In addition to description for the normal-type model,
descriptions about the models with anti-corrosion
(based on JRA Standard light protection and heavy
protection) models are added in this Manual.
PRINTED IN JAPAN, Sep.,2006 ToMo
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its concentration will not
exceed a set limit.
The refrigerant R410A which is used in the air
conditioner is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws to be imposed
which protect the ozone layer. However, since it
contains more than air, it poses the risk of suffocation if
its concentration should rise excessively. Suffocation
from leakage of R410A is almost non-existent. With the
recent increase in the number of high concentration
buildings, however, the installation of multi air
conditioner systems is on the increase because of the
need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying
power etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of
the multi conditioner system is to be installed in a small
room, select a suitable model and installation procedure
so that if the refrigerant accidentally leaks out, its
concentration does not reach the limit (and in the event
of an emergency, measures can be made before injury
can occur).
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device.
The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
≤ Concentration limit (kg/m³)
The concentration limit of R410A which is used in multi
air conditioners is 0.3kg/m³.
NOTE 1 :
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.
e.g., charged
amount (10kg)
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 15kg.
Outdoor unit
e.g.,
charged amount (15kg)
Indoor unit
Important
NOTE 2 :
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit
(3) If an indoor unit is installed in each partitioned room
and the refrigerant piping is interconnected, the
smallest room of course becomes the object. But
when a mechanical ventilation is installed
interlocked with a gas leakage detector in the
smallest room where the density limit is exceeded,
the volume of the next smallest room becomes the
object.
Refrigerant piping
Outdoor unit
Very
small
room
Small
room
Mechanical ventilation device - Gas leak detector
Medium
room
Large room
NOTE 3 :
The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows:
(When the ceiling is 2.7m high)
40
Range below the
35
m²
density limit
of 0.3 kg/m³
30
(countermeasures
not needed)
25
20
15
10
5
Min. indoor floor area
0
102030
Total amount of refrigerant
Range above
the density limit
of 0.3 kg/m³
(countermeasures
needed)
15.EXPLODED VIEWS AND PARTS LIST ................................................ 189
In addition to description for the normal-type model, descriptions about the models with anti-corrosion
(based on JRA Standard light protection and heavy protection) models are added in this Manual.
3
SAFETY CAUTION
The important contents concerned to the safety are described on the product itself and on this Service Manual.
Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication
DANGER
WARNING
CAUTION
∗ Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
Indicates contents assumed that an imminent danger causing a death or serious injury of
the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the
repair engineers, the third parties, and the users due to troubles of the product after work
when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage ( ∗) may be caused on the
repair engineers, the third parties, and the users due to troubles of the product after work
when an incorrect work has been executed.
Explanation
[Explanation of illustrated marks]
MarkExplanation
Indicates prohibited items (Forbidden items to do)
The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do)
The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (including danger/warning)
The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions
(Refer to the Parts disassembly diagram (Outdoor unit).)
If removing the label during parts replace, stick it as the original.
DANGER
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric
shock is caused by high voltage resulted in a death or injury.
During operation, a high voltage with 400V or higher of circuit (∗) at secondary circuit of the highvoltage transformer is applied.
Turn off breaker.
Execute discharge
between terminals.
Prohibition
If touching a high voltage with the naked hands or body, an electric shock is caused even if using an
electric insulator.
∗ : For details, refer to the electric wiring diagram.
When removing the front panel or cabinet, execute short-circuit and discharge between highvoltage capacitor terminals.
If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury.
After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor.
Do not turn on the breaker under condition that the front panel and cabinet are removed.
An electric shock is caused by high voltage resulted in a death or injury.
4
Check earth wires.
Prohibition of modification.
Use specified parts.
Do not bring a child
close to the equipment.
Insulating measures
No fire
Refrigerant
Assembly/Wiring
WARNING
Before troubleshooting or repair work, check the earth wire is connected to the earth
terminals of the main unit, otherwise an electric shock is caused when a leak occurs.
If the earth wire is not correctly connected, contact an electric engineer for rework.
Do not modify the products.
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
For spare parts, use those specified (*).
If unspecified parts are used, a fire or electric shock may be caused.
∗: For details, refer to the parts list.
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except
the repair engineers close to the equipment.
It causes an injury with tools or disassembled parts.
Please inform the users so that the third party (a child, etc.) does not approach the equipment.
