct acting) 1: Reverse Output (reverse acting)
0.0 to 200.0 Sets the sleep function start frequency.
0.0 to 25.5 Sets the sleep function delay time in terms of seconds.
Energy Savings function enable/disable selection. 0: Disabled 1: Enabled
Used to fine-tune the energy savings function when in V/F control method.
Parameter
Timer Function OFF-Delay Time
Internal Dynamic Braking Resistor Protection Selection
Input Phase Loss Detection Level
Proportional Gain Setting
Integral Time Setting
Integral Limit Setting
PI Feedback Reference Missing Detection Selection
PI Feedback Loss Detection Level
PI Feedback Loss Detection Time
PI Output Level Selection
Sleep Function Start Level
Sleep Delay Time
Energy Saving Control Selection
Power Detection Filter Time
Search Operation Voltage Limit
Name
PI Mode Setting
Param.
No.
b4-02
L8-01
L8-06
b5-01
b5-02
b5-03
b5-04
b5-12
b5-13
b5-14
b5-09
b5-15
b5-16
b8-01
b8-05 b8-06
Page 44 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
100
101
102
104
105
106
108
110
111
112 113
Parameter
Name
Time of average KW
MEMOBUS timeout detection
MEMOBUS Stop method selection at communication error (CE)
MEMOBUS Slave address
MEMOBUS Baud rate selection
MEMOBUS Parity selection
Motor no-load current Set unit: 1%
Operator Connection Fault Detect Select
Local/remote Change- over function Select
Low frequency OL starting point
Continuous running level at 0Hz
Description or Selection
Set unit:1 (1=25ms) Set range: 1-200 (25ms=5.0sec)
0: Timeout detection disabled. 1: Timeout detection enabled.
0: Deceleration stop (Decelerate by deceleration time 1) 1: Coast stop 2: Deceleration stop (Decelerate by deceleration time 2) 3: Continue operation (alarm display)
Set unit:1 Set range:0-31 (There is no MEMOBUS communication at set point =0)
0: 2400bps 1: 4800bps 2: 9600bps
0: Parity none 1: Even parity 2: Odd parity
Set range: 0-99% (100%= rated current of motor)
0: Operator connection fault disabled. 1: Operator connection fault enabled.
0: Cycle External run 1: Accept external run
Set unit: 0.1Hz Set range: 0.0-10.0Hz
Set unit: 1% Set range: 25-100%
Description or Selection
0 to 2000 Used to fine-tune the energy savings function when in V/F control method.
Enables or disables the communications timeout fault (CE). 0: Disabled - A communication loss will not cause a communication fault. 1: Enabled - If communication is lost for more than 2 seconds, a CE fault will occur.
Selects the stopping method when a communication timeout fault (CE) is detected. 0: Ramp to Stop 1: Coast to Stop 2: Fast-Stop 3: Alarm Only 4: Run at d1-04
0 to 20 Hex Selects Drive station node number (address) for Modbus terminals R+, R-, S+, S-. The Drive’s power must be cycled for the setting to take effect.
Selects the baud rate for Modbus terminals R+, R-, S+ and S-. The Drive’s power must be cycled for the setting to take effect. 0: 1200 bps 1: 2400 bps 2: 4800 bps 3: 9600 bps 4: 19200 bps
Selects the communication parity for Modbus terminals R+, R-, S+ and S-. The Drive’s power must be cycled for the setting to take effect. 0: No Parity 1: Even Parity 2: Odd Parity
Set to the magnetizing current of the motor as a percentage of full load amps (E2-01). This value is automatically set during rotational Auto-Tuning.
Determines if the Drive will stop when the Digital Operator is removed when in LOCAL mode or b1-02=0. 0: Disabled - The Drive will not stop when the Digital Operator is removed. 1: Enabled - The Drive will fault (OPR) and coast to stop when the operator is removed.
0: Cycle External RUN - If the run command is closed when switching from local mode to remote mode, the Drive will not run. 1: Accept External RUN - If the run command is closed when switching from local mode to remote mode, the Drive will run.
This parameter assists in protecting the output transistors from overheating when output current is high and output frequency is low (6Hz and less). 0: Disabled 1: Enabled (L8-18 is active)
Parameter
Name
Power Detection Filter Time
Communication Error Detection Selection
Stopping Method after Communication Error
Drive Node Address
Communication Speed Selection
Communication Parity Selection
No-Load Current
Operation Selection when Digital Operator is Disconnected
Local/Remote Run Selection
OL2 Characteristic Selection at Low Speeds
b8-05
H5-05
H5-04
H5-01
H5-02
H5-03
E2-03
o2-06
b1-07
L8-15
Param.
No.
Page 45 of 48
Appendix 3- Parameter Cross Reference
GPD506/P5 Parameter P7 Parameter
Param
No.
Nxxx
115
116
Parameter
Description or Selection
Name
KVA selection Set unit: 1
CT/VT selection 0: Constant Torque selection
Set range: PC5 (0~8, 20~29), GPD506/P5(9~F, 2A~35)
1: Variable Torque selection
Description or Selection
0 to FF Sets the kVA of the Drive. Enter the number based on Drive model number. Use the last four digits of the model number. CIMR-P7U. This parameter only needs to be set when installing a new control board. Do not change for any other reason. Refer to Table B.1. in the P7 Instruction Manual
Selects Drive’s rated input and output current, overload capacity, carrier frequency, current limit, and maximum output frequency. See Introduction for details. 1: Normal Duty 1 2: Normal Duty 2
Parameter
Name
Drive/kVA Selection
Reduced Current Rating Standard Current Rating
Param.
No.
o2-04
C6-01
Page 46 of 48
Appendix 3- Parameter Cross Reference
Page left intentionally blank
Page 47 of 48
GPD506/P5 to P7 Product Transition Guide
Yaskawa Electric America, Inc
16555 W. Ryerson Rd
(800)YASKAWA (927-5292) Fax (262) 782-3418
YEA Document Number: PL.P7.06.Transistion 9/24/03
New Berlin, WI
www.drives.com
Loading...