Toshiba RBM-PMV0361E, MCY-MAP0401HT2D, RBM-PMV0901E, MCY-MAP0601HT, MCY-MAP0501HT2D SERVICE MANUAL

...
FILE NO. A05-015
st revised : Jun. 2006
SERVICE MANUAL
Mini-SUPER MODULAR MULTI SYSTEM AIR CONDITIONER
Outdoor Unit
[In verter Unit]
MCY-MAP0401HT, HTZ, HTZG MCY-MAP0501HT, HTZ, HTZG MCY-MAP0601HT, HTZ, HTZG MCY-MAP0401HT2D , HT2DZ, HT2DZG MCY-MAP0501HT2D , HT2DZ, HT2DZG MCY-MAP0601HT2D , HT2DZ, HT2DZG
PMV Kit
RBM-PMV0361E RBM-PMV0901E
In addition to description for the normal-type model, descriptions about the models with anti-corrosion (based on JRA Standard light protection and heavy protection) models are added in this Manual.
PRINTED IN JAPAN, Sep.,2006 ToMo
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
Concentration limit (kg/m³)
The concentration limit of R410A which is used in multi air conditioners is 0.3kg/m³.
NOTE 1 :
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.
e.g., charged amount (10kg)
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg.
Outdoor unit
e.g., charged amount (15kg)
Indoor unit
Important
NOTE 2 :
The standards for minimum room volume are as follows. (1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit
(3) If an indoor unit is installed in each partitioned room
and the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
Refrigerant piping
Outdoor unit
Very small room
Small room
Mechanical ventilation device - Gas leak detector
Medium room
Large room
NOTE 3 :
The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high)
40
Range below the
35
m²
density limit of 0.3 kg/m³
30
(countermeasures not needed)
25 20 15 10
5
Min. indoor floor area
0
10 20 30
Total amount of refrigerant
Range above the density limit of 0.3 kg/m³ (countermeasures needed)
Indoor unit
kg
1st revised : Jun. 2006, 2nd revised : Sep. 2006
CONTENTS
SAFETY CAUTION ............................................................................................ 4
1. DESIGN METHODS................................................................................ 10
2. WIRING DIAGRAM ................................................................................. 18
3. PARTS RATING ...................................................................................... 33
4. REFRIGERANT PIPING SYSTEMATIC DRAWING ............................... 51
5. SWITCH (SW08) SET UP OF THE OUTDOOR UNIT............................. 54
6. CONTROL OUTLINE .............................................................................. 55
7. APPLIED CONTROL .............................................................................. 63
8. PMV KIT OUT LINE ................................................................................ 79
9. TEST OPERATION ................................................................................. 81
10. TROUBLESHOOTING .......................................................................... 110
11. CONFIGURATION OF CONTROL CIRCUIT ........................................ 154
12. BACKUP OPERATIONS (EMERGENCY OPERATION)....................... 168
13. REPLACING PROCEDURE OF PARTS............................................... 169
14. P.C. BOARD .......................................................................................... 183
15. EXPLODED VIEWS AND PARTS LIST ................................................ 189
In addition to description for the normal-type model, descriptions about the models with anti-corrosion (based on JRA Standard light protection and heavy protection) models are added in this Manual.
3
SAFETY CAUTION
The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication
DANGER
WARNING
CAUTION
Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage ( ) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Explanation
[Explanation of illustrated marks]
Mark Explanation
Indicates prohibited items (Forbidden items to do) The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do) The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (including danger/warning) The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions (Refer to the Parts disassembly diagram (Outdoor unit).)
If removing the label during parts replace, stick it as the original.
DANGER
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric shock is caused by high voltage resulted in a death or injury.
During operation, a high voltage with 400V or higher of circuit () at secondary circuit of the high­voltage transformer is applied.
Turn off breaker.
Execute discharge
between terminals.
Prohibition
If touching a high voltage with the naked hands or body, an electric shock is caused even if using an electric insulator.
: For details, refer to the electric wiring diagram.
When removing the front panel or cabinet, execute short-circuit and discharge between high­voltage capacitor terminals.
If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury. After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor.
Do not turn on the breaker under condition that the front panel and cabinet are removed.
An electric shock is caused by high voltage resulted in a death or injury.
4
Check earth wires.
Prohibition of modification.
Use specified parts.
Do not bring a child
close to the equipment.
Insulating measures
No fire
Refrigerant
Assembly/Wiring
WARNING
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs.
If the earth wire is not correctly connected, contact an electric engineer for rework.
Do not modify the products.
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
For spare parts, use those specified (*).
If unspecified parts are used, a fire or electric shock may be caused. : For details, refer to the parts list.
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except the repair engineers close to the equipment.
It causes an injury with tools or disassembled parts. Please inform the users so that the third party (a child, etc.) does not approach the equipment.
Connect the cut-off lead wires with crimp contact, etc, put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables.
(For more details, please refer Page 7 to Page 9)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
Check the used refrigerant name and use tools and materials of the parts which match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service port is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refriger­ating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refrigerant with recover­ing device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
After repair work, surely assemble the disassembled parts, and connect and lead the removed cables as before. Perform the work so that the cabinet or panel does not catch the inner cables.
If incorrect assembly or incorrect cable connection was done, a disaster such as a leak or fire is caused at user’s side.
5
WARNING
Insulator check
Ventilation
Be attentive to
electric shock
Compulsion
After the work has finished, be sure to use an insulation tester set (500V mugger) to check the resistance is 2M metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electr ic shock is caused at user’s side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.
When checking the circuit inevitably under condition of the power-ON, use rubber gloves and others not to touch to the charging section.
If touching to the charging section, an electric shock may be caused.
When the refrigerant gas leaks, find up the leaked position and repair it surely.
If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shor tage of oxygen is caused.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused.
ΩΩ
or more between the charge section and the non-charge
ΩΩ
Check after rerair
Check after reinstallation
Put on gloves
Cooling check
After repair work has finished, check there is no trouble.
If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable. If check is not executed, a fire, an electric shock or an injury is caused.
CAUTION
Be sure to put on gloves (
If not putting on gloves, an injury may be caused with the parts, etc. () Heavy gloves such as work gloves
When the power was turned on, start to work after the equipment has been sufficiently cooled.
As temperature of the compressor pipes and others became high due to cooling/heating operation, a burn may be caused.
∗∗
) during repair work.
∗∗
6
• New Refrigerant (R410A)
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water , dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refrigerant during installation work or service work. If an incorrect work or incorrect service is per­formed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
1) Do not mix the other refrigerant or refrigerating oil. For the tools e xclusive to R410A, shapes of all the joints including the service port differ from those of the
former refrigerant in order to prev ent mixture of them.
2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are specified for R410A.
3) In the installation time , use clean pipe materials and work with great attention so that water and others do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc. Use the clean pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
4) For the earth protection, use a vacuum pump for air purge.
5) R410A refrigerant is azeotropic mixture type refriger ant. Therefore use liquid type to charge the refriger­ant. (If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropri­ate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a minimum.
1) Copper pipe
<Piping>
The pipe thickness, flare finishing size , flare nut and others differ according to a refrigerant type. When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without
seam and one with bonded oil amount 40mg/10m or less . Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
2) Joint The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installa-
tion of the air conditioner. However clear impurities when using them.