Connect the cut-off lead wires with crimp contact, etc, put the closed end side upward
and then apply a water-cut method, otherwise a leak or production of fire is caused at
the users’ side.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire
before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon
monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may
catch the inflammables.
(For more details, please refer Page 7 to Page 9)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the
ozone layer.
Check the used refrigerant name and use tools and materials of the parts which
match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a
position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the
service port is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A.
For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in
the refrigerating cycle changes resulted in change of air conditioner characteristics or
refrigerant over the specified standard amount is charged and an abnormal high pressure is
applied to the inside of the refrigerating cycle resulted in cause of breakage or injury.
Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute
vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time,
never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant
or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the
refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire
such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious
accident such as breakage or injury is caused.
After repair work, surely assemble the disassembled parts, and connect and lead the
removed cables as before. Perform the work so that the cabinet or panel does not
catch the inner cables.
If incorrect assembly or incorrect cable connection was done, a disaster such as a leak or
fire is caused at user’s side.
5
WARNING
Insulator check
Ventilation
Be attentive to
electric shock
Compulsion
After the work has finished, be sure to use an insulation tester set (500V mugger) to
check the resistance is 2M
metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electr ic shock is caused at user’s
side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the
refrigerant and the closed room full with gas is dangerous because a shortage of oxygen
occurs. Be sure to execute ventilation.
When checking the circuit inevitably under condition of the power-ON, use rubber
gloves and others not to touch to the charging section.
If touching to the charging section, an electric shock may be caused.
When the refrigerant gas leaks, find up the leaked position and repair it surely.
If the leaked position cannot be found up and the repair work is interrupted, pump-down
and tighten the service valve, otherwise the refrigerant gas may leak into the room.
The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking
stove though the refrigerant gas itself is innocuous.
When installing equipment which includes a large amount of charged refrigerant such
as a multi air conditioner in a sub-room, it is necessary that the density does not the
limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shor tage of oxygen is
caused.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric
shock or fire is caused.
ΩΩ
Ω or more between the charge section and the non-charge
ΩΩ
Check after rerair
Check after reinstallation
Put on gloves
Cooling check
After repair work has finished, check there is no trouble.
If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off
the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test
run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the
front panel and cabinet.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable.
If check is not executed, a fire, an electric shock or an injury is caused.
CAUTION
Be sure to put on gloves (
If not putting on gloves, an injury may be caused with the parts, etc.
(∗) Heavy gloves such as work gloves
When the power was turned on, start to work after the equipment has been
sufficiently cooled.
As temperature of the compressor pipes and others became high due to cooling/heating
operation, a burn may be caused.
∗∗
∗) during repair work.
∗∗
6
• New Refrigerant (R410A)
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of
refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water , dust, the former
refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with
new refrigerant during installation work or service work. If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R410A to
purpose a safe work.
2. Cautions on Installation/Service
1) Do not mix the other refrigerant or refrigerating oil.
For the tools e xclusive to R410A, shapes of all the joints including the service port differ from those of the
former refrigerant in order to prev ent mixture of them.
2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are
specified for R410A.
3) In the installation time , use clean pipe materials and work with great attention so that water and others do
not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc.
Use the clean pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
4) For the earth protection, use a vacuum pump for air purge.
5) R410A refrigerant is azeotropic mixture type refriger ant. Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the refrigerant changes and then characteristics of the air
conditioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a
minimum.
1) Copper pipe
<Piping>
The pipe thickness, flare finishing size , flare nut and others differ according to a refrigerant type.
When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without
seam” and one with bonded oil amount 40mg/10m or less . Also do not use crushed, deformed, discolored
(especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
2) Joint
The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installa-
tion of the air conditioner. However clear impurities when using them.
7
4. Tools
(1)Required T ools for R410A
Mixing of different types of oil ma y cause generation of sludge, clogging of capillary, etc.
Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conv entional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
Used tool
Flare tool
Copper pipe gauge for
adjusting projection
margin
Torque wrench
Gauge manifold
Charge hose
V acuum pump adapter
Electronic balance for
Refrigerant charge
Gas leakage check
Refrigerant charge
air conditioner installation
Existence of
new equipment
for R410A
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
(Note 2)
R410A
Whether conventional
equipment can be
used
*(Note 1)
*(Note 1)
No
No
No
Yes
No
No
No
Conventional air
conditioner installation
Whether new equipment
can be used with
conventional refrigerant
Yes
*(Note 1)
No
No
Yes
Yes
No
Yes
No
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the f ollowing equipments which serve also for R22 are necessary
as the general tools.
