Disconnect the gas range’s line cord plug from the wall receptacle before you
service any of the components inside the unit. Failure to do this could result in violent
electrical shock.
VOLTAGE CHECKS
When making voltage checks, be sure to observe the following precautions:
1.The floor must be dry. Water and dampness increase the chances of electrical
shock.
2.Set the voltmeter correctly for the voltage being measured.
3.Touch only the insulated parts of the meter probes.
4.Touch the component terminals, or wires, with the meter probe tips only.
5.Touch the meter probe tips only on the terminals being checked. Touching other
components could damage good parts.
PARTS QUALITY
An important step in the appliance repair procedure is the selection of FSP
(FACTORY SPECIFICATION PARTS) as replacements. Use of “fits-all,” or “look
alike” parts could result in early parts failure, safety hazard, or substandard performance of a WHIRLPOOL appliance. It could also result in an unnecessary repeat of
your repair efforts.
To be sure that the part(s) you purchase meet the exacting quality standards used to
build every new WHIRLPOOL appliance, be sure to ask for genuine FSP replacement
parts, as specified for your model. “FSP” is a registered trademark of WHIRLPOOL
CORPORATION.
You can buy your genuine FSP replacement parts from any authorized WHIRLPOOL
Parts Distributor.
WHIRLPOOL CORPORATION assumes no responsibility for
any repair made on our products by anyone other than qualified
®
TECH-CARE
Service Technicians.
®
Copyright 1998 Whirlpool Corporation, Benton Harbor, MI
ii
Table Of Contents
Page
Fundamental Properties Of Gas ............................................................................................ 1-1
This program is designed to teach the servicer basic skills in handling common
service procedures for gas ranges. This program does not cover the diagnosis and
repair of all range problems and components, (oven liner, wiring harness, etc.).
PROGRAM OBJECTIVE
Upon completion of this program, the participants will be able to identify the location
of major range components, as well as diagnose problems, and remove and repair
the components causing the problem.
INSTRUCTIONS
This program has the following sections:
•Fundamental Properties of Gas
•Pressure Regulators
•The Cooktop Burner System
•The Oven Burner System
•Natural And L.P. Gas Conversion
•Testing The Components
TOOLS YOU WILL NEED
Phillips Screwdriver
Long-Nosed Pliers
Adjustable Wrench
Pipe Sealer
Special Tools:
•Volt-Ohmmeter
v
— NOTES —
vi
FUNDAMENTAL PROPERTIES OF GAS
MEASURING HEAT ENERGY
When burning a gas fuel, heat energy is produced. This heat energy is usually expressed in British
Thermal Units, or B.T.U.’s. One B.T.U. is equal to the amount of heat needed to raise one pound
of water one degree Fahrenheit (see Figure 1-1).
1 B.T.U. = the heat necessary to raise 1 lb. of water 1˚F
A wooden kitchen match will produce approximately 1 B.T.U. of heat energy.
ONE POUND
OF WATER
120
110
100
90
80
70
60
50
40
30
20
10
0
˚F
Figure 1-1
90˚F
˚F
120
110
100
90
80
70
60
50
40
30
20
10
0
91˚F
HEAT ENERGY PRODUCED
BY BURNING GAS
Page 1-1
Gas Fuels are categorized as follows:
#1 = Natural Gas
#2 = Mixed Gas
#3 = Manufactured Gas
#4 = Liquefied Petroleum Gas
#1 — NATURAL GAS
FUEL TYPES
Natural Gas
hydrocarbons, such as propane and butane. These hydrocarbons are removed by the gas
company so that only the pure natural gas properties, methane and ethane, are left.
Natural gas is lighter than air, and has a heat value of between 900 and 1200 B.T.U. per-cubic-foot.
is found underground. It is referred to as “wet gas,” because it contains heavy
#2 — MIXED GAS
Mixed Gas
of between 700 and 900 B.T.U. per-cubic-foot.
consists of natural and manufactured gas. It is lighter than air, and has a heat value
#3 — MANUFACTURED GAS
Manufactured Gas
of between 500 and 700 B.T.U. per-cubic-foot.
is made from coal and petroleum. It is lighter than air, and has a heat value
#4 — LIQUEFIED PETROLEUM (L.P.) GAS
Liquefied Petroleum (L.P.) Gas
of these gases are converted from a
can then be stored in a pressurized tank and easily transported. The liquid gas will return to its
gaseous state when it is released into the atmosphere. L.P. gas is heavier than air and will lay in
the lowest spot it can find when released into a room.