7
4. Tools
(1)Required T ools for R410A
Mixing of different types of oil ma y cause generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conv entional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
Used tool
Flare tool Copper pipe gauge for
adjusting projection margin
Torque wrench Gauge manifold Charge hose V acuum pump adapter Electronic balance for
refrigerant charging Refrigerant cylinder Leakage detector Charging cylinder
Usage
Pipe flaring
Flaring by conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
V acuum evacuating
Refrigerant charge
Refrigerant charge Gas leakage check Refrigerant charge
air conditioner installation
Existence of new equipment for R410A
Yes
Yes
Yes
Yes
Yes
Yes
Yes Yes
(Note 2)
R410A
Whether conventional equipment can be used
*(Note 1)
*(Note 1)
No
No
No
Yes
No No No
Conventional air
conditioner installation
Whether new equipment can be used with conventional refrigerant
Yes
*(Note 1)
No
No
Yes
Yes
No
Yes
No
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the f ollowing equipments which serve also for R22 are necessary as the general tools.
1) Vacuum pump Use vacuum pump by attaching vacuum pump adapter.
2) Torque wrench
3) Pipe cutter
4) Reamer
5) Pipe bender
6) Level vial
7) Screwdriver (+, –)
8) Spanner or Monkey wrench
9) Hole core drill
10) Hexagon wrench (Opposite side 4mm)
11) Tape measure
12) Metal saw
Also prepare the following equipments for other installation method and run check.
1) Clamp meter
2) Thermometer
3) Insulation resistance tester (Megger)
4) Electroscope (Volt meter)
8
5. Recharge of Refrigerant
When recharge of the refrigerant is required, charge the new refrigerant with the specified amount in the procedure as described below .
Recover the refrigerant and check there is no refrigerant in the equipment.
Connect the charge hose to the packed valve service ports at gas side, liquid side of the outdoor unit.
Connect the charge hose to vacuum pump adaptor.
Open the packed valves fully at liquid and gas sides, and then return the valve at gas side a little to the closed side.
Open fully PMV of the outdoor unit.
• Turn on power of the outdoor unit.
• Short CN30 on I/F P.C. board of the outdoor unit.
Turn off power of the outdoor unit within 2 minutes after
Open fully the handle on the Low side of the gauge manifold, and then turn on the power of vacuum pump for vacuuming.
When the pressure has lowered until indication of the compound gauge pointed –0.1MPa (–76cmHg), open fully the handle Low and turn off the power of vacuum pump.
Never charge the refrigerant over the specified amount.
Do not charge the additional refrigerant.
shorting CN30
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteris­tics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury.
.
Leave it as it is for 1 to 2 minutes and check the indicator of the compound gauge does not return.
Set the refrigerant cylinder on the electronic balance, connect the charge hose to connecting ports of the cylinder and the gauge manifold, and then charge the liquid refrigerant from the service port at liquid side. (Shield with the gauge manifold so that refrigerant does not flow to gas side.)
Low-
pressure gauge
Connected to indoor unit
Connected to other terminal units
Main pipe
Brazed
Fully tightened
Valve fully closed (gas side)
Center unit
Service port
Copper pipe
Service port
Valve fully closed (liquid side)
VL VH
Ø6.4
4mm-hexagonal wrench is required.
High-
pressure gauge
Gauge manifold
Reducing valve
Nitrogen
Ø6.4 Copper pipe
gas
Set the equipment so that liquid refrigerant can be charged.
When using a cylinder with siphon pipe, liquid can be charged without inverting the cylinder.
[ Cylinder with siphon ] [ Cylinder without siphon ]
Refrigerant
cylinder
Electronic
balance
Gauge manifold
OUTDOOR unit
Electronic
balance
Gauge manifold
cylinder
Refrigerant
OUTDOOR unit
Siphon
R410A refrigerant is consisted with HFC mixed refrigerant. Therefore if the refrigerant gas is charged, the composition of the charged refrigerant changes and characteristics of the equipment changes.
6. Environmental concern
Use Vacuum pump method for an air purge (Discharge of air in the connecting pipe) in installation time.
Do not discharge flon gas into the air to protect the earth environment.
Using the vacuum pump method, clear the remaining air (Nitrogen, etc.) in the unit. If the air remains , the
pressure in the refrigerating cycle becomes abnormally high and an injury could occur through failure of the product.
9
123456789012345678901234567890121234567890123456789012345678901212345678901234567890123456789
1
9
1
9
1
9
1
9
1
9
1
9
1
9
1
9
1
9
1
9
1
9
1
9
1
9
123456789012345678901234567890121234567890123456789012345678901212345678901234567890123456789
1. DESIGN METHODS
1-1. System Overview
1-1-1. Outdoor Units
2nd revised : Sep. 2006
Corresponding HP
4HP 5HP 6HP
MCY-MAP0401HT MCY-MAP0501HT MCY-MAP0601HT
Heat pump (50Hz)
Model name
Heat pump (60Hz)
MCY-MAP0401HTZ MCY-MAP0501HTZ MCY-MAP0601HTZ MCY-MAP0401HTZG MCY-MAP0501HTZG MCY-MAP0601HTZG
MCY-MAP0401HT2D MCY-MAP0501HT2D MCY-MAP0601HT2D MCY-MAP0401HT2DZ MCY-MAP0501HT2DZ MCY-MAP0601HT2DZ MCY-MAP0401HT2DZG MCY-MAP0501HT2DZG MCY-MAP0601HT2DZG
Cooling capacity (kW) ∗1 Heating capacity (kW) ∗1 No.of connectable indoor units
12.1 14.0 15.5
12.5 16.0 18.0 689
1 Rated conditions
Cooling:Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating:Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Inverter unit
Allocation standard of model name
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
MCY- M AP H T 2D
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
2345678901234567890123456789012123456789012345678901234567890121234567890123456789012345678
Z : Anti-corrosion (light protection type) ZG : Anti-corrosion (heavy protection) type
No mark: Power supply specification, 1Ø/220/230/240V (50Hz) 2D : Power supply specification, 1Ø/220V, 60Hz
T : Inverter unit H : Heat pump Development number Capacity rank HP × 10 R410A M : Individual unit Multi Compact type
10
1-1-2. Indoor Units
Type
4-way Air Discharge Cassette T ype
Compact 4-way Air Discharge (600 × 600) Type
2-way Air Discharge Cassette T ype
1-way Air Discharge Cassette T ype
Concealed Duct Standard T ype
Slim Duct Type
Concealed Duct High Static Pressure T ype
Under Ceilling Type
Appearance
Model name
MMU-AP0091H MMU-AP0121H MMU-AP0151H MMU-AP0181H MMU-AP0241H MMU-AP0271H MMU-AP0301H MMU-AP0361H MMU-AP0481H MMU-AP0071MH MMU-AP0091MH MMU-AP0121MH MMU-AP0151MH MMU-AP0181MH MMU-AP0071WH MMU-AP0091WH MMU-AP0121WH MMU-AP0151WH MMU-AP0181WH MMU-AP0241WH MMU-AP0271WH MMU-AP0301WH MMU-AP0071YH MMU-AP0091YH MMU-AP0121YH MMU-AP0152SH MMU-AP0182SH MMU-AP0242SH MMD-AP0071BH MMD-AP0091BH MMD-AP0121BH MMD-AP0151BH MMD-AP0181BH MMD-AP0241BH MMD-AP0271BH MMD-AP0301BH MMD-AP0361BH MMD-AP0481BH MMD-AP0071SPH MMD-AP0091SPH MMD-AP0121SPH MMD-AP0151SPH MMD-AP0181SPH MMD-AP0181H MMD-AP0241H MMD-AP0271H MMD-AP0361H MMD-AP0481H MMC-AP0151H MMC-AP0181H MMC-AP0241H MMC-AP0271H MMC-AP0361H MMC-AP0481H
Capacity
rank