1) Vacuum pump
Use vacuum pump by
attaching vacuum pump adapter.
2) Torque wrench
3) Pipe cutter
4) Reamer
5) Pipe bender
6) Level vial
7) Screwdriver (+, –)
8) Spanner or Monkey wrench
9) Hole core drill
10) Hexagon wrench (Opposite side 4mm)
11) Tape measure
12) Metal saw
Also prepare the following equipments for other installation method and run check.
1) Clamp meter
2) Thermometer
3) Insulation resistance tester (Megger)
4) Electroscope (Volt meter)
8
5. Recharge of Refrigerant
When recharge of the refrigerant is required, charge the new refrigerant with the specified amount in the
procedure as described below .
Recover the refrigerant and check there is no refrigerant in the
equipment.
Connect the charge hose to the packed valve service ports at gas
side, liquid side of the outdoor unit.
Connect the charge hose to vacuum pump adaptor.
Open the packed valves fully at liquid and gas sides, and then return
the valve at gas side a little to the closed side.
Open fully PMV of the outdoor unit.
• Turn on power of the outdoor unit.
• Short CN30 on I/F P.C. board of the outdoor unit.
•
Turn off power of the outdoor unit within 2 minutes after
Open fully the handle on the Low side of the gauge manifold, and
then turn on the power of vacuum pump for vacuuming.
When the pressure has lowered until indication of the compound
gauge pointed –0.1MPa (–76cmHg), open fully the handle Low and
turn off the power of vacuum pump.
Never charge the refrigerant over the specified amount.
Do not charge the additional refrigerant.
shorting CN30
If charging refrigerant additionally when refrigerant gas
leaks, the refrigerant composition in the refrigerating cycle
changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is
charged and an abnormal high pressure is applied to the
inside of the refrigerating cycle resulted in cause of
breakage or injury.
.
Leave it as it is for 1 to 2 minutes and check the indicator
of the compound gauge does not return.
Set the refrigerant cylinder on the electronic balance,
connect the charge hose to connecting ports of the
cylinder and the gauge manifold, and then charge the
liquid refrigerant from the service port at liquid side.
(Shield with the gauge manifold so that refrigerant does
not flow to gas side.)
Low-
pressure gauge
Connected to
indoor unit
Connected to other
terminal units
Main
pipe
Brazed
Fully
tightened
Valve fully closed
(gas side)
Center unit
Service
port
Copper pipe
Service port
Valve fully closed
(liquid side)
VL VH
Ø6.4
4mm-hexagonal wrench is required.
High-
pressure gauge
Gauge
manifold
Reducing
valve
Nitrogen
Ø6.4
Copper pipe
gas
Set the equipment so that liquid refrigerant can be charged.
When using a cylinder with siphon pipe, liquid can be charged without inverting the cylinder.
[ Cylinder with siphon ][ Cylinder without siphon ]
Refrigerant
cylinder
Electronic
balance
Gauge manifold
OUTDOOR unit
Electronic
balance
Gauge manifold
cylinder
Refrigerant
OUTDOOR unit
Siphon
R410A refrigerant is consisted with HFC mixed refrigerant.
Therefore if the refrigerant gas is charged, the composition
of the charged refrigerant changes and characteristics of
the equipment changes.
6. Environmental concern
Use “Vacuum pump method” for an air purge (Discharge of air in the connecting pipe) in installation time.
• Do not discharge flon gas into the air to protect the earth environment.
• Using the vacuum pump method, clear the remaining air (Nitrogen, etc.) in the unit. If the air remains , the
pressure in the refrigerating cycle becomes abnormally high and an injury could occur through failure of
the product.