Propane
cubic-foot.
has a heat value of 2500 B.T.U. per-cubic-foot, and
consists of the heavy hydrocarbons “propane or butane.” Both
gaseous
to a
liquid
state by using pressure. The liquid gas
butane
a value of 3200 B.T.U. per-
Page 1-2
Category 1
Category 2
– Natural Gas –
Contains Methane & Ethane.
Sour Natural Gas
Contains Hydrogen Sulfide
Which Corrodes Copper & Brass.
It Has A Heat Valve Of
900 to 1200 B.T.U. Per-Cubic-Foot.
Specific Gravity Is 0.65 To 0.70.
Category 3
– Manufactured Gas –
Made From Coal & Petroleum.
It Has A Heat Valve Of 500 to 700
B.T.U. Per-Cubic-Foot.
Specific Gravity Is 0.38 To 0.40.
– Mixed Gas –
Contains A Mixture Of
Natural & Manufactured Gases.
It Has A Heat Valve Of 700 to 900
B.T.U. Per-Cubic-Foot.
Specific Gravity Is 0.5.
Category 4
– Liquefied Petroleum (L.P.) Gas –
Made Of Propane Or Butane.
Is Converted To A Liquid State
Under Moderate Pressure For
Easy Transportation In
Pressurized Tanks.
Propane Has A Heat Valve Of
2500 B.T.U. Per-Cubic-Foot.
Specific Gravity Is 1.53.
Gas Fuel Properties
Summary
Page 1-3
CHARACTERISTICS OF GAS FUELS
Each of the four types of gas has a specific boiling point (see Figure 1-2). The
boiling point
is
referred to as the temperature where gas turns from a liquid to a gas at atmospheric pressure. If
temperatures fall below the freezing point (32˚F), the liquid will not turn into a gas, and there will
be no flame.
By itself, gas cannot be ignited. Fuel, oxygen, and heat are necessary for combustion to occur.
Remove one of these, and combustion cannot take place (see Figure 1-3).
200
100
32
Zero
– 44
–100
– 200
– 300
Butane
Propane
FahrenheitDegrees
L.P.
Natural
Mixed
Manufactured
OXYGEN
FUEL
HEAT
THE COMBUSTION PROPERTIES
BOILING POINT OF GAS
Figure 1-2
Figure 1-3
Gases will ignite at temperatures between 900˚F and 1200˚F.
A proper mixture, or ratio, of gas and air is needed to produce a flame. If the air-to-gas ratio is not
correct, incomplete combustion, or an improper flame, will result. The ratio needed to ignite natural
gas (10:1) is shown in Figure 1-4, and the ratio for L.P. gas (24:1) is shown in Figure 1-5.
1000 BTU Heat
1 cu.ft.
Gas
Natural Gas (10:1)
10 cu. ft. Air To 1 cu.ft. Gas
10 cu.ft.
Figure 1-4
Air
Figure 1-5
1000 BTU Heat
1 cu.ft.
Gas
L.P. Gas (24:1)
24 cu. ft. Air To 1 cu.ft. Gas
24 cu.ft.
Air
Page 1-4
DISTRIBUTION OF NATURAL GAS
Utility companies send natural gas through underground pipes, called “mains.” The gas in these
mains is pressurized at between 25 and 60 pounds-per-square-inch (psi).
Branches carry the pressurized gas to the various buildings, and are connected to gas meters.
The meters decrease the main’s gas pressure to 7 inches water column pressure (1/4 pounds) for
use by the appliances inside the buildings (see Figure 1-6).
DISTRIBUTION
REGULATOR
25 To 60 Pounds Pressure “Main”
SERVICE
REGULATOR
7" WCP (1/4 Pound Pressure)
SERVICE
REGULATOR
Figure 1-6
A gas piping system is able to supply gas to all of the appliances in a building at one time. Ranges
generally operate on gas pressure rated at 4 inches water column pressure. Each appliance
usually has its own pressure regulator to more accurately meet the designed requirements (see
Figure 1-7).
Gas Main 25 - 60 Pounds
Gas Meter
(Service Regulator)
Appliance
Regulator
7" WCP (1/4 Pound)
In-House Gas Supply Line
4
"
Range
Furnace
Water
Heater
Dryer
Figure 1-7
Page 1-5
DISTRIBUTION OF L.P. GAS
For Liquid Propane (L.P.) gas, appliances generally operate on gas pressure rated at between 10
and 12 inches water column pressure. Each appliance usually has its own pressure regulator to
more accurately meet the designed requirements (see Figure 1-8).
