YASKAWA TOEPYAIGA5002A GA500 Programming9
1.1 Section Safety
1.1Section Safety
DANGER
Do not ignore the safety messages in this manual.
If you ignore the safety messages in this manual, it will cause serious injury or death. The manufacturer is not
responsible for injuries or damage to equipment.
10YASKAWA TOEPYAIGA5002A GA500 Programming
1.2 How to Read the Parameter List
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.2How to Read the Parameter List
◆ Icons and Terms that Identify Parameters and Control Modes
IconDescription
The parameter is available when operating the drive with V/f Control.
The parameter is available when operating the drive with Open Loop Vector Control.
The parameter is available when operating the drive with Open Loop Vector Control for PM.
The parameter is available when operating the drive with Advanced Open Loop Vector Control for PM.
The parameter is available when operating the drive with EZ Open Loop Vector Control.
Hex.Hexadecimal numbers that represent MEMOBUS addresses to change parameters over network communication.
RUNThe parameter can be changed settings during run.
ExpertThe parameter that is available in Expert Mode only.
*1Set A1-01 = 3 [Access Level Selection = Expert Level] to display and set Expert Mode parameters on the keypad.
Note:
Gray icons identify parameters that are not available in the specified control method.
When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will not
reset this parameter.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
7 : Chinese
8 : Czech
9 : Russian
10 : Turkish
11 : Polish
12 : Greek
Access Level Selection
Sets user access to parameters. The access level controls which parameters the keypad will
display, and which parameters the user can set.
0 : Operation Only
1 : User Parameters
2 : Advanced Level
3 : Expert Level
Control Method Selection
Sets the control method for the drive application and the motor.
0 : V/f Control
2 : Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
8 : EZ Vector Control
Initialize Parameters
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
3330 : 3-Wire Initialization
Password
Entry point for the password set in A1-05 [Password Setting]. The user can view the
settings of parameters that are locked without entering the password. Enter the correct
password in this parameter to change parameter settings.
Password Setting
Set the password to lock parameters and prevent changes to parameter settings. Enter the
correct password in A1-04 [Password] to unlock parameters and accept changes.
Application Preset
Sets the drive to operate in selected application conditions.
0 : General-purpose
1 : Water Supply Pump 2
2 : Conveyor
3 : Exhaust Fan
4 : HVAC Fan
5 : Air Compressor
8 : Conveyor 2
Default
(Range)
0
(0 - 12)
2
(0 - 3)
2
(0, 2, 5, 6, 8)
0
(0 - 3330)
0000
(0000 - 9999)
0000
(0000 - 9999)
0
(0 - 5, 8)
Ref.
139
139
140
141
142
143
143
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming13
1.4 A: Initialization Parameters
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
A1-07
(0128)
NameDescription
DriveWorksEZ Function
Selection
Sets the drive to operate with DriveWorksEZ.
0 : DWEZ Disabled
1 : DWEZ Enabled
2 : Enabled/Disabled wDigital Input
A1-11
(111D)
Expert
Firmware Update Lock
Protects the drive firmware. When you enable the protection, you cannot update the drive
firmware.
0 : Disabled
1 : Enabled
A1-12
(1564)
Bluetooth ID
Sets the password necessary to use Bluetooth to control the drive with a smartphone or
tablet.
◆ A2: User Parameters
No.
(Hex.)
A2-01 to A2-32
(0106 - 0125)
A2-33
(0126)
NameDescription
User Parameters 1 to 32
You can select a maximum of 32 parameters for the drive and save the values to
parameters A2-01 to A2-32. Use Setup Mode to show the saved parameters. You can
immediately access these saved parameters.
User Parameter Auto
Selection
Sets the automatic save feature for changes to parameters A2-17 to A2-32 [UserParameters 17 to 32].
0 : Disabled: Manual Entry Required
1 : Enabled: Auto Save Recent Parms
Note:
When the A1-06 [Application Preset] value changes, the settings for A2-01 to A2-32
change.
Default
(Range)
0
(0 - 2)
0
(0, 1)
-
(0000 - 9999)
Default
(Range)
Parameters in General-
Purpose Setup Mode
(Determined by A1-06)
Determined by A1-06
(0, 1)
Ref.
156
156
156
Ref.
157
157
14YASKAWA TOEPYAIGA5002A GA500 Programming
1.5b: Application
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ b1: Operation Mode Selection
1.5 b: Application
No.
(Hex.)
b1-01
(0180)
b1-02
(0181)
b1-03
(0182)
b1-04
(0183)
b1-06
(0185)
b1-07
(0186)
b1-08
(0187)
b1-14
(01C3)
b1-15
(01C4)
NameDescription
Frequency Reference
Selection 1
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
Run Command Selection
1
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
Stopping Method
Selection
Sets the method to stop the motor after removing a Run command or entering a Stop
command.
Note:
When A1-02 = 5, 6, 8 [Control Method Selection = OLV/PM, AOLV/PM, EZOLV], the
setting range is 0, 1, 3.
0 : Ramp to Stop
1 : Coast to Stop
2 : DC Injection Braking to Stop
3 : Coast to Stop with Timer
Reverse Operation
Selection
Sets the reverse operation function. Disable reverse operation in fan or pump applications
where reverse rotation is dangerous.
0 : Reverse Enabled
1 : Reverse Disabled
Digital Input Reading
Sets the number of times that the drive reads the sequence input command to prevent
malfunction because of electrical interference.
0 : Single Scan
1 : Double Scan
LOCAL/REMOTE Run
Selection
Sets drive response to an existing Run command when the drive receives a second Run
command from a different location.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
Run Command Select in
PRG Mode
Sets the conditions for the drive to accept a Run command entered from an external source
when using the keypad to set parameters.
0 : Disregard RUN while Programming
1 : Accept RUN while Programming
2 : Allow Programming Only at Stop
Phase Order Selection
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can align
the Forward Run command from the drive and the forward direction of the motor without
changing wiring.
0 : Standard
1 : Switch Phase Order
Frequency Reference
Selection 2
Sets the input method for frequency reference 2.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
Default
(Setting Range)
1
(0 - 4)
1
(0 - 3)
0
(0 - 3)
0
(0, 1)
1
(0, 1)
0
(0, 1)
0
(0 - 2)
0
(0, 1)
0
(0 - 4)
Ref.
158
160
160
163
163
164
164
Parameter List
165
1
165
YASKAWA TOEPYAIGA5002A GA500 Programming15
1.5 b: Application
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
b1-16
(01C5)
NameDescription
Run Command Selection
2
Sets the input method for Run Command 2 when the user switches the control circuit
terminals ON/OFF to change the Run command source.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
b1-17
(01C6)
Run Command at Power
Up
Sets drive response when energizing a drive that has an external Run command. Set this
parameter in applications where energizing or de-energizing the drive enables the Run
command.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
b1-35
(1117)
Digital Input Deadband
Time
Sets the deadband time for MFDIs.
Expert
◆ b2: DC Injection Braking and Short Circuit Braking
No.
(Hex.)
b2-01
(0189)
b2-02
(018A)
b2-03
(018B)
b2-04
(018C)
b2-08
(0190)
b2-12
(01BA)
b2-13
(01BB)
b2-18
(0177)
NameDescription
DC Injection/Zero
SpeedThreshold
Sets the frequency to start DC Injection Braking or Short Circuit Braking.
Note:
This parameter is available when b1-03 = 0 [Stopping Method Selection = Ramp to
Stop].
DC Injection Braking
Current
DC Inject Braking Time
at Start
DC Inject Braking Time
at Stop
Magnetic Flux
Compensation Value
Short Circuit Brake Time
@ Start
Short Circuit Brake Time
@ Stop
Short Circuit Braking
Current
Sets the DC Injection Braking current as a percentage of the drive rated current.
Sets the DC Injection Braking Time at stop.
Sets the DC Injection Braking Time at stop.
Sets how much current the drive injects when DC Injection Braking at Start starts (Initial
Excitation) as a percentage of E2-03 [Motor No-Load Current].
Sets the Short Circuit Braking time at start.
Sets the Short Circuit Braking time at stop.
Sets the Short Circuit Braking Current as a percentage of the motor rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5, 6 [OLV/PM, AOLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
Default
(Setting Range)
0
(0 - 3)
0
(0, 1)
0.0 ms
(0.0 to 100.0 ms)
Default
(Range)
Determined by A1-02
(0.0 - 10.0 Hz)
50%
(0 - 75%)
0.00 s
(0.00 - 10.00 s)
Determined by A1-02
(0.00 - 10.00 s)
0%
(0 - 1000%)
0.00 s
(0.00 - 25.50 s)
A1-02 = 8: 0.00 s
Other than A1-02 = 8:
0.50 s
(0.00 - 25.50 s)
100.0%
(0.0 - 200.0%)
Ref.
167
167
168
Ref.
168
169
169
169
170
170
170
171
◆ b3: Speed Search
No.
(Hex.)
b3-01
(0191)
b3-02
(0192)
16YASKAWA TOEPYAIGA5002A GA500 Programming
Speed Search at Start
Selection
SpeedSearch Deactivation
Current
NameDescription
Sets the Speed Search at Start function where the drive will perform Speed Search with
each Run command.
0 : Disable
1 : Enabled
Sets the current level that stops Speed Search as a percentage of the drive rated output
current. Usually it is not necessary to change this setting.
Default
(Range)
Determined by A1-02
(0, 1)
Determined by A1-02
(0 - 200%)
Ref.
174
175
1.5 b: Application
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
b3-03
(0193)
b3-04
(0194)
b3-05
(0195)
b3-06
(0196)
Expert
b3-07
(0197)
Expert
b3-08
(0198)
b3-09
(0199)
b3-10
(019A)
Expert
b3-14
(019E)
b3-17
(01F0)
Expert
b3-18
(01F1)
Expert
b3-19
(01F2)
b3-24
(01C0)
NameDescription
Speed Search
Deceleration Time
Sets the deceleration time during Speed Search operation. Set the length of time to
decelerate from the maximum output frequency to the minimum output frequency.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this parameter takes effect
only in Expert Mode.
V/f Gain during Speed
Search
Sets the ratio used to reduce the V/f during searches to reduce the output current during
speed searches.
Speed Search Delay Time
Sets the Speed Search delay time to activate a magnetic contactor installed between the
drive and motor.
Speed Estimation Current
Level 1
Speed Estimation Current
Level 2
Speed Estimation ACR P
Gain
Speed Estimation ACR I
Time
Speed Estimation
Detection Gain
Bi-directional Speed
Search
Sets the level of current that flows to the motor during Speed Estimation Speed Search as a
coefficient of the motor rated current. Usually it is not necessary to change this setting.
Sets the level of current that flows to the motor during Speed Estimation Speed Search as a
coefficient of E2-03 [Motor No-Load Current] or E4-03 [Motor 2 Rated No-LoadCurrent]. Usually it is not necessary to change this setting.
Sets the proportional gain for the automatic current regulator during Speed Estimation
Speed Search. Also adjusts speed search responsiveness. Usually it is not necessary to
change this setting.
Sets the integral time for the automatic current regulator during Speed Estimation Speed
Search. Also adjusts speed search responsiveness. Usually it is not necessary to change this
setting.
Sets the gain to correct estimated frequencies from Speed Estimation Speed Search.
Sets the direction of Speed Search to the direction of the frequency reference or in the
motor rotation direction as detected by the drive.
0 : Disabled
1 : Enabled
Note:
• When E9-01 = 0 [Motor Type Selection = Induction (IM)] and A1-02 = 0, 2, or 8
[Control Method Selection = V/f, OLV, or EZOLV], the default settings change whenthe setting of b3-24 [Speed Search Method Selection] changes.
• When E9-01 = 1 or 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]
and A1-02 = 0 or 8 [V/f, EZOLV], refer to 108.
When you set A1-02, b3-24, and E9-01, set b3-14.
Speed Est Retry Current
Level
Speed Est Retry
Detection Time
Speed Search Restart
Attempts
Speed Search Method
Selection
Sets the current level for the search retry function in Speed Estimation Speed Search as a
percentage where drive rated current is a setting value of 100%.
Sets the length of time that the drive will wait to retry Speed Estimation Speed Search
when too much current flow stopped the Speed Search.
Sets the number of times to restart Speed Search if Speed Search does not complete.
Sets the Speed Search method when you start the motor or when you restore power after a
momentary power loss.
Note:
• When A1-02 = 8 [Control Method Selection = EZOLV], the default setting changes
when the setting for E9-01 [Motor Type Selection] changes.
• When you set b3-24, it will trigger the drive to initialize b3-14 [Bi-directional Speed
Search]. After you set b3-24, set b3-14.
1 : Speed Estimation
2 : Current Detection 2
Default
(Range)
2.0 s
(0.1 - 10.0 s)
Determined by o2-04
(10 - 100)
0.2 s
(0.0 - 100.0 s)
Determined by o2-04
(0.0 - 2.0)
1.0
(0.0 - 3.0)
Determined by A1-02 and
o2-04
(0.00 - 6.00)
Determined by A1-02
when A1-02 ≠ 5
20.0 when A1-02 = 5
(0.0 - 1000.0 ms)
1.05
(1.00 - 1.20)
Determined by A1-02 and
b3-24
(0, 1)
150%
(0 - 200%)
0.10 s
(0.00 - 1.00 s)
3 times
(0 - 10 times)
2
(1, 2)
Ref.
175
175
175
175
176
176
176
176
176
177
177
Parameter List
177
1
177
YASKAWA TOEPYAIGA5002A GA500 Programming17
1.5 b: Application
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
b3-25
(01C8)
Expert
b3-26
(01C7)
Expert
b3-29
(077C)
Expert
b3-31
(0BC0)
Expert
b3-32
(0BC1)
Expert
b3-33
(0B3F)
Expert
b3-54
(3123)
b3-55
(3124)
Expert
b3-56
(3126)
b3-61
(1B96)
Expert
NameDescription
Speed Search Wait Time
Sets the length of time the drive will wait to start the Speed Search Retry function.
Direction Determination
Level
Speed Search Back-EMF
Threshold
Spd Search Current
Reference Lvl
Spd Search Current
Complete Lvl
Speed Search during Uv
Selection
Sets the level to find the motor rotation direction. Increase the value if the drive cannot
find the direction.
Sets the induced voltage for motors that use Speed Search. The drive will start Speed
Search when the motor induced voltage level is the same as the setting value. Usually it is
not necessary to change this setting.
Sets the current level that decreases the output current during Current Detection Speed
Search.
Sets the current level that completes Speed Search.
Sets the function that starts Speed Search at start-up if the drive detects a Uv[Undervoltage] when it receives a Run command.
0 : Disabled
1 : Enabled
Search Time
Sets the length of time that the drive will run Speed Search.
Current Increment Time
Sets the length of time that the drive will increase the current from zero current to the
setting value of b3-06 [Speed Estimation Current Level 1].
InverseRotationSearch
WaitTime
Initial Pole Detection
Response Gain
Sets the wait time until the drive starts inverse rotation search after it completes forward
search when you do inverse rotation search during Current Detection Speed Search.
Sets the responsiveness for initial motor magnetic pole calculation when A1-02 = 6[Control Method Selection = AOLV/PM]. Set b3-61 > 0.0 for an ordinary IPM motor.
It is automatically set if High Frequency Injection Tuning is used.
Note:
• Set n8-35 = 1 [Initial Pole Calculation Method = High Frequency Injection] to
enable this parameter.
• Set n8-41 [HFI P Gain] to adjust the responsiveness for initial motor magnetic pole
calculation when A1-02 = 5 [OLV/PM].
Default
(Range)
0.5 s
(0.0 - 30.0 s)
1000
(40 to 60000)
10%
(0 - 10%)
1.50
(1.50 - 3.50)
1.20
(0.00 - 1.49)
1
(0, 1)
400 ms
(10 - 2000 ms)
10 ms
(10 - 2000 ms)
Determined by o2-04
(0.1 - 5.0 s)
5.0
(-20.0 - +20.0)
Ref.
178
178
178
178
178
179
179
179
179
179
◆ b4: Timer Function
No.
(Hex.)
b4-01
(01A3)
b4-02
(01A4)
b4-03
(0B30)
Expert
b4-04
(0B31)
NameDescription
Timer Function ONDelay Time
Timer Function OFFDelay Time
Terminal M1-M2 ONDelay Time
Terminal M1-M2 OFFDelay Time
Sets the ON-delay time for the timer input.
Sets the OFF-delay time for the timer input.
Sets the delay time until the contact is turned ON after the function set with H2-01 turns
ON.
Sets the delay time to deactivate the contact after the function set in H2-01 deactivates.
Expert
b4-05
(0B32)
Terminal M3-M4 ONDelay Time
Sets the delay time to activate the contact after the function set in H2-02 activates.
Expert
b4-06
(0B33)
Terminal M3-M4 OFFDelay Time
Sets the delay time to deactivate the contact after the function set in H2-02 deactivates.
Expert
18YASKAWA TOEPYAIGA5002A GA500 Programming
Default
(Range)
0.0 s
(0.0 - 3000.0 s)
0.0 s
(0.0 - 3000.0 s)
0 ms
(0 - 65000 ms)
0 ms
(0 - 65000 ms)
0 ms
(0 - 65000 ms)
0 ms
(0 - 65000 ms)
Ref.
180
180
181
181
181
181
1.5 b: Application
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
b4-07
(0B34)
NameDescription
Terminal P2 ON-Delay
Time
Expert
b4-08
(0B35)
Terminal P2 OFF-Delay
Time
Expert
◆ b5: PID control
No.
(Hex.)
b5-01
(01A5)
b5-02
(01A6)
RUN
b5-03
(01A7)
RUN
b5-04
(01A8)
RUN
b5-05
(01A9)
RUN
b5-06
(01AA)
RUN
b5-07
(01AB)
RUN
b5-08
(01AC)
RUN
Expert
NameDescription
PID Mode Setting
Proportional Gain (P)
Integral Time (I)
Integral Limit
Derivative Time (D)
PID Output Limit
PID Offset Adjustment
PID Primary Delay Time
Constant
Sets the delay time until the contact is turned ON after the function set with H2-03 turns
ON.
Sets the delay time to deactivate the contact after the function set in H2-03 deactivates.
Sets the type of PID control.
0 : Disabled
1 : Standard
2 : Standard (D on feedback)
3 : Fref + PID Trim
4 : Fref + PID Trim (D on feedback)
5 : Same as 7series & prior, b5-01=1
6 : Same as 7series & prior, b5-01=2
7 : Same as 7series & prior, b5-01=3
8 : Same as 7series & prior, b5-01=4
Note:
Use settings 5 to 8 when the drive is a replacement for a previous generation drive.
Sets the proportional gain (P) that is applied to PID input.
Sets the integral time (I) that is applied to PID input.
Sets the upper limit for integral control (I) as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
Sets the length of time that the PID feedback signal must be more than the level set in b5-36 [PID Feedback High Detection Lvl] to cause Excessive PID Feedback [FbH].
Sets the value that the drive sets or shows as the PID setpoint when at the maximum output
frequency.
Sets the number of digits to set and show the PID setpoint.
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
Frequency Reference
Monitor @PID
Sets the contents for monitor U1-01 [Frequency Reference] in PID control.
0 : U1-01 Includes PID Output
1 : U1-01 Excludes PID Output
PID Trim Mode Output
Reverse Sel
Sets reverse motor rotation when the PID control output is negative.
0 : Lower Limit is Zero
1 : Negative Output Accepted
PID Integrator Ramp
Limit
PID Feedback Monitor
Selection
PID Feedback Monitor
Gain
PID Feedback Monitor
Bias
Sets the responsiveness of PID control when the PID feedback changes quickly.
Sets the monitor (Ux-xx) used as the PID Feedback. Set the x-xx part of the Ux-xx[Monitor].
Sets the gain for the monitor set in b5-55 [PID Feedback Monitor Selection].
Sets the bias for the monitor specified in b5-55 [PID Feedback Monitor Selection].
PID Setpoints 2 to 4
Sets the PID setpoint when H1-xx = 3E or 3F [MFDI Function Selection = PID SetpointSelection 1/2]. This value is a percentage of the maximum output frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
Selects the monitor (Ux-xx) used as the PID Differential Feedback. Set the x-xx part of the
Ux-xx [Monitor].
Sets the gain for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
Sets the bias for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
Sets the signal level for the monitor specified in b5-55 [PID Feedback Monitor Selection].
0 : Absolute
1 : Bi-directional (+/-)
PID Differential FB
Monitor Lvl
Sets the signal level for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
0 : Absolute
1 : Bi-directional (+/-)
Sleep Method Selection
Sets sleep and wake up operation when using PID.
0 : Standard
1 : EZ Sleep/Wake-up
EZ Sleep Unit
Sets the measurement units for b5-91 [EZ Sleep Minimum Speed] and b5-92 [EZ SleepLevel].
0 : 0.1Hz units
1 : rev/min
EZ Sleep Minimum
Speed
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the
largest value from b5-91, b5-34 [PID Output Lower Limit Level], and d2-02 [FrequencyReference Lower Limit].
EZ Sleep Level
Sets the value that the output frequency or motor speed must be less than for longer than
b5-93 [EZ Sleep Time] to enter Sleep Mode.
EZ Sleep Time
Sets the length of time that the output frequency or motor speed must be less than b5-92[EZ Sleep Level] to enter Sleep Mode.
EZ Sleep Wake-up Level
Sets the level at which the drive resumes operation when exiting Sleep Mode.
EZ Sleep Wake-up Mode
Sets the wake-up mode to use when exiting Sleep Mode.
0 : Absolute
1 : Setpoint Delta
EZ Sleep Wake-up Time
Sets the EZ Wake-up time.
Default
(Range)
0.00%
(0.00 - 100.00%)
000
(000 - 999)
1.00
(0.00 - 10.00)
0.00
(-10.00 - +10.00)
0
(0, 1)
0
(0, 1)
0
(0, 1)
0
(0, 1)
-1
(r/min))
-1
(r/min))
-1
-1
(r/min)
(r/min)
0.0 Hz or 0 min
(0.0 to 590.0 Hz or 0 to
35400 min
0.0 Hz or 0 min
(0.0 to 590.0 Hz or 0 to
35400 min
5.0 s
(0.0 - 1000.0 s)
0.00%
(0.00 - 600.00%)
0
(0, 1)
1.0 s
(0.0 - 1000.0 s)
Ref.
196
196
196
196
196
196
196
197
197
197
197
197
198
198
22YASKAWA TOEPYAIGA5002A GA500 Programming
◆ b6: Dwell Function
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.5 b: Application
No.
(Hex.)
b6-01
NameDescription
Dwell Reference at Start
(01B6)
b6-02
Dwell Time at Start
(01B7)
b6-03
Dwell Reference at Stop
(01B8)
b6-04
Dwell Time at Stop
(01B9)
◆ b8: Energy Saving
No.
(Hex.)
b8-01
(01CC)
b8-02
(01CD)
RUN
Expert
b8-03
(01CE)
RUN
Expert
b8-04
(01CF)
Expert
b8-05
(01D0)
Expert
b8-06
(01D1)
Expert
b8-16
(01F8)
Expert
b8-17
(01F9)
Expert
b8-18
(01FA)
Expert
b8-19
(0B40)
Expert
b8-20
(0B41)
Expert
NameDescription
Energy Saving Control
Selection
Energy Saving Gain
Energy Saving Filter
Time
Energy Saving
Coefficient Value
Power Detection Filter
Time
Search Operation Voltage
Limit
PM E-Save Coefficient
Ki
PM E-Save Coefficient
Kt
E-Save d-axis Current
FilterTime
E-Save Search Frequency
E-Save Search Width
Sets the output frequency that the drive will hold momentarily when the motor starts.
Sets the length of time that the drive will hold the output frequency when the motor starts.
Sets the output frequency that the drive will hold momentarily when ramping to stop the
motor.
Sets the length of time for the drive to hold the output frequency when ramping to stop the
motor.
Sets the Energy-saving control function.
0 : Disabled
1 : Enabled
2 : Automatic Optimization
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], you can only select setting
2 in Expert Mode.
Sets the gain for Energy-saving control.
Sets the responsiveness for Energy-saving control.
Sets the Energy-saving control coefficient to maintain maximum motor efficiency. The
default setting is for Yaskawa motors.
Sets the time constant to measure output power.
Sets the voltage limit for Search Operation as a percentage of the motor rated voltage.
Sets torque linearity. This parameter uses the Ki value from the motor nameplate. Usually
it is not necessary to change this setting.
Sets torque linearity. This parameter uses the Kt value from the motor nameplate. Usually
it is not necessary to change this setting.
Sets the d-axis current reference filter time constant.
Sets the frequency of Energy-saving control search operations. Usually it is not necessary
to change this setting.
Sets the amplitude of Energy-saving control search operations.
Default
(Range)
0.0
(Determined by A1-02)
0.0 s
(0.0 - 10.0 s)
0.0
(Determined by A1-02)
0.0 s
(0.0 - 10.0 s)
Default
(Range)
0
(0 - 2)
Determined by A1-02
(0.0 - 10.0)
Determined by A1-02,
C6-01 and o2-04
(0.00 - 10.00 s)
Determined by C6-01,
E2-11, and o2-04
(0.00 - 655.00)
20 ms
(0 - 2000 ms)
0%
(0 - 100%)
1.00
(0.00 - 3.00)
1.00
(0.00 - 3.00)
0.100 s
(0.000 - 5.000 s)
Determined by A1-02
(10 - 300 Hz)
1.0 degrees
(0.1 - 5.0 degrees)
Ref.
198
199
199
199
Ref.
199
200
200
200
200
200
201
Parameter List
201
1
201
201
201
YASKAWA TOEPYAIGA5002A GA500 Programming23
1.5 b: Application
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
b8-21
(0B42)
Expert
b8-22
(0B43)
Expert
b8-23
(0B44)
Expert
b8-24
(0B45)
Expert
b8-25
(0B46)
Expert
b8-26
(0B47)
Expert
b8-28
(0B8B)
Expert
b8-29
(0B8C)
NameDescription
PM E-Save Search Gain
Sets the gain of Energy-saving control search operations.
PM E-Save Search LPF
Cutoff Freq
Sets the frequency of the filter used to extract the high-efficiency phase from search
operations. Usually it is not necessary to change this setting.
PM E-Save Search Limit
Sets the search operations output limit. Usually it is not necessary to change this setting.
PM E-Save High Freq
ACR Gain
PM E-Save Search Start
Level
PM E-Save Power
Setpoint
Over Excitation Action
Selection
Sets the gain for high-frequency current control.
Sets the start level for search operations.
Sets a value to increase torque accuracy.
Sets the function for excitation operation.
0 : Disabled
1 : Enabled
Energy Saving Priority
Selection
Sets the priority of drive response between changes to the load or Energy-saving control.
Enable this to prioritize energy-saving control. Disable this to prioritize tracking related to
fast load changes, and prevent motor stall.
0 : Priority: Drive Response
1 : Priority: Energy Savings
Default
(Range)
0.3Hz
(0.1 - 20.0 Hz)
10.0 Hz
(1.0 - 30.0 Hz)
15.0 degrees
(0.0 - 30.0 degrees)
200.0 Hz
(100.0 - 1000.0 Hz)
10.0%
(0.0 - 100.0%)
0.0%
(-10.0 - +10.0%)
0
(0, 1)
0
(0, 1)
Ref.
202
202
202
202
202
202
203
203
24YASKAWA TOEPYAIGA5002A GA500 Programming
1.6C: Tuning
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ C1: Accel & Decel Time
1.6 C: Tuning
No.
(Hex.)
C1-01
(0200)
RUN
C1-02
(0201)
RUN
C1-03
(0202)
RUN
C1-04
(0203)
RUN
C1-05
(0204)
RUN
C1-06
(0205)
RUN
C1-07
(0206)
RUN
C1-08
(0207)
RUN
C1-09
(0208)
RUN
C1-10
(0209)
C1-11
(020A)
C1-14
(0264)
RUN
NameDescription
Acceleration Time 1
Sets the length of time to accelerate from zero to maximum output frequency.
Deceleration Time 1
Sets the length of time to decelerate from maximum output frequency to zero.
Acceleration Time 2
Sets the length of time to accelerate from zero to maximum output frequency.
Deceleration Time 2
Sets the length of time to decelerate from maximum output frequency to zero.
Acceleration Time 3
Sets the length of time to accelerate from zero to maximum output frequency.
Deceleration Time 3
Sets the length of time to decelerate from maximum output frequency to zero.
