The reproduction, transmission or
use of this document or its contents
is not permitted without express
written authority. Offenders will be
liable for damages. All rights,
including rights created by patent
grant or registration of a utility
model _or_ design,_are_ reserved.
English
Print No.: SPB7-250.891.01.04.02 Doc. Gen. Date:08.05
Replaces: SPB7-250.891.01.03.02
Page 2
0 - 2Revision
ChapterPageRevision
allall01
allall02
allall03
allall04
Document revision level
The document corresponds to the version/revision level effective at the time of system delivery.
Revisions to hardcopy documentation are not automatically distributed.
Please contact your local Siemens office to order current revision levels.
Disclaimer
The installation and service of equipment described herein is to be performed by qualified personnel
who are employed by Siemens or one of its affiliates or who are otherwise authorized by Siemens or
one of its affiliates to provide such services.
Assemblers and other persons who are not employed by or otherwise directly affiliated with or authorized by Siemens or one of its affiliates are directed to contact one of the local offices of Siemens or
one of its affiliates before attempting installation or service procedures.
- With distribution of these revision level, all preceding planning guides (PGs), Speed Infos and drafts
lose their validity.
- All layouts issued by the Planning Departments must bear a note referring to the installation and
delivery conditions of Siemens Medical Engineering. The installation and delivery conditions must
be submitted with the layouts.
- Unless otherwise specified, all dimensions are indicated in "mm".
- The symbol indicates a change (see revision status).
- Orientation points
Points specific to system components to which reference is made when positioning system
components to each other or in the room.
The isocenter of a radiographic system is always illustrated as the orientation point.
- Fixpoints
Clearly marked points on system components, installation ceiling, walls or floor on which cable
outlets are located.
Illustration in the drawings: octagon with letter/number-combination.
The cable lengths specify the maximum fixpoint distances and thus the maximum distances
between the individual system components.
- Room height
The room height is the distance measured from the top surface of the floor to the bottom surface of
the ceiling structural elements (Unistrut rails) (bottom surface of drop ceiling).
- Room lighting
According to DIN 68 68-57 (international standard in preparation), the lighting in rooms in which
image playback devices (monitors) are used for diagnosis, the following requirements must be
met:
adjustable, no anti-glare screen, reproducible adjustment of the lighting (e.g. dimmer with
scale),
no glare or reflection from windows, lights and light boxes in the standard working position of
the monitors.
Hotline+ 49 (9191) 18 - 8080
Siemens AGSPB7-250.891.01Page 1 of 6MAMMOMAT Novation
Medical SolutionsRev. 0408.05CS SD 21
DR
Page 6
1 - 2General Notes
Safety1
- The provisions of the relevant fire safety regulations must be observed for the premises.
- The system has been developed according to EN 60601 - 1.
- Minimum dimensions (e.g. room heights, safety distances) indicated in the planning guides are
marked "min."
- Basic resistance to electromagnetic sources of interference.
Result of lightning discharges.
The protection targets of the different lightning protection areas up to the unit connection are also
specified in the IEC 1024, DIN 48810, VDE 0675 and in the DEMVT recommendations.
The acquisition workstation supports the TCP/IP protocol. Due to the required data volumes, we recommend a network of 100 MB/s. Please note that all required network cables, as well as the required
power outlets must be available on site. If needed, an outside contractor must be obtained on site.
Software Installation1
The acquisition workstation is shipped with the software already preinstalled.
DICOM1
For detailed information on the DICOM, see PG TDIT-000.891.02...,
which can be found on the Intranet under: CS/ForService/Planning/General...
Siemens AGSPB7-250.891.01Page 5 of 6MAMMOMAT Novation
Medical SolutionsRev. 0408.05CS SD 21
2 cable conduits (each 2 m) included
in the shipment for "on-the-floor"
laying of cables
For additional cable conduits, see
*2
Focus
*1min. 150 mm if the unit is not secured to the
*3
*3For safety reasons, the acquisition workstation must be set up outside the area,
per IEC 60601-1-1.
floor (in a special service situation, the generator must be swung out from behind at the stand;
for this, the stand must be moved 500 mm away
from the wall).
min. 500 mm if the unit is secured to the floor.
*2If needed, additional cable conduits, Part No. 64
38 795 X041E, can be ordered for the connection between the stand and the radiation shield.
NOTE
Siemens AGSPB7-250.891.01Page 1 of 6MAMMOMAT Novation
Medical SolutionsRev. 0408.05CS SD 21
The room planning example shows one possible arrangement of the units.
Other arrangements are possible, provided the necessary unit distances
based on the available cable lengths are maintained.
DR
Page 12
2 - 2Room Planning
Room Planning Example 2 2
2 cable conduits (each 2 m) included
in the shipment for "on-the-floor"
laying of cables
For additional cable conduits, see
*2
Focus
*1min. 150 mm if the unit is not secured to the
floor (in a special service situation, the generator must be swung out from behind at the stand;
for this, the stand must be moved 500 mm away
from the wall).
min. 500 mm if the unit is secured to the floor.
