Tekmar D 315, tekmarNet4 315 User Manual

Installation & Operation Manual
tN4 Wiring Center 315
Introduction
The tekmarNet®4 (tN4) Wiring Center 315 is designed to operate up to six zone valves in a hydronic heating system. It can be mounted near a remote zone manifold, providing a convenient location to wire both thermostats and zone valves while only requiring two wires to be run back to the mechanical room. When combined with tekmarNet®4 Thermostats, all devices communicate to provide a synchronized end switch that reduces cycling of equipment. A zone group pump relay is also available to switch a pump.
Zone 1
Power
Zone 2
End Switch/ Zone Group Pump
Zone 3 Zone 4 Zone 5 Zone 6
Zoning
Replaces: 04/09
Features
Six 24 V (ac) powered zone outputs
• For use with tekmarNet
• tN4 expansion terminals
• Isolated end switch
• Zone group pump relay
• External diagnostic LEDs
• CSA C US Certified for use in USA and Canada
®
4 Thermostats
D 315
04/11
tN4 Wiring Center 315
Six Zone Valves
Benefi ts
• Compact enclosure for flexible installation
• Reduce equipment cycling when combined with
• tekmarNet®4 Thermostats
Note
Not for use with tekmarNet®2 Thermostats
1 of 12 © 2011 D 315 - 04/11
Table of Contents
---------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------
--------------------------------------------------------------------------------------
Installation ...................................................................... 2
Preparation ................................................................. 2
Physical Dimensions ..................................................3
Installation Location ...................................................3
Rough-In Wiring .........................................................3
Sizing the Transformer ...............................................4
Control Wiring ............................................................4
Testing the Control Wiring ..........................................6
Applic ations .................................................................... 7
User Interface ............................................................... 10
LEDs ........................................................................10
Sequence of Operation ................................................10
tekmarNet® System ..................................................10
Relay Outputs ........................................................... 11
Energy Saving Features ........................................... 11
Troubleshooting ............................................................ 11
Frequently Asked Questions .................................... 11
Technical Data ..............................................................12
Limited Warranty and Product Return Procedure ........12
Getting Started
Congratulations on the purchase of your new tekmarNet This manual covers the complete installation, programming and sequence of operation for this control. You will also find
instruction on testing, commissioning, and troubleshooting the control and system that it operates.
®
Wiring Center!
Installation
Caution
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury or death. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into
the control circuit. Do not attempt to service the control. Refer to qualified personnel for servicing. There are no user serviceable parts. Attempting to do so voids warranty and could result in damage to the equipment and possibly even personal injury or death.
Radio Frequency Interference
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise. Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is determined by turning the control off and on, the user is encouraged to try
Preparation
Tools Required
tekmar or jeweller screwdriver
• Phillips head screwdriver
Materials Required
(2) #10 x 1” wood screws
• (2) wire nuts
• 18 AWG LVT solid wire (low voltage connections)
Power Required
120 V (ac), 1-phase, 15 A service from circuit breaker
Power disconnect (optional)• panel
---------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------
--------------------------------------------------------------------------------------
to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Needle-nose pliers
• Wire stripper
14 AWG solid wire (line voltage connections)
• tekmar 009 (24 V (ac) transformer)
• Cable or conduit connectors
© 2011 D 315 - 04/11 2 of 12
-----------------------------------------------------------------------------------
Physical Dimensions
5–1/2”
(140 mm)
Front View
7/8”
C Zone 2
W tN4CtN4CX
Zone 1
Zone 1 Expansion
Zone 2 Zone 3 Zone 4 Zone 5 Zone 6
End Switch
XC
Input Power
RR
tN4 Wiring Center 315
Six Zone Valves
Zone 1
Zone 2
VlvC
C
WtN4 R
Zone 3
Power End Switch/ Zone Group Pump
Zone 3
Zone 4
VlvC
VlvC
WtN4 R C
VlvC
WtN4 R
H8001B
Zone 4
Zone 5
RWtN4C
WtN4C
Zone 6
R
Zone 5
Zone 6
(75°C) conductors
Use at least 167°F
VlvC
VlvC
Side View Back View
(22 mm)
CL
1–1/8” (30 mm)
5–1/2”
(140 mm)
Installation Location
When choosing the location for the control, consider the
• following:
Keep dry. Avoid potential leakage onto the control.
• RH 90% to 122°F (50°C) in a non-condensing environment.
Do not expose to operating temperatures beyond 32-
• 122°F (0-50°C).
Provide adequate ventilation.
• Keep away from equipment, appliances or other sources
• of electrical interference.
2–1/4”
(57 mm)
1/2” Knock-out (x 4)
315
Strip wires1/2 inch (13 mm).
Installed wires are not removable.
12-18 AWG
7/8” x 1/2” (23 mm x 12 mm)
Knock-out (x 4)
1/2” x 5/8”
(12 mm x 16 mm)
Zone Power L
Ø 1/8” (3 mm)
Zone Group Pump
Knock-out (x 4)
Locate the control near zone valves if possible.
• Provide easy access for wiring and viewing the
• control.
Mount approximately 5 ft. (1.5 m) off the finished floor.
• Install to wall using #10 x 1” wood screws. Wall anchors
• are recommended when mounting to sheet rock, wall­board or masonry.
Rough-In Wiring
Line Voltage Wiring
In most cases, the control can be mounted directly to a wall without the need for any line voltage connections.
As an option, the control may be mounted to a 4” x 4” electrical junction box so that the high voltage electrical connections for the transformer are safely contained.
For ease of service, the circuit breaker or power disconnect should be located in reasonably close proximity to the equipment.
All line voltage wire connections are recommended to be pulled inside a flexible or solid conduit. Always follow proper wiring practices, building and electrical codes for your jurisdiction.
-----------------------------------------------------------------------------------
Each cable must be pulled to the electrical junction box. It is recommended to label each cable for easy identification. All line voltage wires should be stripped to a length of 1/2” (13 mm).
Pull a three conductor 14 AWG cable for the following equipment:
Circuit Breaker or Power Disconnect (if applicable)
• Zone Group Pump (if applicable)
3 of 12 © 2011 D 315 - 04/11
-----------------------------------------------------------------------------------
Low Voltage Wiring
-----------------------------------------------------------------------------------
Each cable must be pulled from the equipment to the control’s plastic enclosure. All low voltage wiring connections enter the enclosure through conduit knockouts on the sides, or through the square knockouts on the rear. It is recommended to label each cable for easy identification. All low voltage wires are to be stripped to a length of 3/8” (9 mm) to ensure proper connection to the control.
Pull two conductor 18 AWG LVT cable, up to 500 feet (150 m) for the following equipment:
tekmarNet®4 Expansion (if applicable)
• 24 V (ac) Power
-----------------------------------------------------------------------------------
Sizing the Transformer
Zone Valves
Boiler T-T (If using End Switch)
Pull three conductor 18 AWG LVT cable, up to 500 feet (150 m) for the following equipment:
tekmarNet
Pull four conductor 18 AWG LVT cable, up to 500 feet (150 m) for the following equipment:
tekmarNet
®
4 Accessories (User Switch, Timer)
®
4 Thermostats
The control requires an external transformer. A tekmar Transformer 009 (or 009K which includes a 4”x 4” electrical box) can supply up to 40 VA, and includes an in-line fuse to protect the transformer and control.
In order to correctly size the external transformer, all loads connected to the control must be taken into account.
When adding up the loads, consider the following:
tekmarNet®4 Thermostats draw approximately 2 VA each.
• Each zone valve must be sized for peak load. This can be
• obtained by multiplying the peak current draw (in Amps) by 24 V (ac).
Zone
Thermostat Load
Zone Valve Load
Total Zone Load
123456
++++++
The total power capacity of the power supply should be larger than the total load of all the devices connected to the control. This total load must not exceed 98 VA. Multiple tekmar Transformer 009’s can be wired together to increase total VA capacity.
The following chart is provided to simplify transformer sizing:
Control Wiring
Line Voltage Wiring
CAUTION: TURN ALL POWER OFF BEFORE PERFORMING ANY WIRING.
-----------------------------------------------------------------------------------
Control
Load (VA)
3
Transformer
must exceed:
VA
Wire the Grounds
Connect the power supply ground and zone group pump
• ground to the electrical box as shown in Figure 1.
Wire the Neutrals (N)
Connect the 115 V (ac) neutral (N) and zone group pump
• neutral wires to the 115 V (ac) side of the transformer. Use a wire nut or approved connector. See Figure 1.
Wire the Power (L)
Connect the 115 V (ac) line voltage (L) wire to the 115 V
• (ac) side of the transformer and to the Power L wire (red) of the zone group pump relay. Use a wire nut or approved connector. See Figure 1.
© 2011 D 315 - 04/11 4 of 12
Wire the Zone Group Pump (L)
Connect the 115 V (ac) line voltage (L) wire from the
• zone group pump to the Zone Group Pump push-in wire connector. See Figure 1.
If the zone group pump is not used, then cut the rear red
• and black wires where they exit the enclosure.
Loading...
+ 8 hidden pages