009 type 012 type 015 type 018 type 024 type 027 type 030 type 036 type 048 type 007 type 009 type 012 type 015 type 018 type 007 type 009 type 012 type 015 type 018 type 024 type 027 type 030 type 007 type 009 type 012 type 015 type 018 type 024 type 007 type 009 type 012 type 015 type 018 type 024 type 027 type 030 type 036 type 048 type 007 type 009 type 012 type 015 type 018 type 018 type 024 type 027 type 036 type 048 type 015 type 018 type 024 type 027 type 036 type 048 type
Capacity
code
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
0.80
1.00
1.25
1.70
2.00
0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
0.80
1.00
1.25
1.70
2.00
2.00
2.50
3.00
4.00
5.00
1.70
2.00
2.50
3.00
4.00
5.00
Cooling
capacity (kW)
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
2.2
2.8
3.6
4.5
5.6
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
2.2
2.8
3.6
4.5
5.6
5.6
7.1
8.0
11.2
14.0
4.5
5.6
7.1
8.0
11.2
14.0
Heating
capacity (kW)
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
2.5
3.2
4.0
5.0
6.3
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
2.5
3.2
4.0
5.0
6.3
6.3
8.0
9.0
10.0
16.0
5.0
6.3
8.0
9.0
12.5
16.0
PMV Kit
—— —— —— —— —— —— —— —— ——
Available Available Available Available Available
—— —— —— —— —— —— —— ——
Available Available Available Available Available Available
—— —— —— —— —— —— —— —— —— ——
Available Available Available Available Available
—— —— —— —— —— —— —— —— —— —— ——
11
1st revised : Jun. 2006, 2nd revised : Sep. 2006
Type
High Wall Type (1 series)
High Wall Type (2 series)
Floor Standing Cabinet T ype
Floor Standing Concealed T ype
Floor Standing Type
Appearance
Model name
MMK-AP0071H MMK-AP0091H MMK-AP0121H MMK-AP0151H MMK-AP0181H MMK-AP0241H
MMK-AP0072H
MMK-AP0092H
MMK-AP0122H MML-AP0071H
MML-AP0091H MML-AP0121H MML-AP0151H MML-AP0181H MML-AP0241H MML-AP0071BH MML-AP0091BH MML-AP0121BH MML-AP0151BH MML-AP0181BH MML-AP0241BH MMF-AP0151H MMF-AP0181H MMF-AP0241H MMF-AP0271H MMF-AP0361H MMF-AP0481H
Capacity
rank
007 type 009 type 012 type 015 type 018 type 024 type
007 type
009 type
012 type 007 type
009 type 012 type 015 type 018 type 024 type 007 type 009 type 012 type 015 type 018 type 024 type 015 type 018 type 024 type 027 type 036 type 048 type
Capacity
code
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
1.70
2.00
2.50
3.00
4.00
5.00
Cooling
capacity (kW)
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
4.5
5.6
7.1
8.0
11.2
14.0
Heating
capacity (kW)
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
5.0
6.3
8.0
9.0
10.0
16.0
PMV Kit
Available Available Available Available Available Available
Available
Available
Available Available
Available Available Available Available Available
—— —— —— —— —— —— —— —— —— —— —— ——
Allocation standard of model name
MM AP H--
Destination C : China H : Heat pump type M : Compact 4-way Cassete Type
W: 2-way Cassette Type S : 1-way Cassette Type Y : Small sized 1-way Cassette Type B : Built-in Type (Built-in Duct Type) (Floor concealed type) SP(S) : Slim Duct Type
Development series No. Based on the cooling capacity (Btu/h) /1,000 R410A
U : Cassette Type C : Under Ceiling Type D : Duct Type K : High Wall Type L : Floor Type (Cabinet type) (Concealed type) F : Floor Standing Type
MM : Modular Multi type
12
1-1-3. Branching Joints and Headers *1
1st revised : Jun. 2006
Model name
Y-shape branching joint
4-branching header *1
8-branching header *1
*1: For each line after branching header, total indoor capacity code must be 6.0 maximum.
RBM-BY53E
RBM-HY1043E
RBM-HY1083E
Appearance
1-1-4. PMV Kit
Model name
RBM-PMV0361E
RBM-PMV0901E
Indoor unit capacity type
007, 009, 012 type
015, 018, 024 type
Appearance
13
1-1-5. Remote Controller
Name
Wired remote controller
Model name
RBC- AMT31ERBC- AS21E2
Appearance Application
Connected to indoor unit
Wired remote
controller
Wired remote
controller
In case of control by
( )
2 remote controllers
Connected to indoor unit
TEST
SETTING
ûC ûF
Function
Star t / Stop
Mode Change
Temperature setting
Fan speed
Timer function
1) On or off elapsed timer with 30 minutes increments. Automatic off function.
2) Weekly when combined with RBC-EXW21E2 weekly schedule operation can be operated.
Filter dirty indicator Displays automatically maintenance time of indoor filter by flashes.
Self-diagnosis function. PressingCHECK button displays status code.
Control by 2 remote controllers is available.
Two remote controllers can be connected to one indoor unit. The indoor unit can be separately operated from a different location.
Star t / Stop
Temperature setting
Change of air flow
Check code display
Simple wired remote controller
Wireless remote controller kit
Simple remote controller
Star t / Stop
Mode change
Temperature setting
Change of air flow
Timer function
On or off timer operation, setting in 30 minutes increments. Automatic Off function.
Control by 2 remote controllers is available. Two wireless remote controllers can operate one indoor unit. The indoor unit can be separately operated from a different location.
Check code display TCB-AX21U(W)-E2 (for 4-way air discharge cassette) RBC-AX22CE2 (for under ceiling) TCB-AX21-E2 (for other units except for the concealed duct high static pressure)
TCB- AX21U(W)-E2 RBC-AX22CE2 TCB-AX21E2
14
Name
Model name
Appearance Application
Performance
Central remote controllerON- OFF controller
ZONE
ALL ZONE GROUP
1234
TEST
UNIT No.
SET DATA
SETTING
R.C.
No.
SELECT ZONE
TCB- SC642TLE2TCB- CC163TLE2
CL
SET
GROUP
CODE
Connected to outdoor unit
or indoor unit
Individual control up to 64 indoor units. Individual control for max. 64 indoor
units divided into 4 zones.
Outdoor unit
(Up to 16 indoor units for each zone) Up to 16 outdoor units are connect-
able. Four selectable central control settings
to restrict individual remote controller operations.
Setting for one of 1 to 4 zones is available.
Can be used with other central control
No.
devices (Up to 10 central control devices with in one control circuit)
Two selectable control modes (Central controller mode.
Central
remote controller
Remote controller mode) Setting of simultaneous ON/OFF 3
times for each day of the week combined with a weekly timer.
Central remote
controller
Indoor
remote controller
Connected to outdoor unit
or indoor unit
Outdoor unit
ON-OFF
controller
Indoor unit
Individual control up to 16 indoor
units.
Setting of simultaneous ON-OFF 3 times for each day of the week when combined with a weekly timer.
Connected to 2 remote controllers is possible.
ON-OFF controller
Indoor
remote controller
15
Name
Model name
Appearance Application
Performance
Weekly timer
PROGRAM1 PROGRAM2 PROGRAM3
WEEKLY TIMER
RBC- EXW21E2
SuMoTuWeTh FrSa
ERROR
Connected to central
remote controller or
wired remote controller
Wired
remote controller
Outdoor unit
Weekly
timer
Weekly schedule operation
1) Setting different start / stop time for
each day of the week
2) ON / OFF can be set 3 times a day.
ON
8:00 12:00 13:00 18:00 19:00 21:00
OFF ON OFF ON OFF
3) CHECK“ “PROGRAM” “DAY button
copying of settings easy.
4) Two different schedules for a week
can be specified. (Summer schedule and winter schedule, etc.)
5) CANCEL” “DAY” button enables
holiday setting.
6) If power supply fails, the setting
contents are stored in the memory for 100 hours.
Central
remote controller
Weekly
timer
16
n Remote controllers
Name
Appearance
Model name
Name
Appearance
Wired remote controller
UNIT No.
R.C. No.
CODE No.
ON / OFF
FAN
MODE
SWING/FIXTIME
VENT
UNITSET CL
FILTER RESET
DATA
SET
TEST
SETTING
H
TEMP.
TIMER SET
TEST
RBC-AMT31E
Receiver section
ADR
Simple wired remote controller
TEST
SETTING
˚C ˚F
RBC-AS21E2
Wireless remote controller kit
ADR
Receiver section
Weekly timer
PROGRAM1 PROGRAM2 PROGRAM3
WEEKLY TIMER
SuMoTuWeThFr Sa
ERROR
RBC-EXW21E2
Receiver section
mounted separately
ADR
Model name
Type
Name
Appearance
Model name
Type
RBC-AX21U (W)-E2
4-way Air Discharge
Cassette type
Central remote controller
ZONE
ALL ZONE GROUP
1234
UNIT No.
SET DATA
SETTING
R.C.
No.
SELECT ZONE
CL
TEST
SET
GROUP
CODE
No.
TCB-SC642TLE2
64 system center controller
RBC-AX22CE2
Under Ceiling type
1-way Air Discharge Cassette
type (MMU-AP✽✽✽2SH Series)
ON, OFF controller
TCB-CC163TLE2
TCB-AX21E2
Separate sensor type
17

2. WIRING DIAGRAM

2-1. Indoor Unit
2-1-1. 4-way Air Discharge Cassette Type
Model: MMU-AP0091H, AP0121H, AP0151H, AP0181H, AP0241H,
18
Indoor unit
Earth screw
Symbol
FM
TA TC1 TCJ TC2
LM1, LM2
DM
FS
RY302
PMV
Flow selector
S(N)R(L)
Power supply
Single phase 220-240V 50Hz 220V 60Hz
Fan motor Indoor temp sensor Temp sensor Temp sensor Temp sensor Louver motor Drain pump motor Float switch Drain control relay Pulse Motor Valve
DM
unit earth
screw
RED
WHI
Closed end connector
Parts name
FM
CN334
5 4 3 2 1 5 4 3 2 1
RY302
RY303
Fuse
T6.3A
250V~
~
~
P301
CN50 (WHI)
CN32 (WHI)
1 2
4 5 6
(Fandrive)
CN304 (GRY)
RED
CN67 (BLK)
WHI
CN66
(WHI) CN44
(BLN)
CN68 (BLU)
1
2
3
1
2
3
BLK
1
2
3
1
2
3
1
2
3
1 2
1 2
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
Color identification
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BRN : BROWN
1 2 3 4 5
(BLU)
1 2 3 4 5 6
Motor drive
circuit
+
CN61 (YEL)
T10
1 2 3 4 51 2 3
BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE GRN : GREEN
CN333
(WHI)
Fuse
T3.15A
250V~
6 4 3 1 2 5 6 4 3 1 2 5
1 2 3 4 5 6 1 2 3 4 5
CN60 (WHI)
1 2
3 4 5 6
(Option)
U2U
1
Outdoor unit
PMV
Power supply circuit
U
U
1
LM2
1 2 3 4 5 1 2 3 4 5
CN82 (BLU)
Indoor control P.C. board
MCC-1402
DC20V DC15V DC12V DC7V
CN81 (BLK)
1 2 3 4 5
BA
2
CN1
(WHI)
1 2 1 2
Wired remote
controller
CN40 (BLU)
1 2 1 2
BLU
WHI BLK
Adaptor for wireless
remote controller
BLU
1 2 1 2
LM1
1 2 3 4 5 1 2 3 4 5
1 2 3 4 5 1 2 3 4 5
CN41 (BLU)
1 2 3 1 2 3
BLK
BLK
BLK
WHI
CN001 (WHI)
1 2 3 4 5 1 2 3 4 5
CN33 (WHI)
CN309
(YEL)
1 2 3 1 2 3
1 2
CN01 (WHI)
3 3 2 2 1 1
CN02 (BLU)
The network adapter MCC1401 cannot be mounted to the Compact 4-way Cassette type (MMU-AP0071MH and MMU-AP0181MH) models.
Network adaptor (Option)
1 2
Network adaptor P.C. board
1 2 1 2
X Y
CN20 (BLU)
1 2 3 4 5
TR
MCC-1401
CN03
(RED)
3 1 321
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRN)
CN80
(GRN)
CN73
(RED)
CN70
(WHI)
FS
CN34
(RED)
121
2
121
2
121
2
121
2
33
1
PNL
2 3
1
EXCT
2 1
Filter input
2
TA
TCJ
TC2
MMU-AP0271H, AP0301H, AP0361H, AP0481H, AP0561H,
MMU-AP0071MH, AP0091MH, AP0121MH, AP0151MH, AP0181MH
TC1
2nd revised : Sep. 2006
19
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
Indoor unit
Earth screw
Flow selector
unit earth
S(N)R(L)
Power supply
Single phase 220-240V 50Hz 220V 60Hz
FM
screw
Closed end connector
CN039
(YEL)
WHI
121
2
RED
343
4
565
6
77
9
(BLK)
CN304
(GRY)
1
2
3
1
2
3
CN066
(WHI)
CN044 (BRW)
TR
Line Filter
1
Outdoor unit
1
2
3
1
2
3
1
2
3
1 2
1 2
U2U
P301
CN067
(BLK)
CN040
(BLU)
1 2 1 2
BLU
U
1
BLU
U
RY004
Fuse
T5.0A
250V~
CN041
(BLU)
1 2 3 1 2 3
BLK
BLK
BA
2
CN1
(WHI)
1 2 1 2
Remote controller
FAN CN083
YX
(WHI)
RED
RY007
3 3
1 1
CN02 (BLU)
RC
BLK
9 8 7 6 9 8 7 6
ORN
5 4 3 2 1 5 4 3 2 1
HML UL
RY006
RY005
CN050
(WHI)
1 2 3 4 5
Network
1 2 1 2
adaptor (Option)
CN01 (WHI)
2
MCC-1401
LM
DP
(BLU)
CN068
RY001
1 2 1 2
1 2 3 1 2 3
LM
(GRN)
CN033
FS
1 2 3 1 2 3
DM
YEL
BLU
1 2 3 1 2 3
RY002
Indoor control P.C. board
Power supply
circuit
CN074
(WHI)
CN075
(WHI)
1 2 3 1 2 3
1 2 3
4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6 1 2 3 4 5 6
1 1
TR
2 2
CN03 (RED)
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
CN02 (YEL)
CN01 (WHI)
CN061
(YEL)
1 2 3 4 5 61 2 3 4 5 6
FS
(RED)
CN030
6 4 3 6 4 3
1 2 3 1 2 3
CN032
(WHI)
1 2
Fan drive
Symbol
FM RC
TR LM TA
TC1,TC2,TCJ
RY001 RY002 RY004
RY005~007
FS
DM
PMV
PMV
1 2 5 1 2 5
PMV
4 5 6
(BLU)
4 5 6
CN082