Acceleration Time 4
Sets the length of time to accelerate from zero to maximum output frequency.
Deceleration Time 4
Sets the length of time to decelerate from maximum output frequency to zero.
Fast Stop Time
Sets the length of time that the drive will decelerate to zero for a Fast Stop.
Note:
• Decelerating too quickly can cause an ov [Overvoltage] fault that shuts off the drive
while the motor to coasts to a stop. Set a Fast Stop time in C1-09 that prevents motor
coasting and makes sure that the motor stops quickly and safely.
• When L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 1]
and you do KEB Auto-Tuning, the drive will automatically set C1-09. If you must
not change the Fast Stop time, do not do KEB Tuning.
Accel/Decel Time Setting
Units
Sets the setting units for C1-01 to C1-08 [Accel/Decel Times 1 to 4], C1-09 [Fast Stop
Time], L2-06 [Kinetic Energy Backup Decel Time], and L2-07 [Kinetic Energy Backup
Accel Time].
0 : 0.01 s (0.00 to 600.00 s)
1 : 0.1 s (0.0 to 6000.0 s)
Accel/Decel Time
Switching Frequency
Accel/Decel Rate
Frequency
Sets the frequency at which the drive will automatically change acceleration and
deceleration times.
Sets the base frequency used to calculate acceleration and deceleration rates.
Default
(Range)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
10.0 s
(0.0 - 6000.0 s)
1
(0, 1)
Determined by A1-02
(0.0 - 590.0 Hz)
0.0 Hz
(0.0 - 590.0 Hz)
Ref.
206
206
206
206
206
206
207
207
207
207
208
208
Parameter List
1
◆ C2: S-Curve Characteristics
No.
(Hex.)
C2-01
(020B)
C2-02
(020C)
NameDescription
S-Curve Time @ Start of
Accel
S-Curve Time @ End of
Accel
Sets the S-curve acceleration time at start.
Sets the S-curve acceleration time at completion.
YASKAWA TOEPYAIGA5002A GA500 Programming25
Default
(Range)
Determined by A1-02
(0.00 - 10.00 s)
0.20 s
(0.00 - 10.00 s)
Ref.
210
210
1.6 C: Tuning
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
C2-03
(020D)
C2-04
(020E)
NameDescription
S-Curve Time @ Start of
Decel
S-Curve Time @ End of
Decel
Sets the S-curve deceleration time at start.
Sets the S-curve deceleration time at completion.
◆ C3: Slip Compensation
No.
(Hex.)
C3-01
(020F)
RUN
C3-02
(0210)
RUN
C3-03
(0211)
C3-04
(0212)
C3-05
(0213)
C3-16
(0261)
Expert
C3-17
(0262)
Expert
C3-18
(0263)
Expert
C3-21
(033E)
RUN
C3-22
(0241)
RUN
C3-23
(0242)
NameDescription
Slip Compensation Gain
Sets the gain for the slip compensation function. Usually it is not necessary to change this
setting.
Note:
Correctly set these parameters before changing the slip compensation gain:
• E2-01 [Motor Rated Current (FLA)]
• E2-02 [Motor Rated Slip]
• E2-03 [Motor No-Load Current]
Slip Compensation Delay
Time
Sets the slip compensation delay time when speed is unstable or when the slip
compensation response is too slow. Usually it is not necessary to change this setting.
Slip Compensation Limit
Sets the upper limit for the slip compensation function as a percentage of the motor rated
slip.
Slip Compensation at
Regen
Sets the slip compensation function during regenerative operation.
0 : Disabled
1 : Enabled Above 6Hz
2 : Enabled Above C3-15
Output Voltage Limit
Selection
Sets the automatic reduction of motor magnetic flux when the output voltage is saturated.
0 : Disabled
1 : Enabled
Vout Modulation Limit
Start Lvl
Vout Modulation Limit
Max Level
Output Voltage Limit
Level
Motor 2 Slip
Compensation Gain
Sets the modulation factor that starts the output voltage limit operation when C3-05 = 1[Output Voltage Limit Selection = Enabled].
Sets the modulation factor used with C3-18 [Output Voltage Limit Level] for the output
voltage limit operation when C3-05 = 1 [Output Voltage Limit Selection = Enabled].
Sets the maximum drop width of the voltage reference when C3-05 = 1 [Output VoltageLimit Selection = Enabled].
Sets the gain for the motor 2 slip compensation function. Usually it is not necessary to
change this setting.
Note:
Correctly set these parameters before changing the slip compensation gain:
• E4-01 [Motor 2 Rated Current]
• E4-02 [Motor 2 Rated Slip]
• E4-03 [Motor 2 Rated No-Load Current]
Motor 2 Slip Comp Delay
Time
Motor 2 Slip
Compensation Limit
Sets the slip compensation delay time for motor 2 when speed is unstable or when the slip
compensation response is too slow. Usually it is not necessary to change this setting.
Sets the upper limit for the slip compensation function as a percentage of the motor 2 rated
slip.
Default
(Range)
0.20 s
(0.00 - 10.00 s)
0.00 s
(0.00 - 10.00 s)
Default
(Range)
Determined by A1-02
(0.0 - 2.5)
Determined by A1-02
(0 - 10000 ms)
200%
(0 - 250%)
0
(0 - 2)
0
(0, 1)
90.0%
(70.0 - 90.0%)
100.0%
(85.0 - 100.0%)
90.0%
(50.0 - 100.0%)
Determined by E3-01
(0.0 - 2.5)
Determined by E3-01
(0 - 10000 ms)
200%
(0 - 250%)
Ref.
210
210
Ref.
211
211
211
212
212
212
213
213
213
213
213
26YASKAWA TOEPYAIGA5002A GA500 Programming
1.6 C: Tuning
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
C3-24
(0243)
NameDescription
Motor 2 Slip Comp
during Regen
Sets the slip compensation during regenerative operation function for motor 2.
0 : Disabled
1 : Enabled Above 6Hz
2 : Enabled Above C3-15
C3-29
(1B5D)
Expert
Slip Compensation Gain
@ Low Spd
Sets the gain for the slip compensation function in the low speed range. Usually it is not
necessary to change this setting.
◆ C4: Torque Compensation
No.
(Hex.)
C4-01
(0215)
RUN
C4-02
(0216)
RUN
C4-03
(0217)
C4-04
(0218)
C4-05
(0219)
C4-06
(021A)
C4-07
(0341)
RUN
C4-23
(1583)
RUN
Expert
NameDescription
Torque Compensation
Gain
Sets the gain for the torque compensation function. Use this parameter value for motor 1
when operating multiple motors.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], you cannot change this
parameter during drive run.
Torque Compensation
Delay Time
Sets the torque compensation delay time. Usually it is not necessary to change this setting.
Note:
If A1-02 = 8 [Control Method Selection = EZOLV], you cannot change the setting
while the drive is running.
Torque Compensation @
FWD Start
Torque Compensation @
REV Start
Torque Compensation
Time
Motor 2 Torque Comp
Delay Time
Motor 2 Torque
Compensation Gain
Set the amount of torque reference for forward start as a percentage of the motor rated
torque.
Sets the amount of torque reference for reverse start as a percentage of the motor rated
torque.
Sets the starting torque constant to use with C4-03 and C4-04 [Torque Compensation @FWD/REV Start].
Sets the value if ov [Overvoltage] occurs with sudden changes in the load, at the end of
acceleration, or at the start of deceleration.
Sets the gain for motor 2 torque compensation function when using the Motor Switch
function.
Current Control Gain
Current control gain. Usually it is not necessary to change this parameter.
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)] to enable this parameter.
ASR Integral Time 1
Sets the ASR integral time.
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)] to enable this parameter.
Default
(Range)
Determined by A1-02
(0.00 - 300.00)
Determined by A1-02
(0.000 - 60.000 s)
Ref.
219
219
YASKAWA TOEPYAIGA5002A GA500 Programming27
Parameter List
1
1.6 C: Tuning
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
C5-03
(021D)
RUN
C5-04
(021E)
RUN
C5-05
(021F)
C5-06
(0220)
C5-07
(0221)
C5-08
(0222)
C5-12
(0386)
C5-29
(0B18)
Expert
C5-39
(030D)
NameDescription
ASR Proportional Gain 2
Sets the gain to adjust ASR response.
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)] to enable this parameter.
ASR Integral Time 2
Sets the ASR integral time.
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)] to enable this parameter.
ASR Limit
Sets the ASR output limit where E1-04 [Maximum Output Frequency] is 100%.
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)] to enable this parameter.
ASR Delay Time
Sets the filter time constant of the torque reference output from the speed loop. Usually it
is not necessary to change this setting.
ASR Gain Switchover
Frequency
Sets the frequency where the drive will switch between these parameters:
C5-01 and C5-03 [ASR Proportional Gain 1/2]
C5-02 and C5-04 [ASR Integral Time 1/2]
ASR Integral Limit
Set the upper limit of the ASR integral amount as a percentage of the rated load.
Integral Operation @
Accel/Decel
Sets ASR integral operation during acceleration and deceleration.
0 : No
1 : Yes
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)] to enable this parameter.
Speed Control Response
Sets the level of speed control responsiveness. Usually it is not necessary to change this
setting.
0 : Standard
1 : High Performance 1
ASR Primary Delay Time
Const 2
Sets the filter time constant used when the torque reference is output from ASR. Usually it
is not necessary to change this parameter.
Default
(Range)
Determined by A1-02
(0.00 - 300.00)
Determined by A1-02
(0.000 - 60.000 s)
5.0%
(0.0 - 20.0%)
Determined by A1-02
(0.000 - 0.500 s)
Determined by A1-02
(Determined by A1-02)
400%
(0 - 400%)
0
(0, 1)
1
(0, 1)
0.000 s
(0.000 - 0.500 s)
Ref.
219
220
220
220
220
220
221
221
221
28YASKAWA TOEPYAIGA5002A GA500 Programming
◆ C6: Duty & Carrier Frequency
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.6 C: Tuning
No.
(Hex.)
C6-01
(0223)
C6-02
(0224)
C6-03
(0225)
C6-04
(0226)
C6-05
(0227)
C6-09
(022B)
NameDescription
Normal / Heavy Duty
Selection
Sets the drive duty rating.
0 : Heavy Duty Rating
1 : Normal Duty Rating
Carrier Frequency
Selection
Sets the carrier frequency for the transistors in the drive.
1 : 2.0 kHz
2 : 5.0 kHz (4.0 kHz for AOLV/PM)
3 : 8.0 kHz
4 : 10.0 kHz
5 : 12.5 kHz
6 : 15.0 kHz
7 : Swing PWM4 (Audible Sound 1)
8 : Swing PWM4 (Audible Sound 2)
9 : Swing PWM4 (Audible Sound 3)
A : Swing PWM4 (Audible Sound 4)
B : Leakage Current Rejection PWM
F : User Defined (C6-03 to C6-05)
Note:
• The setting range changes when the A1-02 [Control Method Selection] value
changes:
–5, 8 [OLV/PM, EZOLV]: You cannot set to 7 to A.
–When 6 [AOLV/PM]: 2 [5.0 kHz (AOLV/PM: 4.0 kHz)] is available.
• The carrier frequency for Swing PWM 1 is equivalent to 2.0 kHz. Swing PWM
applies a special PWM pattern to decrease the audible noise.
Carrier Frequency Upper
Limit
Carrier Frequency Lower
Limit
Carrier Freq Proportional
Gain
Carrier Freq at Rotational
Tune
Sets the upper limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection= User Defined (C6-03 to C6-05)] to set this parameter.
Sets the lower limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection= User Defined (C6-03 to C6-05)] to set this parameter.
Sets the proportional gain for the carrier frequency. Set C6-02 = F [Carrier FrequencySelection = User Defined (C6-03 to C6-05)] to set this parameter.
Sets the Auto-Tuning carrier frequency. Usually it is not necessary to change this setting.
0 : 5 kHz
1 : Use C6-03
Default
(Range)
1
(0, 1)
Determined by A1-02,
C6-01, and o2-04
(Determined by A1-02)
Determined by C6-02
(1.0 - 15.0 kHz)
Determined by C6-02
(1.0 - 15.0 kHz)
Determined by C6-02
(0 - 99)
0
(0, 1)
Ref.
221
222
223
224
224
224
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming29
1.7 d: Reference Settings
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.7d: Reference Settings
◆ d1: Frequency Reference
No.
(Hex.)
d1-01
(0280)
RUN
d1-02
(0281)
RUN
d1-03
(0282)
RUN
d1-04
(0283)
RUN
d1-05
(0284)
RUN
d1-06
(0285)
RUN
d1-07
(0286)
RUN
d1-08
(0287)
RUN
d1-09
(0288)
RUN
d1-10
(028B)
RUN
d1-11
(028C)
RUN
NameDescription
Reference 1
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 2
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 3
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 4
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 5
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 6
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 7
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 8
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 9
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 10
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 11
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
Ref.
228
229
229
229
229
229
230
230
230
230
231
30YASKAWA TOEPYAIGA5002A GA500 Programming
1.7 d: Reference Settings
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
d1-12
(028D)
RUN
d1-13
(028E)
RUN
d1-14
(028F)
RUN
d1-15
(0290)
RUN
d1-16
(0291)
RUN
d1-17
(0292)
RUN
NameDescription
Reference 12
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 13
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 14
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 15
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Reference 16
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Jog Reference
Sets the Jog frequency reference in the units from o1-03 [Frequency Display UnitSelection]. Set H1-xx = 6 [MFDI Function Select = Jog Reference Selection] to use the
Jog frequency reference.
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03
= 1 [0.01% (100% = E1-04)].
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
6.00 Hz
(0.00 - 590.00 Hz)
Ref.
231
231
231
231
232
232
◆ d2: Reference Limits
No.
(Hex.)
d2-01
(0289)
d2-02
(028A)
d2-03
(0293)
NameDescription
Frequency Reference
Upper Limit
Frequency Reference
Lower Limit
Analog Frequency Ref
Lower Limit
Sets maximum limit for all frequency references. The maximum output frequency is 100%.
Sets minimum limit for all frequency references. The maximum output frequency is 100%.
Sets the lower limit for the master frequency reference (the first frequency of the multistep speed reference) as a percentage. The maximum output frequency is 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
• A1-02 ≠ 8: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
Default
(Range)
100.0%
(0.0 - 110.0%)
0.0%
(0.0 - 110.0%)
0.0%
(0.0 - 110.0%)
Ref.
232
233
233
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming31
1.7 d: Reference Settings
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ d3: Jump Frequency
No.
(Hex.)
d3-01
(0294)
d3-02
(0295)
d3-03
(0296)
d3-04
(0297)
NameDescription
Jump Frequency 1
Sets the median value of the frequency band that the drive will avoid.
Jump Frequency 2
Sets the median value of the frequency band that the drive will avoid.
Jump Frequency 3
Sets the median value of the frequency band that the drive will avoid.
Jump Frequency Width
Sets the width of the frequency band that the drive will avoid.
◆ d4: Frequency Ref Up/Down & Hold
No.
(Hex.)
d4-01
(0298)
d4-03
(02AA)
RUN
d4-04
(02AB)
RUN
d4-05
(02AC)
RUN
d4-06
(02AD)
d4-07
(02AE)
RUN
d4-08
(02AF)
RUN
NameDescription
Freq Reference Hold
Selection
Sets the function that saves the frequency reference or the frequency bias (Up/Down 2)
after a Stop command or when de-energizing the drive.
Set H1-xx [MFDI Function Selection] to one of these values to enable this parameter:
• A [Accel/Decel Ramp Hold]
• 10/11 [Up/Down Command]
• 75/76 [Up/Down 2 Command]
0 : Disabled
1 : Enabled
Up/Down 2 Bias Step
Frequency
Up/Down 2 Ramp
Selection
Sets the bias that the Up/Down 2 function adds to or subtracts from the frequency
reference.
Sets the acceleration and deceleration times for the Up/Down 2 function to apply the bias
to the frequency reference.
0 : Use Selected Accel/Decel Time
1 : Use Accel/Decel Time 4
Up/Down 2 Bias Mode
Selection
Sets the function that saves the bias value to the drive when you open or close the two Up/Down 2 Commands [H1-xx = 75, 76]. Set d4-03 [Up/Down 2 Bias Step Frequency] = 0.00
before you set this parameter.
0 : Hold when Neither Up/Down Closed
1 : Reset when Neither / Both Closed
Frequency Ref Bias (Up/
Down 2)
Saves the bias value from the Up/Down 2 Command where the Maximum Output
Frequency is 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
If the frequency reference changes for more than the level set to this parameter, then the
bias value will be held. The value is set as a percentage of the Maximum Output
Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
Sets the lower frequency limit for the Up/Down function.
0 : Greater of d2-02 or Analog
1 : d2-02
◆ d6: Field Weakening /Forcing
No.
(Hex.)
d6-01
(02A0)
d6-02
(02A1)
d6-03
(02A2)
d6-06
(02A5)
NameDescription
Field Weakening Level
Sets the drive output voltage as a percentage of E1-05 [Maximum Output Voltage] when
H1-xx = 63 [Field Weakening] is activated.
Field Weakening
Frequency Limit
Sets the minimum output frequency to start field weakening.
Field Forcing Selection
Sets the field forcing function.
0 : Disabled
1 : Enabled
Field Forcing Limit
Sets the limit value for field forcing to increase the motor excitation current reference as a
percentage of E2-03 [Motor No-Load Current]. Usually it is not necessary to change this
setting.
Default
(Range)
0.0%
(-99.9 - 0.0%)
0
(0, 1)
Default
(Range)
80%
(0 - 100%)
0.0 Hz
(0.0 - 590.0 Hz)
0
(0, 1)
400%
(100 - 400%)
Ref.
239
239
Ref.
240
240
240
240
◆ d7: Offset Frequency
No.
(Hex.)
d7-01
(02B2)
RUN
d7-02
(02B3)
RUN
d7-03
(02B4)
RUN
NameDescription
Offset Frequency 1
Uses H1-xx = 44 [MFDI Function Select = Add Offset Frequency 1 (d7-01)] as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
Offset Frequency 2
Uses H1-xx = 45 [MFDI Function Select = Add Offset Frequency 2 (d7-02)] as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
Offset Frequency 3
Uses H1-xx = 46 [MFDI Function Select = Add Offset Frequency 3 (d7-03)] as a
percentage of the Maximum Output Frequency to add or subtract the set frequency to/from
the frequency reference.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
NOTICE: Set parameter E1-01 to align with the drive input
voltage (not motor voltage). If this parameter is incorrect, the
protective functions of the drive will not operate correctly and it
can cause damage to the drive.
V/f Pattern Selection
Maximum Output
Frequency
Maximum Output Voltage
Base Frequency
Mid Point A Frequency
Mid Point A Voltage
Minimum Output
Frequency
Minimum Output Voltage
Mid Point B Frequency
Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you
can make a custom pattern.
0 : Const Trq, 50Hz base, 50Hz max
1 : Const Trq, 60Hz base, 60Hz max
2 : Const Trq, 50Hz base, 60Hz max
3 : Const Trq, 60 Hz base, 72 Hz max
4 : VT, 50Hz, 65% Vmid reduction
5 : VT, 50Hz, 50% Vmid reduction
6 : VT, 60 Hz, 65% Vmid reduction
7 : VT, 60 Hz, 50% Vmid reduction
8 : High Trq, 50Hz, 25% Vmin Boost
9 : High Trq, 50Hz, 65% Vmin Boost
A : High Trq, 60 Hz, 25% Vmin Boost
B : High Trq, 60 Hz, 65% Vmin Boost
C : Const Trq, 60 Hz base, 90 Hz max
D : Const Trq, 60 Hz base, 120 Hz max
E : Const Trq, 60 Hz base, 180 Hz max
F : V/f Pattern Selection
Note:
• When A1-02 = 2 [Control Method Selection = OLV], settings 0 to E are not
available.
• Set the correct V/f pattern for the application and operation area. An incorrect V/f
pattern can decrease motor torque and increase current from overexcitation.
Sets the maximum output frequency for the V/f pattern.
Sets the maximum output voltage for the V/f pattern.
Sets the base frequency for the V/f pattern.
Sets a middle output frequency for the V/f pattern.
Sets a middle output voltage for the V/f pattern.
Sets the minimum output frequency for the V/f pattern.
Sets the minimum output voltage for the V/f pattern.
Sets a middle output frequency for the V/f pattern.
Default
(Range)
200 V Class: 240 V, 400
V: 480 V
(200 V Class: 155 to 255
V, 400 V Class: 310 to
510 V)
F
(Determined by A1-02)
Determined by A1-02 and
E5-01
(Determined by A1-02
and E5-01)
200 V Class: 230.0 V, 400
V: 460.0 V
(200 V Class: 0.0 - 255.0
V, 400 V Class: 0.0 -
510.0 V)
Determined by A1-02 and
E5-01
(0.0 - E1-04)
Determined by A1-02
(0.0 - E1-04)
Determined by A1-02,
C6-01 and o2-04
(200 V Class: 0.0 - 255.0
400 V Class: 0.0 - 510.0
Determined by A1-02 and
V,
V)
E5-01
(Determined by A1-02,
E1-04, and E5-01)
Determined by A1-02
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to
510.0 V)
0.0 Hz
(0.0 - E1-04)
Ref.
243
243
248
249
249
249
249
249
249
249
34YASKAWA TOEPYAIGA5002A GA500 Programming
1.8 E: Motor Parameters
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
E1-12
(030B)
NameDescription
Mid Point B Voltage
Sets a middle point voltage for the V/f pattern.
Expert
E1-13
(030C)
Base Voltage
Sets the base voltage for the V/f pattern.
Expert
◆ E2: Motor Parameters
No.
(Hex.)
E2-01
(030E)
E2-02
(030F)
E2-03
(0310)
E2-04
(0311)
E2-05
(0312)
E2-06
(0313)
E2-07
(0314)
E2-08
(0315)
E2-09
(0316)
Expert
E2-10
(0317)
E2-11
(0318)
NameDescription
Motor Rated Current
(FLA)
Sets the motor rated current in amps.
Motor Rated Slip
Sets motor rated slip.
Motor No-Load Current
Sets the no-load current for the motor in amps when operating at the rated frequency and
the no-load voltage.
Motor Pole Count
Sets the number of motor poles.
Motor Line-to-Line
Resistance
Motor Leakage
Inductance
Motor Saturation
Coefficient 1
Motor Saturation
Coefficient 2
Sets the line-to-line resistance for the motor stator windings.
Sets the voltage drop from motor leakage inductance when the motor is operating at the
rated frequency and rated current. This value is a percentage of Motor Rated Voltage.
Sets the motor iron-core saturation coefficient at 50% of the magnetic flux.
Sets the motor iron-core saturation coefficient at 75% of the magnetic flux.
Motor Mechanical Loss
Sets the mechanical loss of the motor. It is set as a percentage of E2-11 [Motor RatedPower]. Usually it is not necessary to change this setting.
Motor Iron Loss
Sets the motor iron loss.
Motor Rated Power
Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].
Note:
• When A1-02 = 0 [Control Method Selection = V/f], the maximum value is 120.
• When A1-02 = 2 [OLV], the maximum value is 48.
Default
(Range)
0.0 V
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to
510.0 V)
0.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 -
510.0 V)
Default
(Range)
Determined by o2-04,
C6-01
(10% to 200% of the
drive rated current)
Determined by o2-04,
C6-01
(0.000 - 20.000 Hz)
Determined by o2-04,
C6-01
(0 to E2-01)
4
(2 - 120)
Determined by o2-04,
C6-01
(0.000 - 65.000 Ω)
Determined by o2-04,
C6-01
(0.0 - 60.0%)
0.50
(0.00 - 0.50)
0.75
(E2-07 - 0.75)
0.0%
(0.0 - 10.0%)
Determined by o2-04,
C6-01
(0 - 65535 W)
Determined by o2-04,
C6-01
(0.00 - 650.00 HP)
Ref.
250
250
Ref.
250
251
251
251
251
252
252
252
252
252
253
Parameter List
◆ E3: V/f Pattern for Motor 2
No.
(Hex.)
E3-01
(0319)
NameDescription
Motor 2 Control Mode
Selection
Sets the control method for motor 2.
Default
(Range)
0
(0, 2)
Ref.
253
1
Note:
When you change this setting, the drive will set all parameters that are dependent on
this parameter to their default settings.
0 : V/f Control
2 : Open Loop Vector
E3-04
(031A)
Motor 2 Maximum
Output Frequency
Set the maximum output frequency for the motor 2 V/f pattern.
Determined by E3-01
(40.0 - 590.0 Hz)
254
YASKAWA TOEPYAIGA5002A GA500 Programming35
1.8 E: Motor Parameters
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
E3-05
(031B)
E3-06
(031C)
E3-07
(031D)
E3-08
(031E)
E3-09
(031F)
E3-10
(0320)
E3-11
(0345)
Expert
E3-12
(0346)
Expert
E3-13
(0347)
Expert
NameDescription
Motor 2 Maximum
Output Voltage
Sets the maximum output voltage for the motor 2 V/f pattern.
Motor 2 Base Frequency
Sets the base frequency for the motor 2 V/f pattern.
Motor 2 Mid Point A
Frequency
Motor 2 Mid Point A
Voltage
Motor 2 Minimum
Output Frequency
Motor 2 Minimum
Output Voltage
Motor 2 Mid Point B
Frequency
Motor 2 Mid Point B
Voltage
Sets a middle output frequency for the motor 2 V/f pattern.
Sets a middle output voltage for the motor 2 V/f pattern.
Sets the minimum output frequency for the motor 2 V/f pattern.
Sets the minimum output voltage for the motor 2 V/f pattern.
Sets a middle output frequency for the motor 2 V/f pattern. Set this parameter to adjust the
V/f pattern for the constant output range. Usually it is not necessary to change this
parameter.
Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/
f pattern for the constant output range. Usually it is not necessary to change this parameter.
Motor 2 Base Voltage
Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f
pattern for the constant output range. Usually it is not necessary to change this parameter.
Default
(Range)
Determined by E3-01
(200 V Class: 0.0 - 255.0
400 V Class: 0.0 - 510.0
V,
V)
Determined by E3-01
(0.0 - E3-04)
Determined by E3-01
(0.0 - E3-04)
Determined by E3-01
(200 V Class: 0.0 - 255.0
400 V Class: 0.0 - 510.0
V,
V)
Determined by E3-01
(0.0 - E3-04)
Determined by E3-01
(200 V Class: 0.0 - 255.0
400 V Class: 0.0 - 510.0
V,
V)
0.0 Hz
(0.0 - E3-04)
0.0 V
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to
510.0 V)
0.0 V
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to
510.0 V)
Ref.
254
254
254
254
254
254
254
255
255
◆ E4: Motor 2 Parameters
No.
(Hex.)
E4-01
(0321)
E4-02
(0322)
E4-03
(0323)
E4-04
(0324)
E4-05
(0325)
E4-06
(0326)
E4-07
(0343)
E4-08
(0344)
E4-09
(033F)
Expert
NameDescription
Motor 2 Rated Current
Sets the motor rated current for motor 2 in amps.
Motor 2 Rated Slip
Sets the motor rated slip for motor 2.
Motor 2 Rated No-Load
Current
Sets the no-load current for motor 2 in amps when operating at the rated frequency and the
no-load voltage.
Motor 2 Motor Poles
Sets the number of poles for motor 2.
Motor 2 Line-to-Line
Resistance
Motor 2 Leakage
Inductance
Motor 2 Saturation
Coefficient 1
Motor 2 Saturation
Coefficient 2
Sets the line-to-line resistance for the motor 2 stator windings.
Sets the voltage drop from motor 2 leakage inductance as a percentage of Motor Rated
Voltage when motor 2 operates at the rated frequency and rated current.
Sets the motor 2 iron-core saturation coefficient at 50% of the magnetic flux.
Sets the motor 2 iron-core saturation coefficient at 75% of the magnetic flux.
Motor 2 Mechanical Loss
Sets the mechanical loss of motor 2. It is set as a percentage of E4-11 [Motor 2 RatedPower]. Usually it is not necessary to change this setting.
Default
(Range)
Determined by o2-04,
C6-01
(10% to 200% of the
drive rated current)
Determined by o2-04,
C6-01
(0.000 - 20.000 Hz)
Determined by o2-04,
C6-01
(0 to E4-01)
4
(2 - 120)
Determined by o2-04,
C6-01
(0.000 - 65.000 Ω)
Determined by o2-04,
C6-01
(0.0 - 60.0%)
0.50
(0.00 - 0.50)
0.75
(E4-07 - 0.75)
0.0%
(0.0 - 10.0%)
Ref.