009 type
012 type
015 type
018 type
024 type
027 type
030 type
036 type
048 type
007 type
009 type
012 type
015 type
018 type
007 type
009 type
012 type
015 type
018 type
024 type
027 type
030 type
007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
015 type
018 type
024 type
027 type
030 type
036 type
048 type
007 type
009 type
012 type
015 type
018 type
018 type
024 type
027 type
036 type
048 type
015 type
018 type
024 type
027 type
036 type
048 type
Capacity
code
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
0.80
1.00
1.25
1.70
2.00
0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
0.80
1.00
1.25
1.70
2.00
2.00
2.50
3.00
4.00
5.00
1.70
2.00
2.50
3.00
4.00
5.00
Cooling
capacity (kW)
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
2.2
2.8
3.6
4.5
5.6
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
2.2
2.8
3.6
4.5
5.6
5.6
7.1
8.0
11.2
14.0
4.5
5.6
7.1
8.0
11.2
14.0
Heating
capacity (kW)
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
2.5
3.2
4.0
5.0
6.3
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
2.5
3.2
4.0
5.0
6.3
6.3
8.0
9.0
10.0
16.0
5.0
6.3
8.0
9.0
12.5
16.0
PMV Kit
——
——
——
——
——
——
——
——
——
Available
Available
Available
Available
Available
——
——
——
——
——
——
——
——
Available
Available
Available
Available
Available
Available
007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
015 type
018 type
024 type
015 type
018 type
024 type
027 type
036 type
048 type
Capacity
code
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
1.70
2.00
2.50
3.00
4.00
5.00
Cooling
capacity (kW)
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
4.5
5.6
7.1
8.0
11.2
14.0
Heating
capacity (kW)
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
5.0
6.3
8.0
9.0
10.0
16.0
PMV Kit
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
——
——
——
——
——
——
——
——
——
——
——
——
Allocation standard of model name
MMAPH--
Destination C : China
H : Heat pump type
M : Compact 4-way Cassete Type
W: 2-way Cassette Type
S : 1-way Cassette Type
Y : Small sized 1-way Cassette Type
B : Built-in Type (Built-in Duct Type) (Floor concealed type)
SP(S) : Slim Duct Type
Development series No.
Based on the cooling capacity (Btu/h) /1,000
R410A
U : Cassette Type
C : Under Ceiling Type
D : Duct Type
K : High Wall Type
L : Floor Type (Cabinet type) (Concealed type)
F : Floor Standing Type
MM : Modular Multi type
12
1-1-3. Branching Joints and Headers *1
1st revised : Jun. 2006
Model name
Y-shape branching joint
4-branching header *1
8-branching header *1
*1: For each line after branching header, total indoor capacity code must be 6.0 maximum.
RBM-BY53E
RBM-HY1043E
RBM-HY1083E
Appearance
1-1-4. PMV Kit
Model name
RBM-PMV0361E
RBM-PMV0901E
Indoor unit capacity type
007, 009, 012 type
015, 018, 024 type
Appearance
13
1-1-5. Remote Controller
Name
Wired remote controller
Model
name
RBC- AMT31ERBC- AS21E2
AppearanceApplication
Connected to indoor unit
Wired remote
controller
Wired remote
controller
In case of control by
( )
2 remote controllers
Connected to indoor unit
TEST
SETTING
ûC
ûF
Function
• Star t / Stop
• Mode Change
• Temperature setting
• Fan speed
• Timer function
1) On or off elapsed timer with
30 minutes increments.
Automatic off function.
2) Weekly when combined with
RBC-EXW21E2 weekly schedule
operation can be operated.
• Filter dirty indicator
Displays automatically maintenance time
of indoor filter by flashes.
• Self-diagnosis function. Pressing
“CHECK” button displays status code.
• Control by 2 remote controllers is available.
Two remote controllers can be connected
to one indoor unit.
The indoor unit can be separately
operated from a different location.
• Star t / Stop
• Temperature setting
• Change of air flow
• Check code display
Simple wired remote controller
Wireless remote controller kit
Simple remote controller
• Star t / Stop
• Mode change
• Temperature setting
• Change of air flow
• Timer function
On or off timer operation, setting in 30
minutes increments.
Automatic Off function.
• Control by 2 remote controllers is available.
Two wireless remote controllers can
operate one indoor unit.
The indoor unit can be separately
operated from a different location.
• Check code display
TCB-AX21U(W)-E2
(for 4-way air discharge cassette)
RBC-AX22CE2 (for under ceiling)
TCB-AX21-E2 (for other units except for
the concealed duct high static pressure)
TCB- AX21U(W)-E2RBC-AX22CE2TCB-AX21E2
14
Name
Model
name
AppearanceApplication
Performance
Central remote controllerON- OFF controller
ZONE
ALL
ZONE
GROUP
1234
TEST
UNIT No.