10
" - 12"
L.P. Gas Main 28" WCP (1 lb.)
WCP In-House Gas Supply Line
L.P. Gas Tank
Figure 1-8
Service
Regulator
Water
Heater
10
"
Appliance
Regulator
Range
Furnace
Dryer
Page 1-6
PRESSURE REGULATORS
FUNCTIONS
A
Gas Pressure Regulator
•Reduces higher incoming gas pressure to a desired lower outgoing gas pressure.
•Maintains a steady, even flow of gas as it leaves the regulator.
The
Appliance Pressure Regulator
for the particular application (see Figure 2-1). This is the final stage of gas regulation. It controls
gas at a lower pressure and flow rate.
Appliance Pressure Regulator
It is recommended that the pressure regulator be connected to a manual gas shutoff valve, via a
flexible line (depending on local codes), so that it will be easy to shut off the gas supply to the range
before servicing it (see Figure 2-2).
is a mechanical device that performs the following two functions:
is used to further reduce the gas pressure to the desired level
N
N
Figure 2-1
Figure 2-2
Pressure
Regulator
Fitting
Flexible
Gas Line
Fitting
Manual Gas
Shutoff Valve
Page 2-1
REGULATOR OPERATION
The pressure of the gas coming into the pressure regulator pushes against a spring-loaded
diaphragm, forcing it upward. The diaphragm spring puts pressure on the diaphragm. In order to
control the flow rate, the diaphragm has a tapered plug suspended from it to restrict or increase
the gas flow pressure (see Figure 2-3).
Vent (Through
Hole In Cap)
Cap
Tension
Spring
Diaphragm
Valve Seat & Valve
(Tapered Plug)
Gas Outlet
To Cooktop
Burners
Gas Outlet
To Oven
Burners
Lower Chamber
Gas Inlet
Manual Gas
Shutoff Valve
To Oven Burner
Upper Chamber
Figure 2-3
As the gas pressure against the diaphragm drops, the tension from the spring pushes the
diaphragm downward, moving the tapered plug away from the valve seat, allowing more gas
pressure to flow to the burners (see Figure 2-4). Additional gas may then flow into the regulator,
pushing the diaphragm back up, thus restricting the flow of gas pressure into the passage way, and
the cycle can repeat. In this way, the diaphragm and tapered plug maintain a constant gas pressure
level to the burners.
Gas Inlet
Cap (In Natural Gas
Position)
Tension
Spring
Diaphragm
Gas Outlet
To Cooktop
Burners
Gas Outlet
To Oven
Burners
Figure 2-4
Page 2-2
The amount of spring tension applied to the diaphragm determines the output pressure of the
regulator (see Figure 2-5).
Cap (L.P. Position)
Tension Spring
Diaphragm
Gas Outlet
Gas Inlet
To Cooktop
Burners
Gas Outlet
To Oven
Burners
Figure 2-5
A manual gas shutoff on some pressure regulators will allow the gas to be turned off to the oven
burners during service to allow gas flow to the cooktop to remain on. The gas to the oven burners
is turned off by moving the manual shutoff lever in the direction shown in Figure 2-6.
Gas Inlet
Manual Shutoff
Lever
CLOSED POSITION
Cap (L.P. Position)
Tension Spring
Diaphragm
Gas Outlet
To Cooktop
Burners
Gas Outlet
To Oven
Burners
Manual Shutoff
Lever
OPEN POSITION
Figure 2-6
Page 2-3
VENTING
Pressure regulators contain an air vent in the upper chamber to allow a free flow of air in and out
of the chamber during operation (see Figure 2-7). The vent’s secondary purpose is to safely control
the flow of gas to the atmosphere (200cc-per-hour or 7 BTU-per-hour) in case the diaphragm
ruptures. If the vent is partially or completely plugged, the regulator will become sluggish. It can
also become fixed in the high or low position, depending on which position the diaphragm was in
when it became plugged.
Vent (Through
Hole In Cap)
Cap
Figure 2-7
REGULATOR DIAGNOSTICS
Common causes for regulator failure are:
A. Ruptured diaphragm.
B. Broken or worn valve.
C. Debris accumulating around the valve seat.
D. Restricted (plugged) vent.
E. Internal corrosion due to water in the L.P. gas system. Keep the tank full to prevent this
from occurring.
As a safety feature, the regulator will “lock-up” and restrict all gas flow during any situation that
applies extreme pressure to the incoming gas supply line. The pressure regulator can be unlocked
by removing the cap, and pushing down on the diaphragm with the eraser end of a pencil.
Usually the appliance regulator is replaced rather than serviced, since it has few replaceable or
serviceable parts, and is a relatively inexpensive device.
Page 2-4
MEASURING GAS PRESSURE
Gas pressure is measured in
Inches of Water Column Pressure (WCP)
. It takes 28" WCP to
equal one pound per-square-inch (PSI).
In most locations, natural gas pressure entering the home is regulated to 7 inches water column.
L.P. gas is regulated between 10 and 12 inches water column. The appliance regulator reduces
the incoming pressure to the required amount for the appliance. The model/serial plate on the gas
range (see Figure 2-8) provides information about the proper water column pressure. Whirlpool
ranges operate on 4 inches water column on natural gas, and 10 inches WCP on L.P.
it becomes necessary to measure these pressures, two instruments are available: a manometer,
and a magnehelic gauge.
When it becomes necessary to measure these pressures, there are two instruments available that
you can use: a manometer and a magnehelic gauge.
A manometer is basically a U-shaped tube with a scale, marked in inches of water column. To
prepare and use the manometer, use the following steps:
1.Check the appliance model/serial plate and note the gas pressure
rating.
2.Turn off the gas pressure to the range.
Hose
3.Prepare the manometer by filling the U-shaped tube with water so
that both sides of the tube fill to the
zero
point (see Figure 2-9).
NOTE: Use a little food coloring in the water to help make reading
the meter easier.
4.Connect the tubing that is supplied with the manometer over one
end of the manometer.
5.Remove a burner from the appliance and place the free end of the
tubing over the burner orifice.
6.Turn on the gas supply to the range.
Balanced
Water Columns
4
3
2
1
0
1
2
3
4
7.Turn on the gas valve to the orifice being tested and light at least
one other burner to serve as a load.
Figure 2-9
Page 2-5
8.Observe the movement of the water in the manometer. The gas pressure is read by adding
the water movement in both legs of the tube, as shown in Figure 2-10. It should measure within
the pressure rating stated on the rating plate.
Incoming
Gas Flow
Hose
4
3
2
Total Change In
Water Column =
4.00 IN. W.C.
2.00 IN.
2.00 IN.
1
0
1
2
3
New Water
4
Levels
Figure 2-10
The Magnehelic gauge (see Figure 2-11) can also help measure gas pressure. This type of gauge
is easier and faster to use that a manometer.
To use the gauge:
l.Check the appliance model/serial plate and note
the gas pressure rating (see Figure 2-8 on the
previous page ).
2.Turn off the gas pressure to the range.
3.Remove a burner from the appliance and place
the free end of the tubing over the burner orifice.
4.Turn on the gas supply to the range.
5.Read the gas pressure directly from the scale of
the gauge. It should measure within the pressure
rating stated on the rating plate. Some gauges
have numerous scales on the dial face. Read the
water column pressure scale when taking the
measurement.
2
5
1
Rubber Hose
Magnehelic Gauge
4
15
3
10
8
4
0
O
0
U
N
I
N
C
H
0
20
12
20
C
.
E
Q
S
S
P
R
E
R
E
E
S
T
A
O
W
F
K
S
I
L
L
O
A
P
C
A
S
Figure 2-11
5
6
25
7
16
30
8
.
N
I
35
9.8
Page 2-6
THE COOKTOP BURNER SYSTEM
GAS DISTRIBUTION
After gas passes through the gas pressure regulator, it enters the gas manifold for distribution to
the cooktop burners, or the oven safety valve. The components that provide the safe distribution
and operation of the cooktop burner system (see Figure 3-1) will be discussed in this section.
GAS MANIFOLD—After gas passes through the appliance gas pressure regulator, it enters a
manifold. A manifold is simply a formed pipe through which the incoming gas is distributed to each
of the burner valves.
GAS VALVE—The gas valve controls the gas flow to the individual burners. The valves on all
Whirlpool ranges are push-to-turn types to keep them from being turned on accidentally. When the
valve is turned on, gas flows through the valve and out an orifice.
ORIFICE—The orifice is a special fitting at the outlet of the valve that controls the amount of gas
released through the valve. The orifice controls the gas flow and directs it into the venturi and air
shutter assembly.
AIR SHUTTER & VENTURI—From the orifice, the gas flows through an air shutter into the venturi,
and finally to the burner head, where it exits a series of small holes, called “ports,” and is ignited
by the pilot flame, or spark.
Gas Pressure
Regulator
Gas Manifold
Venturi
Air Shutter
Gas Valves
& Orifices
Burner
Heads
Figure 3-1
Venturi
Gas Valve
Orifice
Page 3-1
Adjustable Air Shutter
GAS VALVE
A typical Whirlpool gas valve and its component breakdown is shown in Figure 3-2. The gas valves
are used to control the gas flow to the top burners. The gas valves are usually mounted to the top
of the manifold pipe with a screw and rubber washer. The gas valve housing contains a hollow gas
control seat. As the valve stem is rotated, the hole in the seat rotates to align with the hole in the
top of the valve housing (see Figure 3-3). Gas from the manifold then flows through the holes to
the orifice.
There are two types of gas valves used, depending on the model of the range. The first type of valve
goes from closed to completely open by manually rotating the valve stem from 0˚ to 90˚. The second
type of valve has a stem rotation of 220˚.
The 220˚ gas valve has a
low flame adjustment screw
that is located inside the shaft of the valve
stem (see Figure 3-4). To adjust the control, use a small screwdriver, and turn the control until the
desired flame is produced.
Manifold
Mounting Screw
Gas From Manifold
Enters Here And Is
Stopped Here
Gas Control Seat
Gas From Manifold
Flows Through Hole
In Seat To Orifice
Gas Control Seat
Figure 3-3
OFF
On
OFF
Gas
Openings
Rubber Washer
Orifice
Rubber Washer
Gas Valve Housing
Gas “On” Position
Gas Control Seat
Spring
Detent Collar
Stem Housing
Screw
Gas Manifold
Pipe
Orifice
Gas Inlet Hole
OFF POSITION
Manifold
Orifice
Gas Inlet Hole
ON POSITION
Figure 3-2
Stem
Stem
Figure 3-4
Page 3-2
220˚ Rotation
Gas Valve
Low Flame
Adjustment Screw
GAS VALVE ORIFICES
An orifice is an opening used to control the direction and amount of gas that is discharged to a
burner. Orifices are available in different sizes and shapes and can be removed and replaced
without replacing the valve.
PLUG-TYPE ORIFICES
The cooktop burner orifice uses a
plug-type
orifice, as shown in Figure 3-5. The orifice is generally
constructed of brass, and consists of a threaded seat, a chamber, and a metered hole. The
threaded seat allows the orifice to be securely fastened to the burner valve. The chamber is used
as a passageway to allow gas to flow through the orifice opening. The orifice is used to control, or
limit, the amount of gas going to the burner. This type of orifice is not adjustable.
Natural Gas
Orifice Drill Size No.
(Stamped On Top)
Threaded Seat
55
Orifice
Orifice Opening
Gas Flow
Out
Threaded Seat
Gas Flow
In
Chamber
L.P. Gas
Orifice Drill Size No.
(Stamped On Top)
Threaded Seat
65
Orifice
L.P. Gas
Identification
Notch In Orifice Cap
Orifice
Gas Valve
Figure 3-5
Page 3-3
L.P. AND NATURAL GAS ORIFICES
The actual size and configuration of each orifice depends on several factors. The most important
factor, however, is the type of gas that will be used by the gas range system. The two most
frequently used types are:
liquefied petroleum (L.P.)
gas, and
natural
gas.
L.P. gas is generally heavier than natural gas and has a higher heat output.
For example, when one cubic foot of L.P. gas is burned, it gives off approximately 2,500 B.T.U. of
heat, while one cubic foot of natural gas will yield only 1,000 B.T.U. Since the heat density of L.P.
gas is higher than natural gas, it takes less cubic feet of L.P. gas to produce the same amount of
heat. An L.P. orifice will always be smaller than a natural gas orifice with an equivalent B.T.U. rating
(see the following “Orifice Specifications Chart” ). It is also important to remember that much more
air is needed with the L.P. gas system (24 cu. ft.) than with the natural gas system (10 cu. ft.). The
identification color location on the valve is shown in Figure 3-6.
Gas cooking systems for both L.P. gas and natural gas
can be used without changing orifices by using a
sal
orifice.
The universal orifice consists of an L.P. gas insert that is
threaded into a cap orifice. This insert is actually an
orifice itself. When natural gas is used, the cap is in the
position shown in Figure 3-7. Gas enters through both
the cap and the insert. The amount of gas leaving the
orifice is controlled by the size of the cap orifice.