255
255
256
256
256
256
257
257
257
36YASKAWA TOEPYAIGA5002A GA500 Programming
1.8 E: Motor Parameters
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
E4-10
(0340)
E4-11
(0327)
NameDescription
Motor 2 Iron Loss
Sets the motor iron loss for motor 2.
Motor 2 Rated Power
Sets the motor rated power in the units from o1-58 [Motor Power Unit Selection].
◆ E5: PM Motor Settings
No.
(Hex.)
E5-01
(0329)
E5-02
(032A)
E5-03
(032B)
E5-04
(032C)
E5-05
(032D)
E5-06
(032E)
E5-07
(032F)
E5-09
(0331)
E5-24
(0353)
E5-25
(035E)
Expert
NameDescription
PM Motor Code Selection
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to
automatically set some parameters to their correct settings.
PM Motor Rated Power
Sets the PM motor rated output in the units from o1-58 [Motor Power Unit Selection].
Motor Rated Current
(FLA)
Sets the PM motor rated current (FLA).
PM Motor Pole Count
Sets the number of PM motor poles.
Note:
When A1-02 = 5, 6 or 8 [OLV/PM, AOLV/PM or EZOLV], the maximum value is 48.
PM Motor Resistance
(ohms/phase)
PM d-axis Inductance
(mH/phase)
PM q-axis Inductance
(mH/phase)
PM Back-EMF Vpeak
(mV/(rad/s))
PM Back-EMF L-L Vrms
(mV/rpm)
Polarity Estimation
Timeout
Sets the resistance per phase of a PM motor. Set 50% of the line-to-line resistance.
Sets the PM motor d-axis inductance.
Sets the PM motor q-axis inductance.
Sets the peak value of PM motor induced voltage.
Sets the RMS value for PM motor line voltage.
Sets the function that switches polarity for initial polarity estimation. Usually it is not
necessary to change this setting.
0 : Disabled
1 : Enabled
Default
(Range)
Determined by o2-04,
C6-01
(0 - 65535 W)
Determined by o2-04,
C6-01
(0.00 - 650.00 HP)
Default
(Range)
FFFF
(0000 - FFFF)
Determined by o2-04,
C6-01
(0.10 - 30.00 kW)
Determined by o2-04,
C6-01
(10% to 200% of the
drive rated current)
4
(2 - 120)
0.100 Ω
(0.000 - 65.000 Ω)
1.00 mH
(0.00 - 300.00 mH)
1.00 mH
(0.00 - 600.00 mH)
0.0 mV/(rad/sec)
(0.0 - 2000.0 mV/(rad/s))
200 V class: 100.0 mV/
400 V class: 200.0 mV/
min
min
-1
-1
(0.0 - 6500.0 mV/min-1)
0
(0, 1)
Ref.
257
257
Ref.
258
258
258
258
259
259
259
259
260
260
◆ E9: Motor Setting
No.
(Hex.)
E9-01
(11E4)
NameDescription
Motor Type Selection
Sets the type of motor.
Default
(Range)
0
(0 to 2)
Ref.
260
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
E9-02
(11E5)
E9-03
(11E6)
E9-04
(11E7)
Maximum Speed
Rated Speed
Base Frequency
Sets the maximum speed of the motor.
Sets the rated rotation speed of the motor.
Sets the rated frequency of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
Determined by E9-01
(100 - 7200 min
-1
Determined by E9-01
(40.0 - 120.0 Hz)
260
261
)
261
YASKAWA TOEPYAIGA5002A GA500 Programming37
Parameter List
1
1.8 E: Motor Parameters
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
E9-05
(11E8)
E9-06
(11E9)
E9-07
(11EA)
E9-08
(11EB)
E9-09
(11EC)
E9-10
(11ED)
NameDescription
Motor Rated Voltage
Sets the rated voltage of the motor.
Motor Rated Current
(FLA)
Sets the motor rated current in amps.
Motor Rated Power
Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].
Motor Pole Count
Sets the number of motor poles.
Motor Rated Slip
Sets the motor rated slip.
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for the motor stator windings.
Default
(Range)
200 V Class: 230.0 V, 400
V: 460.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 -
510.0 V)
Determined by E9-01 and
o2-04
(10% to 200% of the
drive rated current)
Determined by E9-02 and
o2-04
(0.00 - 650.00 kW)
4
(2 to 120)
0.000 Hz
(0.000 - 20.000 Hz)
Determined by o2-04
(0.000 - 65.000 Ω)
Ref.
261
261
261
262
262
262
38YASKAWA TOEPYAIGA5002A GA500 Programming
1.9F: Options
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ F1: Fault Detection in PG Speed Control
1.9 F: Options
No.
(Hex.)
F1-02
(0381)
F1-03
(0382)
F1-04
(0383)
F1-08
(0387)
F1-09
(0388)
F1-10
(0389)
NameDescription
Encoder Signal Loss
Detect Sel
Sets the method to stop the motor or let the motor continue operating when the drive
detects PGo [Encoder (PG) Feedback Loss].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)] to enable this parameter.
Overspeed Detection
Selection
Sets the method to stop the motor or let the motor continue to operate when the drive
detects oS [Overspeed].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)] to enable this parameter.
Speed Deviation
Detection Select
Sets the method to stop the motor or let the motor continue to operate when the drive
detects dEv [Speed Deviation].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)] to enable this parameter.
Overspeed Detection
Level
Sets the detection level of oS [Overspeed] as a percentage when the maximum output
frequency is 100%.
Note:
• Parameter A1-02 [Control Method Selection] selects which parameter is the
• When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
Overspeed Detection
Delay Time
Sets the length of time that the speed feedback must be more than the F1-08 level to cause
oS [Overspeed].
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)] to enable this parameter.
Speed Deviation
Detection Level
Sets the detection level of dEv [Speed Deviation] as a percentage when the maximum
output frequency is 100%.
Note:
• Parameter A1-02 [Control Method Selection] selects which parameter is the
• When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP
Pulse Train Function = Speed Feedback (V/F Control)] to enable this parameter.
Default
(Range)
1
(0 - 4)
1
(0 - 3)
3
(0 - 3)
115%
(0 - 120%)
Determined by A1-02
(0.0 - 2.0 s)
10%
(0 - 50%)
Ref.
263
263
264
264
265
265
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming39
1.9 F: Options
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
F1-11
(038A)
NameDescription
Speed Deviation Detect
DelayTime
Sets the length of time that the difference between the frequency reference and speed
feedback must be more than the level in F1-10 to cause dEv [Speed Deviation].
Note:
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP Pulse
Train Function = Speed Feedback (V/F Control)] to enable this parameter.
F1-14
(038D)
Encoder Open-Circuit
Detect Time
Sets the length of time that the drive must not receive a pulse signal to cause PGo[Encoder (PG) Feedback Loss].
Note:
Motor speed and load conditions can cause ov [Overvoltage] and oC [Overcurrent]
faults.
When A1-02 = 0 [Control Method Selection = V/f], set H6-01 = 3 [Terminal RP PulseTrain Function = Speed Feedback (V/F Control)] to enable this parameter.
◆ F6: Communication Options
No.
(Hex.)
F6-01
(03A2)
F6-02
(03A3)
F6-03
(03A4)
F6-04
(03A5)
F6-06
(03A7)
F6-07
(03A8)
F6-08
(036A)
NameDescription
Communication Error
Selection
Sets the method to stop the motor or let the motor continue operating when the drive
detects bUS [Option Communication Error].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm (Run at d1-04)
5 : Alarm - Ramp Stop
Comm External Fault
(EF0) Detect
Sets the conditions at which EF0 [Option Card External Fault] is detected.
0 : Always Detected
1 : Detected during RUN Only
Comm External Fault
(EF0) Select
Sets the method to stop the motor or let the motor continue operating when the drive
detects EF0 [Option Card External Fault].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
bUS Error Detection
Time
Sets the delay time for the drive to detect bUS [Option Communication Error].
Note:
When you install a CC-Link option (SI-C3) to the drive, the setting value changes to
0.0 s.
Torque Reference/Limit
by Comm
Sets the function that enables and disables the torque reference and torque limit received
from the communication option.
0 : Disabled
1 : Enabled
Multi-Step Ref @
NetRef/ComRef
Sets the function that enables and disables the multi-step speed reference when the
freqency reference source is NetRef or ComRef (communication option card or
MEMOBUS/Modbus communications).
0 : Disable Multi-Step References
1 : Enable Multi-Step References
Comm Parameter Reset
@Initialize
Sets the function to initialize F6-xx and F7-xx parameters when the drive is initialized
with A1-03 [Initialize Parameters].
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
Default
(Range)
0.5 s
(0.0 - 10.0 s)
2.0 s
(0.0 - 10.0 s)
Default
(Range)
1
(0 - 5)
0
(0, 1)
1
(0 - 3)
2.0 s
(0.0 - 12.0 s)
0
(0, 1)
1
(0, 1)
0
(0, 1)
Ref.
265
265
Ref.
271
272
272
272
272
273
273
40YASKAWA TOEPYAIGA5002A GA500 Programming
1.9 F: Options
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
F6-10
(03B6)
F6-11
(03B7)
F6-14
(03BB)
F6-15
(0B5B)
F6-16
(0B8A)
F6-20
(036B)
F6-21
(036C)
F6-22
(036D)
F6-23
(036E)
F6-24
(036F)
NameDescription
CC-Link Node Address
Sets the node address for CC-Link communication. Restart the drive after you change the
parameter setting.
Note:
Be sure to set a node address that is different than all other node addresses. Do not set
this parameter to 0. Incorrect parameter settings will cause AEr [Station AddressSetting Error] errors and the L.ERR LED on the option will come on.
CC-Link Communication
Speed
Sets the communication speed for CC-Link communication. Restart the drive after you
change the parameter setting.
0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps
BUS Error Auto Reset
Sets the automatic reset function for bUS [Option Communication Errors].
0 : Disabled
1 : Enabled
Comm. Option
Parameters Reload
Sets the update method when you change F6-xx, F7-xx [Communication Options].
0 : Reload at Next Power Cycle
1 : Reload Now
2 : Cancel Reload Request
Gateway Mode
Sets the gateway mode operation and the number of connected slave drives.
0 : Disabled
1 : Enabled: 1 Slave Drives
2 : Enabled: 2 Slave Drives
3 : Enabled: 3 Slave Drives
4 : Enabled: 4 Slave Drives
MECHATROLINK
Station Address
Sets the station address for MECHATROLINK communication. Change the parameter then
cycle power on the drive.
Note:
• The setting range changes if using MECHATROLINK-II or MECHATROLINK-III:
–MECHATROLINK-II (SI-T3) range: 20 - 3F
–MECHATROLINK-III (SI-ET3) range: 03 - EF
• Be sure to set a node address that is different than all other node addresses. Incorrect
parameter settings will cause AEr [Station Address Setting Error] errors and the L.
ERR LED on the option will come on.
• The drive detects AEr errors when the station address is 20 or 3F.
MECHATROLINK
Frame Size
Sets the frame size for MECHATROLINK communication. Restart the drive after you
change the parameter setting.
0 : 32byte (M-2) / 64byte (M-3)
1 : 17byte (M-2) / 32byte (M-3)
MECHATROLINK Link
Speed
Sets the communications speed for MECHATROLINK-II. Restart the drive after you
change the parameter setting.
Note:
This parameter is only available with the MECHATROLINK-II option.
0 : 10 Mbps
1 : 4 Mbps
MECHATROLINK
Monitor Select (E)
MECHATROLINK
Monitor Select (F)
Sets the MEMOBUS register used for the monitor functions of INV_CTL (drive operation
control command) and INV_I/O (drive I/O control command). Restart the drive after you
change the parameter setting.
Sets the MEMOBUS register used for the monitor functions of INV_CTL (drive operation
control command) and INV_I/O (drive I/O control command). Restart the drive after you
change the parameter setting.
Default
(Range)
0
(0 - 64)
0
(0 - 4)
0
(0, 1)
0
(0 - 2)
0
(0 to 4)
0021h
(MECHATROLINK-II:
0020h - 003Fh,
MECHATROLINK-III:
0003h - 00EFh)
0
(0, 1)
0
(0, 1)
0000h
(0000h - FFFFh)
0000h
(0000h - FFFFh)
Ref.
273
273
274
274
274
274
275
275
Parameter List
1
275
275
YASKAWA TOEPYAIGA5002A GA500 Programming41
1.9 F: Options
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
F6-25
(03C9)
F6-26
(03CA)
F6-30
(03CB)
F6-31
(03CC)
F6-32
(03CD)
F6-35
(03D0)
F6-36
(03D1)
F6-50
(03C1)
F6-51
(03C2)
F6-52
(03C3)
NameDescription
MECHATROLINK
Watchdog Error Sel
Sets the method to stop the motor or let the motor continue operating when the drive
detects E5 [MECHATROLINK Watchdog Timer Err].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
MECHATROLINK
Allowable No of Err
PROFIBUS-DP Node
Address
Sets the number of times that the option must detect a bUS alarm to cause a bUS [OptionCommunication Error].
Sets the node address for PROFIBUS-DP communication. Restart the drive after you
change the parameter setting.
Note:
Be sure to set an address that is different than all other node addresses. Do not set this
parameter to 0.
PROFIBUS-DP Clear
Mode Selection
Sets what the drive will do after it receives the Clear Mode command.
0 : Reset
1 : Hold Previous State
PROFIBUS-DP Data
Format Select
Sets the data format of PROFIBUS-DP communication. Restart the drive after you change
the parameter setting.
0 : PPO Type
1 : Conventional
2 : PPO (bit0)
3 : PPO (Enter)
4 : Conventional (Enter)
5 : PPO (bit0, Enter)
CANopen Node ID
Selection
Sets the node address for CANopen communication. Restart the drive after you change the
parameter setting.
Note:
Be sure to set an address that is different than all other node addresses. Do not set this
parameter to 0. Incorrect parameter settings will cause AEr [Station Address SettingError] errors and the L.ERR LED on the option will come on.
CANopen
Communication Speed
Sets the CANopen communications speed. Restart the drive after you change the parameter
setting.
0 : Detect Automatically
1 : 10 kbps
2 : 20 kbps
3 : 50 kbps
4 : 125 kbps
5 : 250 kbps
6 : 500 kbps
7 : 800 kbps
8 : 1 Mbps
DeviceNet MAC Address
Sets the MAC address for DeviceNet communication. Restart the drive after you change
the parameter setting.
Note:
Be sure to set a MAC address that is different than all other node addresses. Do not set
this parameter to 0. Incorrect parameter settings will cause AEr [Station AddressSetting Error] errors and the MS LED on the option will flash.
DeviceNet Baud Rate
Sets the DeviceNet communications speed. Restart the drive after you change the
parameter setting.
0 : 125 kbps
1 : 250 kbps
2 : 500 kbps
3 : Adjustable from Network
4 : Detect Automatically
DeviceNet PCA Setting
Sets the format of data that the DeviceNet communication master sends to the drive.
Default
(Range)
1
(0 - 3)
2
(2 - 10 times)
0
(0 - 125)
0
(0, 1)
0
(0 - 5)
0
(0 - 126)
6
(0 - 8)
64
(0 - 64)
4
(0 - 4)
21
(0 - 255)
Ref.
275
276
276
276
276
277
277
277
277
278
42YASKAWA TOEPYAIGA5002A GA500 Programming
1.9 F: Options
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
F6-53
(03C4)
F6-54
(03C5)
F6-55
(03C6)
F6-56
(03D7)
F6-57
(03D8)
F6-58
(03D9)
F6-59
(03DA)
F6-60
(03DB)
F6-61
(03DC)
F6-62
(03DD)
F6-63
(03DE)
F6-64 to F6-67
(03DF - 03E2)
F6-68 to F6-71
(03E3, 03E4,
03C7, and
03C8)
F6-72
(081B)
NameDescription
DeviceNet PPA Setting
Sets the format of data that the drive sends to the DeviceNet communication master.
DeviceNet Idle Fault
Detection
Sets the function to detect EF0 [Option Card External Fault] when the drive does not
receive data from the DeviceNet master.
0 : Enabled
1 : Disabled, No Fault Detection
2 : Vendor Specific
3 : RUN Forward
4 : Reverse run
DeviceNet Baud Rate
Monitor
Sets the function to see the actual DeviceNet communications speed using the keypad.
This parameter functions as a monitor only.
0 : 125 kbps
1 : 250 kbps
2 : 500 kbps
DeviceNet Speed Scaling
Sets the speed scale for DeviceNet communication.
DeviceNet Current
Scaling
DeviceNet Torque
Scaling
Sets the current scale of the DeviceNet communication master.
Sets the torque scale of the DeviceNet communication master.
DeviceNet Power Scaling
Sets the power scale of the DeviceNet communication master.
DeviceNet Voltage
Scaling
Sets the voltage scale of the DeviceNet communication master.
DeviceNet Time Scaling
Sets the time scale of the DeviceNet communication master.
DeviceNet Heartbeat
Interval
DeviceNet Network
MAC ID
Dynamic Out Assembly
109 Param 1 to 4
Dynamic In Assembly
159 Param 1 to 4
Sets the heartbeat for DeviceNet communication. Set this parameter to 0 to disable the
heartbeat function.
Sets the function to see the actual DeviceNet MAC address using the keypad. This
parameter functions as a monitor only.
Sets Configurable Outputs 1 to 4 written to the MEMOBUS register.
Sets Configurable Inputs 1 to 4 read from the MEMOBUS register.
PowerLink Node Address
Sets the node ID for PowerLink communication.
Note:
Be sure to set an address that is different than all other node addresses. Do not set this
parameter to 0.
Default
(Range)
71
(0 - 255)
0
(0 - 4)
0
(0 - 2)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0
(0 - 10)
63
(0 - 63)
0000h
(0000h - FFFFh)
0000h
(0000h - FFFFh)
0
(0 - 255)
Ref.
278
278
278
278
278
279
279
279
279
279
279
279
279
280
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming43
1.9 F: Options
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ F7: Communication Options
No.
(Hex.)
F7-01
(03E5)
F7-02
(03E6)
F7-03
(03E7)
F7-04
(03E8)
F7-05
(03E9)
F7-06
(03EA)
F7-07
(03EB)
F7-08
(03EC)
F7-09
(03ED)
F7-10
(03EE)
F7-11
(03EF)
NameDescription
IP Address 1
Sets the first octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
IP Address 2
Sets the second octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
IP Address 3
Sets the third octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
IP Address 4
Sets the fourth octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 4] to set the IP Address. Be sure to set a
different IP address for each drive on the network.
• Also set parameters F7-01 to F7-12.
Subnet Mask 1
Sets the first octet of the subnet mask of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
Subnet Mask 2
Sets the second octet of the subnet mask of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
Subnet Mask 3
Sets the third octet of the subnet mask of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
Subnet Mask 4
Sets the fourth octet of the subnet mask of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
Gateway Address 1
Sets the first octet of the gateway address of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
Gateway Address 2
Sets the second octet of the gateway address of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
Gateway Address 3
Sets the third octet of the gateway address of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
Default
(Range)
192
(0 - 255)
168
(0 - 255)
1
(0 - 255)
20
(0 - 255)
255
(0 - 255)
255
(0 - 255)
255
(0 - 255)
0
(0 - 255)
192
(0 - 255)
168
(0 - 255)
1
(0 - 255)
Ref.
280
280
280
280
280
281
281
281
281
281
281
44YASKAWA TOEPYAIGA5002A GA500 Programming
1.9 F: Options
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
F7-12
(03F0)
F7-13
(03F1)
F7-14
(03F2)
F7-15
(03F3)
F7-16
(03F4)
F7-17
(03F5)
F7-18
(03F6)
F7-19
(03F7)
F7-20
(03F8)
F7-21
(03F9)
F7-22
(03FA)
F7-23
(03FB)
F7-24
(03FC)
NameDescription
Gateway Address 4
Sets the fourth octet of the gateway address of the connected network.
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
Address Mode at Startup
Sets the method to set option card IP addresses.
0 : Static
1 : BOOTP
2 : DHCP
Note:
• The following setting values are available when using the PROFINET
communication option card (SI-EP3).
–0: Static
–2: DHCP
• When F7-13 = 0, set parameters F7-01 to F7-12 [IP Address 1 to Gateway Address
4] to set the IP Address. Be sure to set a different IP address for each drive on the
network.
Duplex Mode Selection
Sets the duplex mode setting method.
0 : Half/Half
1 : Auto/Auto
2 : Full/Full
3 : Half/Auto
4 : Half/Full
5 : Auto/Half
6 : Auto/Full
7 : Full/Half
8 : Full/Auto
Communication Speed
Selection
Sets the communications speed.
10 : 10/10 Mbps
100 : 100/100 Mbps
101 : 10/100 Mbps
102 : 100/10 Mbps
Timeout Value
Sets the detection time for a communications timeout.
Note:
Set this parameter to 0.0 to disable the connection timeout function.
EtherNet/IP Speed
Scaling Factor
EtherNet/IP Current Scale
Factor
EtherNet/IP Torque Scale
Factor
EtherNet/IP Power
Scaling Factor
EtherNet/IP Voltage Scale
Factor
Sets the scaling factor for the speed monitor in the EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the output current monitor in the EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the torque monitor in the EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the power monitor in the EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the voltage monitor in the EtherNet/IP Class ID 2AH Object.
EtherNet/IP Time Scaling
Sets the scaling factor for the time monitor in the EtherNet/IP Class ID 2AH Object.
Dynamic Out Param 1 for
CommCard
Dynamic Out Param 2 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set
this parameter to set to configurable output 1.
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set
this parameter to set to configurable output 2.
Default
(Range)
1
(0 - 255)
2
(0 - 2)
1
(0 - 8)
10
(10, 100 - 102)
0.0 s
(0.0 - 30.0 s)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0
(-15 - +15)
0284
0284
Ref.
282
282
282
282
283
283
283
283
283
283
283
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming45
1.9 F: Options
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
F7-25
(03FD)
F7-26
(03FE)
F7-27
(03FF)
F7-28
(0370)
F7-29
(0371)
F7-30
(0372)
F7-31
(0373)
F7-32
(0374)
F7-33
(0375)
F7-34
(0376)
F7-35
(0377)
F7-36
(0378)
F7-37
(0379)
NameDescription
Dynamic Out Param 3 for
CommCard
Dynamic Out Param 4 for
CommCard
Dynamic Out Param 5 for
CommCard
Dynamic Out Param 6 for
CommCard
Dynamic Out Param 7 for
CommCard
Dynamic Out Param 8 for
CommCard
Dynamic Out Param 9 for
CommCard
Dynamic Out Param 10
for CommCard
Dynamic In Param 1 for
CommCard
Dynamic In Param 2 for
CommCard
Dynamic In Param 3 for
CommCard
Dynamic In Param 4 for
CommCard
Dynamic In Param 5 for
CommCard
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set
this parameter to set to configurable output 3.
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set
this parameter to set to configurable output 4.
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0. When you use a ProfiNet option, set
this parameter to set to configurable output 5.
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0.
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0.
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0.
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0.
Sets Output Assembly 116 when you use an Ethernet/IP option. The drive writes the values
from Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for
each parameter. The drive will not write the values from Output Assembly 116 to the
registers when the MEMOBUS/Modbus address is 0.
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 1.
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 2.
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 3.
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 4.
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a ProfiNet option, set this parameter to set to configurable input 5.
Default
(Range)
0284
0284
0284
0284
0284
0284
0284
0284
0284
0284
0284
0284
0284
Ref.
46YASKAWA TOEPYAIGA5002A GA500 Programming
1.9 F: Options
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
F7-38
(037A)
F7-39
(037B)
F7-40
(037C)
F7-41
(037D)
F7-42
(037E)
F7-60
(0780)
F7-61
(0781)
F7-62
(0782)
F7-63
(0783)
F7-64
(0784)
F7-65
(0785)
F7-66
(0786)
F7-67
(0787)
F7-68
(0788)
F7-69
(0789)
F7-70
(078A)
F7-71
(078B)
NameDescription
Dynamic In Param 6 for
CommCard
Dynamic In Param 7 for
CommCard
Dynamic In Param 8 for
CommCard
Dynamic In Param 9 for
CommCard
Dynamic In Param 10 for
CommCard
PZD1 Write (Control
Word)
PZD2 Write (Frequency
Reference)
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values
from the MEMOBUS/Modbus address registers stored for each parameter to Input
Assembly 166. The drive returns the default register value for the option card when the
MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD1 (PPO
output). PZD1 (PPO output) functions as the STW when F7-60 = 0 to 2.
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD2 (PPO
output). PZD2 (PPO output) functions as the HSW when F7-61 = 0 to 2.
PZD3 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD3 (PPO
output). A value of 0, 1, or 2 will disable the PZD3 (PPO output) write operation to the
MEMOBUS/Modbus register.
PZD4 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD4 (PPO
output). A value of 0, 1, or 2 will disable the PZD4 (PPO output) write operation to the
MEMOBUS/Modbus register.
PZD5 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD5 (PPO
output). A value of 0, 1, or 2 will disable the PZD5 (PPO output) write operation to the
MEMOBUS/Modbus register.
PZD6 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD6 (PPO
output). A value of 0, 1, or 2 will disable the PZD6 (PPO output) write operation to the
MEMOBUS/Modbus register.
PZD7 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD7 (PPO
output). A value of 0, 1, or 2 will disable the PZD7 (PPO output) write operation to the
MEMOBUS/Modbus register.
PZD8 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD8 (PPO
output). A value of 0, 1, or 2 will disable the PZD8 (PPO output) write operation to the
MEMOBUS/Modbus register.
PZD9 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD9 (PPO
output). A value of 0, 1, or 2 will disable the PZD9 (PPO output) write operation to the
MEMOBUS/Modbus register.
PZD10 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD10 (PPO
output). A value of 0, 1, or 2 will disable the PZD10 (PPO output) write operation to the
MEMOBUS/Modbus register.
PZD1 Read (Status Word)
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD1 (PPO
input). PZD1 (PPO input) functions as the ZSW when F7-70 = 0.
PZD2 Read (Output
Frequency)
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD2 (PPO
input). PZD2 (PPO input) functions as the HIW when F7-71 = 0.
Default
(Range)
0284
0284
0284
0284
0284
0284
0284
0284
0284
0284
0285
0285
0285
0285
0285
0285
0285
Ref.
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming47
1.9 F: Options
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
F7-72
(078C)
F7-73
(078D)
F7-74
(078E)
F7-75
(078F)
F7-76
(0790)
F7-77
(0791)
F7-78
(0792)
F7-79
(0793)
NameDescription
PZD3 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD3 (PPO
input). A value of 0 will disable the PZD3 (PPO input) load operation from the
MEMOBUS/Modbus register.
PZD4 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD4 (PPO
input). A value of 0 will disable the PZD4 (PPO input) load operation from the
MEMOBUS/Modbus register.
PZD5 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD5 (PPO
input). A value of 0 will disable the PZD5 (PPO input) load operation from the
MEMOBUS/Modbus register.
PZD6 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD6 (PPO
input). A value of 0 will disable the PZD6 (PPO input) load operation from the
MEMOBUS/Modbus register.
PZD7 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD7 (PPO
input). A value of 0 will disable the PZD7 (PPO input) load operation from the
MEMOBUS/Modbus register.
PZD8 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD8 (PPO
input). A value of 0 will disable the PZD8 (PPO input) load operation from the
MEMOBUS/Modbus register.
PZD9 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD9 (PPO
input). A value of 0 will disable the PZD9 (PPO input) load operation from the
MEMOBUS/Modbus register.
PZD10 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD10 (PPO
input). A value of 0 will disable the PZD10 (PPO input) load operation from the
MEMOBUS/Modbus register.
Default
(Range)
0286
0286
0286
0286
0286
0286
0286
0286
Ref.
48YASKAWA TOEPYAIGA5002A GA500 Programming
1.10H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ H1: Digital Inputs
1.10 H: Terminal Functions
No.
(Hex.)
H1-01
(0438)
H1-02
(0439)
H1-03
(0400)
H1-04
(0401)
H1-05
(0402)
H1-06
(0403)
H1-07
(0404)
H1-21
(0B70)
H1-22
(0B71)
H1-23
(0B72)
H1-24
(0B73)
H1-25
(0B74)
H1-26
(0B75)
H1-27
(0B76)
H1-40
(0B54)
H1-41
(0B55)
H1-42
(0B56)
NameDescription
Terminal S1 Function
Selection
Sets the function for MFDI terminal S1.