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100 (BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN060
(WHI)
1 2 3 4 5 6
Option
Parts name
Fan motor Running capacitor Transformer Louver motor Indoor temp sensor Temp sensor Louver control relay Drain control relay Heater control relay Fan motor control relay Float switch Drain pump motor Pulse Motor Valve
2
2
2
2
1 2 3
1 2
1 2
1 2 3 4 5
121
121
121
121
33
PNL
EXCT
1 2
TA
TCJ
TC2
Filter
TC1
2-1-2. 2-way Air Discharge Cassette Type
Model: MMU-AP0071WH, AP0091WH, AP0121WH, AP0151WH, AP0181WH,
MMU-AP0241WH, AP0271WH, AP0301WH, AP0481WH
2-1-3. 1-way Air Discharge Cassette Type (Compact type)
Model: MMU-AP0071YH, AP0091YH, AP0121YH
20
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
Indoor unit
Earth screw
Flow selector
WHI
RED
RED
S(N)R(L)
Power supply Single phase
220-240V 50Hz
220V 60Hz
FM
unit earth
screw
Closed end connector
WHI
RC
2
4
6
CN304 (GRY)
CN309
(YEL)
AC IN
CN066
(WHI)
BLU
121
343
565
CN301
(BLK)
Heater
1
2
3
1
2
3
TR
Line Filter
1
Outdoor
unit
1
2
3
1
2
3
1
2
3
1 2
U2U
CN067
(BLK)
CN044
(BRW)
1 2 1 2
BLU
U
1
BLU
RY004
Fuse
T5.0A
CN040
(BLU)
1 2 1 2
BLU
BLK
BLU
U
2
1 2 1 2
Remote controller
BLK
BA
CN1
(WHI)
CN041
1 2 3 1 3
FAN CN083
(BLU)
YX
AI-NET central control terminal
(WHI)
BLK
RED
9 8 7 6 9 8 7 6
HML UL
RY007
CN050
(WHI)
1 2 3 4 5
MCC-1401
CN01 (WHI)
1 1
Network
2 2
adaptor
CN03
P.C. board
(RED)
ORN
5 4 3 2 1 5 4 3 2 1
RY006
RY005
Network
1 2
adaptor (Option)
1 2
2 1
233 1
DM
1 2 3 1 2 3
YEL
BLU
RY002
1 2 3 1 2 3
CN068
DP
(BLU)
RY001
LM
2 1 2 1
1 2 3 1 2 3
LM
(GRN)
CN033
Indoor control P.C. board
Power supply
circuit
4 5 6
CN075
(WHI)
CN02 (YEL)
CN01 (WHI)
TR
CN074
(WHI)
1 2 3 1 2 3
1 2 3
1 2 3 4 5 6 1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6 1 2 3 4 5 6
CN02 (BLU)
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
2 1 2 1
1 2 3 1 2 3
1 2 3 4 5 61 2 3 4 5 6
FS
CN061
(YEL)
FS
(RED)
CN030
6 4 3 6 4 3
1 2 3 1 2 3
CN032
(WHI)
1 2
Fan drive
Symbol
FM RC TR LM TA
TC1,TCJ
RY001 RY002 RY004
RY005~007
FS DM
PMV
PMV
1 2 5 1 2 5
4 5 6 4 5 6
CN082
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100 (BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN060
(WHI)
1 2 3 4 5 6
Option
Fan motor Running capacitor Power transformer Louver motor Indoor temp sensor Temp sensor Louver motor control relay Drain pump control relay Heater control relay Fan motor control relay Float switch Drain pump motor Pulse Motor Valve
PMV
(BLU)
121
2
121
2
TCJ
1 2
121
2
33
1
PNL
2 3
1
EXCT
2 1
1
Filter
2
2
1 2 3 4 5
Parts name
TA
TC1
2-1-4. 1-way Air Discharge Cassette Type
Model: MMU-AP0152SH, AP0182SH, AP0242SH
21
Indoor unit
earth screw
S(N)R(L)
Power supply single phase
220-240V 50Hz
220V 60Hz
FM TA TC1 TCJ TC2 LM DM FS RY302 PMV TR
Flow selector unit
earth screw
RED
WHI
Closed-end
connector
U
U
1
Outdoor
unit
Symbol
1
2
U2U
Fan motor Indoor temp sensor Temp sensor Temp sensor Temp sensor Louver motor Drain pump motor Float switsh Drain control relay Pulse motor valve Transformer
BA
A B
Wired
remote
controller
Parts name
WHI
WHI
2
112
CN001(WHI)
Adapter for
wireless remote
controller
BLK
BLK
Color
indication
RED: RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY: GRAY PNK: PINK ORN: ORANGE BRN: BRWN GRN: GREEN
TR
131 2 3
MCC-1401
AI-NET
Network adapter
CN02 (BLU)
(Option)
RED WHI
112
CN01
(WHI) CN03
(RED)
112
X Y
PMV
FM
5 5
CN82 (BLU)
6
CN112
Power supply
circuit
Control P.C. board
CN32 (WHI)
Fan
drive
High ceiling setup
1 2 1 2 1 2 1 2
CN111
(WHI)
(WHI)
DC20V DC15V DC12V DC7V
for indoor unit
MCC-1402
CN60
(WHI)
1 2 3 4 5 6
Option
CN110
(WHI)
1 2 3 4 5
1
2
3
4
6
1
2
3
4
6
CN334
5 4 1
(WHI)
313
1
3
1
T6.3A 250V~
3
1 2
2 2
131 2 3
RY302
RY303
P301
CN66 (WHI)
CN40 (BLU)
CN41 (BLU)
Fuse
5
1
3
1
3
CN68 (BLU)
1
DM
CN304 (GRY)
1
CN67 (BLK)
3
BLK
BLU
1 1
2
2
BLU BLK
BLK
CN309
(YEL)
1 1
Motor drive
CN50 (WHI)
1 2 3 4 5
CN333
1 2 3 4 5 6
5
3
(WHI)
1
2
3
4
54 3
32 1
5
circuit
Fuse
T3.15A
250V~
CN061
(YEL)
1 2 1 23 4 5 6 1 2 3 4 5
T10 GRL
1. indicates the terminal bolock letter. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side
LM
1 2 3 4 5 1 2
3
1 2 3 4 5 1 2 3 4 5
CN71 (CHK) CN72 (DISP)
CN81 (BLK)
4 5
CN33 (WHI)
CN20 (BLU)
1 3 1 2 3
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN80
(GRN)
CN73
(RED)
CN70 (WHI)
FS
CN34 (RED)
212
212
1 2
131
1 2 3
1 2
1 2
1
1
1 2
3
PNL
EXCT
Filter
TA
TCJ
TC2
TC1
3. indicates a control P.C. board.
2-1-5. Concealed Duct Standard Type
Model: MMD-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH
22
Indoor unit
S(N)R(L)
Earth screw
Indoor unit power supply
Single phase
220-240V 50Hz
220V 60Hz
RED
WHI
Closed end connector
Outdoor unit
1 3 1 2 2
Reactor
WHI
Flow selector
U2U
1
DM
unit earth
screw
U
U
1
Wired remote
CN304 (GRY)
RED
CN67 (BLK)
WHI
CN66 (WHI)
CN44
(BRW)
2
1 2 1 2
controller
CN68 (BLU)
1
2
3
1
2
3
BLK
BA
CN1
(WHI)
1
2
3
1
2
3
1
2
3
1 2
1 2
5
CN334
RY302
(WHI)
Fuse
T6.3A
250V~
P301
CN41
CN40
(BLU)
(BLU)
1 2 3
1 2
1 2
1 2 3
BLK
BLU
BLU
WHI BLK
1 2 1 2
Adaputor for wired
remote controller
11223445
BLK
BLK
WHI
CN001 (WHI)
545
FM
4
11
PMV
6 4 3 1 2 5 6 4 3 1 2 5
1 2 3 4 5 6 1 2 3 4 5 6
Fuse
T3.15A
250V~
4 5 6
T10
Power supply
circuit
CN61 (YEL)
~
~
CN309
(YEL)
CN333
(WHI)
1 2 3 1 2 3
1 3 1 3 5
Motor drive
circuit
+
5
CN50 (WHI)
1 2 3
TR
CN02 (BLU)
3 3 2 2 1 1
CN01 (WHI)
1 2 1 2
Network adaptor P.C. board
1 2 1 2
Network adaptor (Option)
CN03 (RED)
X Y
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
CN82
(BLU)
Indoor control P.C. board
DC20V DC15V DC12V DC7V
CN32 (WHI)
CN60 (WHI)
1 21 2 3 4 5 61 2 3 4 51 2 31 2 3
(Signal output)(Fan drive)
1 2 3 4 5
Color identification
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BRW : BROWN
Symbol
FM TA
TC1,TC2,TCJ
DM FS
RY302
PMV
CN33 (WHI)
CN81 (BLK)
1 2 3 4 5
1 2 3 4 5
BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE GRN : GREEN
Parts name
Fan motor Indoor temp sensor Indoor temp sensor Drain pump motor Float switch Drain pump control relay Pulse Motor Valve
CN20 (BLU)
3 1 321
CN104
(YEL)
CN102 (RED)
CN101
(BLK)
CN100 (BRN)
CN80
(GRN)
CN73
(RED)
CN70 (WHI)
FS
CN34 (RED)
2
2
2
2
1 2 3
1 2
1 2
121
121
121
121
33
PNL
EXCT
MMD-AP0271BH, AP0301BH, AP0361BH, AP0481BH, AP0561BH
TA
TCJ
TC2
TC1
23
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
RED
WHI
Closed end connector
Indoor unit
Earth screw
S(N)R(L)
Power supply
Single phase 220-240V 50Hz 220V 60Hz
(BLK)
CN304
(GRY)
1
2
3
1
2
3
TR
Flow selector
unit earth
screw
T10A,250V~
Closed end connector
Surge
absorber
87
43F1
FAN CN083
(WHI)
P301
1
RY004
2
3
1
CN309
2
(YEL)
3
CN067
(BLK)
1
2
3
1 2
YEL
CN066
(WHI)
CN044 (BRW)
EMG
U2U
1
Outdoor unit
REDRED F
RED
6
43F1
4
Fuse
T5.0A
CN040
(BLU)
1 21 2 1 2
OC
U
1
WHI
1 2 3 4
RC
U
2
Remote controller
5
43F1
3
RED
GRY
1 2 3 4
WHI
RED
REDWHI
CN041
(BLU)
1 2 3 1 3
1 2 1 2
GRY
9 8 7 6
9 8 7 6
RY007
BA
5 4 3 2 1
HML UL
RY006
CN01 (WHI)
3 3
2
1 1
CN1
CN02
(WHI)
(BLU)
WHI
RC
FM
4 2
RY002
RY005
CN050
(WHI)
1 2 3 4 5
Network adaptor (Option)
MCC-1401
1 2 1 2
CN03
1 2
(RED)
1 2
X Y
A
F1F2F3F
BLU
ORN
BLK
(Option)
DM
1 2 3 1 2 3
DP
(BLU)
CN068
RY001
1 2 3 1 2 3
LM
(GRN)
CN033
1 2 3 1 2 3
FS
CN030
(RED)
TA
1 2 1 2
CN104
(YEL)
Indoor control P.C. board
Power supply
circuit
CN074
(WHI)
1 2 3
1 2 3
1 2 3
4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6 1 2 3 4 5 6
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
4. When attaching a drain pump, exchange CN030 connector with the connector of the float switch.
5. A part is connected to the terminal block. When exchanging to the outside static pressure necessary at the local site, check the terminal No. and lead color of the fan motor in the below diagram, and then exchange the lead wire indicated by the arrow mark ( ).
4
BRN
Wired for MMD-AP0481 only (BRN Wire)
Motor over heating protection switch
CN075
BLK WHI
GRY RED
(WHI)
1 2 3 4 5 61 2 3 4 5 6
T10
CN02 (YEL)
CN01 (WHI)
TR
CN061
(YEL)
49F
TCJ
1 2 1 2
CN102 (RED)
CN032
(WHI)
1 2
Fan drive
BLU ORN
BRN
CN060
(WHI)
TC1
1 2 3 1 2 3
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN082
(BLU)
TC2
1 2 1 2
CN101
(BLK)
1 2 3 4 5 6
Option
Sold
separately
CN100
(BRN)
1 2
PNL
3 1
EXCT
2 1
Filter
2 1
2 3 4 5
6
6
5
5
4
4
3
3
2
2
1
1
Symbol
FM RC TR TA
TC1,TC2,TCJ
RY005~007
RY001 RY002
PMV
F
43F1
DM FS
5
5
2
2
1
1
PMV
3
3
4
4
6
6
Parts name
Fan motor Running capacitor Transformer Indoor temp sensor Temp sensor Fan motor control relay Louver motor control relay Drain control relay Pulse Motor Valve Fuse Fan motor control relay Drain pump motor Float switch
2-1-6. Concealed Duct High Static Pressure Type
Model: MMD-AP0181H, AP0241H, AP0271H, AP0361H, AP0481H
FM
2-1-7. Under Ceiling Type
Model: MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H
PMV
1
2
3
4
6
4
6
5
1
2
3
5
LM
1 2 3 4 5 1 2 3 4 5
FS
24
Indoor unit
Earth screw
Power supply
single phase 200-240V 50Hz 200V 60Hz
RED
S(N)R(L)
WHI
RED
WHI
Flow selector
unit earth
screw
Closed end
terminal
DM
U2U
1
Outdoor unit
CN304
(GRY)
CN67 (BLK)
BLU BLU
BLK
BLK
1
CN68
(BLU)
1
1
RY302
2
2
3
3
1
RY303
2
3
1
1
Fuse
2
2
T6.3A
3
3
250V~
P301
BLK
1
CN66 (WHI)
2
121
CN40 (BLU)
2
121
CN41
(BLU)
33
U2U
1 2 1 2
Wired remote
controller
BA
(WHI)
CN1
5 4 1 5 4 3 2 1
1 2 3
CN334
(WHI)
~
~
CN50
CN309
(WHI)
(YEL)
BLK
WHI
BLKWHI
CN001 (WHI)
1 2 1 2
Adaptor for wireless
remote controller
1 2 3 4 5 1 2 3 4 5
Motor drive
circuit
+
CN333
(WHI)
Fuse
T3.15A
CN61 (YEL)
4 5 6
TR
3 3 2 2 1 1
CN02 (BLU)
T10
CN01 (WHI)
Network adaptor P.C. board
1 2 1 2
1 2 1 2
Network adaptor (Option)
CN03
(RED)
1 2 3 4 5 1
2
3
Indoor control P.C. board
Power supply
circuit
CN32 (WHI)
CN82
6
(BLU)
4
5
6
DC20V DC15V DC12V DC7V
CN60 (WHI)
1 21 2 3 4 5 6
Option GRLFandrive
X Y
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
1 2 3 4 5 1 2 3 4 5
CN81 (BLK)
1 2 3 4 51 2 3 4 51 2 31 2 3
Sold separately
CN33 (WHI)
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BRW : BROWN
TC,TC2,TCJ
CN20 (BLU)
1 2 3 4 5
Color identification
Symbol
FM TA
LM
RY302
DM FS
CN34
1 3
(RED)
123
CN104
(YEL)
2
CN102
(RED)
2
CN101
(BLK)
2
CN100
2
(BRW)
1
CN80
2
(GRN)
3 1
CN73
(RED)
2 1
CN70
(WHI)
2
BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE GRN : GREEN
Parts name
Fan motor Indoor temp sensor Temp sensor Louver motor Drain control relay Drain pump motor Float switch
121
121
121
121
33
PNL
EXCT
FILTER
TA
TCJ
TC2
TC1
2-1-8. High W all T ype
545
4
FM
Model: MMK-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H
25
RED
WHI
R(L) S(N)
Power supply
single phase
220-240V 50Hz
220V 60Hz Indoor unit
Earth screw
Flow selector
unit earth
screw
Closed-end
connector
RED
WHI
U1 U2
Outdoor
unit
U1 U2
1
CN68
(BLU)
3
1
LM
CN304
(GRY)
1
3
CN67 (BLK)
P301
BLK
CN66 (WHI)
313
1
3
1 2
A B X Y
WHI BLK
2
112
CN1
(WHI)
Wired remote
controller
CN334
(WHI)
RY302
RY303
FUSE
T6.3A 250V~
CN40
(BLU)
1 231 3
BLU
BLU
BLK
GRY
GRY
WHI BLK
2
112
CN001
(WHI)
Adaptor for
wireless remote
controller
BLK
5
CN41 (BLU)
1 21 2
11
1 2 3 1 2 3
CN333
1 2 3 4 5 6 1
223445
1 3
BLK
WHI
(WHI)
CN309
(YEL)
TR
3
1 1
1 3 1 3 5
Motor drive
circuit
CN50 (WHI)
1 2 31 3
CN01(WHI)
3
CN02
2
(BLU)
CN03(RED)
5
4 5
2
112
2
112
1 1 2 3 4 5 6
T3.15A 250V~
Network adaptor
(Option)
MCC-1401
PMV
1 234 56 1 234 56
CN82 (BLU)
FUSE
CN61 (YEL)
1 2 3 4 5
CN33 (WHI)
Power
supply
circuit
CN32 (WHI)
6
1 2
Fandrive
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
TC2
TCJ
113
CN34 (RED)
TA
3
21212121212
CN104
CN102
(YEL)
(RED)
CN101
(BLK)
TC1
1
112 31 2 3 4 5 CN100
(BRW)
Control P.C. board
for Indoor unit
DC20V DC15V DC12V DC7V
CN60 (WHI)
1 2 3 4 5 6
Option
MCC-1402
CN81 (BLK)
1 2 3 4 5
CN20 (BLU)
1 2 3 4 5
1. indicates the terminal bolock. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicates the control P.C. board.