SET DATA
SETTING
R.C.
No.
SELECT ZONE
TCB- SC642TLE2TCB- CC163TLE2
CL
SET
GROUP
CODE
Connected to outdoor unit
or indoor unit
Individual control up to 64 indoor units.
Individual control for max. 64 indoor
units divided into 4 zones.
Outdoor unit
(Up to 16 indoor units for each zone)
Up to 16 outdoor units are connect-
able.
Four selectable central control settings
to restrict individual remote controller
operations.
Setting for one of 1 to 4 zones is
available.
Can be used with other central control
No.
devices (Up to 10 central control
devices with in one control circuit)
Two selectable control modes
(Central controller mode.
Central
remote controller
Remote controller mode)
Setting of simultaneous ON/OFF 3
times for each day of the week
combined with a weekly timer.
Central
remote
controller
Indoor
remote controller
Connected to outdoor unit
or indoor unit
Outdoor unit
ON-OFF
controller
Indoor unit
• Individual control up to 16 indoor
units.
• Setting of simultaneous ON-OFF 3
times for each day of the week when
combined with a weekly timer.
• Connected to 2 remote controllers is
possible.
ON-OFF
controller
Indoor
remote controller
15
Name
Model
name
AppearanceApplication
Performance
Weekly timer
PROGRAM1
PROGRAM2
PROGRAM3
WEEKLY TIMER
RBC- EXW21E2
SuMoTuWeTh FrSa
ERROR
Connected to central
remote controller or
wired remote controller
Wired
remote controller
Outdoor unit
Weekly
timer
Weekly schedule operation
1) Setting different start / stop time for
each day of the week
2) ON / OFF can be set 3 times a day.
ON
8:0012:00 13:00 18:00 19:00 21:00
OFF ONOFF ONOFF
3) “CHECK“ “PROGRAM” “DAY” button
copying of settings easy.
4) Two different schedules for a week
can be specified.
(Summer schedule and winter
schedule, etc.)
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Indoor unit
Earth screw
Flow selector
unit earth
S(N)R(L)
Power supply
Single phase
220-240V 50Hz
220V 60Hz
FM
screw
Closed end
connector
CN039
(YEL)
WHI
121
2
RED
343
4
565
6
77
9
(BLK)
CN304
(GRY)
1
2
3
1
2
3
CN066
(WHI)
CN044
(BRW)
TR
Line Filter
1
Outdoor unit
1
2
3
1
2
3
1
2
3
1
2
1
2
U2U
P301
CN067
(BLK)
CN040
(BLU)
1 2
1 2
BLU
U
1
BLU
U
RY004
Fuse
T5.0A
250V~
CN041
(BLU)
1 2 3
1 2 3
BLK
BLK
BA
2
CN1
(WHI)
1 2
1 2
Remote controller
FAN
CN083
YX
(WHI)
RED
RY007
3 3
1 1
CN02
(BLU)
RC
BLK
9 8 7 6
9 8 7 6
ORN
5 4 3 2 1
5 4 3 2 1
HML UL
RY006
RY005
CN050
(WHI)
1 2 3 4 5
Network
1 2
1 2
adaptor
(Option)
CN01
(WHI)
2
MCC-1401
LM
DP
(BLU)
CN068
RY001
1 2
1 2
1 2 3
1 2 3
LM
(GRN)
CN033
FS
1 2 3
1 2 3
DM
YEL
BLU
1 2 3
1 2 3
RY002
Indoor control P.C. board
Power supply
circuit
CN074
(WHI)
CN075
(WHI)
1 2 3
1 2 3
1 2 3
4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6
1 2 3 4 5 6
1 1
TR
2 2
CN03
(RED)
1. indicates the terminal block, letter at inside
indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
CN02
(YEL)
CN01
(WHI)
CN061
(YEL)
1 2 3 4 5 61 2 3 4 5 6
FS
(RED)
CN030
6 4 3
6 4 3
1 2 3
1 2 3
CN032
(WHI)
1 2
Fan drive
Symbol
FM
RC
TR
LM
TA
TC1,TC2,TCJ
RY001
RY002
RY004
RY005~007
FS
DM
PMV
PMV
1 2 5
1 2 5
PMV
4 5 6
(BLU)
4 5 6
CN082
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN060
(WHI)
1 2 3 4 5 6
Option
Parts name
Fan motor
Running capacitor
Transformer
Louver motor
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Heater control relay
Fan motor control relay
Float switch
Drain pump motor
Pulse Motor Valve
2-1-3. 1-way Air Discharge Cassette Type (Compact type)
Model: MMU-AP0071YH, AP0091YH, AP0121YH
20
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Indoor unit
Earth screw
Flow selector
WHI
RED
RED
S(N)R(L)
Power supply
Single phase
220-240V 50Hz
220V 60Hz
FM
unit earth
screw
Closed end
connector
WHI
RC
2
4
6
CN304
(GRY)
CN309
(YEL)
AC IN
CN066
(WHI)
BLU
121
343
565
CN301
(BLK)
Heater
1
2
3
1
2
3
TR
Line Filter
1
Outdoor
unit
1
2
3
1
2
3
1
2
3
1
2
U2U
CN067
(BLK)
CN044
(BRW)
1 2
1 2
BLU
U
1
BLU
RY004
Fuse
T5.0A
CN040
(BLU)
1 2
1 2
BLU
BLK
BLU
U
2
1 2
1 2
Remote controller
BLK
BA
CN1
(WHI)
CN041
1 2 3
13
FAN
CN083
(BLU)
YX
AI-NET
central control
terminal
(WHI)
BLK
RED
9 8 7 6
9 8 7 6
HML UL
RY007
CN050
(WHI)
1 2 3 4 5
MCC-1401
CN01
(WHI)
1 1
Network
2 2
adaptor
CN03
P.C. board
(RED)
ORN
5 4 3 2 1
5 4 3 2 1
RY006
RY005
Network
1 2
adaptor
(Option)
1 2
2 1
2331
DM
1 2 3
1 2 3
YEL
BLU
RY002
1 2 3
1 2 3
CN068
DP
(BLU)
RY001
LM
2 1
2 1
1 2 3
1 2 3
LM
(GRN)
CN033
Indoor control P.C. board
Power supply
circuit
4 5 6
CN075
(WHI)
CN02
(YEL)
CN01
(WHI)
TR
CN074
(WHI)
1 2 3
1 2 3
1 2 3
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6
1 2 3 4 5 6
CN02
(BLU)
1. indicates the terminal block, letter at inside
indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
2 1
2 1
1 2 3
1 2 3
1 2 3 4 5 61 2 3 4 5 6
FS
CN061
(YEL)
FS
(RED)
CN030
6 4 3
6 4 3
1 2 3
1 2 3
CN032
(WHI)
1 2
Fan drive
Symbol
FM
RC
TR
LM
TA
TC1,TCJ
RY001
RY002
RY004
RY005~007
FS
DM
PMV
PMV
1 2 5
1 2 5
4 5 6
4 5 6
CN082
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN060
(WHI)
1 2 3 4 5 6
Option
Fan motor
Running capacitor
Power transformer
Louver motor
Indoor temp sensor
Temp sensor
Louver motor control relay
Drain pump control relay
Heater control relay
Fan motor control relay
Float switch
Drain pump motor
Pulse Motor Valve
PMV
(BLU)
121
2
121
2
TCJ
1
2
121
2
33
1
PNL
2
3
1
EXCT
2
1
1
Filter
2
2
1
2
3
4
5
Parts name
TA
TC1
2-1-4. 1-way Air Discharge Cassette Type
Model: MMU-AP0152SH, AP0182SH, AP0242SH
21
Indoor unit
earth screw
S(N)R(L)
Power supply
single phase
220-240V 50Hz
220V 60Hz
FM
TA
TC1
TCJ
TC2
LM
DM
FS
RY302
PMV
TR
Flow selector unit
earth screw
RED
WHI
Closed-end