Note:
When you initialize the drive for 3-Wire Initialization [A1-03 = 3330], the default
setting is F.
Terminal S2 Function
Selection
Sets the function for MFDI terminal S2.
Note:
When you initialize the drive for 3-Wire Initialization [A1-03 = 3330], the default
setting is F.
Terminal S3 Function
Selection
Terminal S4 Function
Selection
Terminal S5 Function
Selection
Sets the function for MFDI terminal S3.
Sets the function for MFDI terminal S4.
Sets the function for MFDI terminal S5.
Note:
When you set 3-Wire Initialization [A1-03 = 3330] to initialize the drive, the default
setting is 0.
Terminal S6 Function
Selection
Sets the function for MFDI terminal S6.
Note:
When you set 3-Wire Initialization [A1-03 = 3330] to initialize the drive, the default
setting is 3.
Terminal S7 Function
Selection
Sets the function for MFDI terminal S7.
Note:
When you set 3-Wire Initialization [A1-03 = 3330] to initialize the drive, the default
setting is 4.
Terminal S1 Function
Selection 2
Terminal S2 Function
Select 2
Terminal S3 Function
Selection 2
Terminal S4 Function
Selection 2
Terminal S5 Function
Selection 2
Terminal S6 Function
Selection 2
Terminal S7 Function
Selection 2
Mbus Reg 15C0h bit0
Input Func
Mbus Reg 15C0h bit1
Input Func
Mbus Reg 15C0h bit2
Input Func
Sets the second function for MFDI terminal S1.
Sets the second function for MFDI terminal S2.
Sets the second function for MFDI terminal S3.
Sets the second function for MFDI terminal S4.
Sets the second function for MFDI terminal S5.
Sets the second function for MFDI terminal S6.
Sets the second function for MFDI terminal S7.
Sets MFDI function to set to bit 0 of the MEMOBUS register 15C0 (Hex.).
Sets MFDI function to set to bit 1 of the MEMOBUS register 15C0 (Hex.).
Sets MFDI function to set to bit 2 of the MEMOBUS register 15C0 (Hex.).
Default
(Range)
40
(1 - 1FF)
41
(1 - 1FF)
24
(0 - 1FF)
14
(0 - 1FF)
3
(0 - 1FF)
4
(0 - 1FF)
6
(0 - 1FF)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
Ref.
288
288
288
288
288
289
289
289
289
289
289
290
290
290
290
290
291
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming49
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
■ H1-xx: MFDI Setting Values
Setting ValueFunctionDescriptionRef.
03-Wire Sequence
1LOCAL/REMOTE
Selection
2External Reference 1/2
Selection
3Multi-Step Speed
Reference 1
4Multi-Step Speed
Reference 2
5Multi-Step Speed
Reference 3
6Jog Reference Selection
7Accel/Decel Time
Selection 1
8Baseblock Command (N.
O.)
9Baseblock Command (N.
C.)
AAccel/Decel Ramp Hold
BOverheat Alarm (oH2)
CAnalog Terminal Enable
Selection
EASR Integral Reset
FNot Used
10Up Command
11Down Command
12Forward Jog
Sets the direction of motor rotation for 3-wire sequence.
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
ON : LOCAL
OFF : REMOTE
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
Sets the drive to use the JOG Frequency Reference (JOG command) set in d1-17. The JOG Frequency Reference (JOG
command) overrides Frequency References 1 to 16 (d1-01 to d1-16).
Sets the drive to use Acceleration/Deceleration Time 1 [C1-01, C1-02] or Acceleration/Deceleration Time 2 [C1-03,C1-04].
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
ON : Baseblock (drive output stop)
OFF : Normal operation
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
ON : Normal operation
OFF : Baseblock (drive output stop)
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency
that was stored in the drive at the time of the pause, and restarts motor operation.
Sets the drive to display an oH2 [Drive Overheat Warning] alarm when the input terminal is ON. The alarm does not
have an effect on drive operation.
Sets the command that enables or disables the terminals selected in H3-14 [Analog Input Terminal Enable Sel].
ON : Input to the terminal selected with H3-14 is enabled
OFF : Input to the terminal selected with H3-14 is disabled
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : P control
OFF : PI control
Use this setting for unused terminals or to use terminals in through mode.
Sets the command to use a push button switch to increase the drive frequency reference. You must also set Setting 11[Down Command].
ON : Increases the frequency reference.
OFF : Holds the current frequency reference.
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set Setting 10[Up Command].
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
Sets the command to operate the motor in the forward direction at the Jog Frequency set in d1-17 [Jog Reference].
291
292
292
292
292
292
293
293
293
293
293
294
294
294
294
294
296
297
50YASKAWA TOEPYAIGA5002A GA500 Programming
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
Setting ValueFunctionDescriptionRef.
13Reverse Jog
14Fault Reset
15Fast Stop (N.O.)
16Motor 2 Selection
17Fast Stop (N.C.)
18Timer Function
19PID Disable
1AAccel/Decel Time
Selection 2
1BProgramming Lockout
1EReference Sample Hold
20 to 2FExternal fault
30PID Integrator Reset
31PID Integrator Hold
32Multi-Step Speed
Reference 4
34PID Soft Starter Disable
Sets the command to operate the motor in reverse at the Jog Frequency set in d1-17 [Jog Reference].
Sets the command to reset the current fault when the Run command is inactive.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before
trying to reset a fault.
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
activated while the drive is operating.
Sets the command for the drive to operate motor 1 or motor 2. Stop the motors before switching.
ON : Operate motor 2
OFF : Operate motor 1
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
activated while the drive is operating.
Sets the command to start the timer function. Use this setting with Timer Output [H2-xx = 12].
Sets the command to disable PID control when b5-01 = 1 to 8 [PID Mode Setting = Enabled].
ON : PID control disabled
OFF : PID control enabled
Set this function and H1-xx = 7[Accel/Decel Time Selection 1] together. Sets the drive to use Acceleration/Deceleration Time 3 [C1-05, C1-06] or Acceleration/Deceleration Time 4 [C1-07, C1-08].
Sets the command to prevent parameter changes when the terminal is OFF.
ON : Programming Lockout
OFF : Parameter Write Prohibit
Sets the command to sample the frequency reference at terminal A1 or A2, and hold the frequency reference at that
frequency.
Sets a command to stop the drive when a failure or fault occurs on an external device.
20 : External Fault (NO-Always-Ramp)
21 : External Fault (NC-Always-Ramp)
22 : External Fault (NO-@Run-Ramp)
23 : External Fault (NC-@Run-Ramp)
24 : External Fault (NO-Always-Coast)
25 : External Fault (NC-Always-Coast)
26 : External Fault (NO-@Run-Coast)
27 : External Fault (NC-@Run-Coast)
28 : External Fault (NO-Always-FStop)
29 : External Fault (NC-Always-FStop)
2A : External Fault (NO-@Run-FStop)
2B : External Fault (NC-@Run-FStop)
2C : External Fault (NO-Always-Alarm)
2D : External Fault (NC-Always-Alarm)
2E : External Fault (NO-@Run-Alarm)
2F : External Fault (NC-@Run-Alarm)
Sets the command to reset and hold the PID control integral to 0 when the terminal is ON.
Sets the command to hold the integral value of the PID control while the terminal is activated.
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
Sets the PID soft starter function.
ON : No
OFF : Yes
297
297
297
298
298
299
299
299
299
299
300
301
301
301
301
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming51
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
Setting ValueFunctionDescriptionRef.
35PID Input (Error) Invert
3EPID Setpoint Selection 1
3FPID Setpoint Selection 2
40Forward RUN (2-Wire)
41Reverse RUN (2-Wire)
42Run Command (2-Wire
43FWD/REV (2-Wire
44Add Offset Frequency 1
45Add Offset Frequency 2
46Add Offset Frequency 3
Sequence 2)
Sequence 2)
(d7-01)
(d7-02)
(d7-03)
47Node Setup (CANopen)
60DC Injection Braking
Command
61Speed Search from Fmax
Sets the command to turn the terminal ON and OFF to switch the PID input level (polarity).
Set this function and H1-xx = 3F [PID Setpoint Selection 2] together. Sets the function to switch the PID setpoint to
b5-58 to b5-60 [PID Setpoint 2 to 4].
Set this function and H1-xx = 3E [PID Setpoint Selection 1] at the same time. Sets the function to switch the PID
setpoint to b5-58 to b5-60 [PID Setpoint 2 to 4].
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 41 [Reverse Run Command (2-Wire Seq)] at the same time.
ON : Forward Run
OFF : Run Stop
Note:
• If you activate the Forward Run command terminal and the Reverse Run command terminal, the drive will detect
minor fault/alarm EF [FWD/REV Run Command Input Error] and the motor will ramp to stop.
• Initialize the drive with a 2-wire sequence to set the Forward Run command to terminal S1.
• This function will not operate at the same time as H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire
Seq 2)].
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 40 [Forward Run Command (2-Wire Seq)] at the same time.
ON : Reverse Run
OFF : Run Stop
Note:
• If you activate the Forward Run command terminal and the Reverse Run command terminal, the drive will detect
minor fault/alarm EF [FWD/REV Run Command Input Error] and the motor will ramp to stop.
• Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal S2.
• This function will not operate at the same time as H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire
Seq 2)].
Sets the Run command for 2-wire sequence 2. Set this function and H1-xx = 43 [FWD/REV Command (2-Wire Seq 2)]
at the same time.
ON : Run
OFF : Stop
Note:
This function will not operate at the same time as H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire Seq)].
Sets the direction of motor rotation for 2-wire sequence 2. Set this function and H1-xx = 42 [Run Command (2-WireSequence 2)] together.
ON : Reverse run
OFF : Forward run
Note:
This function will not operate at the same time as H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire Seq)].
Sets the function to add the offset frequency set in d7-01 [Offset Frequency 1] to the frequency reference when the
terminal activates.
Sets the function to add the offset frequency set in d7-02 [Offset Frequency 2] to the frequency reference when the
terminal activates.
Sets the function to add the offset frequency set in d7-03 [Offset Frequency 3] to the frequency reference when the
terminal activates.
Sets the function in CANopen communications to start the Node Setup function to set the drive node address from the
host controller.
Sets the command to use DC Injection Braking to stop the motor.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available with a PM motor.
Sets the function to start speed search using an external reference although b3-01 = 0 [Speed Search Selection at Start= Disabled].
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 61 and 62 are set at the same time.
302
302
302
302
302
303
303
303
303
303
304
304
304
52YASKAWA TOEPYAIGA5002A GA500 Programming
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
Setting ValueFunctionDescriptionRef.
62Speed Search from Fref
63Field Weakening
65KEB Ride-Thru 1
66KEB Ride-Thru 1
67Communications Test
68High Slip Braking (HSB)
Activate (N.C.)
Activate (N.O.)
Mode
Activate
6ADrive Enable
75Up 2 Command
76Down 2 Command
77ASR Gain (C5-03) Select
7AKEB Ride-Thru 2
7BKEB Ride-Thru 2
7CShort Circuit Braking (N.
7DShort Circuit Braking (N.
Activate (N.C.)
Activate (N.O.)
O.)
C.)
Sets the function to use an external reference to start speed search although b3-01 = 0 [Speed Search Selection at Start= Disabled].
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 61 and 62 are set at the same time.
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in d6-01[Field Weakening Level] and d6-02 [Field Weakening Frequency Limit] when the input terminal is activated.
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
Set the function for the drive to self-test RS-485 serial communications operation.
Sets the command to use high-slip braking to stop the motor.
Sets the function to show dnE [Drive Enabled] on the keypad and ignore Run commands when the terminal is OFF.
Sets the function to increase the frequency reference bias value to accelerate the motor when the terminal is activated.
Set this function and H1-xx = 76 [Down 2 Command] together.
Note:
When you use this function, use d4-08 and d4-09 [Up/Down 2 Bias Upper Limit/Lower Limit] to set the optimal
bias limit value.
Sets the function to decrease the frequency reference bias value to decelerate the motor when the terminal is activated.
Set this function and H1-xx = 75 [Up 2 Command] at the same time.
Note:
When you use this function, use d4-08 and d4-09 [Up/Down 2 Bias Upper Limit/Lower Limit] to set the optimal
bias limit value.
Sets the function to switch the ASR proportional gain set in C5-01 [ASR Proportional Gain 1] and C5-03 [ASRProportional Gain 1/2].
ON : C5-03
OFF : C5-01
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
Sets operation of Short Circuit Braking (N.O.).
ON : Short Circuit Braking is enabled.
OFF : Normal operation
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
Sets operation of Short Circuit Braking (N.C.).
ON : Normal operation
OFF : Short Circuit Braking is enabled.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
304
304
305
305
305
305
305
306
307
307
307
308
308
308
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming53
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
Setting ValueFunctionDescriptionRef.
7EReverse Rotation
Identifier
Set the motor rotation direction when you use Simple Closed Loop V/f Control method.
ON : Reverse run
OFF : Forward run
90 - 96DWEZ Digital Inputs 1 to
7
Sets digital inputs used with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
9FDWEZ Disable
Sets operation of the DriveWorksEZ program saved in the drive.
ON : No
OFF : Yes
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Digital input] to enable this function.
101 to 19FInverse Input of 1 to 9FSets the function of the selected MFDI to operate inversely. To select the function, enter “1xx”, where the “xx” is the
function setting value.
Note:
You cannot use inverse input for all functions. Refer to Table 2.49 for more information.
◆ H2: Digital Outputs
308
308
309
309
No.
(Hex.)
H2-01
(040B)
H2-02
(040C)
H2-03
(040D)
H2-06
(0437)
H2-07
(0B3A)
H2-08
(0B3B)
H2-09
(0B3C)
H2-10
(0B3D)
H2-20
(1540)
H2-21
(1541)
H2-22
(1542)
NameDescription
Term MA/MB-MC
Function Selection
Sets the function set for MFDO terminal MA-MC or MB-MC.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
Term P1-C1 Function
Selection
Sets the function for MFDO terminal P1-C1.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
Term P2-C2 Function
Selection
Sets the function for MFDO terminal P2-C2.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
Watt Hour Output Unit
Selection
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection= Watt Hour Pulse Output].
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
Modbus Register 1
Address Select
Modbus Register 1 Bit
Select
Modbus Register 2
Address Select
Modbus Register 2 Bit
Select
Comparator 1 Monitor
Selection
Comparator 1 Lower
Limit
Comparator 1 Upper
Limit
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For
example, set H2-20 = 102 to monitor U1-02 [Output Frequency].
Sets the lower limit detection level for comparator 1 when the full scale analog output for
the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
Sets the upper limit detection level for comparator 1 when the full scale analog output for
the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
Default
(Range)
E
(0 - 1FF)
0
(0 - 1FF)
2
(0 - 1FF)
0
(0 - 4)
0001
(0001 - 1FFF)
0000
(0000 - FFFF)
0001
(0001 - 1FFF)
0000
(0000 - FFFF)
102
(000 - 999)
0.0%
(0.0 - 300.0%)
0.0%
(0.0 - 300.0%)
Ref.
311
311
312
312
312
312
313
313
313
313
313
54YASKAWA TOEPYAIGA5002A GA500 Programming
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
H2-23
(1543)
H2-24
(1544)
H2-25
(1545)
H2-26
(1546)
H2-27
(1547)
H2-28
(1548)
H2-29
(1549)
H2-30
(154A)
H2-31
(154B)
H2-32
(159A)
H2-33
(159B)
H2-34
(159C)
H2-35
(159D)
H2-36
(159E)
H2-37
(159F)
H2-40
(0B58)
H2-41
(0B59)
H2-42
(0B5A)
H2-60
(1B46)
Expert
H2-61
(1B47)
Expert
NameDescription
Comparator 1 Hysteresis
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for
the monitor selected in H2-20 [Comparator 1 Monitor Selection].
Comparator 1 On-Delay
Time
Comparator 1 Off-Delay
Time
Comparator 2 Monitor
Selection
Comparator 2 Lower
Limit
Comparator 2 Upper
Limit
Sets the on-delay time for comparator 1.
Sets the off-delay time for comparator 1.
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx [Monitor]. For
example, set H2-26 = 103 to monitor U1-03 [Output Current].
Sets the lower limit detection level for comparator 2 as a percentage of the full scale
analog output for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
Sets the upper limit detection level for comparator 2 as a percentage of the full scale
analog output for the monitor selected in H2-26 [Comparator 2 Monitor Selection].
Comparator 2 Hysteresis
Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output for
the monitor selected in H2-26 [Comparator 2 Monitor Selection].
Comparator 2 On-Delay
Time
Comparator 2 Off-Delay
Time
Sets the on-delay time for comparator 2.
Sets the off-delay time for comparator 2.
Comparator 1 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output
of the monitor selected with H2-20 [Comparator 1 Monitor Selection].
Comparator1 Protection
Selection
Sets drive operation when it detects CP1 [Comparator1 Limit Fault].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Digital Output Only
Comparator 2 Filter Time
Sets the time constant that is applied to the primary delay filter used for the analog output
of the monitor selected with H2-26 [Comparator 2 Monitor Selection].
Comparator2 Protection
Selection
Sets drive operation when it detects CP2 [Comparator2 Limit Fault].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Digital Output Only
Comparator 1 Ineffective
Time
Comparator 2 Ineffective
Time
Mbus Reg 15E0h bit0
Output Func
Mbus Reg 15E0h bit1
Output Func
Mbus Reg 15E0h bit2
Output Func
Term MA,MB,MC
Secondary Function
Term MA,MB,MC
Logical Operation
Sets the length of time that CP1 [Comparator1 Limit Fault] is disabled.
Sets the length of time that CP2 [Comparator2 Limit Fault] is disabled.
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.).
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.).
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.).
Sets the second function for terminal MA/MB-MC. Outputs the logical calculation results
of the terminals set to functions by H2-01 [Term MA,MB,MC Function Selection].
Sets the logical operation for the functions set in H2-01 [Term MA,MB,MC FunctionSelection] and H2-60 [Term MA,MB,MC Secondary Function].
Default
(Range)
0.0%
(0.0 - 10.0%)
0.0 s
(0.0 - 600.0 s)
0.0 s
(0.0 - 600.0 s)
103
(000 - 999)
0.0%
(0.0 - 300.0%)
0.0%
(0.0 - 300.0%)
0.0%
(0.0 - 10.0%)
0.0 s
(0.0 - 600.0 s)
0.0 s
(0.0 - 600.0 s)
0.0s
(0.0 - 10.0 s)
4
(0 - 4)
0.0s
(0.0 - 10.0 s)
4
(0 - 4)
0.0 s
(0.0 - 1000.0 s)
0.0 s
(0.0 - 1000.0 s)
F
(0 - 1FF)
F
(0 - 1FF)
F
(0 - 1FF)
F
(0 - FF)
0
(0 - 8)
Ref.
313
314
314
314
314
314
314
315
315
315
315
315
316
316
316
316
316
317
317
317
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming55
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
H2-62
(1B48)
Expert
H2-63
(1B49)
Expert
H2-64
(1B4A)
Expert
H2-65
(1B4B)
Expert
H2-66
(1B4C)
Expert
H2-67
(1B4D)
Expert
H2-68
(1B4E)
Expert
NameDescription
Term MA,MB,MC
Minimum ON Time
Terminal P1 Secondary
Function
Terminal P1 Logical
Operation
Terminal P1 Minimum
ON Time
Terminal P2 Secondary
Function
Terminal P2 Logical
Operation
Terminal P2 Minimum
ON Time
Sets the minimum ON time that the drive uses to output the logical calculation results from
terminal MA/MB-MC.
Sets the second function for terminal P1-C1. Outputs the logical calculation results of the
terminals set to functions by H2-02 [Term P1 Function Selection].
Sets the logical operation for the functions set in H2-02 [Term P1 Function Selection] and
H2-63 [Terminal P1 Secondary Function].
Sets the minimum ON time used to output the logical calculation results from terminal P1C1.
Sets the second function for terminal P2-C2. Outputs the logical calculation results of the
terminals assigned to functions by H2-03 [Term P2 Function Selection].
Sets the logical operation for the functions set in H2-03 [Term P2 Function Selection] and
H2-66 [Terminal P2 Secondary Function].
Sets the minimum ON time used to output the logical calculation results from terminal P2C2.
■ H2-xx: MFDO Setting Values
Default
(Range)
0.1 s
(0.0 - 25.0 s)
F
(0 - FF)
0
(0 - 8)
0.1 s
(0.0 - 25.0 s)
F
(0 - FF)
0
(0 - 8)
0.1 s
(0.0 - 25.0 s)
Ref.
317
317
317
317
318
318
318
Setting ValueFunctionDescriptionRef.
0During Run
318
The terminal activates when you input a Run command and when the drive is outputting voltage.
ON : Drive is running
OFF : Drive is stopping
1Zero Speed
The terminal turns on when the output frequency drops below the value of E1-09 [Minimum Output Frequency] or b2-01 [DC Injection/Zero SpeedThreshold].
318
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 SettingControl Method SelectionParameter Used as the Reference
0V/fE1-09
2OLVb2-01
5OLV/PME1-09
6AOLV/PME1-09
8EZOLVE1-09
ON : Output frequency < value of E1-09 or b2-01.
OFF : Output frequency ≥ value of E1-09 or b2-01.
2Speed Agree 1
The terminal activates when the output frequency is in the range of the frequency reference ± L4-02 [Speed AgreeDetection Width].
319
ON : The output frequency is in the range of “frequency reference ± L4-02”.
OFF : The output frequency does not align with the frequency reference although the drive is running.
3User-Set Speed Agree 1
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02[Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.
319
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency is within the range as defined by the result of “L4-01 ± L4-02” and the range of frequency
reference ± L4-02.
OFF : The output frequency is not in the range of “L4-01 ± L4-02” nor the range of frequency reference ± L4-02.
56YASKAWA TOEPYAIGA5002A GA500 Programming
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
Setting ValueFunctionDescriptionRef.
4Frequency Detection 1
5Frequency Detection 2
6Drive ready
7DC Bus Undervoltage
8During Baseblock (N.O.)
9Frequency Reference
from Keypad
ARun Command Source
BTorque Detection 1 (N.
O.)
CFrequency Reference
Loss
DBraking Resistor Fault
EFault
FNot Used
10Alarm
11Fault Reset Command
Active
12Timer Output
The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level] +L4-02 [Speed Agree Detection Width]. After the terminal turns off, the terminal continues to remain off until the output
frequency reaches the level set with L4-01.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency is less than the value of L4-01 or does not exceed the value of L4-01 + L4-02.
OFF : The output frequency is higher than the value of L4-01 + L4-02.
The terminal activates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level].
After the terminal activates, the terminal stays activated until the output frequency is at the value of L4-01 - L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency is higher than the value of L4-01.
OFF : The output frequency is less than the value of “L4-01 - L4-02,” or it does not exceed the value of L4-01.
The terminal activates when the drive is ready and running.
The terminal activates when the DC bus voltage or control circuit power supply is less than the voltage set with L2-05[Undervoltage Detection Lvl (Uv1)]. The terminal also turns on when there is a fault with the DC bus voltage.
ON : The DC bus voltage is less than the setting value of L2-05.
OFF : The DC bus voltage is more than the setting value of L2-05.
The terminal turns on during baseblock. When the drive is in baseblock, the drive output transistor stops switching and
does not make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF : Parameter b1-01 or b1-15 [Frequency Reference Selection 1 or 2] is the frequency reference source.
Shows the selected Run command source.
ON : The keypad is the Run command source.
OFF : Parameter b1-02 or b1-16 [Run Command Selection 1 or 2] is the Run command source.
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque > L6-02 [Torque Detection Level 1], or < L6-02 for longer than the time set with L6-03[Torque Detection Time 1].
The terminal activates when the drive detects a loss of frequency reference.
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor
fault.
The terminal activates when the drive detects a fault.
Note:
The terminal will not activate for CPF00 and CPF01 [Control Circuit Error] faults.
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact
output via MEMOBUS/Modbus or the communication option. This signal does not function if signals from the PLC
are not configured.
The terminal turns on when the drive detects a minor fault.
The terminal turns on when the drive receives the Reset command from the control circuit terminal, serial
communications, or the communication option.
Use this setting when the drive uses the timer function as an output terminal.
320
320
321
321
321
321
322
322
322
322
322
322
322
323
323
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming57
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
Setting ValueFunctionDescriptionRef.
13Speed Agree 2
14User-Set Speed Agree 2
15Frequency Detection 3
16Frequency Detection 4
17Torque Detection 1 (N.C.)
18Torque Detection 2 (N.
O.)
19Torque Detection 2 (N.C.)
1ADuring reverse
1BDuring Baseblock (N.C.)
1CMotor 2 Selected
1EExecuting Auto-Restart
1FMotor Overload Alarm
20Drive Overheat Pre-
(oL1)
Alarm (oH)
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed AgreeDetection Width(+/-)].
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of “frequency reference ± L4-04”.
OFF : The output frequency is not in the range of “frequency reference ± L4-04”.
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detection Level(+/-)] ± L4-04[Speed Agree Detection Width(+/-)] and in the range of the frequency reference ± L4-04.
Note:
The detection level set with L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is in the range of “L4-03 ± L4-04” and the range of frequency reference ± L4-04.
OFF : The output frequency is not in the range of “L4-03 ± L4-04” nor the range of frequency reference ± L4-04.
The terminal deactivates when the output frequency is higher than the value of “L4-03 [Speed Agree Detection Level(+/-)] + L4-04 [Speed Agree Detection Width(+/-)]”. After the terminal deactivates, the terminal stays deactivated until
the output frequency is at the value of L4-03.
Note:
The detection level set with L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is less than the value of L4-03 or does not exceed the value of L4-03 + L4-04.
OFF : The output frequency is higher than the value of L4-03 + L4-04.
The terminal activates when the output frequency is higher than the value of L4-03 [Speed Agree Detection Level
(+/-)]. After the terminal activates, the terminal stays activated until the output frequency is at the value of L4-03 - L4-
04.
Note:
The detection level set with L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is higher than the value of L4-03.
OFF : The output frequency is less than the value of “L4-03 - L4-04,” or it does not exceed the value of L4-03.
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque is more than the torque value set with L6-02 [Torque Detection Level 1], or the level
is less than the torque value set with L6-02 [Torque Detection Level 1] for longer than the time set with L6-03 [TorqueDetection Time 1].
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque is more than the torque value set with L6-05 [Torque Detection Level 2], or the level is
less than the torque value set with L6-05 [Torque Detection Level 2] for longer than the time set with L6-06 [TorqueDetection Time 2].
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque is more than the torque value set with L6-05 [Torque Detection Level 2], or the level
is less than the torque value set with L6-05 [Torque Detection Level 2] for longer than the time set with L6-06 [TorqueDetection Time 2].
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
The terminal activates when motor 2 is selected.
ON : Motor 2 Selection
OFF : Motor 1 Selection
The terminal activates when the Auto Restart function is trying to restart after a fault.
The terminal activates when the electronic thermal protection value of the motor overload protective function is a
minimum of 90% of the detection level.
The terminal activates when the drive heatsink temperature is at the level set with L8-02 [Overheat Alarm Level].
323
323
324
324
325
325
325
325
326
326
326
326
326
58YASKAWA TOEPYAIGA5002A GA500 Programming
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
Setting ValueFunctionDescriptionRef.
21Safe Torque OFF
22Mechanical Weakening
Detection
2FMaintenance Notification
30During Torque Limit
37During Frequency Output
38Drive Enabled
39Watt Hour Pulse Output
3CLOCAL Control Selected
3DDuring Speed Search
3EPID Feedback Low
3FPID Feedback High
4ADuring KEB Ride-Thru
4BDuring Short Circuit
Braking
4CDuring Fast Stop
4DoH Pre-Alarm Time Limit
4EBraking Transistor Fault
4FBraking Resistor
61Pole Position Detection
62Modbus Reg 1 Status
(rr)
Overheat (rH)
Complete
Satisfied
The terminal activates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly and
when terminals H1-HC and H2-HC are OFF (Open).
ON : Safety stop state
OFF : Safety circuit fault or RUN/READY
The terminal activates when the drive detects mechanical weakening.
The terminal activates when drive components are at their estimated maintenance period.
Tells the user about the maintenance period for these items:
• IGBT
• Cooling fan
• Capacitor
• Soft charge bypass relay
The terminal activates when the torque reference is the torque limit set with L7 parameters or H3-02 or H3-10 [MFAI
Function Selection].