*2If needed, additional cable conduits, Part No. 64
38 795 X041E, can be ordered for the connection between the stand and the radiation shield.
*3
*3For safety reasons, the acquisition workstation must be set up outside the area,
per IEC 60601-1-1.
NOTE
The room planning example shows one possible arrangement of the units.
Other arrangements are possible, provided the necessary unit distances
based on the available cable lengths are maintained.
Installing the Control Console on the Wall or on a Table2
If the system is not equipped with the optional radiation shield, install the control console on the wall or
on a table that is located behind one of the on-site radiation shields. The parts required for vertical or
horizontal installation of the control console on the wall are included in the shipment.
NOTE
Installing the Control Console on the Wall (two possibilities)
Screw anchors and screws are not included in the shipment. Please obtain
these locally and make sure that they are suitable for the particular type of wall
construction.
Cable conduit, on-site
Installation of the Control Console on a Table
Siemens AGSPB7-250.891.01Page 5 of 6MAMMOMAT Novation
Medical SolutionsRev. 0408.05CS SD 21
DR
Page 16
2 - 6Room Planning
Acquisition Workstation2
Comprised of: 18" color display, PC, keyboard, mouse
Table (option)
1 : 20
The height of table for the acquisition workstation can be adjusted using a motor.
If the table (option) for the acquisition workstation is not ordered, it must be
provided by the customer.
DR
SPB7-250.891.01Page 6 of 6Siemens AG
Page 17
Preparation for Installation3
3 - 1
Stand Floor Plate3
(The floor plate is designed to also be the unit base)3
If due to local regulations (e.g. in earthquake regions) or due to the quality of the floor covering, floor
installation is required, the stand can be installed using heavy-duty expansion bolts or threaded rods
(with a counter-plate). Heavy-duty expansion bolts and threaded rods must be obtained locally.
Cable lead-in from the floor only if the on-the-floor cable conduits included in the
shipment cannot be used. For on-the-floor cable conduits, see Pages 2-1, 2-2
Slots for cable
lead-in
Cable lead-in from the floor left or
right. Obtain cable conduits on site.
1 : 10
View Z
See Page 3-2
*1See *1 Pages 2-1, 2-2
The max. pull forces that occur per mounting point: 1.5 kN
Siemens AGSPB7-250.891.01Page 1 of 4MAMMOMAT Novation
Medical SolutionsRev. 0408.05CS SD 21
DR
Page 18
3 - 2Preparation for Installation
Radiation Shield Floor Plate (Option)3
The radiation shield must always be installed on the floor in accordance with IEC 60601-2-32.
Z
Max. pull forces that occur per
mounting point: 1.5 kN
For mounting example, see below
1 : 10
Installation example
Z (1 : 2)
Leveling screw
Cover plate
Room for cable lead-in in floor
Floor plate
Caulk all around using
sanitary silicon
E.g. Hilti heavy duty anchor bolts
HSL M8/20
If safety screws are used, the
manufacturer’s specifications
and instructions must be
observed
With installation on the a solid
floor, cut out the floor covering.
Concrete quality for the solid
floor, min. C20/25
Recommendation for an on-site power distributor per DIN VDE 0100-710 or national regulations
Must be constructed on site
Power cable for radiation
To external conductive parts
FI switch, 63 A/I
current and pulsed DC fault currents (recommendation:
Siemens FI 5SZ3 466 0KG05 all current sensitive or
ABB No. F 804 - 63 /0.03. Can be ordered from ABB
Stotz - contact Heidelberg, Tel. 06221 701-00). For other
power line voltages, an appropriate FI switch must be
obtained locally.
System power switch
N 30 mA, UN = 400/415 V ∼ for AC
∆
Emergency off switch with latch mechanism
SIEMENS
On/off switch with pilot lamp
Data corresponds to free lengths in m
This is a dedicated power cable. Thus the following may not be connected:
• Electrical systems
• Heating/air conditioning units
• Elevators
• General electrical equipment
Siemens AGSPB7-250.891.01Page 3 of 4MAMMOMAT Novation
Medical SolutionsRev. 0408.05CS SD 21
DR
Page 20
3 - 4Preparation for Installation
On-site Electrical Installation3
Recommendation for an on-site power distributor per DIN VDE 0100-710 or national regulations
Must be constructed on site
2-phase
Power cable for radiation
SIEMENS
To external conductive parts
FI switch 63 A/I
pulsed DC fault currents (recommendation: Siemens FI
5SZ3 466 0KG05 all current sensitive or ABB No. F 804
- 63 /0.03. Can be ordered from ABB Stotz - contact
Heidelberg, Tel. 06221 701-00). For other line voltages,
an appropriate FI switch must be obtained locally.
System power switch
N 30 mA, UN = 400/415 V ∼ for AC and
∆
Emergency off switch with latch mechanism
SIEMENS
On/off switch with pilot lamp
Data corresponds to free lengths in m
This is a dedicated power cable. Thus the following may not be connected: