White Rodgers 1361-103, 1361-102, 1361-104 Troubleshooting

4 (1)
White Rodgers 1361-103, 1361-102, 1361-104 Troubleshooting

 

 

RESIDENTIAL

WIRING

 

ZONE VALVES

 

 

 

 

 

 

 

 

 

 

1361 Two Wire Zone Valve

TERMINALS 1, 2 = POWER TO VALVE 1= 24 VAC NEUTRAL

2 = 24 VAC HOT

TERMINALS 2, 4 = SPST THERMOSTAT MAKE TO OPEN, BREAK TO CLOSE

TERMINALS 2, 3 = AUXILIARY SWITCH

2, 3 BECOME SAME POINT ON CALL FOR HEAT

 

 

WARP SWITCH CONTACTS

 

 

 

 

NORMALLY CLOSED

 

 

THERMOSTAT

 

 

TO AUXILIARY CIRCUIT.

 

5

 

2

(NOTE: IF SAME TRANS-

 

 

 

 

FORMER POWERS BOTH

 

 

 

 

THE AUXILIARY CIRCUIT

 

 

 

 

AND THE WATER VALVE,

 

 

 

 

CONNECT AUXILIARY CIR-

 

 

OPEN

3

CUITTOTERMINALS1AND

R

W

3 INSTEAD OF 2 AND 3.)

POSITION

 

 

 

 

 

 

 

SIDE "A"

 

 

 

4

 

 

 

 

 

 

 

OPEN POSITION

 

SIDE "A" OF

 

 

SIDE "B"

 

 

 

 

 

MOTOR SWITCH

 

 

SIDE "B" OF

 

 

 

 

 

 

 

 

MOTOR SWITCH

 

INTERNAL

 

 

 

 

WIRING

 

 

 

 

EXTERNAL

MOTOR

 

LINE

 

WIRING

 

 

 

 

1

 

 

HOLDING

 

 

 

 

 

 

 

CONTACT

WARP SWITCH HEATER

 

 

 

 

 

 

TRANSFORMER

TERMINALS 1, 3 = POWER OUT TO AUXILIARY CIRCUIT ON CALL FOR HEAT

TROUBLESHOOTING:

1)Attach a voltmeter to terminals 1 and 2. Power (24 volts) should always be present on 1 and 2. If power is interrupted check transformer or power source.

2)With voltmeter attached as above, jumper terminals 2 and 4 to verify the valve opens. If power is present on 1 and 2 but the valve fails to open check connections. Replace motor assembly (Replacement Motor # F19-0104) if condition persists. When the jumper is removed between 2 and 4 the valve should close. If the valve fails to close replace motor assembly.

3)Terminals 2 and 3 (auxiliary circuit) become the same point electrically when the valve opens. Because terminal 2 is 24 volts hot, a voltmeter should read 24 volts between terminal 3 and terminal 1 (neutral) when the valve is open.

Note: If the auxiliary circuit terminals (2 and 3) are being attached to a control circuit with a separate transformer the transformers must be in phase or one transformer may be damaged. If phasing the transformers is not possible a 24 volt isolation relay can be installed with the coil attached to terminals 1 and 3 and the contacts can be used to operate the control circuit. The relay will energize when the valve opens.

For complete installation instructions visit our website.

TECHNICAL HELP

? TECHNICAL HELP

1311 Troubleshooting . . . . . . . . see previous page

See previous page

226

www.white-rodgers.com

Loading...