The terminal activates when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
This terminal activates when the H1-xx = 6A [Drive Enable] terminal activates.
Outputs the pulse that shows the watt hours.
The terminal activates when the Run command source or frequency reference source is LOCAL.
ON : LOCAL
OFF : REMOTE
The terminal activates when the drive is doing speed search.
The terminal activates when the drive detects FbL [PID Feedback Loss].
The terminal activates when the drive detects FbH [Excessive PID Feedback].
The activates during KEB Ride-Thru.
The terminal activates during Short Circuit Braking.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
The terminal activates when the fast stop is in operation.
The terminal activates when L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)] and oH[Heatsink Overheat] does not clear after the drive decreases the frequency for 10 cycles.
The terminal activates when the internal braking transistor overheats and the drive detects an rr [Dynamic BrakingTransistor Fault] fault.
The terminal activates when the braking resistor overheats and the drive detects an rH [Braking Resistor Overheat]
fault.
The terminal activates when drive receives a Run command and the drive detects the motor magnetic pole position of
the PM motor.
The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register
address set with H2-07 [Modbus Register 1 Address Select] activates.
327
327
327
327
327
328
328
328
328
329
329
329
329
329
329
330
330
330
330
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming59
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
Setting ValueFunctionDescriptionRef.
63Modbus Reg 2 Status
66Comparator1
67Comparator2
69External Power 24V
6AData Logger Error
90 - 92DWEZ Digital Output 1
100 - 192Inverse output of 0 to 92
Satisfied
Supply
to 3
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register
address set with H2-09 [Modbus Register 2 Address Select] activates.
The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the values
of H2-21 [Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24 [Comparator1 On-Delay Time].
The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of the
values of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-30[Comparator 2 On-Delay Time].
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
The terminal activates when the drive detects LoG [Com Error / Abnormal SD card].
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function
to inversely output.
330
330
331
331
331
331
331
◆ H3: Analog Inputs
No.
(Hex.)
H3-01
(0410)
H3-02
(0434)
H3-03
(0411)
RUN
H3-04
(0412)
RUN
H3-09
(0417)
H3-10
(0418)
H3-11
(0419)
RUN
H3-12
(041A)
RUN
H3-13
(041B)
NameDescription
Terminal A1 Signal Level
Select
Terminal A1 Function
Selection
Terminal A1 Gain Setting
Terminal A1 Bias Setting
Terminal A2 Signal Level
Select
Terminal A2 Function
Selection
Terminal A2 Gain Setting
Terminal A2 Bias Setting
Analog Input FilterTime
Constant
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
4 : -10 to +10V (Bipolar Reference)
Sets the function for MFAI terminal A1.
Sets the gain of the analog signal input to MFAI terminal A1.
Sets the bias of the analog signal input to MFAI terminal A1.
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
3 : 0 to 20 mA
4 : -10 to +10V (Bipolar Reference)
Sets the function for MFAI terminal A2.
Sets the gain of the analog signal input to MFAI terminal A2.
Sets the bias of the analog signal input to MFAI terminal A2.
Sets the time constant for primary delay filters on MFAI terminals.
Default
(Range)
0
(0, 4)
0
(0 - 32)
100.0%
(-999.9 - +999.9%)
0.0%
(-999.9 - +999.9%)
2
(0, 2 - 4)
0
(0 - 32)
100.0%
(-999.9 - +999.9%)
0.0%
(-999.9 - +999.9%)
0.03 s
(0.00 - 2.00 s)
Ref.
334
334
334
334
335
335
335
335
336
60YASKAWA TOEPYAIGA5002A GA500 Programming
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
H3-14
(041C)
NameDescription
Analog Input Terminal
Enable Sel
Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select = AnalogTerminal Enable Selection] is ON.
Default
(Range)
7
(1, 2, 7)
1 : Terminal A1 only
2 : Terminal A2 only
7 : Terminals A1 and A2
H3-16
(02F0)
H3-17
(02F1)
H3-40
(0B5C)
H3-41
(0B5F)
H3-42
(0B62)
H3-43
(117F)
Terminal A1 Offset
Terminal A2 Offset
Mbus Reg 15C1h Input
Function
Mbus Reg 15C2h Input
Function
Mbus Reg 15C3h Input
Function
Mbus Reg Inputs
FilterTime Const
Sets the offset level for analog signals input to terminal A1. Usually it is not necessary to
change this setting.
Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to
change this setting.
Sets the MEMOBUS AI1 function.
Sets the MEMOBUS AI2 function.
Sets the MEMOBUS AI3 function.
Sets the time constant to apply a primary delay filter to the MEMOBUS analog input
register values.
0
(-500 - +500)
0
(-500 - +500)
F
(4 - 2F)
F
(4 - 2F)
F
(4 - 2F)
0.00 s
(0.00 - 2.00 s)
■ H3-xx: MFAI Setting Values
Setting ValueFunctionDescriptionRef.
0Frequency Reference
1Frequency Gain
2Auxiliary Frequency
Reference 1
3Auxiliary Frequency
Reference 2
4Output Voltage Bias
5Accel/Decel Time Gain
6DC Injection Braking
Current
7Torque Detection Level
8Stall Prevent Level during
Run
The input value from the MFAI terminal set with this function becomes the master frequency reference.
The drive multiplies the analog frequency reference with the input value from the MFAI set with this function.
Sets Reference 2 through multi-step speed reference to enable the command reference (Auxiliary Frequency Reference
1) from the analog input terminal set here. This value is a percentage where the Maximum Output Frequency setting is
a setting value of 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.
Set this parameter to input a bias signal to amplify the output voltage.
Enters a signal to adjust the gain used for C1-01 to C1-08 [Acceleration/Deceleration Times 1 to 4] and C1-09 [FastStop Time] when the full scale analog signal (10 V or 20 mA) is 100%.
Enters a signal to adjust the current level used for DC Injection Braking when the drive rated output current is 100%.
Enters a signal to adjust the overtorque/undertorque detection level.
Note:
Use this function with L6-01 [Torque Detection Selection 1]. This parameter functions as an alternative to L6-02
[Torque Detection Level 1].
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
Ref.
336
336
336
336
337
337
337
337
337
338
338
338
338
339
339
339
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming61
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
Setting ValueFunctionDescriptionRef.
9Output Frequency Lower
Limit
BPID Feedback
CPID Setpoint
DFrequency Bias
EMotor Temperature (PTC
Input)
FNot Used
10Forward Torque Limit
11Reverse Torque Limit
12Regenerative Torque
13Torque Reference /
Limit
Torque Limit
14Torque Compensation
15General Torque Limit
16Differential PID
Feedback
1FNot Used
30DWEZ Analog Input 1
31DWEZ Analog Input 2
Enters a signal to adjust the output frequency lower limit level as a percentage of the maximum output frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.
Uses the motor Positive Temperature Coefficient (PTC) thermistor to prevent heat damage to the motor as a percentage
of the current value when the 10 V analog signal is input.
Use this setting for unused terminals or to use terminals in through mode.
Enters the forward torque limit if the motor rated torque is 100%.
Enters the load torque limit if the motor rated torque is 100%.
Enters the regenerative torque limit if the motor rated torque is 100%.
Enters the torque reference if the motor rated torque is 100%. This setting is the torque limit for speed control.
Enters the torque compensation value if the motor rated torque is 100%.
Enters the torque limit that is the same for all quadrants for forward, reverse, and regenerative operation if the motor
rated torque is 100%.
Enters the PID differential feedback value if the full scale analog signal (10 V or 20 mA) is 100%.
Use this setting for unused terminals or to use terminals in through mode.
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
339
340
340
340
340
340
340
342
342
342
342
342
342
342
343
343
62YASKAWA TOEPYAIGA5002A GA500 Programming
◆ H4: Analog Outputs
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.10 H: Terminal Functions
No.
(Hex.)
H4-01
(041D)
H4-02
(041E)
RUN
H4-03
(041F)
RUN
H4-07
(0423)
NameDescription
Terminal AM Analog
Output Select
Terminal AM Analog
Output Gain
Terminal AM Analog
Output Bias
Terminal AM Signal
Level Select
Sets the monitoring number to be output from the MFAO terminal AM.
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-01 = 102 to monitor U1-02[Output Frequency].
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
Sets the analog signal output level from the terminal AM at 10 V or 20 mA as 100% when
an output for monitoring items is 100%.
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AM terminal at 10 V or 20 mA as 0%.
Sets the MFAO terminal AM output signal level.
Note:
Make sure that you set jumper S5 on the control circuit terminal board when you
change these parameters.
0 : 0-10V
2 : 4 to 20 mA
H4-20
(0B53)
Analog Power Monitor
100% Level
Sets the level at 10 V when U1-08 [Output Power] is set for analog output.
◆ H5: Modbus Communication
No.
(Hex.)
H5-01
(0425)
H5-02
(0426)
H5-03
(0427)
H5-04
(0428)
NameDescription
Drive Node Address
Sets the communication slave address for drives.
Note:
• Re-energize the drive or set H5-10 = 1 [Modbus Register 0025H Unit Sel= 1 V units]
after you change the parameter setting.
• Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
Communication Speed
Selection
Sets the communications speed for MEMOBUS/Modbus communications.
Note:
Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload
Now] after you change the parameter setting.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
Communication Parity
Selection
Sets the communications parity used for MEMOBUS/Modbus communications.
Note:
Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload
Now] after you change the parameter setting.
0 : No parity
1 : Even parity
2 : Odd parity
Communication Error
Stop Method
Sets the motor Stopping Method when the drive detects CE [MEMOBUS/ModbusCommunication Err] issues.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
Default
(Range)
102
(000 - 999)
100.0%
(-999.9 - +999.9%)
0.0%
(-999.9 - +999.9%)
0
(0, 2)
0.00 kW
(0.00 - 650.00 kW)
Default
(Range)
1FH
(0 - FFH)
3
(0 - 8)
0
(0 - 2)
3
(0 - 3)
Ref.
344
344
344
345
345
Ref.
345
345
346
346
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming63
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
H5-05
(0429)
H5-06
(042A)
H5-09
(0435)
H5-10
(0436)
H5-11
(043C)
RUN
H5-12
(043D)
H5-17
(11A1)
Expert
H5-18
(11A2)
H5-20
(0B57)
H5-22
(11CF)
H5-25
(1589)
RUN
H5-26
(158A)
RUN
H5-27
(158B)
RUN
H5-28
(158C)
RUN
NameDescription
Comm Fault Detection
Selection
Sets the function that detects CE [Modbus Communication Error] issues during
MEMOBUS/Modbus communications.
0 : Disabled
1 : Enabled
Drive Transmit Wait
Time
Sets the time to wait to send a response message after the drive receives a command
message from the master.
Note:
Restart the drive after changing the parameter setting.
CE Detection Time
Sets the detection time for CE [Modbus Communication Error] issues when
communication stops.
Modbus Register 0025H
Unit Sel
Sets the unit of measure used for the MEMOBUS/Modbus communications monitor
register 0025H (output voltage reference monitor).
0 : 0.1 V units
1 : 1 V units
Comm ENTER
Command Mode
Sets the function to make the Enter command necessary to change parameters through
MEMOBUS/Modbus communications.
0 : ENTER Command Required
1 : ENTER Command Not Required
Run Command Method
Selection
Sets the input method for the Run command when b1-02 = 2 [Run Command Selection 1 =
Sets operation when the EEPROM write command is sent without EEPROM write
available. Usually it is not necessary to change this setting.
0 : Ignore Command(No ROM/RAM Write)
1 : Write to RAM Only
Motor Speed Filter over
Comms
Communication
Parameters Reload
Sets the filter time constant used when monitoring motor speed during MEMOBUS/
Modbus communications or with a communication option.
Sets the function to immediately enable updated MEMOBUS/Modbus communications
parameters.
0 : Reload at Next Power Cycle
1 : Reload Now
Speed Search from
MODBUS
Enables the MEMOBUS/Modbus communication register Speed Search function (bit0 of
15DFH).
0 : Disabled
1 : Enabled
Function 5A Register 1
Selection
Function 5A Register 2
Selection
Function 5A Register 3
Selection
Function 5A Register 4
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
Default
(Range)
1
(0, 1)
5 ms
(0 - 65 ms)
2.0 s
(0.0 - 25.0 s)
0
(0, 1)
1
(0, 1)
0
(0, 1)
0
(0, 1)
0 ms
(0 - 100 ms)
0
(0, 1)
0
(0, 1)
0044H (U1-05)
(0000H - FFFFH)
0045H (U1-06)
(0000H - FFFFH)
0042H (U1-03)
(0000H - FFFFH)
0049H (U1-10)
(0000H - FFFFH)
Ref.
346
347
347
347
347
347
348
348
348
348
349
349
349
349
64YASKAWA TOEPYAIGA5002A GA500 Programming
◆ H6: Pulse Train Input/Output
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.10 H: Terminal Functions
No.
(Hex.)
H6-01
(042C)
H6-02
(042D)
RUN
H6-03
(042E)
RUN
H6-04
(042F)
RUN
H6-05
(0430)
RUN
H6-06
(0431)
RUN
H6-07
(0432)
RUN
H6-08
(043F)
NameDescription
Terminal RP Pulse Train
Function
Sets the function for pulse train input terminal RP.
0 : Frequency Reference
1 : PID Feedback Value
2 : PID Setpoint
3 : Speed Feedback (V/F Control)
Terminal RP Frequency
Scaling
Terminal RP Function
Gain
Terminal RP Function
Bias
Sets the frequency of the pulse train input signal used when the item selected with H6-01[Terminal RP Pulse Train Function] is input at 100%.
Sets the gain used when the function in H6-01 [Terminal RP Pulse Train Function] is input
to terminal RP.
Sets the bias used when the function in H6-01 [Terminal RP Pulse Train Function] is input
to terminal RP. Sets a value at the time when the pulse train is 0 Hz.
Terminal RP Filter Time
Sets the time constant for the pulse train input primary delay filters.
Terminal MP Monitor
Selection
Terminal MP Frequency
Scaling
Terminal RP Minimum
Frequency
Sets a function for pulse train monitor output terminal MP. Sets the “x-xx” part of the Ux-xx
monitor.
Sets the frequency of the pulse train output signal used when the monitor set with H6-06[Terminal MP Monitor Selection] is 100%.
Sets the minimum frequency of the pulse train signal that terminal RP can detect.
Sets the function to enable and disable the virtual I/O function. Set this parameter to 1 to
operate the virtual I/O function.
0 : Disabled
1 : Enabled
Virtual Multi-Function
Input 1
Sets the function that enters the virtual input set in H7-10 [Virtual Multi-Function Output1].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
Virtual Multi-Function
Input 2
Sets the function that enters the virtual input set in H7-12 [Virtual Multi-Function Output2].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
Virtual Multi-Function
Input 3
Sets the function that enters the virtual input set in H7-14 [Virtual Multi-Function Output3].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
Virtual Multi-Function
Input 4
Sets the function that enters the virtual input set in H7-16 [Virtual Multi-Function Output4].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
Default
(Range)
0
(0, 1)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
Ref.
353
353
353
354
354
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming65
1.10 H: Terminal Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
H7-10
(11A4)
Expert
H7-11
(11A5)
Expert
H7-12
(11A6)
Expert
H7-13
(11A7)
Expert
H7-14
(11A8)
Expert
H7-15
(11A9)
Expert
H7-16
(11AA)
Expert
H7-17
(11AB)
Expert
H7-30
(1177)
Expert
H7-31
(1178)
RUN
Expert
H7-32
(1179)
RUN
Expert
H7-40
(1163)
H7-41
(1164)
H7-42
(1165)
NameDescription
Virtual Multi-Function
Output 1
Virtual Output 1 Delay
Time
Virtual Multi-Function
Output 2
Virtual Output 2 Delay
Time
Virtual Multi-Function
Output 3
Virtual Output 3 Delay
Time
Virtual Multi-Function
Output 4
Virtual Output 4 Delay
Time
Virtual Analog Input
Selection
Virtual Analog Input
Gain
Sets the function for virtual digital output 1.
Sets the minimum ON time for virtual digital output 1.
Sets the function for virtual digital output 2.
Sets the minimum ON time for virtual digital output 2.
Sets the function for virtual digital output 3.
Sets the minimum ON time for virtual digital output 3.
Sets the function for virtual digital output 4.
Sets the minimum ON time for virtual digital output 4.
Sets the virtual analog input function.
Sets the virtual analog input gain.
Virtual Analog Input Bias
Sets the virtual analog input bias.
Virtual Analog Out
Signal Select
Sets the signal level of the virtual analog output.
0 : 0 to 100% (Absolute Value)
1 : -100 to 100%
2 : 0 to 100% (Lower Limit at 0)
Virtual Analog Output
Function
Virtual Analog Output
FilterTime
Sets the monitor to be output from the virtual analog output.
Set the x-xx part of the Ux-xx [Monitor]. For example, set H7-41 = 102 to monitor U1-02[Output Frequency].
Sets the time constant for a primary filter of the virtual analog output.
Default
(Range)
F
(0 - 1A7)
0.1 s
(0.0 - 25.0 s)
F
(0 - 1A7)
0.1 s
(0.0 - 25.0 s)
F
(0 - 1A7)
0.1 s
(0.0 - 25.0 s)
F
(0 - 1A7)
0.1 s
(0.0 - 25.0 s)
F
(0 - 32)
100.0%
(-999.9 - 999.9%)
0.0%
(-999.9 - 999.9%)
0
(0 - 2)
102
(0 - 999)
0.00 s
(0.00 - 2.00 s)
Ref.
354
354
354
354
354
355
355
355
355
355
355
355
356
356
66YASKAWA TOEPYAIGA5002A GA500 Programming
1.11L: Protection Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ L1: Motor Protection
1.11 L: Protection Functions
No.
(Hex.)
L1-01
(0480)
L1-02
(0481)
L1-03
(0482)
L1-04
(0483)
L1-05
(0484)
L1-08
(1103)
L1-09
(1104)
L1-13
(046D)
L1-22
(0768)
RUN
L1-23
(0769)
RUN
NameDescription
Motor Overload (oL1)
Protection
Sets the motor overload protection with electronic thermal protectors.
0 : No
1 : Variable Torque
2 : Constant Torque 10:1 Speed Range
3 : Constant Torque 100:1 SpeedRange
4 : PM Variable Torque
5 : PM Constant Torque
6 : Variable Torque (50Hz)
Note:
When only one motor is connected to a drive, set L1-01 = 1 to 6 [Enabled]. External
thermal relays are not necessary in these conditions.
Motor Overload
Protection Time
Motor Thermistor oH
Alarm Select
Sets the operation time for the electronic thermal protector of the drive to prevent damage
to the motor. Usually it is not necessary to change this setting.
Sets drive operation when the PTC input signal entered into the drive is at the oH3 [MotorOverheat Alarm] detection level.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop
3 : Alarm Only
Motor Thermistor oH
Fault Select
Sets the drive operation when the PTC input signal to the drive is at the oH4 [MotorOverheat Fault (PTC Input)] detection level.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop
Motor Thermistor Filter
Time
Sets the primary delay time constant for the PTC input signal entered to the drive. This
parameter prevents accidental motor overheat faults.
oL1 Current Level
Sets the reference current for the motor 1 thermal overload detection. When the current
level > 0.0 A, you cannot set this value < 10% of drive rated current.
oL1 Current Level for
Motor 2
Motor Overload Memory
Selection
Sets the reference current for the motor 2 thermal overload detection. When the current
level > 0.0 A, you cannot set this value < 10% of drive rated current.
Sets the function that keeps the current electronic thermal protector value when the drive
stops receiving power.
0 : Disabled
1 : Enabled
Leakage Current Filter
Time1
Sets the leakage current detection reduction filter time constant during constant speed run.
Note:
You can set this parameter when C6-02 = B [Carrier Frequency Selection = Leakage
Current Detection Reduction Rate PWM].
Leakage Current Filter
Time2
Sets the leakage current detection reduction filter time constant during acceleration/
deceleration.
Note:
• You can set this parameter when C6-02 = B [Carrier Frequency Selection = Leakage
Current Detection Reduction Rate PWM].
• When the setting value increases, the current monitor also starts up slowly. Examine
the relevant sequence for problems.
Default
(Range)
Determined by A1-02
(0 - 6)
1.0 min
(0.1 - 5.0 min)
3
(0 - 3)
1
(0 - 2)
0.20 s
(0.00 - 10.00 s)
0.0 A
(0.0 A or 10% to 150% of
the drive rated current)
0.0 A
(0.0 A or 10 to150% of
the drive rated current)
1
(0, 1)
Determined by C6-02
(0.0 - 60.0 s)
Determined by C6-02
(0.0 - 60.0 s)
Ref.
358
361
362
362
362
362
363
363
363
363
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming67
1.11 L: Protection Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ L2: Power Loss Ride Through
No.
(Hex.)
L2-01
(0485)
L2-02
(0486)
L2-03
(0487)
L2-04
(0488)
L2-05
(0489)
L2-06
(048A)
Expert
L2-07
(048B)
Expert
L2-08
(048C)
Expert
L2-09
(048D)
Expert
L2-10
(048E)
Expert
L2-11
(0461)
Expert
L2-29
(0475)
Expert
NameDescription
Power Loss Ride Through
Select
Sets the drive operation after a momentary power loss.
0 : Disabled
1 : Enabled for L2-02 Time
2 : Enabled while CPU Power Active
3 : Kinetic Energy Backup: L2-02
4 : Kinetic Energy Backup: CPU Power
5 : Kinetic Energy Backup: DecelStop
Power Loss Ride Through
Time
Minimum Baseblock
Time
Powerloss V/f Recovery
Ramp Time
Undervoltage Detection
Lvl (Uv1)
Sets the maximum time that the drive will wait until trying to restart after power loss.
Sets the minimum time to continue the drive output block (baseblock) after a baseblock.
Sets the time for the drive output voltage to go back to correct voltage after completing
speed searches.
Sets the voltage at which a Uv1 [DC Bus Undervoltage] fault is triggered or at which the
KEB function is activated. Usually it is not necessary to change this setting.
NOTICE: Damage to Equipment. When you set this parameter
to a value lower than the default, you must install an AC reactor
on the input side of the power supply. If you do not install an AC
reactor, it will cause damage to the drive circuitry.
Kinetic Energy Backup
Decel Time
Kinetic Energy Backup
Accel Time
Frequency Gain at KEB
Start
KEB Minimum
Frequency Level
Minimum KEB Time
KEB DC Bus Voltage
Setpoint
Kinetic Energy Backup
Method
Sets the deceleration time during KEB operation used to decrease the maximum output
frequency to 0.
Note:
When L2-29 = 1, 2, or 3 [Kinetic Energy Backup Method = Single Drive KEB RideThru 2, System KEB Ride-Thru 1, or System KEB Ride-Thru 2] and you do KEB Auto-
Tuning, the drive will automatically set this value.
Sets the acceleration time to return the frequency to the frequency reference before a power
loss after canceling KEB operation.
Sets the quantity of output frequency reduction used when KEB operation starts as a
percentage of the motor rated slip before starting KEB operation.
Sets the quantity of output frequency reduction used as a percentage of E2-02 [MotorRated Slip] when KEB operation starts.
Sets the minimum length of time to operate the KEB after the drive detects a momentary
power loss.
Sets the target value that controls the DC bus voltage to a constant level in Single Drive
KEB Ride-Thru 2. Sets the DC bus voltage level that completes the KEB operation for all
other KEB methods.
Sets the KEB function operation mode.
0 : Single Drive KEB Ride-Thru 1
1 : Single Drive KEB Ride-Thru 2
2 : System KEB Ride-Thru 1
3 : System KEB Ride-Thru 2
Default
(Range)
0
(0 - 5)
Determined by o2-04,
C6-01
(0.0 - 25.5 s)
Determined by o2-04,
C6-01
(0.1 - 5.0 s)
Determined by o2-04,
C6-01
(0.0 - 5.0 s)
Determined by o2-04 and
E1-01
(200 V Class: 150 - 210
V, 400 V Class: 300 - 420
V)
0.0 s
(0.0 - 6000.0 s)
0.0 s
(0.0 - 6000.0 s)
100%
(0 - 300%)
20%
(0 - 100%)
50 ms
(0 - 25500 ms)
Determined by E1-01
(Determined by E1-01)
0
(0 - 3)
Ref.
369
370
370
370
371
371
371
372
372
372
373
373
68YASKAWA TOEPYAIGA5002A GA500 Programming
1.11 L: Protection Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
L2-30
(045E)
NameDescription
KEB Zero Speed
Operation
Expert
L2-31
(045D)
KEB Start Voltage Offset
Level
Expert
◆ L3: Stall Prevention
No.
(Hex.)
L3-01
(048F)
L3-02
(0490)
L3-03
(0491)
L3-04
(0492)
L3-05
(0493)
NameDescription
Stall Prevention during
Accel
Stall Prevent Level during
Accel
Stall Prevent Limit during
Accel
Stall Prevention during
Decel
Stall Prevention during
RUN
Sets the operation when the output frequency decreases below the zero level (DC braking
injection starting frequency) during KEB deceleration when L2-01 = 3 to 5 [Power Loss
Ride Through Select = Kinetic Energy Backup: L2-02, Kinetic Energy Backup: CPU
Power, or Kinetic Energy Backup: DecelStop].
0 : Baseblock
1 : DC/SC Braking
Sets the KEB start voltage offset.
Sets the method of the Stall Prevention During Acceleration.
0 : Disabled
1 : Enabled
2 : Intelligent (Ignore Decel Ramp)
3 : Current Limit Acceleration
Sets the output current level at which the Stall Prevention function operates during
acceleration where the drive rated output current is 100%.
Note:
The upper limit to the setting range changes when the setting for C6-01 [Normal /
Heavy Duty Selection] changes.
• 150% when C6-01 = 0 [Heavy Duty Rating]
• 120% when C6-01 = 1 [Normal Duty Rating]
Sets the lower limit for the stall prevention level used in the constant output range as a
percentage of the drive rated output current.
Sets the method that the drive will use to prevent overvoltage faults when decelerating.
Note:
1. To connect a dynamic braking option (braking resistor or braking resistor unit) to
the drive, set this parameter to 0 or 3. Parameter settings 1, 2, 4, 5, and 7 will
enable Stall Prevention function during deceleration, and the dynamic braking
option will not function.
2. The setting range changes when the A1-02 [Control Method Selection] value
changes:
• When A1-02 = 5 [OLV/PM], the setting range is 0 to 2.
• When A1-02 = 6 or 8 [AOLV/PM or EZOLV], the setting range is 0 or 1.
0 : No
1 : General Purpose
2 : Intelligent (Ignore Decel Ramp)
3 : General Purpose w/ DB resistor
4 : Overexcitation/High Flux
5 : Overexcitation/High Flux 2
7 : Overexcitation/High Flux 3
Sets the function to enable and disable Stall Prevention During Run.
Note:
• An output frequency less than 6 Hz disables Stall Prevention during Run. The setting
values of L3-05 and L3-06 [Stall Prevent Level during Run] do not have an effect.
• The setting range changes when the A1-02 [Control Method Selection] value
changes:
Sets the output current level at which the Stall Prevention function is enabled during run
when the drive rated output current is 100%.
Note:
• This parameter is applicable when L3-05 = 1, 2 [Stall Prevention during RUN =
Deceleration Time 1 (C1-02), Deceleration Time 2 (C1-04)].
• The upper limit to the setting range changes when the setting for C6-01 [Normal /
Heavy Duty Selection] changes.
–150% when C6-01 = 0 [Heavy Duty Rating]
–120% when C6-01 = 1 [Normal Duty Rating]
Overvoltage Suppression
Select
Sets the overvoltage suppression function.
0 : Disabled
1 : Enabled
DC Bus Regulation Level
Sets the target value for the DC bus voltage when the overvoltage suppression function and
the Decel Stall Prevention function (Intelligent Stall Prevention) are active.
DC Bus Voltage
Adjustment Gain
OVSuppression Accel/
Decel P Gain
PM Stall Prevention
Decel Time
Stall P Reduction at
Constant HP
Sets the proportional gain used to control the DC bus voltage.
Sets the proportional gain to calculate acceleration and deceleration rates.
Sets the momentary deceleration time that the drive will use when it tries to accelerate a
PM motor and detected motor stalls. This function is applicable when L3-01 = 1 [StallPrevent Select duringAccel = General Purpose].
Sets the function to automatically decrease the Stall Prevention Level during Run for
constant output ranges.
