Operation & Installation Manual
Novelty Ice Cream Case
Model NIC183R01
The Novelty Ice Cream Case has been safety and performance-test approved by Intertek, a safety regulatory
testing agency. In the course of new installations or periodic inspections, reference to agency approvals may be
required. The regulatory agency file number is ETL File #4007858, complying with ANSI/UL 471, CSA C22.2
and NSF /ANSI 7.
ETL File #4007858
Document Part #: 1251406 Rev: A
ECN: 54483 Date: 1-25-16

REFRIGERATION INSTALLATION
START-UP & OPERATING INFORMATION
Start-up and Performance Check
Operating Guidelines
Controller Operation & Error Codes
SERVICE PARTS & ELECTRICAL SCHEMATIC
Electrical Schematic
CONTENTS
1251406a

Maintain product temperature at or below 12⁰F
Maximum indoor 80⁰F and relative humidity 54%
Structure
Outer / Inner Box
Powder coated steel / zinc coated steel
208 - 220 VAC, 12 amp, 60 Hz, single phase
Hermetic direct acting solenoid valve for refrigeration (24V DC)
Refrigeration
Connections
Fin tube type, forced convection
External equalized automatic thermal expansion valve
Digital programmable controller with Modbus communication
protocol
Five 2 inch diameter casters
Agency Approvals
ANSI/UL 471, CSA C22.2, NSF/ANSI 7
SPECIFICATIONS
1251406a

SAFETY PRECAUTIONS
•
Electrical service installation should only be performed by qualified, licensed Electricians.
•
Mechanical service should only be performed by qualified, licensed Service Technicians.
•
Use adequate equipment when moving the Novelty Ice Cream Case (NIC).
•
Test for proper grounding to reduce the risk of electrical shock and fire.
•
High voltage is present in the NIC. Disconnect power before servicing.
•
Use only fully trained service technicians for power-on servicing.
•
Use only authorized replacement parts.
•
Lines are pressurized with nitrogen. Use caution when opening lines.
•
Use refrigeration lines with adequate wall thickness to handle refrigeration pressures.
•
Replacement fuse must have identical ratings as the fuse being replaced.
•
The NIC is designed for indoor use only, in a controlled environment that typically does not exceed
80ºF (27ºC). Check room and system airflow as described in this document to ensure food is
maintained at required temperatures.
INITIAL SET-UP
It is the responsibility of the installer to ensure the unit is installed and working properly. The following
instructions provide step-by-step set-up, piping, condensate drain connections (if applicable), electrical
connection, start-up, performance and maintenance guidelines.
For Parts or Technical Service, please call: 1-800-344-7216 or FAX: 1-800-541-5684 or email:
customerservice@vendoco.com. Additional reference manuals can be obtained at www.vendoco.com
CABINET LOCATION AND SETUP
Choose a location for your new Novelty Ice Cream case. Avoid placing the cabinet near equipment that releases
heat, near an outside door, or in direct sunlight. To protect all electrical parts, do not place the cabinet
where it will be subjected to rain, splashed liquid, or excessive humidity.
Check the airflow around the cabinet, since strong airflow may displace the cooled air in the Showcase. Place
the cabinet where the airflow speed is less than 50 feet/minute (see following figures). Also, avoid
areas subject to wind.
1251406a