Symbol
FM TA TC1,TC2,TCJ PMV LM RY303
Parts name
Fan motor Indoor temp sensor Temp sensor Pulse motor valve Louver motor Louver control relay
3
CN103
(GRN)
CN080
(GRN)
CN73
(RED)
CN70 (WHI)
1 2
1 2 3
1 2
1 2
EXCT
26
Heat exchanger
GRN & YEL
Power Supply
Single phase
220-240V 50Hz
220V 60Hz
RED
WHI
GRN & YEL
GRN & YEL
1 3
CN67 (BLK)
CN309 (YEL)
1 3 5
Color identification
BRW
RED
WHI YEL BLU
BLK GRY PNK
ORN
GRN & YEL
GRN
F301 Fuse T3. 15A 250V~
CN81 (BLK)
1 3 1 3
WHI
WHI
RED
Flow selector unit
(Sold separately)
:
BROWN
:
RED
:
WHITE
:
YELLOW
:
BLUE
:
BLACK
:
GRAY
:
PINK
:
ORANGE
:
GREEN & YELLOW
:
GREEN
54321 54321
BRW
YEL
GRY
54321
PNK
Pulse motor valve
BLK
F
S
CN22
CN213 (WHI)
WHI
BRW
YEL
GRY
1011
7899
Infrared rays receive
and indication parts
(MCC-861)
ORN
Louver motor
Fan
motor
RED
BRW
HBS
54321 21
CN50 (WHI)
10
987654321
10
9874321
RED
BLU
BLU
6
CN82 (BLU)
ORN
YEL
WHI
12345 123456
BLU
CN210
(WHI)
YEL
WHI
BLK
RED
13456 13456
(MCC-1510)
Control P.C.board for indoor unit
234567
123456
CN32 (WHI)
Fan drive
CN61 (YEL)
65432121 654321 321 654321
4321
HA
YEL
YEL
(WHI)
Power
supply
circuit
CN60 (WHI)
Option
YEL
CN33
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the
12345
wiring at site.
3. indicates the control P.C. board.
YEL
WHI
23456
123456
CN44
(BRW)
DC 15V
DC 0V DC 12V
DC 7V
CN80
(GRN)
PNL/EMG
CN40 (BLU)
CN41 (BLU)
CN100
(BRW)
CN101
(BLU)
CN103
(GRN)
CN102
(YEL)
CN104
(WHI)
BLU
121
BLU
2
BLK
313
2
WHI
1
BLK
131
2
BLK
3
BLK
121
BLK
2
1
TF
2
BLK
121
BLK
2
BLK
121
BLK
2
Heat exchanger sensor (TC1)
Heat exchanger sensor (TC2)
Heat exchanger sensor (TCJ)
Thermo sensor (TA)
Outdoor unit
221
1
CN1(WHI)
Wierd remote
controller
(Sold separately)
Model: MMK-AP0072H, AP0092H, AP0122H
27
Indoor unit
earth screw
220-240V 50Hz
AC IN RED
R(L) S(N)
Power supply
single phase
220V 60Hz
FM
RC
WHI
Flow selector
unit earth
screw
RED
Closed-end
connector
WHI
2
323 4
4
5
5
6
6
P301
(BLK)
313
313
T5.0A 250V~
313
212
CN040
(BLU)
U1
RY004
(GRY) CN304
(YEL) CN309
FUSE
CN041
(BLU)
2
1 233 1 2 3 4 5
112
1
BLU
BLU
BLK
U2 A B
1
1
1
CN067
(BLK)
CN066
(WHI)
1
TR
Line filter
U1 U2
Outdoor unit Remote controller
112
CN1
RED BLK ORN BLU YEL
FAN
CN083
(WHI)
9 5 3 1
RY007
RC
BLK
2
5 3 1779
M LUL
H
RY006
RY005
CN050
(WHI)
3
3
CN02
2
(BLU)
1 1
CN03(RED)
2
112
CN01(WHI)
2
112
X Y
1
113
DP
3
3
1 3
RY001
Power supply
circuit
1 2 3 4 5 6 1 2 1 23 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
Sub P .C. board
MCC-1520
1 2 3 4 5 6 1 2 3 4 5 6
Network adapter
(Option)
CN068
(BLU)
RY002
CN074
(WHI)
LM
MCC-1401
1. indicates the terminal block. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicates the control P.C. board.
CN033 (GRN)
1 2 3 4 5 6 1 2 3 4 5 6
Control P.C. board
for Indoor unit
MCC-1403
CN061
CN075
(YEL)
(WHI)
T10
CN02 (YEL)
CN01 (WHI)
TR
PMV
2-1-9. Floor Standing Cabinet Type
Model: MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H
1 234 56 1 234 56
PMV CN082
(BLU)
CN032
(WHI)
112 3
CN060
(WHI)
FS
3
CN030
(RED)
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRN)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
212
212
1 2
212
1 2 3
1 2
1 2
1 2 3 4 5
1
1
1 2
1
PNL
EXCT
Filter
TA
TCJ
TC2
TC1
Color
indication
RED : RED WHI : WHITE
Fan
drive
Option
YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
Symbol
FM RC TR TA TC1,TC2,TCJ RY001 RY002 RY004 RY005~007 PMV
Parts name
Fan motor Running capacitor Transformer Indoor temp sensor Temp sensor Louver control relay Drain control relay Heater control relay Fan motor control relay Pulse motor valve
28
Indoor unit
earth screw
RED
WHI
RED
R(L) S(N)
Power supply single phase
220-240V 50Hz
220V 60Hz
Flow selector
unit earth
screw
Closed-end
connector
WHI
WHI
1
GRN
1
3
3
2
2
4
4
FM
5
5
6
6
RED
RED BLK ORN BLU YEL
FAN
CN083
(WHI)
9 5 3 1
RC
GRN
FM
RED
5 3 1779
WHI
For AP0071BH,AP0091BH,AP0121BH
R301 (BLK)
1
3
1
313
AC IN
1
T5.0A 250V~
313
1
CN066 (WHI)
2
1
CN044 (BRW)
2
EMG
2
112
Network
adaptor
3 2
112
CN01(WHI)
CN02 (BLU)
CN03(RED)
MCC-1401
2
(Option)
1 1 2 2
CN03
(RED)
TR
U1 U2
U1 U2
Outdoor unit
A B X Y
2
112
CN1
Remote controller
3
1 1
1. indicates the terminal block. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicates the control P.C. board.