0 : Use L3-06 for Entire Speed Range
1 : Automatic Reduction @ CHP Region
Motor Accel Time @
Rated Torque
Sets the motor acceleration time to reach the maximum frequency at the motor rated torque
for stopped single-drive motors.
Load Inertia Ratio
Sets the ratio between motor inertia and machine inertia.
Additional DC Bus
Capacitors
Stall Prevention
Detection Time
Sets the capacity for external main circuit capacitors. Usually it is not necessary to change
this setting. Sets this parameter when you use the KEB Ride-Thru function.
Sets a delay time between reaching the Stall Prevention level and starting the Stall
Prevention function.
Torque Limit Delay Time
Sets the filter time constant that returns the torque limit to its initial value when KEB
operation operates in Single Drive KEB Ride-Thru mode.
Speed Agree Width for
Auto Decel
Current Suppression
Gain@Accel
Current Limit P Gain @
Accel
Current Limit I Time @
Accel
Sets the width for speed agreement when L3-04 = 2 [Decel Stall Prevention Selection =Automatic Decel Reduction]. Usually it is not necessary to change this setting.
Sets the gain to suppress current and motor speed hunting during operation when L3-01 =3 [Stall Prevention during Accel = Current Limit Method]. Usually it is not necessary to
change this setting.
Suppresses current hunting during acceleration. Usually it is not necessary to change this
setting.
Suppresses current hunting and overshooting that occurs when the drive stalls during
acceleration. Usually it is not necessary to change this setting.
Default
(Range)
Determined by C6-01
(5 - 150%)
0
(0, 1)
200 V Class: 375 V, 400
V: 750 V
(200 V Class: 150 to 400
V, 400 V Class: 300 to
800 V)
Determined by A1-02
(0.00 - 5.00)
Determined by A1-02
(0.10 - 10.00)
0.0 s
(0.0 - 6000.0 s)
0
(0, 1)
Determined by o2-04,
C6-01, E2-11, and E5-01
(0.001 - 10.000 s)
1.0
(0.1 - 1000.0)
0 μF
(0 to 65000 μF)
60 ms
(0 - 5000 ms)
Determined by A1-02
(0.000 - 1.000 s)
0.00 Hz
(0.00 - 1.00 Hz)
Determined by A1-02
(0.0 - 100.0)
5 ms
(0 - 100 ms)
10.0
(0.0 - 100.0)
Ref.
379
380
380
380
381
381
381
381
382
382
382
382
383
383
383
383
70YASKAWA TOEPYAIGA5002A GA500 Programming
1.11 L: Protection Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
L3-39
(11D3)
L3-40
(11D4)
NameDescription
Current Limit Filter Time
@Accel
Current Limit S-Curve @
Acc/Dec
Sets the time constant to adjust the acceleration rate when L3-01 = 3 [Stall Preventionduring Accel = Current Limit Method]. Usually it is not necessary to change this setting.
Sets the function to enable and disable the best S-curve characteristic used for currentlimited acceleration.
0 : Disabled
1 : Enabled
◆ L4: Speed Detection
No.
(Hex.)
L4-01
(0499)
L4-02
(049A)
L4-03
(049B)
L4-04
(049C)
L4-05
(049D)
L4-06
(04C2)
L4-07
(0470)
L4-08
(047F)
NameDescription
Speed Agree Detection
Level
Speed Agree Detection
Width
Speed Agree Detection
Level(+/-)
Speed Agree Detection
Width(+/-)
Fref Loss Detection
Selection
Sets the level to detect speed agree or motor speed.
Sets the level to detect speed agree or motor speed when H2-01 to H2-03 = 2, 3, 4, 5
[MFDO Function Selection = Speed Agree 1, User-set Speed Agree 1, Frequency
Detection 1, Frequency Detection 2].
Sets the width to detect speed agree or motor speed.
Sets the width to detect speed agree or motor speed when H2-01 to H2-03 = 2, 3, 4, 5
[MFDO Function Selection = Speed Agree 1, User-set Speed Agree 1, Frequency
Detection 1, Frequency Detection 2].
Sets the level to detect speed agree or motor speed.
Sets the level to detect speed agree or motor speed when H2-01 to H2-03 = 13, 14, 15, 16
[MFDO Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency
Detection 3, Frequency Detection 4].
Sets the width to detect speed agree or motor speed.
Sets the width to detect speed agree or motor speed when H2-01 to H2-03 = 13, 14, 15, 16
[MFDO Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency
Detection 3, Frequency Detection 4].
Sets the operation when the drive detects a loss of frequency reference.
0 : Stop
1 : Run at (L4-06 x Last Reference)
Frequency Reference
@Loss of Ref
Speed Agree Detection
Selection
Sets the frequency reference as a percentage to continue drive operation after it detects a
frequency reference loss. The value is a percentage of the frequency reference before the
drive detected the loss.
Sets the condition that activates speed detection.
0 : No Detection during Baseblock
1 : Detection Always Enabled
Speed Agree Source
Selection
Sets the drive to use the soft starter output frequency or the motor speed (estimation value)
for speed detection.
0 : Softstarter Output (Reference)
1 : Motor Speed (Actual Speed)
◆ L5: Fault Restart
Default
(Range)
100.0 ms
(1.0 - 1000.0 ms)
0
(0, 1)
Default
(Range)
Determined by A1-02
(Determined by A1-02)
Determined by A1-02
(Determined by A1-02)
Determined by A1-02
(Determined by A1-02)
Determined by A1-02
(Determined by A1-02)
0
(0, 1)
80.0%
(0.0 - 100.0%)
0
(0, 1)
0
(0, 1)
Ref.
383
383
Ref.
384
384
384
384
384
385
385
385
Parameter List
1
No.
(Hex.)
L5-01
(049E)
L5-02
(049F)
NameDescription
Number of Auto-Restart
Attempts
Fault Contact at Restart
Select
Sets the number of times that the drive will try to restart.
Sets the function that sends signals to the MFDO terminal set for Fault [H2-xx = E] while
the drive is automatically restarting.
Default
(Range)
0
(0 - 10 times)
0
(0, 1)
Ref.
387
387
0 : Active Only when Not Restarting
1 : Always Active
YASKAWA TOEPYAIGA5002A GA500 Programming71
1.11 L: Protection Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
L5-04
(046C)
L5-05
(0467)
L5-07
(0B2A)
L5-08
(0B2B)
NameDescription
Interval Method Restart
Time
Sets the time interval between each Auto Restart attempt. This function is enabled when
L5-05 = 1 [Auto Restart Operation Selection = Use L5-04 Time].
Auto-Restart Method
Sets the count method for the Auto Restart operation.
0 : Continuous/Immediate Attempts
1 : Interval/Attempt after L5-04 sec
Fault Reset Enable Select
Grp1
Use these 4 digits to set the Auto Restart function for oL1 to oL4. From left to right, the
digits set oL1, oL2, oL3, and oL4, in order.
0000 : Disabled
0001 : Enabled (—/—/—/oL4)
0010 : Enabled (—/—/oL3/—)
0011 : Enabled (—/—/oL3/oL4)
0100 : Enabled (—/oL2/—/—)
0101 : Enabled (—/oL2/—/oL4)
0110 : Enabled (—/oL2/oL3/—)
0111 : Enabled (—/oL2/oL3/oL4)
1000 : Enabled (oL1/—/—/—)
1001 : Enabled (oL1/—/—/oL4)
1010 : Enabled (oL1/—/oL3/—)
1011 : Enabled (oL1/—/oL3/oL4)
1100 : Enabled (oL1/oL2/—/—)
1101 : Enabled (oL1/oL2/—/oL4)
1110 : Enabled (oL1/oL2/oL3/—)
1111 : Enabled (oL1/oL2/oL3/oL4)
Fault Reset Enable Select
Grp2
Use these 4 digits to set the Auto Restart function for Uv1, ov, oH1, and GF. From left to
right, the digits set Uv1, ov, oH1, and GF, in order.
0000 : Disabled
0001 : Enabled (—/–/—/GF)
0010 : Enabled (—/–/oH1/–)
0011 : Enabled (—/–/oH1/GF)
0100 : Enabled (—/ov/—/–)
0101 : Enabled (—/ov/—/GF)
0110 : Enabled (—/ov/oH1/–)
0111 : Enabled (—/ov/oH1/GF)
1000 : Enabled (Uv1/–/—/–)
1001 : Enabled (Uv1/–/—/GF)
1010 : Enabled (Uv1/–/oH1/–)
1011 : Enabled (Uv1/–/oH1/GF)
1100 : Enabled (Uv1/ov/—/–)
1101 : Enabled (Uv1/ov/—/GF)
1110 : Enabled (Uv1/ov/oH1/–)
1111 : Enabled (Uv1/ov/oH1/GF)
Default
(Range)
10.0 s
(0.5 - 600.0 s)
0
(0, 1)
1111
(0000 - 1111)
1111
(0000 - 1111)
Ref.
387
387
387
388
72YASKAWA TOEPYAIGA5002A GA500 Programming
◆ L6: Torque Detection
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.11 L: Protection Functions
No.
(Hex.)
L6-01
(04A1)
L6-02
(04A2)
L6-03
(04A3)
L6-04
(04A4)
L6-05
(04A5)
L6-06
(04A6)
L6-07
(04E5)
L6-08
(0468)
L6-09
(0469)
NameDescription
Torque Detection
Selection 1
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
Torque Detection Level 1
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated
output current = 100% value. In vector control, motor rated torque = 100% value.
Torque Detection Time 1
Sets the detection time for Overtorque/Undertorque Detection 1.
Torque Detection
Selection 2
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
Torque Detection Level 2
Sets the detection level for Overtorque/Undertorque Detection 2. In V/f control, drive rated
output current = 100% value. In vector control, motor rated torque = 100% value.
Torque Detection Time 2
Sets the detection time for Overtorque/Undertorque Detection 2.
Torque Detection Filter
Time
Mechanical Fatigue
Detect Select
Sets the time constant for a primary filter to the torque reference or to the output current
used to detect overtorque/undertorque.
Sets the speed where the drive detects mechanical deterioration and how the drive operates
(operation status) after detection.
0 : Disabled
1 : oL5 @ Speed > L6-09 - Alarm
2 : oL5 @ |Speed| > L6-09 - Alarm
3 : oL5 @ Speed > L6-09 - Fault
4 : oL5 @ |Speed| > L6-09 - Fault
5 : UL5 @ Speed < L6-09 - Alarm
6 : UL5 @ |Speed| < L6-09 - Alarm
7 : UL5 @ Speed < L6-09 - Fault
8 : UL5 @ |Speed| < L6-09 - Fault
Mech Fatigue Detect
Speed Level
Sets the speed level where the drive will operate the mechanical deterioration detection
function, as a percentage of the Maximum Output Frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
Sets the time for mechanical deterioration detection.
Sets the time that the drive will start mechanical deterioration detection triggered by the
cumulative operation time of the drive.
Sets the torque limit value for forward motoring as a percentage, where motor rated torque
is the 100% value.
Sets the torque limit value for reversed motoring as a percentage, where motor rated torque
is the 100% value.
Sets the torque limit value for forward regenerative conditions as a percentage of the motor
rated torque.
Sets the torque limit value for reversed regenerative conditions as a percentage of the
motor rated torque.
Sets the integral time constant for the torque limit function.
Sets the torque limit function during acceleration and deceleration.
0 : Proportional only
1 : Proportional & Integral control
Assigns a time filter to allow the torque limit to build at start.
0 : Disabled
1 : Enabled
Default
(Range)
0.1 s
(0.0 - 10.0 s)
0 h
(0 - 65535 h)
Default
(Range)
200%
(0 - 300%)
200%
(0 - 300%)
200%
(0 - 300%)
200%
(0 - 300%)
200 ms
(5 - 10000 ms)
0
(0, 1)
1
(0, 1)
Ref.
394
394
Ref.
395
395
396
396
396
396
397
◆ L8: Drive Protection
No.
(Hex.)
L8-01
(04AD)
L8-02
(04AE)
L8-03
(04AF)
L8-05
(04B1)
NameDescription
3% ERF DB Resistor
Protection
Sets the function to enable braking resistor protection with a Yaskawa ERF series braking
resistor (3% ED) installed on the heatsink.
0 : No
1 : Yes
Overheat Alarm Level
Sets the oH detection level in temperature.
Overheat Pre-Alarm
Selection
Sets the operation of drives when an oH alarm is detected.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Operate at Reduced Speed (L8-19)
Input Phase Loss
Protection Sel
Sets the function to enable and disable input phase loss detection.
0 : Disable
1 : Enabled
Default
(Range)
0
(0, 1)
Determined by o2-04,
C6-01
(50 - 150 °C)
3
(0 - 4)
1
(0, 1)
Ref.
397
397
397
398
74YASKAWA TOEPYAIGA5002A GA500 Programming
1.11 L: Protection Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
L8-07
(04B3)
L8-09
(04B5)
L8-10
(04B6)
L8-11
(04B7)
L8-12
(04B8)
L8-15
(04BB)
L8-18
(04BE)
L8-19
(04BF)
L8-27
(04DD)
L8-29
(04DF)
L8-31
(04E1)
NameDescription
Output Phase Loss
Protection Sel
Sets the function to enable and disable output phase loss detection. The drive starts output
phase loss detection when the output current decreases to less than 5% of the drive rated
current.
Note:
The drive can incorrectly start output phase loss detection in these conditions:
• The motor rated current is very small compared to the drive rating.
• The drive is operating a PM motor with a small load.
0 : Disabled
1 : Fault when one phase is lost
2 : Fault when two phases are lost
Output Ground Fault
Detection
Sets the function to enable and disable ground fault protection.
0 : Disabled
1 : Enabled
Heatsink Fan Operation
Selection
Sets operation of the heatsink cooling fan.
0 : During Run, w/ L8-11 Off-Delay
1 : Always On
2 : On when Drive Temp Reaches L8-64
Heatsink Fan Off-Delay
Time
Ambient Temperature
Setting
Sets the length of time that the drive will wait before it stops the cooling fan after it cancels
the Run command when L8-10 = 0 [Heatsink Cooling Fan Ope Select = Dur Run(OffDly)].
Sets the ambient temperature of the drive installation area.
Note:
The setting range changes when the L8-35 [Installation Method Selection] value
changes:
• 0 [IP20/UL Open Type]: -10 °C to +60 °C
• 1 [Side-by-Side Mounting]: -10 °C to +50 °C
• 2 [IP20/UL Type 1]: -10 °C to +50 °C
• 3 [External Heatsink]: -10 °C to +50 °C
Drive oL2 @ Low Speed
Protection
Sets the function to decrease drive overload at low speeds to prevent damage to the main
circuit transistor during low speed operation (at 6 Hz or slower) to prevent oL2 [DriveOverloaded].
Note:
Contact Yaskawa or your nearest sales representative before disabling this function at
low speeds. If you frequently operate drives with high output current in low speed
ranges, it can cause heat stress and decrease the life span of drive IGBTs.
0 : Disabled (No Additional Derate)
1 : Enabled (Reduced oL2 Level)
Software Current Limit
Selection
Set the software current limit selection function to prevent damage to the main circuit
transistor caused by too much current.
0 : Disabled
1 : Enabled
Freq Reduction @ oH
Pre-Alarm
Overcurrent Detection
Gain
Sets the ratio at which the drive derates the frequency reference during an oH alarm.
Sets the PM motor overcurrent detection level as a percentage of the motor rated current
value.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 ≠ 8[EZOLV]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8: E9-06 [Motor Rated Current (FLA)]
Output Unbalance
Detection Sel
Sets the function to detect LF2.
0 : Disabled
1 : Enabled
LF2 Detection Time
Sets the LF2 [Output Current Imbalance] detection time.
Default
(Range)
1
(0 - 2)
Determined by o2-04
(0, 1)
0
(0 - 2)
60 s
(0 - 300 s)
40 °C
(-10 °C - +60 °C)
1
(0, 1)
0
(0, 1)
0.8
(0.1 - 0.9)
300.0%
(0.0 - 1000.0%)
1
(0, 1)
3
(1 – 100)
Ref.
399
399
399
400
400
400
400
401
401
401
401
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming75
1.11 L: Protection Functions
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
L8-35
(04EC)
L8-40
(04F1)
L8-41
(04F2)
L8-51
(0471)
Expert
L8-52
(0472)
Expert
L8-53
(0473)
Expert
L8-54
(0474)
Expert
L8-55
(045F)
L8-56
(047D)
Expert
L8-57
(047E)
Expert
L8-90
(0175)
Expert
L8-93
(073C)
Expert
L8-94
(073D)
Expert
L8-95
(077F)
Expert
NameDescription
Installation Method
Selection
Sets the type of drive installation.
0 : IP20/UL Open Type
1 : Side-by-Side Mounting
2 : IP20/UL Type 1
3 : External Heatsink
Carrier Freq Reduction
Off-Delay
High Current Alarm
Selection
Sets the length of time until the automatically reduced carrier frequency returns to the
condition before the reduction.
Sets the function to cause an HCA [Current Alarm] when the output current is more than
150% of the drive rated current.
0 : No
1 : Yes
STPo I Detection Level
Sets the STPo [Motor Step-Out Detected] detection level as a percentage of the motor
rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5 [OLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
STPo Integration Level
Sets the detection level for STPo [Motor Step-Out Detected] related to the ACR integral
value.
STPo Integration Time
Sets the length of time until the drive detects STPo after it is more than the value of L8-51[STPo I Detection Level].
STPo Id Diff Detection
Sets the Id deviation detection function for STPo [Motor Step-Out Detected].
0 : Disabled
1 : Enabled
Internal DB
TransistorProtection
Sets the protection function for the internal braking transistor.
0 : Disable
1 : Protection Enabled
Stall P @ Accel
Activation Time
Stall Prevention Retry
Counts
STPo Detection Level
(Low Speed)
Low Speed Pull-out
DetectionTime
Low Speed Pull-out
Detect Level
Low Speed Pull-out
Amount
Sets the length time that the acceleration stall prevention function can continue to operate
before the drive detects an STPo [Motor Step-Out Detected].
Sets the number of times the acceleration stall prevention function can operate until speeds
agree before the drive detects an STPo [Motor Step-Out Detected].
Sets the detection level that the control fault must be equal to or more than to cause an
STPo [Motor Step-Out Detected].
Sets the length of time the drive will wait to start baseblock after detecting LSo [LowSpeed Motor Step-Out].
Sets the detection level for LSo [Low Speed Motor Step-Out] as a percentage of E1-04[Maximum Output Frequency].
Sets the average count of LSo [Low Speed Motor Step-Out] detections.
Default
(Range)
0
(0 - 3)
Determined by A1-02
(0.00 - 2.00 s)
0
(0, 1)
0.0%
(0.0 - 300.0%)
1.0
(0.1 - 2.0)
1.0 s
(1.0 - 10.0 s)
1
(0, 1)
1
(0, 1)
5000 ms
(100 - 5000 ms)
10
(1 - 10 times)
Determined by A1-02
(0 - 5000 times)
1.0 s
(0.0 - 10.0 s)
3%
(0 - 10%)
10
(1 - 50 times)
Ref.
401
402
402
402
403
403
403
403
403
404
404
404
404
404
76YASKAWA TOEPYAIGA5002A GA500 Programming
1.12n: Special Adjustment
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ n1: Hunting Prevention
1.12 n: Special Adjustment
No.
(Hex.)
n1-01
(0580)
n1-02
(0581)
Expert
n1-03
(0582)
Expert
n1-05
(0530)
Expert
n1-13
(1B59)
Expert
n1-14
(1B5A)
Expert
NameDescription
Hunting Prevention
Selection
Sets the function to prevent hunting.
Note:
When you replace a V1000-series drive with a GA500 drive, set n1-01 = 1 [Hunting
Prevention Selection = Enabled].
0 : Disable
1 : Enabled
Hunting Prevention Gain
Setting
Hunting Prevention Time
Constant
Hunting Prevent Gain in
Reverse
DC Bus Stabilization
Control
Sets the performance of the hunting prevention function. Usually it is not necessary to
change this parameter.
Sets the primary delay time constant of the hunting prevention function. Usually it is not
necessary to change this parameter.
Sets the performance of the hunting prevention function. This parameter adjusts Reverse
run. Usually it is not necessary to change this parameter.
Sets the oscillation suppression function for the DC bus voltage.
0 : Disabled
1 : Enabled
DC Bus Stabilization
Time
Adjusts the responsiveness of the oscillation suppression function for the DC bus voltage.
Set n1-13 = 1 [DC Bus Stabilization Control = Enabled] to enable this parameter.
Default
(Range)
0
( 0, 1 )
1.00
(0.00 - 2.50)
Determined by o2-04
(0 - 500 ms)
0.00
(0.00 - 2.50)
0
(0, 1)
100.0 ms
(50.0 - 500.0 ms)
Ref.
405
405
405
405
406
406
◆ n2: Auto Freq Regulator (AFR)
No.
(Hex.)
n2-01
(0584)
n2-02
(0585)
n2-03
(0586)
NameDescription
Automatic Freq Regulator
Gain
Automatic Freq Regulator
Time 1
Automatic Freq Regulator
Time 2
Sets the gain of the AFR function as a magnification value. Usually it is not necessary to
change this setting.
Sets the time constant that sets the rate of change for the AFR function. Usually it is not
necessary to change this setting.
Sets the time constant that sets the speed difference of the AFR function. Use this
parameter for speed searches or regeneration. Usually it is not necessary to change this
setting.
◆ n3: High Slip/Overexcite Braking
No.
(Hex.)
n3-01
(0588)
Expert
n3-02
(0589)
Expert
NameDescription
HSB Deceleration
Frequency Width
Sets the amount by which the output frequency is to be lowered during high-slip braking,
as a percentage of E1-04 [Maximum Output Frequency], which represents the 100% value.
HSB Current Limit Level
Sets the maximum current output during high-slip braking as a percentage, where E2-01[Motor Rated Current (FLA)] is 100%. Also set the current suppression to prevent
exceeding drive overload tolerance.
Note:
The upper limit to the setting range changes when the setting for C6-01 [Normal /
Heavy Duty Selection] changes.
• 150% when C6-01 = 0 [Heavy Duty Rating]
• 120% when C6-01 = 1 [Normal Duty Rating]
Default
(Range)
1.00
(0.00 - 10.00)
50 ms
(0 - 2000 ms)
750 ms
(0 - 2000 ms)
Default
(Range)
5%
(1 - 20%)
Determined by C6-01
(0 - 150%)
Ref.
406
407
407
Ref.
409
409
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming77
1.12 n: Special Adjustment
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
n3-03
(058A)
Expert
n3-04
(058B)
Expert
n3-13
(0531)
n3-14
(0532)
Expert
NameDescription
HSB Dwell Time at Stop
Sets the dwell time, a length of time when high-slip braking is ending and during which the
motor speed decreases and runs at a stable speed. For a set length of time, the drive will
hold the actual output frequency at the minimum output frequency set in E1-09.
HSB Overload Time
Sets the time used to detect oL7 [High Slip Braking Overload], which occurs when the
output frequency does not change during high-slip braking. Usually it is not necessary to
change this parameter.
OverexcitationBraking
(OEB) Gain
OEB High Frequency
Injection
Sets the gain value that the drive multiplies by the V/f pattern output value during
overexcitation deceleration to calculate the overexcitation level.
Sets the function that injects harmonic signals during overexcitation deceleration.
0 : Disabled
1 : Enabled
n3-21
(0579)
n3-23
(057B)
HSB Current Suppression
Level
Overexcitation Braking
Operation
Sets the upper limit of the current that is suppressed at the time of overexcitation
deceleration as a percentage of the drive rated current.
Sets the direction of motor rotation where the drive will enable overexcitation.
0 : Disabled
1 : Enabled Only when Rotating FWD
2 : Enabled Only when Rotating REV
◆ n5: Feed Forward Control
Default
(Range)
1.0 s
(0.0 - 10.0 s)
40 s
(30 - 1200 s)
1.10
(1.00 - 1.40)
0
(0, 1)
100%
(0 - 150%)
0
(0 - 2)
Ref.
409
409
410
410
410
410
No.
(Hex.)
n5-01
(05B0)
n5-02
(05B1)
n5-03
(05B2)
n5-04
(05B3)
NameDescription
Feed Forward Control
Selection
Motor Inertia
Acceleration Time
Feed Forward Control
Gain
Speed Response
Frequency
RUN
Expert
◆ n6: Online Tuning
No.
(Hex.)
n6-01
(0570)
n6-05
(05C7)
Expert
NameDescription
Online Tuning Selection
Online Tuning Gain
Sets the feed forward function.
0 : Disabled
1 : Enabled
Sets the length of time for the motor to accelerate from the stopped to the maximum
frequency with a single motor at the rated torque. Inertia Tuning automatically sets the
motor acceleration time.
Sets the ratio between load inertia and motor inertia. Inertia Tuning automatically sets the
Feedforward Control Gain value.
Sets the response frequency for the speed reference. Usually it is not necessary to change
this parameter.
Sets the type of motor data that Online Tuning uses for OLV control.
0 : Disabled
1 : Line-to-Line Resistance Tuning
2 : Voltage Correction Tuning
Sets the compensation gain when n6-01 = 2 [Online Tuning Selection = VoltageCorrection Tuning]. Usually it is not necessary to change this parameter.
Default
(Range)
0
(0, 1)
Determined by C6-01,
E5-01, and o2-04
(0.001 - 10.000 s)
1.00
(0.00 - 100.00)
Determined by A1-02
(0.00 - 500.00 Hz)
Default
(Range)
0
(0 - 2)
1.0
(0.1 - 50.0)
Ref.
411
412
412
413
Ref.
413
414
78YASKAWA TOEPYAIGA5002A GA500 Programming
◆ n7: EZ Drive
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.12 n: Special Adjustment
No.
(Hex.)
n7-01
(3111)
Expert
n7-05
(3115)
Expert
n7-07
(3117)
Expert
n7-08
(3118)
Expert
n7-10
(311A)
Expert
n7-17
(3122)
n7-19
(3128)
Expert
NameDescription
Damping Gain for Low
Frequency
Response Gain for Load
Changes
Sets the oscillation suppression gain for the low speed range.
Sets the response gain related to changes in the load.
Speed Calculation Gain1
Sets the speed calculation gain during usual operation. Usually it is not necessary to
change this setting.
Speed Calculation Gain2
Sets the speed calculation gain during a speed search.
Pull-in Current Switching
Speed
Resistance
TemperatureCorrection
Sets the speed range to operate with the pull-in current command. Drive rated frequency =
100% value. If there is a large quantity of oscillation when you operate in the low speed
range, increase the setting value.
Sets the function to adjust for changes in the motor resistance value caused by changes in
the temperature.
0 : Invalid
1 : Valid (Only 1 time)
2 : Valid (Every time)
Flux Error Compensation
Gain
Sets the gain for magnetic flux compensation. Usually it is not necessary to change this
setting.
Default
(Range)
1.0
(0.1 - 10.0)
50
(10 - 1000)
15.0 Hz
(1.0 - 50.0 Hz)
25.0 Hz
(1.0 - 50.0 Hz)
10.0%
(0.0 - 100.0%)
1
(0 to 2)
5000%
(0 - 50000%)
Ref.
414
414
414
414
415
415
415
◆ n8: PM Motor Control Tuning
No.
(Hex.)
n8-01
(0540)
n8-02
(0541)
n8-11
(054A)
n8-14
(054D)
Expert
n8-15
(054E)
Expert
n8-21
(0554)
Expert
n8-23
(0556)
Expert
n8-24
(0557)
Expert
n8-25
(0558)
Expert
NameDescription
Pole Position Detection
Current
Pole Alignment Current
Level
Observer Calculation
Gain 2
Polarity Compensation
Gain 3
Polarity Compensation
Gain 4
Motor Back-EMF (Ke)
Gain
Sets, as a percentage, the Initial Rotor Position Estimated Current, taking the E5-03 [MotorRated Current (FLA)] as the 100% value. Usually it is not necessary to change this setting.
Sets the current at the time of polar attraction as a percentage where E5-03 [motor ratedcurrent] is 100%. Usually it is not necessary to change this setting.
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
ACR q Gain @PoleEst
Sets the proportional gain for current regulator q-axis control when the drive estimates the
initial pole. Usually it is not necessary to change this setting.
ACR q Integral Time
@PoleEst
Sets the integral time for current regulator q-axis control when the drive estimates the
initial pole. Usually it is not necessary to change this setting.