connector
U
U
1
Outdoor
unit
Symbol
1
2
U2U
Fan motor
Indoor temp sensor
Temp sensor
Temp sensor
Temp sensor
Louver motor
Drain pump motor
Float switsh
Drain control relay
Pulse motor valve
Transformer
BA
A B
Wired
remote
controller
Parts name
WHI
WHI
2
112
CN001(WHI)
Adapter for
wireless remote
controller
BLK
BLK
Color
indication
RED: RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY: GRAY
PNK: PINK
ORN: ORANGE
BRN: BRWN
GRN: GREEN
TR
131
2
3
MCC-1401
AI-NET
Network adapter
CN02
(BLU)
(Option)
RED
WHI
112
CN01
(WHI)
CN03
(RED)
112
X Y
PMV
FM
5
5
CN82
(BLU)
6
CN112
Power
supply
circuit
Control P.C. board
CN32
(WHI)
Fan
drive
High ceiling setup
1 2
1 21 21 2
CN111
(WHI)
(WHI)
DC20V
DC15V
DC12V
DC7V
for indoor unit
MCC-1402
CN60
(WHI)
1 2 3 4 5 6
Option
CN110
(WHI)
1 2 3 4 5
1
2
3
4
6
1
2
3
4
6
CN334
5 41
(WHI)
313
1
3
1
T6.3A 250V~
3
1
2
2
2
131
2
3
RY302
RY303
P301
CN66
(WHI)
CN40
(BLU)
CN41
(BLU)
Fuse
5
1
3
1
3
CN68
(BLU)
1
DM
CN304
(GRY)
1
CN67
(BLK)
3
BLK
BLU
1
1
2
2
BLU
BLK
BLK
CN309
(YEL)
1
1
Motor drive
CN50
(WHI)
1 2 3 4 5
CN333
1 2 3 4 5 6
5
3
(WHI)
1
2
3
4
54 3
32 1
5
circuit
Fuse
T3.15A
250V~
CN061
(YEL)
1 21 23 4 5 61 2 3 4 5
T10GRL
1. indicates the terminal bolock letter.
Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the
wiring at side
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
RED
WHI
Closed
end
connector
Indoor unit
Earth screw
S(N)R(L)
Power supply
Single phase
220-240V 50Hz
220V 60Hz
(BLK)
CN304
(GRY)
1
2
3
1
2
3
TR
Flow selector
unit earth
screw
T10A,250V~
Closed end
connector
Surge
absorber
87
43F1
FAN
CN083
(WHI)
P301
1
RY004
2
3
1
CN309
2
(YEL)
3
CN067
(BLK)
1
2
3
1
2
YEL
CN066
(WHI)
CN044
(BRW)
EMG
U2U
1
Outdoor unit
REDREDF
RED
6
43F1
4
Fuse
T5.0A
CN040
(BLU)
1 21 2
1 2
OC
U
1
WHI
1 2 3 4
RC
U
2
Remote controller
5
43F1
3
RED
GRY
1 2 3 4
WHI
RED
REDWHI
CN041
(BLU)
1 2 3
13
1 2
1 2
GRY
9 8 7 6
9 8 7 6
RY007
BA
5 4 3 2 1
HML UL
RY006
CN01
(WHI)
3 3
2
1 1
CN1
CN02
(WHI)
(BLU)
WHI
RC
FM
42
RY002
RY005
CN050
(WHI)
1 2 3 4 5
Network adaptor
(Option)
MCC-1401
1 2
1 2
CN03
1 2
(RED)
1 2
X Y
A
F1F2F3F
BLU
ORN
BLK
(Option)
DM
1 2 3
1 2 3
DP
(BLU)
CN068
RY001
1 2 3
1 2 3
LM
(GRN)
CN033
1 2 3
1 2 3
FS
CN030
(RED)
TA
1 2
1 2
CN104
(YEL)
Indoor control P.C. board
Power
supply
circuit
CN074
(WHI)
1 2 3
1 2 3
1 2 3
4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6
1 2 3 4 5 6
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
4. When attaching a drain pump, exchange CN030 connector with the connector
of the float switch.
5. A part is connected to the terminal block.
When exchanging to the outside static pressure necessary at the local site,
check the terminal No. and lead color of the fan motor in the below diagram,
and then exchange the lead wire indicated by the arrow mark ( ).