When L.P. gas is used, the cap is tightened down
2-1/2 turns so that it rests against the L.P. insert,
closing off the spacing between the two (see Figure
3-8). The amount of gas leaving the orifice is now
controlled by the size of the L.P. insert.
univer-
Natural Gas Position
Cap Orifice
Gas Flow
Cap
Insert
Gas Flow
Figure 3-7
Figure 3-8
Page 3-5
GAS VALVE ORIFICE DIAGNOSTICS
A gas valve orifice is often a source for gas range problems. Some of the problems that arise with
an orifice are as follows:
1.The orifice may become clogged from dirt, or slag in the gas lines. The result will be an overrestricted gas flow, causing the mixture to become too “lean”. This means that not enough gas
will be mixed with air in the burner for efficient burning to occur.
2.The orifice may become cross-threaded when it is installed and allow one of three conditions
to occur:
a) The orifice may not be aligned correctly with the venturi tube so that the gas flows straight
into the burner, causing inefficient burning.
b) The orifice may not be secured because of the cross-threading, causing a small gas leak.
The mixture will again be too lean, and inefficient burning will occur.
c) The orifice size may be incorrect. If a conversion is made from natural to L.P. gas, the orifice
must be changed to maintain the desired heat output. The orifice size may also be too small
due to a high consumption rate, so that the burner cannot meet its maximum B.T.U. output.
If it becomes necessary to clean an orifice, there are three methods that can be used:
1.Blowing forced air into the chamber.
2.Using a mild solvent and soaking the orifice for 15 to 30 minutes (the orifice can then be blown
out and reinstalled).
3.Using a drill bit to clean the orifice. The bit is inserted into the orifice, then, using a slow in and
out motion, the debris can be removed. A chart on page 3-4 shows the proper drill bit size to
use for a particular orifice.
Page 3-6
PERFORMANCE CHECK
1.Remove the gas valves.
2.Remove the orifices.
Page 3-7
BURNER OPERATION
To understand how a burner operates, it is important to understand the following terms (see Figure
3-9):
Gas:
Primary Air:
Secondary Air:
Air/Gas Ratio:
The fuel used by the burner, either natural or L.P.
The air mixed with the gas in order to make the gas combustible.
The supplemental, or ambient air, surrounding the flame.
Comparison of amounts of fuel gas and air to act as primary and
secondary air.
Secondary Air
Gas
Primary Air
Primary Air
Figure 3-9
For proper operation, a burner needs the correct amount of gas mixed with the correct amount of
air, referred to as the “air/gas ratio.” A correct air/gas ratio will result in a flame that is stable without
yellow tips. The ratio depends upon the fuel gas type being used. Ten cubic feet of air are needed
to completely burn one cubic foot of natural gas (10 to 1 ratio) and twenty-four cubic feet of air are
needed to completely burn one cubic foot of L.P. gas (24 to 1 ratio). (See Figure 3-10).
When broken down, 70% to 80% of the total air required is mixed with the gas as primary air. The
remaining 20% to 30% is pulled into the flame as secondary air.
1000 BTU Heat
1 cu.ft.
Gas
Natural Gas
10 cu. ft. Air To 1 cu.ft. Gas
10 cu.ft.
Air
Figure 3-10
1000 BTU Heat
1 cu.ft.
Gas
L.P. Gas
24 cu. ft. Air
To 1 cu.ft. Gas
24 cu.ft.
Air
Page 3-8
The
Cooktop Burner Assembly
controls the combustion of gas and directs its flame (see Figure
3-11). Burners are manufactured from galvanized steel and have common component parts:
1.An
2.A
Air Shutter
Venturi
to provide a pathway for gas to flow to the burner from the orifice. Air enters the
to control the amount of primary air to be mixed with the gas.
burner through the venturi tube, and is used as a pathway for gas, as well as an area for gas
and air to be mixed together for combustion.
3.A
Burner Head
to provide an exit for gas so it can be ignited. The exits are normally holes,
or slots, called “burner ports.”
Burner Head
Figure 3-11
Venturi
Air Shutter
AIR SHUTTER & VENTURI
An inlet for primary air is provided before the gas supply reaches the burner port. This inlet is called
an “air shutter” (see Figure 3-12). The air shutter is adjustable to allow a better adjustment of the
air-gas mixture needed for combustion, and results in more efficient combustion.
Gas Inlet
Adjustment
Screw
Venturi
(Constricting
Area)
Adjustable
Air Shutter
Primary Air
= Gas
= Air
Expanding
Area
Mixed Air &
Gas Outlet
Figure 3-12
Page 3-9
Loading...
+ 61 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.