ACR q Limit @PoleEst
Sets the q-axis limit of the current regulator when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
Default
(Range)
50%
(0 - 100%)
80%
(0 - 150%)
Determined by n8-72
(0.0 - 1000.0)
1.000
(0.000 - 10.000)
0.500
(0.000 - 10.000)
0.90
(0.80 - 1.00)
0
(0 - 2000)
0.0 ms
(0.0 - 100.0 ms)
0%
(0 - 150%)
Ref.
415
416
416
416
416
416
416
416
417
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming79
1.12 n: Special Adjustment
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
n8-26
(0559)
Expert
n8-27
(055A)
Expert
n8-28
(055B)
Expert
n8-35
(0562)
n8-36
(0563)
n8-37
(0564)
Expert
n8-39
(0566)
n8-41
(0568)
Expert
n8-42
(0569)
Expert
n8-45
(0538)
n8-46
(0539)
Expert
n8-47
(053A)
n8-48
(053B)
RUN
NameDescription
ACR d Gain @PoleEst
Sets the proportional gain for current regulator d-axis control when the drive estimates the
initial pole. Usually it is not necessary to change this setting.
ACR d Integral Time
@PoleEst
Sets the integral time for current regulator d-axis control when the drive estimates the
initial pole. Usually it is not necessary to change this setting.
ACR d Lim @PoleEst
Sets the d-axis limit of the current regulator when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
Initial Pole Detection
Method
Sets how the drive detects the position of the rotor when the motor starts.
Note:
• When you use an SPM motor, set n8-35 = 0. When you use an IPM motor, set n8-35
= 0 to 2.
• When you set n8-35 = 1, do High Frequency Injection Auto-Tuning.
0 : Pull-in
1 : High Frequency Injection
2 : Pulse Injection
HFI Frequency Level for
L Tuning
HFI Voltage Amplitude
Level
Sets the injection frequency for high frequency injection.
Note:
• Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57
= 1 [HFI Overlap Selection = Enabled] to enable this parameter.
• The drive automatically calculates this value when High Frequency Injection Auto-
Tuning completes successfully.
Sets the high frequency injection amplitude as a percentage where 200 V = 100% for 200
V class drives and 400 V = 100% for a 400 V class drives. Usually it is not necessary to
change this setting.
Note:
• Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57
= 1 [HFI Overlap Selection = Enabled] to enable this parameter.
• The drive automatically calculates this value when High Frequency Injection Auto-
Tuning completes successfully.
HFI LPF Cutoff Freq
Sets the low-pass filter shut-off frequency for high frequency injection.
Note:
• Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57
= 1 [HFI Overlap Selection = Enabled] to enable this parameter.
• The drive automatically calculates this value when High Frequency Injection Auto-
Tuning completes successfully.
HFI P Gain
Sets the response gain for the high frequency injection speed estimation.
Note:
• Set n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57
= 1 [HFI Overlap Selection = Enabled] to enable this parameter.
• When A1-02= 6 [Control Method Selection = AOLV/PM], if you do High Frequency
Injection Auto-Tuning, the drive automatically sets this parameter .
HFI I Time
Sets the integral time constant for the high frequency injection speed estimation. Usually it
is not necessary to change this setting.
Speed Feedback
Detection Gain
PM Phase Compensation
Gain
Pull-in Current Comp
Filter Time
Pull-in/Light Load Id
Current
Sets the internal speed feedback detection reduction unit gain as a magnification value.
Usually it is not necessary to change this setting.
Sets the gain to compensate for phase differences. Usually it is not necessary to change this
setting.
Sets the time constant the drive uses to align the pull-in current reference value with the
actual current value. Usually it is not necessary to change this setting.
On the basis that parameter E5-03 [Motor Rated Current (FLA)] is the 100% value, this
parameter sets the d-axis current that flows to the motor during run at constant speed as a
percentage.
Default
(Range)
500
(0 - 2000)
0.0 ms
(0.0 - 100.0 ms)
100%
(0 - 150%)
Determined by A1-02
(0 - 2)
500 Hz
(200 - 1000 Hz)
20.0%
(0.0 - 50.0%)
250 Hz
(0 - 1000 Hz)
2.5
(-10.0 - +10.0)
0.10 s
(0.00 - 9.99 s)
0.80
(0.00 - 10.00)
0.3
(0.0 - 10.0)
5.0 s
(0.0 - 100.0 s)
30%
(0 - 200%)
Ref.
417
417
417
417
418
418
418
418
418
419
419
419
419
80YASKAWA TOEPYAIGA5002A GA500 Programming
1.12 n: Special Adjustment
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
n8-49
(053C)
RUN
Expert
n8-50
(053D)
Expert
n8-51
(053E)
n8-54
(056D)
Expert
n8-55
(056E)
n8-57
(0574)
n8-62
(057D)
Expert
n8-63
(057E)
Expert
n8-65
(065C)
Expert
n8-69
(065D)
Expert
n8-72
(0655)
Expert
n8-74
(05C3)
Expert
n8-75
(05C4)
Expert
n8-77
(05CE)
Expert
NameDescription
Heavy Load Id Current
Sets the d-axis current to that the drive will supply to the motor to run it at a constant speed
with a heavy load. Considers E5-03 [PM Motor Rated Current (FLA)] to be 100%. Usually
it is not necessary to change this setting.
Medium Load Iq Level
(High)
Pull-in Current @
Acceleration
Sets the load current level at which heavy load control starts where E5-03 [Motor RatedCurrent (FLA)] is 100%. Usually it is not necessary to change this setting.
Sets the pull-in current allowed to flow during acceleration/deceleration as a percentage of
the motor rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5 [OLV/PM]: E5-03 [Motor Rated Current (FLA)]
• A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
Voltage Error
Compensation Time
Motor to Load Inertia
Ratio
Sets the time constant that the drive uses when adjusting for voltage errors.
Sets the ratio between motor inertia and machine inertia.
0 : Below 1:10
1 : Between 1:10 and 1:30
2 : Between 1:30 and 1:50
3 : Beyond 1:50
HFI Overlap Selection
Sets the function that detects motor speed with high frequency injection.
Note:
When you set n8-57 = 1, do High Frequency Injection Auto-Tuning.
0 : Disabled
1 : Enabled
Output Voltage Limit
Level
Sets the output voltage limit to prevent saturation of the output voltage. Usually it is not
necessary to change this parameter.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], the default settings are:
• 200 V class: 230.0 V
• 400 V class: 460.0 V
Output Voltage Limit P
Gain
Speed Fdbk Gain @ oV
Suppression
Speed Observer Control P
Gain
Speed Estimation Method
Select
Sets the proportional gain for output voltage control. Usually it is not necessary to change
this setting.
Sets the gain of internal speed feedback detection suppression while the overvoltage
suppression function is operating as a magnification value. Usually it is not necessary to
change this parameter.
Usually it is not necessary to change this setting. Sets the Proportional gain that the drive
uses for speed estimation.
Selects the speed estimation method. Usually it is not necessary to change this setting.
0 : Method 1
1 : Method 2
Light Load Iq Level
Set n8-48 [Pull-in/Light Load Id Current] to the percentage of load current (q-axis current)
that you will apply, where E5-03 [Motor Rated Current (FLA)] = a setting value of 100%.
Medium Load Iq Level
(low)
Set n8-78 [Medium Load Id Current] to the percentage of load current (q-axis current) that
you will apply, where E5-03 [Motor Rated Current (FLA)] = a setting value of 100%.
Heavy Load Iq Level
Set n8-49 [Heavy Load Id Current] to the percentage of load current (q-axis current) that
you will apply, where E5-03 [Motor Rated Current (FLA)] = a setting value of 100%.
Default
(Range)
Determined by E5-01
(-200.0 - +200.0%)
80%
(50 - 255)
Determined by A1-02
(0 - 200%)
1.00 s
(0.00 - 10.00 s)
0
(0 - 3)
0
(0, 1)
200 V Class: 200.0 V, 400
V: 400.0 V
(200 V Class: 0.0 to 240.0
V, 400 V Class: 0.0 to
480.0 V)
1.00
(0.00 - 100.00)
1.50
(0.00 - 10.00)
1.00
(0.00 - 20.00)
1
(0, 1)
30%
(0 - 255%)
50%
(0 - 255%)
90%
(0 - 255%)
Ref.
420
420
420
420
421
421
422
422
422
422
422
423
423
423
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming81
1.12 n: Special Adjustment
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
n8-78
(05F4)
RUN
Expert
n8-79
(05FE)
n8-84
(02D3)
Expert
n8-87
(02BC)
n8-88
(02BD)
n8-89
(02BE)
n8-90
(02BF)
n8-91
(02F7)
n8-94
(012D)
Expert
n8-95
(012E)
Expert
NameDescription
Medium Load Id Current
Sets the level of the pull-in current as a percentage, where E5-03 [PM Motor RatedCurrent (FLA)] = 100%.
Pull-in Current @
Deceleration
Sets the pull-in current that can flow during deceleration as a percentage of the E5-03 [PMMotor Rated Current (FLA)].
Note:
When n8-79 = 0, the drive will use the value set in n8-51 [Pull-in Current @
Acceleration].
Polarity Detection
Current
Output Voltage Limit
Method
Sets the current that the drive uses to estimate the initial motor magnetic pole as a
percentage where E5-03 [PM Motor Rated Current (FLA)] = 100%.
Sets the method of output voltage limit. If there is vibration in the constant output range,
set Feedforward Method. Usually it is not necessary to change this setting.
0 : Feedback Method
1 : Feedforward Method
Vout Limit Switching
Level
Sets the current level at which output voltage limit sequence selection occurs as a
percentage where the motor rated current is 100%. Normally there is no need to change
this setting.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5, 6 [OLV/PM, AOLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8[EZOLV]: E9-06 [PM Motor Rated Current (FLA)]
Vout Limit Switching
Hysteresis
Sets the hysteresis width of the current level at which output voltage limit sequence
selection occurs as a percentage where the motor rated current is 100%. Normally there is
no need to change this setting.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5, 6 [OLV/PM, AOLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8[EZOLV]: E9-06 [PM Motor Rated Current (FLA)]
Vout Limit Switching
Speed
Sets the speed level at which output voltage limit sequence selection occurs as a
percentage where the maximum output frequency is 100%. Usually it is not necessary to
change this setting.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum
output frequency.
Sets the limit value of feedback output voltage limit Id operation. Enabled when n8-87 = 0[Output Voltage Control Selection = Speed Feedback Form]. Usually it is not necessary to
change this setting.
Sets the criteria that the drive uses to find changes in speed or load. Usually it is not
necessary to change this setting.
0 : Softstarter
1 : Speed Feedback
Flux Position Est Filter
Time
Sets the time constant of the filter used for the recognition criteria value for speed and load
changes. Usually it is not necessary to change this setting.
Default
(Range)
0%
(0 - 255%)
50%
(0 - 200%)
100%
(0 - 150%)
0
(0, 1)
400%
(0 - 400%)
3%
(0 - 400%)
200%
(0 - 200%)
-50%
(-200 - 0%)
1
(0, 1)
30 ms
(0 - 100 ms)
Ref.
423
423
424
424
424
424
424
424
425
425
◆ nA: PM Motor Control Tuning
No.
(Hex.)
nA-01
(3129)
Expert
82YASKAWA TOEPYAIGA5002A GA500 Programming
NameDescription
Observer Calc Gain 3
Sets the gain for speed estimation. Usually it is not necessary to change this setting.
Default
(Range)
30.0
(0.0 - 1000.0)
Ref.
425
1.13o: Keypad-Related Settings
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ o1: Keypad Display
1.13 o: Keypad-Related Settings
No.
(Hex.)
o1-01
(0500)
RUN
o1-02
(0501)
RUN
o1-03
(0502)
o1-04
(0503)
o1-05
(0504)
RUN
o1-10
(0520)
o1-11
(0521)
o1-24 to o1-35:
(11AD - 11B8)
RUN
o1-36
(11B9)
RUN
o1-37
(11BA)
RUN
o1-38
(11BB)
RUN
o1-39
(11BC)
RUN
NameDescription
User Monitor Selection
Sets the U monitor for the Drive Mode. This parameter is only available when you use an
LED keypad.
Monitor Selection at
Power-up
Sets the monitor item that the keypad screen shows after energizing the drive. Refer to “U:
Monitors” for information about the monitor items that the keypad screen can show. This
parameter is only available when you use an LED keypad.
1 : Frequency Reference (U1-01)
2 : Direction
3 : Output Frequency (U1-02)
4 : Output Current (U1-03)
5 : User Monitor (o1-01)
Frequency Display Unit
Selection
Sets the display units for the frequency reference and output frequency.
0 : 0.01Hz units
1 : 0.01% units
2 : Revolutions Per Minute (RPM)
3 : User Units
V/f Pattern Display Unit
Sets the setting unit for parameters that set the V/f pattern frequency.
0 : Hz
-1
1 : min
(r/min) unit
LCD Contrast
Adjustment
User Units Maximum
Value
User Units Decimal
Position
Sets the contrast of the LCD display on the keypad.
Sets the value that the drive shows as the maximum output frequency.
Sets the number of decimal places for frequency reference and monitor values.
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
Custom Monitor 1 to 12
Sets a maximum of 12 monitors as user monitors. This parameter is only available when
using an LCD keypad.
LCD Backlight
Brightness
LCD Backlight ON/OFF
Selection
Sets the intensity of the LCD keypad backlight.
Sets the automatic shut off function for the LCD backlight.
0 : OFF
1 : ON
LCD Backlight Off-Delay
Sets the time until the LCD backlight automatically turns off.
Show Initial Setup Screen
Sets the function to show the LCD keypad initial setup screen each time the drive is
energized. This parameter is only available when using an LCD keypad.
0 : No
1 : Yes
Default
(Range)
106
(104 - 855)
1
(1 - 5)
Determined by A1-02
(0 - 3)
Determined by A1-02
(0, 1)
5
(0 - 10)
Determined by o1-03
(1 - 60000)
Determined by o1-03
(0 - 3)
o1-24: 101
o1-25: 102
o1-26: 103
o1-27 to o1-35: 0
(0, 101 - 999)
5
(1 - 5)
1
(0, 1)
60 s
(10 - 300 s)
1
(0, 1)
Ref.
427
427
427
428
429
429
429
429
430
430
430
431
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming83
1.13 o: Keypad-Related Settings
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
o1-40
(11BD)
RUN
o1-41
(11C1)
RUN
o1-42
(11C2)
RUN
o1-43
(11C3)
RUN
o1-44
(11C4)
RUN
o1-45
(11C5)
RUN
o1-46
(11C6)
RUN
o1-47
(11C7)
RUN
o1-48
(11C8)
RUN
o1-49
(11C9)
RUN
o1-50
(11CA)
RUN
o1-51
(11CB)
RUN
o1-55
(11EE)
RUN
NameDescription
Home Screen Display
Selection
Sets the monitor display mode for the Home screen. This parameter is only available when
using an LCD keypad.
0 : Custom Monitor
1 : Bar Graph
2 : Analog Gauge
3 : Trend Plot
1st Monitor Area
Selection
Sets the horizontal range used to display the monitor set in o1-24 [Custom Monitor 1] as a
bar graph. This parameter is only available when using an LCD keypad.
0 : +/- Area ( - o1-42 ~ o1-42 )
1 : + Area ( 0 ~ o1-42 )
2 : - Area ( - o1-42 ~ 0 )
1st Monitor Area Setting
Sets the horizontal axis value used to display the monitor set in o1-24 [Custom Monitor 1]
as a bar graph. This parameter is only available when using an LCD keypad.
2nd Monitor Area
Selection
Selects the horizontal range used to display the monitor set in o1-25 [Custom Monitor 2]
as a bar graph. This parameter is only available when using an LCD keypad.
0 : +/- Area ( - o1-44 ~ o1-44 )
1 : + Area ( 0 ~ o1-44 )
2 : - Area ( - o1-44 ~ 0 )
2nd Monitor Area Setting
Sets the horizontal axis value used to display the monitor set in o1-25 [Custom Monitor 2]
as a bar graph. This parameter is only available when using an LCD keypad.
3rd Monitor Area
Selection
Sets the horizontal range used to display the monitor set in o1-26 [Custom Monitor 3] as a
bar graph. This parameter is only available when using an LCD keypad.
0 : +/- Area ( - o1-46 ~ o1-46 )
1 : + Area ( 0 ~ o1-46 )
2 : - Area ( - o1-46 ~ 0 )
3rd Monitor Area Setting
Sets the horizontal axis value used to display the monitor set in o1-26 [Custom Monitor 3]
as a bar graph. This parameter is only available when using an LCD keypad.
Trend Plot 1 Scale
Minimum Value
Trend Plot 1 Scale
Maximum Value
Trend Plot 2 Scale
Minimum Value
Trend Plot 2 Scale
Maximum Value
Trend Plot Time Scale
Setting
Analog Gauge Area
Selection
Sets the horizontal axis minimum value used to display the monitor set in o1-24 [CustomMonitor 1] as a trend plot. This parameter is only available when using an LCD keypad.
Sets the horizontal axis maximum value used to display the monitor set in o1-24 [CustomMonitor 1] as a trend plot. This parameter is only available when using an LCD keypad.
Sets the horizontal axis minimum value used to display the monitor set in o1-25 [CustomMonitor 2] as a trend plot. This parameter is only available when using an LCD keypad.
Sets the horizontal axis maximum value used to display the monitor set in o1-25 [CustomMonitor 2] as a trend plot. This parameter is only available when using an LCD keypad.
Sets the time scale (horizontal axis) to display the trend plot. When you change this setting,
the drive automatically adjusts the data sampling time. This parameter is only available
when using an LCD keypad.
Sets the range used to display the monitor set in o1-24 [Custom Monitor 1] as an analog
gauge. This parameter is only available when using an LCD keypad.
0 : +/- Area ( - o1-56 ~ o1-56 )
1 : + Area ( 0 ~ o1-56 )
Default
(Range)
0
(0 - 3)
0
(0 - 2)
100.0%
(0.0 - 100.0%)
0
(0 - 2)
100.0%
(0.0 - 100.0%)
0
(0 - 2)
100.0%
(0.0 - 100.0%)
-100.0%
(-300.0 - +300.0%)
100.0%
(-300.0 - +300.0%)
-100.0%
(-300.0 - +300.0%)
100.0%
(-300.0 - +300.0%)
300 s
(1 - 3600 s)
1
(0, 1)
Ref.
431
431
431
431
432
432
432
432
432
432
432
433
433
84YASKAWA TOEPYAIGA5002A GA500 Programming
1.13 o: Keypad-Related Settings
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
o1-56
(11EF)
RUN
o1-58
(3125)
NameDescription
Analog Gauge Area
Setting
Motor Power Unit
Selection
Sets the value used to display the monitor set in o1-24 [Custom Monitor 1] as an analog
meter. This parameter is only available when using an LCD keypad.
Sets the setting unit for parameters that set the motor rated power.
0 : kW
1 : HP
◆ o2: Keypad Operation
No.
(Hex.)
o2-01
(0505)
o2-02
(0506)
o2-03
(0507)
o2-04
(0508)
o2-05
(0509)
o2-06
(050A)
o2-07
(0527)
o2-09
(050D)
o2-19
(061F)
Expert
o2-23
(11F8)
RUN
NameDescription
LO/RE Key Function
Selection
Sets the function that lets you useto switch between LOCAL and REMOTE
Modes.
0 : Disabled
1 : Enabled
STOP Key Function
Selection
Sets the function to useon the keypad to stop the drive when the Run command
source for the drive is REMOTE (external) and not assigned to the keypad.
0 : Disabled
1 : Enabled
User Parameter Default
Value
Sets the function to keep the settings of changed parameters as user parameter defaults to
use during initialization.
0 : No change
1 : Set defaults
2 : Clear all
Drive Model (KVA)
Selection
Home Mode Freq Ref
Entry Mode
Sets the Drive Model code. Set this parameter after replacing the control board.
Sets the function that makes it necessary to pushto use the keypad to change the
frequency reference value while in Drive Mode.
0 : ENTER Key Required
1 : Immediate / MOP-style
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from
the drive or if you damage the cable while the keypad is the Run command source.
0 : Disabled
1 : Enabled
Keypad RUN Direction
@ Power-up
Sets the direction of motor rotation when the drive is energized and the keypad is the Run
command source.
0 : Forward
1 : Reverse
Reserved--436
Parameter Write during
Uv
Lets you change parameters during Uv [Undervoltage].
0 : Disable
1 : Enabled
External 24V Powerloss
Detection
Sets the function to give a warning if the backup external 24 V power supply turns off
when the main circuit power supply is in operation.
0 : Disable
1 : Enabled
Default
(Range)
100.0%
(0.0 - 100.0%)
1
(0, 1)
Default
(Range)
1
(0, 1)
1
(0, 1)
0
(0 - 2)
Determined by the drive
(-)
0
(0, 1)
1
(0, 1)
0
(0, 1)
0
( 0, 1 )
0
(0, 1)
Ref.
433
433
Ref.
433
434
434
435
435
436
436
Parameter List
1
436
437
YASKAWA TOEPYAIGA5002A GA500 Programming85
1.13 o: Keypad-Related Settings
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
o2-26
(1563)
NameDescription
Alarm display at ext. 24V
power
When you connect a backup external 24 V power supply, this parameter sets the function
to trigger an alarm when the main circuit power supply voltage decreases.
Note:
The drive will not run when it is operating from one 24-V external power supply.
0 : No
1 : Yes
o2-27
(1565)
bCE Detection Selection
Sets drive operation if the Bluetooth device is disconnected when you operate the drive in
Bluetooth Mode.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
◆ o3: Copy Keypad Function
No.
(Hex.)
o3-01
(0515)
o3-02
(0516)
o3-04
(0B3E)
o3-05
(0BDA)
o3-06
(0BDE)
o3-07
(0BDF)
NameDescription
Copy Keypad Function
Selection
Sets the function that saves and copies drive parameters to a different drive with the
keypad.
0 : Copy Select
1 : Backup (drive → keypad)
2 : Restore (keypad → drive)
3 : Verify (check for mismatch)
4 : Erase (backup data of keypad)
Copy Allowed Selection
Sets the copy function when o3-01 = 1 [Copy Keypad Function Selection = Backup (drive→ keypad)].
0 : Disabled
1 : Enabled
Select Backup/Restore
Location
Sets the storage location for drive parameters when you back up and restore parameters.
This parameter is only available when using an LCD keypad.
0 : Memory Location 1
1 : Memory Location 2
2 : Memory Location 3
3 : Memory Location 4
Select Items to Backup/
Restore
Sets which parameters are backed up, restored, and referenced. This parameter is only
available when using an LCD keypad.
0 : Standard Parameters
1 : Standard + DWEZ Parameters
Auto Parameter Backup
Selection
Sets the function that automatically backs up parameters. This parameter is only available
when using an LCD keypad.
0 : Disabled
1 : Enabled
Auto Parameter Backup
Interval
Sets the interval at which the automatic parameter backup function saves parameters from
the drive to the keypad.
Note:
This parameter is only available when using an LCD keypad.
0 : Every 10 minutes
1 : Every 30 minutes
2 : Every 60 minutes
3 : Every 12 hours
Default
(Range)
1
(0, 1)
3
(0 - 4)
Default
(Range)
0
(0 - 4)
0
(0, 1)
0
(0 - 3)
1
(0, 1)
1
(0, 1)
1
(0 - 3)
Ref.
437
437
Ref.
437
438
438
438
439
439
86YASKAWA TOEPYAIGA5002A GA500 Programming
◆ o4: Maintenance Monitors
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.13 o: Keypad-Related Settings
No.
(Hex.)
o4-01
(050B)
o4-02
(050C)
o4-03
(050E)
o4-05
(051D)
o4-07
(0523)
o4-09
(0525)
o4-11
(0510)
o4-12
(0512)
o4-13
(0528)
o4-22
NameDescription
Elapsed Operating Time
Setting
Elapsed Operating Time
Selection
Fan Operation Time
Setting
Capacitor Maintenance
Setting
Softcharge Relay
Maintenance Set
IGBT Maintenance
Setting
Fault Trace/History Init
(U2/U3)
kWh Monitor
Initialization
RUN Command Counter
@ Initialize
Time Format
(154F)
RUN
o4-23
Date Format
(1550)
RUN
o4-24
bAT Detection Selection
(310F)
RUN
◆ o5: Log Function
Sets the initial value of the cumulative drive operation time in 10-hour units.
Sets the condition that counts the cumulative operation time.
0 : U4-01 Shows Total Power-up Time
1 : U4-01 Shows Total RUN Time
Sets the value from which to start the cumulative drive cooling fan operation time in 10hour units.
Sets the U4-05 [CapacitorMaintenance] monitor value.
Sets the U4-06 [PreChargeRelayMainte] monitor value.
Sets the U4-07 [IGBT Maintenance] monitor value.
Resets the records of Monitors U2-xx [Fault Trace] and U3-xx [Fault History].
0 : Disabled
1 : Enabled
Resets the monitor values for U4-10 [kWh, Lower 4 Digits] and U4-11 [kWh, Upper 5Digits].
0 : No Reset
1 : Reset
Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [Number of Runs(Low)], and U4-25 [Number of Runs (High)].
0 : No Reset
1 : Reset
Sets the time display format. This parameter is only available when using an LCD keypad.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
Sets the date display format. This parameter is only available when using an LCD keypad.
0 : YYYY/MM/DD
1 : DD/MM/YYYY
2 : MM/DD/YYYY
Sets the operation when the drive detects bAT [Keypad Battery Low Voltage] and TiM[Keypad Time Not Set]. This parameter is only available when you use an LCD keypad.
0 : Disable
1 : Enable (Alarm Detected)
2 : Enable (Fault Detected)
Default
(Range)
0 h
(0 - 9999 h)
0
(0, 1)
0 h
(0 - 9999 h)
0%
(0 - 150%)
0%
(0 - 150%)
0%
(0 - 150%)
0
(0, 1)
0
(0, 1)
0
(0, 1)
1
(0 - 2)
2
(0 - 2)
0
(0 - 2)
Ref.
439
440
440
440
440
440
441
441
441
441
442
442
Parameter List
1
No.
(Hex.)
o5-01
(1551)
RUN
NameDescription
Log Start/Stop Selection
Sets the data log function. This parameter is only available when using an LCD keypad.
0 : OFF
Default
(Range)
0
(0 - 1)
Ref.
445
1 : ON
o5-02
(1552)
RUN
Log Sampling Interval
Sets the data log sampling cycle. This parameter is only available when using an LCD
keypad.
100 ms
(100 - 60000 ms)
445
YASKAWA TOEPYAIGA5002A GA500 Programming87
1.13 o: Keypad-Related Settings
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
o5-03
(1553)
RUN
o5-04
(1554)
RUN
o5-05
(1555)
RUN
o5-06
(1556)
RUN
o5-07
(1557)
RUN
o5-08
(1558)
RUN
o5-09
(1559)
RUN
o5-10
(155A)
RUN
o5-11
(155B)
RUN
o5-12
(155C)
RUN
NameDescription
Log Monitor Data 1
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Log Monitor Data 2
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Log Monitor Data 3
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Log Monitor Data 4
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Log Monitor Data 5
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Log Monitor Data 6
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Log Monitor Data 7
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Log Monitor Data 8
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Log Monitor Data 9
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Log Monitor Data 10
Sets the data log monitor. This parameter is only available when using an LCD keypad.
Default
(Range)
101
(000, 101 - 999)
102
(000, 101 - 999)
103
(000, 101 - 999)
107
(000, 101 - 999)
108
(000, 101 - 999)
V/f, OLV/PM : 000, OLV,
AOLV/PM, EZOLV : 105
(000, 101 - 999)
110
(000, 101 - 999)
112
(000, 101 - 999)
000
(000, 101 - 999)
000
(000, 101 - 999)
Ref.
445
445
445
446
446
446
446
446
447
447
88YASKAWA TOEPYAIGA5002A GA500 Programming
1.14q: DriveWorksEZ Parameters
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ q1-01 to qx-xx: Reserved for DriveWorksEZ
1.14 q: DriveWorksEZ Parameters
No.
(Hex.)
q1-01 to qx-xx
(1600 - xxxx)
NameDescription
Reserved for DriveWorksEZ
These parameters are reserved for use with DriveWorksEZ.
Default
(Range)
Refer to “DriveWorksEZ
Operation Manual”.