4
BRN
Wired for MMD-AP0481 only
(BRN Wire)
Motor over heating protection switch
CN075
BLK
WHI
GRY
RED
(WHI)
1 2 3 4 5 61 2 3 4 5 6
T10
CN02
(YEL)
CN01
(WHI)
TR
CN061
(YEL)
49F
TCJ
1 2
1 2
CN102
(RED)
CN032
(WHI)
1 2
Fan drive
BLU
ORN
BRN
CN060
(WHI)
TC1
1 2 3
1 2 3
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN082
(BLU)
TC2
1 2
1 2
CN101
(BLK)
1 2 3 4 5 6
Option
Sold
separately
CN100
(BRN)
1
2
PNL
3
1
EXCT
2
1
Filter
2
1
2
3
4
5
6
6
5
5
4
4
3
3
2
2
1
1
Symbol
FM
RC
TR
TA
TC1,TC2,TCJ
RY005~007
RY001
RY002
PMV
F
43F1
DM
FS
5
5
2
2
1
1
PMV
3
3
4
4
6
6
Parts name
Fan motor
Running capacitor
Transformer
Indoor temp sensor
Temp sensor
Fan motor control relay
Louver motor control relay
Drain control relay
Pulse Motor Valve
Fuse
Fan motor control relay
Drain pump motor
Float switch
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Symbol
FM
RC
TR
TA
TC1,TC2,TCJ
RY001
RY002
RY004
RY005~007
PMV
Parts name
Fan motor
Running capacitor
Transformer
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Heater control relay
Fan motor control relay
Pulse motor valve
28
Indoor unit
earth screw
RED
WHI
RED
R(L) S(N)
Power supply
single phase
220-240V 50Hz
220V 60Hz
Flow selector
unit earth
screw
Closed-end
connector
WHI
WHI
1
GRN
1
3
3
2
2
4
4
FM
5
5
6
6
RED
RED BLK ORN BLU YEL
FAN
CN083
(WHI)
95 3 1
RC
GRN
FM
RED
5 3 1779
WHI
For AP0071BH,AP0091BH,AP0121BH
R301
(BLK)
1
3
1
313
AC IN
1
T5.0A 250V~
313
1
CN066
(WHI)
2
1
CN044
(BRW)
2
EMG
2
112
Network
adaptor
3
2
112
CN01(WHI)
CN02
(BLU)
CN03(RED)
MCC-1401
2
(Option)
1 1
2 2
CN03
(RED)
TR
U1 U2
U1 U2
Outdoor unit
A BX Y
2
112
CN1
Remote controller
3
1 1
1. indicates the terminal block.
Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicates the control P.C. board.
(GRY)
CN304
(YEL)
CN309
FUSE
(BLK)
CN067
RC
RY004
CN040
(BLU)
112
2
2
424
5
5
6
6
3
3
RED BLK ORN BLU YEL
FAN
CN083
(WHI)
CN041
(BLU)
1 2331 2 3 4 5
1
5 3 1779
95 3 1
M LUL
H
RY007
RY006
CN050
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
RY005
(WHI)
CN068
(BLU)
RY002
CN074
(WHI)
133
1
113
3
3
CN033
(GRN)
113
RY001
Control P.C. board
for undoor unit
Power supply
circuit
CN075
MCC-1520
(WHI)
CN02
(YEL)
CN01
(WHI)
TR
1 2 3 4 5 6 1 21 23 4 5 61 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. boar d
1 2 3 4 5 6
1 2 3 4 5 6
MCC-1403
CN061
(YEL)
112 3
CN030
(RED)
Symbol
FM
RC
TR
TA
TC1,TC2,TCJ
RY001
RY002
RY004
RY005~007
PMV
PMV
1 23456
1 23456
3
CN032
(WHI)
Fan
drive
1 2 3 4 5 6
1 2 3 4 5 6
CN082
(BLU)
CN060
(WHI)
Option
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
PMV
1
212
1
212
1
1
2
2
131
2
3
1
2
3
1
2
1
2
1
2
3
4
5
Parts name
Fan motor
Running capacitor
Transformer
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Heater control reley
Fan motor control relay
Pulse motor valve
1. indicates the terminal block, letter.
Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate
the wiring at side.
3. indicates the control P.C. board.
3
CN030
112 3
MCC-1403
CN061
(YEL)
(RED)
CN032
(WHI)
Fan
drive
PMV
1 23456
1 23456
1 2 3 4 5 6
1 2 3 4 5 6
CN060
(WHI)
Option
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN082
Symbol
FM
RC
TR
LM
TA
TC1,TC2,TCJ
RY001
RY002
RY005~007
PMV
PMV
(BLU)
TA
1
212
TCJ
1
212
TC2
1
1
2
2
131
1
2
3
1
2
1
2
1
2
3
4
5
TC1
3
PNL
EXCT
Filter
Fan motor
Running capacitor
Transformer
Louver motor
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Fan motor control relay
Pulse motor valve
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN