The reproduction, transmission or
use of this docu men t or its con tent s
is not permitted without express
written authority. Offenders will be
liable for damages. All rights,
including rights created by patent
grant or registration of a utility
model _or_ design,_are_ reserved.
English
Print No.: SPB7-230.031.18.01.02 Doc . Gen. Date:10.00
Replaces: n.a65 68 641
Page 2
0 - 2Revision
ChapterPageRevision
AllAll01
OpdimarSPB7-230.031.18Page 2 of 4Siemens-Elema AB
InstallationRev. 0110.00SPS-UDSolna, Sweden
Siemens-Elema ABSPB7-230.031.18Page 3 of 4Opdimar
Solna, SwedenRev . 0110.00SPS-UDInstallation
Page 4
0 - 4Contents
This page intentionally left blank.
OpdimarSPB7-230.031.18Page 4 of 4Siemens-Elema AB
InstallationRev. 0110.00SPS-UDSolna, Sweden
Page 5
Prerequisites1
General1
This document is an instruction how to i nstall the workstation table, a mot orized vertically
adjustable table that shall be used with the Opdima
for use - Workstation table", "Planning Guide" and "Disposal Instruct ions" are also
enclosed with the delivery of the workstation table.
r system. The documents "Ins tructions
1 - 1
The "Disposal Instruction s" is also delivered with the Opdima
an older version of the "Disposal instruct ions" th e one delivered with th e workstation tabl e
shall replace it. If an Opdima
table, both deliveries include a "Disposal Instructions". The one delivered with the workstation table shall then be used.
Trained personnel shall perform the installation.
r system is delivered on the same delivery as the workstati on
r system. If a customer has
Tools required1
Standard installation tools are required for this installation.
Siemens-Elema ABSPB7-230.031.18Page 1 of 2Opdimar
Solna, SwedenRev . 0110.00SPS-UDInstallation
Page 6
1 - 2Prerequisites
This page intentionally left blank.
OpdimarSPB7-230.031.18Page 2 of 2Siemens-Elema AB
InstallationRev. 0110.00SPS-UDSolna, Sweden
Page 7
Installation2
NOTICE
General2
The workstation table, a motorized vert ically adjustable table, shall be used to put the
workstation components to the Opdima
includes a transformer, which is not mounted on delivery.
Additional equipment is added on own risk and the maximum load of
80 kg must not be exceeded.
Preparing the workstation table2
3
Handschalter
r system on. The vertical adjustment device
1
2 - 1
2
4
Fig. 1
5
Opd00494
1.Remove the screws on the underside of the tabl etop and use them when
mounting the transformer (1/Fig . 1).
Place the transformer so that the co nnectors are turned to the column.
2.Connect the cable from the control uni t (2/Fig. 1) for the vertical ly adjustment to
the connector marked "Handschalter" (3/Fig. 1).
3.Connect the cable from the motor (4/F ig. 1) for the vertically adj ustment to the
other connector (5/Fig. 1) .
Siemens-Elema ABSPB7-230.031.18Page 1 of 4Opdimar
Solna, SwedenRev . 0110.00SPS-UDInstallation
Page 8
2 - 2Installation
NOTICE
4.Place the workstation table outs ide the patient environment of safety reasons.
Patient environment is determined by IEC 6060 1-1-1 as 1.5 m away from the
patient.
Cables 8 m
Cable 1,5 m
Biopsy
controller
Stand
Biopsy unit
Min.1,5 m
Cable (workstation table) 2 m
Workstation
CCD camera holder
150
Cable duct
CCD camera
Generator
Fig. 2
OPD00489
There must be enough space around the workst ation table so i t can be
safely vertical adjusted.
5.If the workstation table st ands on an uneven floor, it can be adjusted wit h the
adjustable screws on the framework.
OpdimarSPB7-230.031.18Page 2 of 4Siemens-Elema AB
InstallationRev. 0110.00SPS-UDSolna, Sweden
Page 9
Installation2 - 3
CAUTION
Connecting the cables2
HEWLETT
PACKARD
Fig. 3
1.Place the monitor, the keyboard and the mouse on the tabletop. Make sure that all
the equipment is within the edge s of the tabletop.
2.Let the cables from the monitor, the keyboard and t he mouse pass through the
hole at the back of the tabletop.
2
1
OPD00502
3.Place the computer unit to the r ight on its shelf (1/Fig. 3 ).
4.Mount the MO unit shelf close to the computer unit (2/Fig. 3).
5.Place the MO unit to the right on the shel f (2/Fig. 3).
6.Connect the cables to the computer unit as shown i n the figure below:
Power cord
Keyboard
Monitor
A
Biopsy controller
B
MO unit
Printer (option)
Camera controller
Network
Fig. 4
Connecting a cable to a wrong connector may cause severe damage to the equipment.
Siemens-Elema ABSPB7-230.031.18Page 3 of 4Opdimar
Solna, SwedenRev . 0110.00SPS-UDInstallation
Page 10
2 - 4Installation
Strain relieving the cables2
To avoid that the cables from the workstation components and from the Mammomat can
cause any harm, they must be strain relieved with cable clamps at the back of the MO unit
shelf according to the figure below (Fig. 5).
• To ensure that the cables have enough length for the vertical adjustment, let th e
workstation table be in its highest possible position when strain relie ving the cables.
• Use cable ties to arrange the cables in an organi zed way and make sure that the cables
can run without a risk of getting caught .
1
3
SCSI CONNECTOR
Fig. 5
OPD00503
Keyboard
Printer
(option)
Biopsy controllerMonitorCamera controller
Printer (Option)2
If there is a printer (opti on) included in t he Opdimar system the ca ble from the pr inter shall
be connected to the computer unit as shown in (Fig. 4) and strain relieved as shown in
(Fig. 5).
Functional test2
Before the installed workstation t able is handed over to the customer, check that the workstation table can be vertically adjuste d between the highest and lowest possi ble posi tions
properly and safety.
OpdimarSPB7-230.031.18Page 4 of 4Siemens-Elema AB
InstallationRev. 0110.00SPS-UDSolna, Sweden
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.