SILENT KNIGHT IDP-Photo, IDP-Photo-T, IDP-Acclimate Installation And Maintenance Manual

(57.2°C) fixed temperature heat detector.
CAUTION
Please refer to the operation manual for the UL listed control unit for specific operation of the IDP-Photo, IDP­Photo-T and IDP-Acclimate.
The IDP-Photo, IDP-Photo-T and IDP-Acclimate require compatible addressable communications to function properly. Connect these sensors to listed-compatible
control panels only.
IDP-Photo, IDP-Photo-T and IDP-Acclimate Intelligent Photoelectric Smoke Sensors Installation and Maintenance Instructions
SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC
Standby Current: 300µA @ 24 VDCMax. Alarm Current (LED on): 6.5 mA @ 24 VDC
Operating Humidity Range: 10% to 93% Relative Humidity, non condensing
Operating Temperature Range: 0° to 49°C (32° to 120°F); IDP-Photo 0° to 38°C (32° to 100°F); IDP- Photo-T, IDP-Acclimate
Height: 2.0 inches (51mm) installed in SS-B6 Base
Diameter: 6.1 inches (155 mm) installed in SS-B6 Base
4.1 inches (104 mm)
Weight: 5.2 oz. (147 g)
This sensor must be installed in compliance with the control panel system installation manual. The installation must meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when installed in compliance with the National Fire Protection Association (NFPA); see NFPA 72.
installed in B501 Base
SPACING
Silent Knight recommends spacing sensors in compliance with NFPA 72. In low air flow applications with smooth ceilings, space sensors 30 feet apart. For specific information regarding sensor spacing, placement, and special applications, refer to NFPA 72.
Duct Applications: IDP-Photo and IDP-Photo-T are listed for use in ducts.
NOTE: These products are not listed for use inside duct smoke detectors.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mistakes and ease system troubleshooting. Improper connections will prevent a system from responding properly in the event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the wiring diagram, see Figure 1.
2. Set the desired address on the sensor address switches, see Figure 2.
3. Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control unit and activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
GENERAL DESCRIPTION
Models IDP-Photo, IDP-Photo-T and IDP-Acclimate are plug-in type smoke sensors that combine a photoelectronic sensing chamber with addressable­analog communications. The sensors transmit an analog representation of smoke density over a communication line to a control panel. Rotary decade switches are provided for setting the sensor’s address.
Two LEDs on the sensor are controlled by the panel to indicate sensor status. An output is provided for connection to an optional remote LED annunciator (P/N RA400Z). Models IDP-Acclimate and IDP-Photo-T combines a photoelectronic sensing chamber and 135°F
K200-04-00 1 I56-2720-00R
Dust covers provide limited protection against airborne dust particles during shipping. Dust covers must be removed before the sensors can sense smoke. Remove
sensors prior to heavy remodeling or construction.
TAMPER-RESISTANCE
Models IDP-Photo, IDP-Photo-T and IDP-Acclimate include a tamper-resistant capability that prevents their removal from the bracket without the use of a tool. Refer to the base manual for details on making use of this capability.
TESTING
LED Status
Indicators
Magnet T est
Marker
Tes t
Magnet
Position
Tes t
Magnet
Position
Magnet T est
Marker
TENS ONES
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
3
2
1
3
2
1
+
+
OPTIONAL RETURN LOOP
REMOTE ANNUNCIATOR
+
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable the system to prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when tested and maintained in compliance with NFPA 72.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test
magnet. The test magnet electronically simulates smoke in the sensing chamber, testing the sensor electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 3.
2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel
to indicate sensor status. Coded signals, transmitted from the panel, can cause the LEDs to blink, latch on, or latch off. Refer to the control panel technical documentation for sensor LED status operation and expected delay to alarm.
B. Smoke Entry: Aerosol Generator (Gemini 501 or
other UL lised devices)
The GEMINI model 501 aerosol generator can be
used for smoke entry testing. Other UL listed smoke generating devices may be used as well. Set the generator to represent 4%/ft to 5%/ft obscuration as described in the GEMINI 501 manual. Using the bowl shaped applicator, apply aerosol until the panel alarms.
For IDP-Acclimate, smoke entry testing should be performed immediately following the magnet test. Magnet test initiates an approximately 10 minute period when the detector’s signal processing software routines are not active. Failure to first perform the magnet test will introduce a time delay before the detector alarms.
C. Direct Heat Method (Hair dryer of 1000-1500
watts). IDP-Photo-T and IDP-Acclimate only.
A hair dryer of 1000-1500 watts should be used to
test the thermistors. Direct the heat toward either of the two thermistors, holding the heat source approximately 12 inches from the detector in order to avoid damaging the plastic housing. The detector will reset only after it has had sufficient time to cool. Make sure both thermistors are tested individually.
A sensor that fails any of these tests should be cleaned as described under CLEANING, and retested. If the sensor fails after cleaning, it must be replaced and returned for repair.
When testing is complete, restore the system to normal operation and notify the proper authorities that the system is back in operation.
K200-04-00 2 I56-2720-00R
CONTROL PANEL
UL LISTED COMPATIBLE
Figure 1. Wiring Diagram
Caution: Do Not Loop Wire Under Terminal 1 or 2.
Break Wire Run To Provide Supervision of Connections.
Figure 2. Rotary Address Switches
Figure 3.
C0100-00
C0146-00
C0145-00
Loading...
+ 2 hidden pages