(GRY) CN304
(YEL) CN309
FUSE
(BLK) CN067
RC
RY004
CN040
(BLU)
112
2
2
424 5
5
6
6
3
3
RED BLK ORN BLU YEL
FAN
CN083
(WHI)
CN041
(BLU)
1 233 1 2 3 4 5 1
5 3 1779
9 5 3 1
M LUL
H
RY007
RY006
CN050
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
RY005
(WHI)
CN068
(BLU)
RY002
CN074
(WHI)
133 1
113
3
3
CN033 (GRN)
113
RY001
Control P.C. board
for undoor unit
Power supply
circuit
CN075
MCC-1520
(WHI)
CN02 (YEL)
CN01 (WHI)
TR
1 2 3 4 5 6 1 2 1 23 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
Sub P.C. boar d
1 2 3 4 5 6 1 2 3 4 5 6
MCC-1403
CN061
(YEL)
112 3 CN030
(RED)
Symbol
FM RC TR TA TC1,TC2,TCJ RY001 RY002 RY004 RY005~007 PMV
PMV
1 234 56 1 234 56
3
CN032
(WHI)
Fan
drive
1 2 3 4 5 6 1 2 3 4 5 6
CN082
(BLU)
CN060
(WHI)
Option
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
PMV
1
212
1
212
1
1
2
2
131 2
3
1 2 3
1 2
1 2
1 2 3 4 5
Parts name
Fan motor Running capacitor Transformer Indoor temp sensor Temp sensor Louver control relay Drain control relay Heater control reley Fan motor control relay Pulse motor valve
PNL
EXCT
Filter
TCJ
TC2
2-1-10. Floor Standing Concealed Type
Model: MML-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH
TA
TC1
29
Indoor unit
earth screw
RED
WHI
R(L) S(N)
Power supply
single phase
220-240V 50Hz
220V 60Hz
FM
Flow selector
unit earth
screw
Closed-end
connector
1
RC 313 4
4
5
5
6
6
787
BRW
P301
(BLK)
1
(GRY)
3
CN304
1
(YEL)
313
CN309
AC IN
1
FUSE
T5.0A 250V~
313
(BLK) CN067
CN066 (WHI)
1 2
CN044 (BRW)
1
CN040
2
(BLU)
EMG
112
BLU
TR
112
Line filter
U1
U1 U2
Outdoor unit Remote controller
CN083
RY004
CN041
(BLU)
2
1 233 1 2 3 4 5 1
BLU
BLK
BLK
2
U2 A B
2 112 CN1
RED BLK ORN BLU YEL
FAN
(WHI)
9 5 3 1
RY007
RC
3
1 1
LM
1
221
5 3 1779
M LUL
H
RY006
RY005
CN050
(WHI)
CN01(WHI)
3
CN02
2
(BLU)
CN03(RED)
Network adaptor
2
112
2
112
MCC-1401
X Y
(Option)
CN068
(BLU)
RY002
CN074
(WHI)
1
113
DP
3
RY001
3
LM
3
CN033 (GRN)
113
Control P.C. board
for Indoor unit
Power supply
circuit
CN075
1 2 3 4 5 6 1 2 1 23 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 6 1 2 3 4 5 6
Sub P .C. boar d
MCC-1520
1 2 3 4 5 6 1 2 3 4 5 6
(WHI)
CN02 (YEL)
CN01
(WHI)
TR
1. indicates the terminal block, letter. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicates the control P.C. board.
3
CN030
112 3
MCC-1403
CN061
(YEL)
(RED)
CN032
(WHI)
Fan
drive
PMV
1 234 56 1 234 56
1 2 3 4 5 6 1 2 3 4 5 6
CN060
(WHI)
Option
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN082
Symbol
FM RC TR LM TA TC1,TC2,TCJ RY001 RY002 RY005~007 PMV
PMV
(BLU)
TA
1
212
TCJ
1
212
TC2
1
1
2
2
131
1 2 3
1 2
1 2
1 2 3 4 5
TC1
3
PNL
EXCT
Filter
Fan motor Running capacitor Transformer Louver motor Indoor temp sensor Temp sensor Louver control relay Drain control relay Fan motor control relay Pulse motor valve
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW : BROWN GRN : GREEN
Parts name
2-1-11. Floor Standing Type
Model: MMF-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H, AP0561H
30
Flow
Selector unit
Earth screw
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRN : BRWN GRN : GREEN
Closed-end
connector
Indoor unit
Earth screw
Color
WHI
RED
220-240V~, 50Hz
R(L) S(N)
Power supply
220V~, 60Hz
Non Drain pump type ("SH" T ype)
CN68
(BLU)
1
3
Drain pump type ("SPH" T ype)
DM
U1 U2
RED
WHI
CN44
(BRW)
CN68
(BLU)
1
1
3
BLK
A B
2-1-12. Slim Duct Type
Model: MMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH
Non Drain pump type
PMV
FM
1
2
3
4
6 6
CN333
5
3
(WHI)
54 3
32 1
circuit
CN309
(YEL)
1. indicates the terminal bolock. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side
Fuse T3.15A 250V~
CN50 (WHI)
1 2 3 4 5
1 2 3 4 5 6 1
BLU
CN41 (BLU)
1 233
BLK
CN334 (WHI)
BLK
1 1
Motor drive
31
5 4 1 5
RY302
313
1
CN304
(GRY)
3
Fuse T6.3A 250V~
1
3
CN67 (BLK)
P301
1
CN66 (WHI)
2 1
CN40 (BLU)
2
11221
BLU
3. indicate a control P.C. board.
5
4
2
3
3
Power supply circuit
1
4
(External static pressure setup)
2
5
CN82
1 2
(BLU)
1 2
5 3
6
CN112
(WHI)
DC20V DC15V DC12V DC7V
CN61 (YEL)
1 2 3 4 5 6
1 2
CN111
CN110
(WHI)
(WHI)
Control P.C. board
for undoor unit
CN32 (WHI)
1 2
1 2 3 4 5 6
Fan drive
1 2 1 2
MCC-1402
CN60 (WHI)
Option
Symbol
FM TA TC1,TC2,TCJ RY302 PMV DM FS
("SH" T ype)
1 3 1 2 3
CN33 (WHI)
4 5
CN71
(CHK)
CN72
(DISP)
CN81 (BLK)
1 2 3 4 5
Parts name
Fan motor Indoor temp sensor Temp sensor Drain control relay Pulse motor valve Drain pump motor Float switch
Drain pump type ("SPH" T ype)
CN34 (RED)
CN20 (BLU)
1 2 3 4 5
1 3 1 2 3
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100 (BRW)
CN80
(GRN)
CN73
(RED)
CN70 (WHI)
FS
CN34 (RED)
212
212
1 2
131
1 2 3
1 2
1 2
1
1
1 2
3
PNL
EXCT
TA
TCJ
TC2
TC1
U1 U2
Outdoor unit
A B
Wired remote controller
Loading...
+ 164 hidden pages