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming89
1.15 r: DWEZ Connection 1-20
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.15r: DWEZ Connection 1-20
◆ r1-01 to r1-40: DriveWorksEZ Connection Parameters 1 to 20 (Upper / Lower)
No.
(Hex.)
r1-01 to r1-40:
(1840 - 1867)
NameDescription
DriveWorksEZ Connection
Parameters 1 to 20 (Upper /
Lower)
DriveWorksEZ Connection Parameters 1 to 20 (Upper / Lower)
Default
(Range)
0
(0 - FFFFH)
90YASKAWA TOEPYAIGA5002A GA500 Programming
1.16T: Motor Tuning
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
◆ T0: Tuning Mode Selection
1.16 T: Motor Tuning
No.
(Hex.)
T0-00
(1197)
NameDescription
Tuning Mode Selection
Sets the type of Auto-Tuning.
0 : Motor Parameter Tuning
1 : Control Tuning
◆ T1: Induction Motor Auto-Tuning
No.
(Hex.)
T1-00
(0700)
T1-01
(0701)
T1-02
(0702)
T1-03
(0703)
T1-04
(0704)
T1-05
(0705)
T1-06
(0706)
T1-07
(0707)
T1-09
(0709)
T1-10
(070A)
T1-11
(070B)
NameDescription
Motor 1/Motor 2
Selection
Sets which motor to tune when motor 1/2 switching is enabled.
You can only use the keypad to set this parameter. You cannot use external input terminals
to set it.
Note:
This parameter is enabled when H1-xx = 16 [Motor 2 Selection] is set. When H1-xx ≠
16 the keypad will not show this parameter.
1 : Motor 1
2 : Motor 2
Tuning Mode Selection
Sets the type of Auto-Tuning.
0 : Rotational Auto-Tuning
1 : Stationary Auto-Tuning 1
2 : Stationary Line-Line Resistance
Motor Rated Power
Uses the units set in o1-58 [Motor Power Unit Selection] to set the motor rated output
power.
Motor Rated Voltage
Sets the rated voltage (V) of the motor. Enter the base speed voltage for constant output
motors.
Motor Rated Current
Sets the rated current (A) of the motor.
Motor Base Frequency
Sets the base frequency (Hz) of the motor.
Number of Motor Poles
Sets the number of motor poles.
Motor Base Speed
Sets the motor base speed for Auto-Tuning (min
Motor No-Load Current
Sets the no-load current of the motor.
Motor Rated Slip
Frequency
Sets motor rated slip.
Motor Iron Loss
Sets the iron loss for calculating the energy-saving coefficient.
-1
(r/min)).
Default
(Range)
0
(0, 1)
Default
(Range)
1
(1, 2)
Determined by A1-02
(Determined by A1-02)
Determined by o2-04,
C6-01
(0.00 - 650.00 HP)
Determined by o2-04,
C6-01
(200 V Class: 0.0 - 255.5
V, 400 V Class: 0.0 -
511.0 V)
Determined by o2-04
(10% to 200% of the
drive rated current)
60.0 Hz
(0.0 - 590.0 Hz)
4
(2 to 120)
-1
1750 min
(0 - 35400 min
(r/min)
-1
(r/min))
-
(0A - T1-04; max. of
2999.9)
-
(0.000 - 20.000 Hz)
Determined by E2-11 or
E4-11
(0 - 65535 W)
Ref.
448
Ref.
448
449
449
449
449
449
450
450
450
450
450
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming91
1.16 T: Motor Tuning
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
T1-12
(0BDB)
NameDescription
Test Mode Selection
Sets the function to enable Test Mode after Stationary Auto-Tuning. When you can operate
the motor with a light load attached after Stationary Auto-Tuning is complete, enable this
parameter.
Note:
You must first set T1-10 = 0 [Motor Rated Slip Frequency = 0 Hz] to enable this
parameter.
0 : No
1 : Yes
T1-13
(0BDC)
No-load voltage
Sets the no-load voltage of the motor. When the no-load voltage at rated speed is available,
for example on the motor test report, set the voltage in this parameter. If the no-load
voltage is not available, do not change this parameter.
Note:
• To get the same qualities as a Yaskawa 1000-series drive or previous series drive, set
this parameter = T1-03 [Motor Rated Voltage].
• The default setting is different for different models.
–B001 - B006, 2001 - 2008, 4001 - 4004: T1-03 × 0.85
If the drive is operating an SMRD, SMRA, or SSR1 series Yaskawa PM motor, enter the
PM motor code in to align with the rotation speed and motor output.
PM Motor Type
Sets the type of PM motor the drive will operate.
0 : IPM motor
1 : SPM motor
PM Motor Rated Power
Uses the units set in o1-58 [Motor Power Unit Selection] to set the PM motor rated output
power.
PM Motor Rated Voltage
Sets the rated voltage (V) of the motor.
PM Motor Rated Current
Sets the rated current (A) of the motor.
PM Motor Base
Frequency
Number of PM Motor
Poles
Sets the base frequency (Hz) of the motor.
Sets the number of motor poles.
PM Motor Base Speed
Sets the motor base speed (min
PM Motor Stator
Resistance
Sets the stator resistance for each motor phase.
Note:
This parameter does not set line-to-line resistance.
PM Motor d-Axis
Inductance
PM Motor q-Axis
Inductance
Sets the d-axis inductance of the motor on a per phase basis.
Sets the q-Axis inductance of the motor on a per phase basis.
-1
(r/min)).
Default
(Range)
0
(0, 1)
T1-03 × 0.9
(200 V Class: 0.0 - 255.0
V, 400 V Class: 0.0 -
510.0 V)
Default
(Range)
0
(Determined by A1-02)
FFFF
(0000 - FFFF)
1
(0, 1)
Determined by o2-04,
C6-01
(0.00 - 650.00 HP)
200 V Class: 230.0 V, 400
V: 460.0 V
(200 V Class: 0.0 - 255.0
V, 400 V Class: 0.0 -
510.0 V)
Determined by o2-04
(10% to 200% of the
drive rated current)
60.0 Hz
(0.0 - 590.0 Hz)
4
(2 - 48)
-1
1750 min
(0 - 34500 min
(r/min)
-1
(r/min))
Determined by T2-02
(0.000 - 65.000 Ω)
Determined by T2-02
(0.00 - 600.00 mH)
Determined by T2-02
(0.00 - 600.00 mH)
Ref.
450
451
Ref.
451
451
452
452
452
452
452
452
452
453
453
453
92YASKAWA TOEPYAIGA5002A GA500 Programming
1.16 T: Motor Tuning
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
T2-13
(0755)
NameDescription
Back-EMF Units
Selection
Sets the units that the drive uses to set the induced voltage constant.
0 : mV/(rev/min)
1 : mV/(rad/sec)
T2-14
(0737)
T2-15
(0756)
Back-EMF Voltage
Constant (Ke)
Pull-In Current Level
Sets the motor induced voltage constant (Ke).
Sets the level of the pull-in current as a percentage of E5-03 [PM Motor Rated Current(FLA)]. Usually it is not necessary to change this setting.
◆ T3: ASR and Inertia Tuning
No.
(Hex.)
T3-00
(1198)
NameDescription
Control Loop Tuning
Selection
Sets the type of Control Auto-Tuning.
2 : Deceleration Rate Tuning
3 : KEB Tuning
◆ T4: EZ Tuning
No.
(Hex.)
T4-01
(3130)
T4-02
(3131)
T4-04
(3133)
T4-05
(3134)
T4-06
(3135)
T4-07
(3136)
T4-08
(3137)
T4-09
(3138)
NameDescription
EZ Tuning Mode
Selection
Sets the type of Auto-Tuning for EZOLV control.
0 : Motor Parameter Setting
1 : Line-to-Line Resistance
Motor Type Selection
Sets the type of motor.
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
Motor Rated Revolutions
Sets rated rotation speed (min
Motor Rated Frequency
Sets the rated frequency (Hz) of the motor.
Motor Rated Voltage
Sets the rated voltage (V) of the motor.
Motor Rated Current
Sets the rated current (A) of the motor.
Motor Rated Capacity
Sets the motor rated power in the units set in o1-58 [Motor Power Unit Selection].
Number of Poles
Sets the number of motor poles.
-1
) of the motor.
Default
(Range)
0
(0, 1)
Determined by T2-13
(0.0 - 2000.0)
30%
(0 - 120%)
Default
(Range)
2
(2, 3)
Default
(Range)
0
(0, 1)
0
(0, 1, 2)
-
((40 Hz to 120 Hz) × 60 ×
2/E9-08)
Determined by E9-01 and
o2-04
(40.0 - 120.0 Hz)
200 V Class: 230.0 V, 400
V: 460.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 -
510.0 V)
Determined by o2-04,
C6-01
(10% to 200% of the
drive rated current)
Determined by E9-10
(0.10 - 650.00 HP)
Determined by E9-01
(2 - 48)
Ref.
453
453
453
Ref.
454
Ref.
454
454
454
455
455
455
455
455
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming93
1.17 U: Monitors
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.17U: Monitors
◆ U1: Operation Status Monitors
No.
(Hex.)
U1-01
(0040)
U1-02
(0041)
U1-03
(0042)
U1-04
(0043)
U1-05
(0044)
U1-06
(0045)
U1-07
(0046)
U1-08
(0047)
U1-09
(0048)
NameDescriptionMFAO Signal Level
Frequency Reference
Output frequency
Output Current
Control method selection
Motor Speed
Output Voltage Ref
DC Bus Voltage
Output Power
Torque Reference
Shows the frequency reference value. Parameter o1-03 [Keypad Display Unit Selection] sets the
display units.
Unit: 0.01 Hz
Shows the output frequency. Parameter o1-03 [Keypad Display Unit Selection] sets the display units.
Unit: 0.01 Hz
Shows the actual output current.
The keypad shows the value of U1-03 in amperes (A). When looking at the monitor through
MEMOBUS/Modbus communications, the current is “8192 = drive rated current (A)”. Calculate the
current from the monitor value that is in at MEMOBUS/Modbus communications using “Numerals
being displayed / 8192 × drive rated current (A).
Unit: When the drive model changes, the display units for this parameter also change.
Shows the detected motor speed. Parameter o1-03 [Keypad Display Unit Selection] sets the display
units.
Unit: 0.01 Hz
Shows the output voltage reference.
Unit: 0.1 V
Shows the DC bus voltage.
Unit: 1 V
Shows the internally-calculated output power.
When you change A1-02 [Control Method Selection], it will also change the signal level of the
analog output.
• A1-02 = 0: Drive capacity (kW)
• A1-02 = 2: Motor Rated Power [E2-11] (kW)
• A1-02 = 5, 6: PM Motor Rated Power [E5-02] (kW)
• A1-02 = 8: Motor Rated Power [E9-07] (kW)
Unit: When the drive model changes, the display units for this parameter also change.
• 0.01 A units: B001 to B018, 2001 to 2042, 4001 to 4023
• 0.1A units: 2056 - 2082, 4031 - 4060
Shows the internal torque reference value.
Unit: 0.1%
10 V = Maximum frequency
(0 V to +10 V)
10 V = Maximum frequency
(0 V to +10 V)
10 V = Drive rated current
No signal output available
10 V = Maximum frequency
(0 V to +10 V)
200 V class: 10 V = 200
Vrms
400 V class: 10 V = 400
Vrms
200 V class: 10 V = 400 V
400 V class: 10 V = 800 V
10 V: Drive capacity (motor
rated power) kW
(0 V to +10 V)
10 V = Motor rated torque (0
V to +10 V)
94YASKAWA TOEPYAIGA5002A GA500 Programming
1.17 U: Monitors
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
U1-10
(0049)
U1-11
(004A)
U1-12
(004B)
NameDescriptionMFAO Signal Level
Input Terminal Status
Output Terminal Status
Drive Status
Shows the status of the MFDO terminal where = ON and = OFF.
For example, U1-10 showswhen terminals S1 and S3 are ON.
bit0 : Terminal S1 (MFDI 1)
bit1 : Terminal S2 (MFDI 2)
bit2 : Terminal S3 (MFDI 3)
bit3 : Terminal S4 (MFDI 4)
bit4 : Terminal S5 (MFDI 5)
bit5 : Terminal S6 (MFDI 6)
bit6 : Terminal S7 (MFDI 7)
bit7 : Not used (normal value of [ ]).
Shows the status of the MFDO terminal where = ON and = OFF.
For example, U1-11 showswhen terminals MA and P2 are ON.
Note:
When H2-xx = 100 to 1A7 [U1-11 Inverse U1-11 Output of Function], U1-11 does not show the
status in inverse.
bit0 : Terminal MA/MB-MC
bit1 : Terminal P1-C1
bit2 : Terminal P2-C2
bit3 : Not used (normal value of [ ]).
bit4 : Not used (normal value of [ ]).
bit5 : Not used (normal value of [ ]).
bit6 : Not used (normal value of [ ]).
bit7 : Not used (normal value of [ ]).
Shows drive status where = ON and = OFF.
No signal output available
No signal output available
No signal output available
U1-13
(004E)
U1-14
(004F)
U1-16
(0053)
U1-18
(0061)
Terminal A1 Level
Terminal A2 Level
SFS Output Frequency
oPE Fault Parameter
For example, U1-12 showsduring run with the Reverse Run command.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive Ready
bit6 : During minor fault detection
bit7 : During fault detection
Shows the signal level of terminal A1.
Unit: 0.1%
Shows the signal level of terminal A2.
Unit: 0.1%
Shows the output frequency after soft start. Shows the frequency with acceleration and deceleration
times and S-curves. Parameter o1-03 [Keypad Display Unit Selection] sets the display units.
Unit: 0.01 Hz
Shows the parameter number that caused the oPE02 [Parameter Range Setting Error] or oPE08[Parameter Selection Error].
10 V = 100% (0 V to +10 V)
10 V = 100% (0 V to +10 V)
10 V = Maximum frequency
(0 V to +10 V)
No signal output available
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming95
1.17 U: Monitors
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
U1-19
(0066)
U1-24
(007D)
U1-25
(004D)
U1-26
(005B)
U1-50
(1199)
Expert
U1-91
(154E)
Expert
NameDescriptionMFAO Signal Level
MEMOBUS/Modbus Error
Code
Input Pulse Monitor
Software number
SoftwareNumber ROM
Virtual Analog Input
Output Voltage
Shows the contents of the MEMOBUS/Modbus communication error where =”error” and = “no
error”.
For example, U1-19 showswhen the drive detects a CRC error.
bit0 : CRC Error
bit1 : Data Length Error
bit2 : Not used (normal value of [ ]).
bit3 : Parity Error
bit4 : Overrun Error
bit5 : Framing Error
bit6 : Timed Out
bit7 : Not used (normal value of [ ]).
Shows the frequency to pulse train input terminal RP.
Unit: 1 Hz
Shows the ID.
Shows the ROM ID.
Shows the virtual analog input value.
Shows the drive internal output voltage reference.
Unit: 0.1 V
No signal output available
Determined by H6-02
No signal output available
No signal output available
Determined by H7-40
200 V class: 10 V = 200
Vrms
400 V class: 10 V = 400
Vrms
◆ U2: Fault Trace
No.
(Hex.)
U2-01
(0080)
U2-02
(0081)
U2-03
(0082)
U2-04
(0083)
U2-05
(0084)
U2-06
(0085)
Current Fault
Previous Fault
Freq Reference@Fault
Output Freq @ Fault
Output Current@Fault
Motor Speed @ Fault
NameDescriptionMFAO Signal Level
Shows the fault that the drive has when viewing the monitor.
Shows the fault that occurred most recently.
Shows the frequency reference at the fault that occurred most recently.
Use U1-01 [Frequency Reference] to monitor the frequency reference value.
Unit: 0.01 Hz
Shows the output frequency at the fault that occurred most recently.
Use U1-02 [Output Frequency] to monitor the actual output frequency.
Unit: 0.01 Hz
Shows the output current at the fault that occurred most recently.
Use U1-03 [Output Current] to monitor the actual output current. The keypad shows the value of U1-03 in amperes (A).
When looking at the monitor through MEMOBUS/Modbus communications, the current is “8192 =
drive rated current (A)”. Calculate the current from the monitor value that is in at MEMOBUS/
Modbus communications using “Numerals being displayed / 8192 × drive rated current (A).
Unit: When the drive model changes, the display units for this parameter also change.
Shows the motor speed at the fault that occurred most recently.
Use U1-05 [Motor Speed] to monitor the motor speed.
Unit: 0.01 Hz
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
96YASKAWA TOEPYAIGA5002A GA500 Programming
1.17 U: Monitors
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
U2-07
(0086)
U2-08
(0087)
U2-09
(0088)
U2-10
(0089)
U2-11
(008A)
U2-12
(008B)
NameDescriptionMFAO Signal Level
Output Voltage@Fault
DC Bus Voltage@Fault
Output Power @ Fault
Torque Ref @ Fault
Input Terminal Status @
Fault
Output Terminal Status @
Fault
Shows the output voltage reference at the fault that occurred most recently.
Use U1-06 [Output Voltage Ref] to monitor the output voltage reference.
Unit: 0.1 V
Shows the DC bus voltage at the fault that occurred most recently.
Use U1-07 [DC Bus Voltage] to monitor the DC bus voltage.
Unit: 1 V
Shows the output power at the fault that occurred most recently.
Use U1-08 [Output Power] to monitor the output power.
Unit: 0.1 kW
Shows the torque reference at the fault that occurred most recently as a percentage of the motor rated
torque.
Use U1-09 [Torque Reference] to monitor the torque reference.
Unit: 0.1%
Shows the status of the MFDI terminals at the most recent fault where = ON and = OFF.
For example, U2-11 showswhen terminals S1 and S3 are ON.
Use U1-10 [Input Terminal Status] to monitor the actual MFDI terminal status.
bit0 : Terminal S1
bit1 : Terminal S2
bit2 : Terminal S3
bit3 : Terminal S4
bit4 : Terminal S5
bit5 : Terminal S6
bit6 : Terminal S7
bit7 : Not used (normal value of [ ]).
Shows the status of the MFDO terminals at the most recent fault where = ON and = OFF.
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
U2-13
(008C)
Operation Status @ Fault
For example, U2-12 showswhen terminals MA and P2 are ON.
Use U1-11 [Output Terminal Status] to monitor the actual MFDO terminal status.
bit0 : Terminal MA/MB-MC
bit1 : Terminal P1-C1
bit2 : Terminal P2-C2
bit3 : Not used (normal value of [ ]).
bit4 : Not used (normal value of [ ]).
bit5 : Not used (normal value of [ ]).
bit6 : Not used (normal value of [ ]).
bit7 : Not used (normal value of [ ]).
Shows the status of the MFDO terminals at the most recent fault where = ON and = OFF.
For example, U2-13 showsduring run.
Use U1-12 [Drive Status] to monitor the actual MFDO terminal status.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive Ready
bit6 : During minor fault detection
bit7 : During fault detection
No signal output available
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming97
1.17 U: Monitors
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
U2-14
(008D)
U2-15
(07E0)
U2-16
(07E1)
U2-17
(07E2)
U2-19
(07E4)
U2-20
(008E)
U2-21
(1166)
Expert
NameDescriptionMFAO Signal Level
Elapsed Time @ Fault
SFS Output @ Fault
q-Axis Current@Fault
d-Axis Current@Fault
ControlDeviation@Flt
Heatsink Temp @Fault
STPo Detect @ Fault
Shows the cumulative operation time of the drive at the fault that occurred most recently.
No signal output available
Use U4-01 [Cumulative Ope Time] to monitor the cumulative operation time.
Unit: 1 h
No signal output available
Shows the output frequency after soft start at the fault that occurred most recently.
Use U1-16 [SFS Output Frequency] to monitor the output frequency after soft start.
Unit: 0.01 Hz
No signal output available
Shows the q-Axis current of the motor at the fault that occurred most recently.
Use U6-01 [Iq Secondary Current] to monitor the q-Axis current of the motor.
Unit: 0.1 %
No signal output available
Shows the d-Axis current of the motor at the fault that occurred most recently.
Use U6-02 [Id ExcitationCurrent] to monitor the d-Axis current of the motor.
Unit: 0.1 %
No signal output available
Shows the amount of control axis deviation (Δθ) at the fault that occurred most recently.
Use U6-10 [ContAxisDeviation Δθ] to monitor the actual amount of control axis deviation (Δθ).
Unit: 0.1 °
No signal output available
Shows the heatsink temperature at the fault that occurred most recently.
Use U4-08 [Heatsink Temperature] to monitor the temperature of the heatsink.
Unit: 1 °C
No signal output available
Monitors conditions to detect STPo [Motor Step-Out Detected] faults. The bit for each condition is
shown as = ON or = OFF.
◆ U3: Fault History
No.
(Hex.)
U3-01 to U3-04
(0090 - 0093)
(0800 - 0803)
U3-05 to U3-10
(0804 - 0809)
U3-11 to U3-14
(0094 - 0097)
(080A - 080D)
U3-15 to U3-20
(080E - 0813)
1st to 4th MostRecent Fault
5th to 10th MostRecent Fault
ElapsedTime@1st to
4thFault
ElapsedTime@5th to
10thFault
NameDescriptionMFAO Signal Level
For example, U2-21 showswhen the drive detects excessive current.
bit0 : Excessive current
bit1 : Induced voltage deviation
bit2 : d-axis current deviation
bit3 : Motor lock at startup
bit4 : Acceleration stall continue
bit5 : Acceleration stall repeat
bit6 : Not used (normal value of [ ]).
bit7 : Not used (normal value of [ ]).
Shows the fault history of the first to fourth most recent faults.
Note:
The drive saves the U3-01 to U3-04 [1st to 4th MostRecent Fault] fault histories to two types of
registers at the same time for the MEMOBUS/Modbus communications.
Shows the fault history of the fifth to tenth most recent faults.
Shows the cumulative operation time when the first to fourth most recent faults occurred.
Unit: 1 h
Note:
The drive saves the U3-11 to U3-14 [ElapsedTime@1st to 4thFault] the cumulative operation
time to two types of registers at the same time for the MEMOBUS/Modbus communications.
Shows the cumulative operation time when the fifth to tenth most recent faults occurred.
Unit: 1 h
No signal output available
No signal output available
No signal output available
No signal output available
98YASKAWA TOEPYAIGA5002A GA500 Programming
◆ U4: Maintenance Monitors
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
1.17 U: Monitors
No.
(Hex.)
U4-01
(004C)
U4-02
(0075)
U4-03
(0067)
U4-04
(007E)
U4-05
(007C)
U4-06
(07D6)
U4-07
(07D7)
U4-08
(0068)
NameDescriptionMFAO Signal Level
Cumulative Ope Time
Num of Run Commands
Cooling Fan Ope Time
Cool Fan Maintenance
CapacitorMaintenance
PreChargeRelayMainte
IGBT Maintenance
Heatsink Temperature
Shows the cumulative operation time of the drive.
Use parameter o4-01 [Elapsed Operating Time Setting] to reset this monitor. Use parameter o4-02[Elapsed Operating Time Selection] to select the cumulative operation times from:
• The time from when the drive is energized until it is de-energized.
• The time at which the Run command is turned ON.
The maximum value that the monitor will show is 99999. After this value is more than 99999, the
drive automatically resets it and starts to count from 0 again.
Unit: 1 h
Note:
The MEMOBUS/Modbus communication data is shown in 10 h units. Use register 0099H for
data in 1 h units.
Shows how many times that the drive has received a Run command.
Use parameter o4-13 [RUN Command Counter @ Initialize] to reset this monitor. The maximum
value that the monitor will show is 65535. After this value is more than 65535, the drive
automatically resets it and starts to count from 0 again.
Unit: 1
Shows the cumulative operation time of the cooling fans.
Use parameter o4-03 [Fan Operation Time Setting] to reset this monitor. The maximum value that
the monitor will show is 99999. After this value is more than 99999, the drive automatically resets it
and starts to count from 0 again.
Unit: 1 h
Note:
The MEMOBUS/Modbus communication data is shown in 10 h units. Use register 009BH for
data in 1 h units.
Shows the cumulative operation time of the cooling fans as a percentage of the replacement life of
the cooling fans.
Use parameter o4-03 [Fan Operation Time Setting] to reset this monitor.
Unit: 1%
Note:
Replace the cooling fans when this monitor is 90%.
Shows the operation time of the electrolytic capacitors for the main circuit and control circuit as a
percentage of the replacement life of the electrolytic capacitors.
Use parameter o4-05 [Capacitor Maintenance Setting] to reset this monitor.
Unit: 1%
Note:
Replace the electrolytic capacitor when this monitor is 90%.
Shows the operation time of the soft charge bypass relay as a percentage of the replacement life of
the soft charge bypass relay.
Use parameter o4-07 [Softcharge Relay Maintenance Set] to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is 90%.
Shows the operation time of the IGBTs as a percentage of the replacement life of the IGBTs.
Set parameter o4-09 [IGBT Maintenance Setting] to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is 90%.
Shows the heatsink temperature of the drive.
Unit: 1 °C
10 V: 99999 h
10 V: 65535 times
10 V: 99999 h
10 V: 100%
10 V: 100%
10 V: 100%
10 V: 100%
10 V: 100 °C
Parameter List
1
YASKAWA TOEPYAIGA5002A GA500 Programming99
1.17 U: Monitors
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PMOLV/PM
AOLV/PM
EZOLV
No.
(Hex.)
U4-09
(005E)
U4-10
(005C)
U4-11
(005D)
U4-13
(07CF)
U4-14
(07D0)
U4-16
(07D8)
U4-18
(07DA)
NameDescriptionMFAO Signal Level
LED Check
kWh, Lower 4 Digits
kWh, Upper 5 Digits
Peak Hold Current
PeakHold Output Freq
Motor oL1 Level
Reference Source
Turns on all of the keypad LEDs to make sure that the LEDs operate correctly.
1.With U4-09 displayed, press.
All LEDs on the keypad will turn on.
Note:
When Safety input 2 CH is open (STo), READY will flash.
Shows the lower 4 digits of the watt hour value for the drive.
Unit: 1 kWh
Note:
The watt hour is displayed in 9 digits. Monitor U4-11 [kWh, Upper 5 Digits] shows the upper 5
digits and U4-10 shows the lower 4 digits.
Example for 12345678.9 kWh:
U4-10: 678.9 kWh
U4-11: 12345 MWh
Shows the upper 5 digits of the watt hour value for the drive.
Unit: 1 MWh
Note:
Monitor U4-11 shows the upper 5 digits and U4-10 [kWh, Lower 4 Digits] shows the lower 4
digits.
Example for 12345678.9 kWh:
U4-10: 678.9 kWh
U4-11: 12345 MWh
Shows the hold value of the peak value (rms) for the drive output current.
Use U4-14 [PeakHold Output Freq] to show the drive output frequency at the time that the drive
holds the output current.
The drive will hold the peak hold current at the next start up and restart of the power supply. The
drive keeps the value that was under hold during baseblock (during stop).
The keypad shows the value of U4-13 in amperes (A). When looking at the monitor through
MEMOBUS/Modbus communications, the current is “8192 = drive rated current (A)”. Calculate the
current from the monitor value that is in at MEMOBUS/Modbus communications using “Numerals
being displayed / 8192 × drive rated current (A).
Unit: When the drive model changes, the display units for this parameter also change.
Shows the output frequency at which the peak value (rms) of the drive output current is held.
The peak hold current can be monitored by U4-13 [Peak Hold Current].
The peak hold output frequency will be cleared at the next startup and restart of the power supply.
The drive keeps the value that was under hold during baseblock (during stop).
Unit: 0.01 Hz
Shows the integrated value of oL1 [Motor Overload] as a percentage of oL1 detection level.
Unit: 0.1%
Shows the selected frequency reference source.
The keypad shows the frequency reference source as “XY-nn” as specified by these rules:
X: External Reference 1/2 Selection [H1-xx = 2] selection status
• 1: b1-01 [Frequency Reference Selection 1]
• 2: b1-15 [Frequency Reference Selection 2]
Y-nn: Frequency reference source
• 0-01: Keypad (d1-01 [Reference 1])
• 1-00: Analog input (unassigned)
• 1-01: MFAI terminal A1
• 1-02: MFAI terminal A2
• 2-02 to 2-17: Multi-step speed reference (d1-02 to d1-17 [Reference 2 to 16, Jog Reference])
• 3-01: MEMOBUS/Modbus communications
• 4-01: Communication option card
• 5-01: Pulse train input
• 7-01: DriveWorksEZ
• 9-01: Up/Down command
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
10 V: 100%
No signal output available