Siemens MAMMOMAT 1000 Installation Instructions

Page 1
MAMMOMAT 1000/3000/3000 Nova - Opdimar
Installation
Installation Instructions
Workstation table
© Siemens AG 2000
The reproduction, transmission or use of this docu men t or its con tent s is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model _or_ design,_are_ reserved.
English
Print No.: SPB7-230.031.18.01.02 Doc . Gen. Date: 10.00
Replaces: n.a 65 68 641
Page 2
0 - 2 Revision
Chapter Page Revision
All All 01
Opdimar SPB7-230.031.18 Page 2 of 4 Siemens-Elema AB Installation Rev. 01 10.00 SPS-UD Solna, Sweden
Page 3
Contents 0 - 3
Page
1 _______Prerequisites __________________________________________________1 - 1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 1
Tools required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 - 1
2 _______Installation ____________________________________________________2 - 1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 1
Preparing the workstation table . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 - 1
Connecting the cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 3
Strain relieving the cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 4
Printer (Option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 4
Functional test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 4
Siemens-Elema AB SPB7-230.031.18 Page 3 of 4 Opdimar Solna, Sweden Rev . 01 10.00 SPS-UD Installation
Page 4
0 - 4 Contents
This page intentionally left blank.
Opdimar SPB7-230.031.18 Page 4 of 4 Siemens-Elema AB Installation Rev. 01 10.00 SPS-UD Solna, Sweden
Page 5

Prerequisites 1

General 1

This document is an instruction how to i nstall the workstation table, a mot orized vertically adjustable table that shall be used with the Opdima for use - Workstation table", "Planning Guide" and "Disposal Instruct ions" are also enclosed with the delivery of the workstation table.
r system. The documents "Ins tructions
1 - 1
The "Disposal Instruction s" is also delivered with the Opdima an older version of the "Disposal instruct ions" th e one delivered with th e workstation tabl e shall replace it. If an Opdima table, both deliveries include a "Disposal Instructions". The one delivered with the work­station table shall then be used.
Trained personnel shall perform the installation.
r system is delivered on the same delivery as the workstati on
r system. If a customer has

Tools required 1

Standard installation tools are required for this installation.
Siemens-Elema AB SPB7-230.031.18 Page 1 of 2 Opdimar Solna, Sweden Rev . 01 10.00 SPS-UD Installation
Page 6
1 - 2 Prerequisites
This page intentionally left blank.
Opdimar SPB7-230.031.18 Page 2 of 2 Siemens-Elema AB Installation Rev. 01 10.00 SPS-UD Solna, Sweden
Page 7

Installation 2

NOTICE

General 2

The workstation table, a motorized vert ically adjustable table, shall be used to put the workstation components to the Opdima includes a transformer, which is not mounted on delivery.
Additional equipment is added on own risk and the maximum load of 80 kg must not be exceeded.

Preparing the workstation table 2

3
Handschalter
r system on. The vertical adjustment device
1
2 - 1
2
4
Fig. 1
5
Opd00494
1. Remove the screws on the underside of the tabl etop and use them when mounting the transformer (1/Fig . 1). Place the transformer so that the co nnectors are turned to the column.
2. Connect the cable from the control uni t (2/Fig. 1) for the vertical ly adjustment to the connector marked "Handschalter" (3/Fig. 1).
3. Connect the cable from the motor (4/F ig. 1) for the vertically adj ustment to the other connector (5/Fig. 1) .
Siemens-Elema AB SPB7-230.031.18 Page 1 of 4 Opdimar Solna, Sweden Rev . 01 10.00 SPS-UD Installation
Page 8
2 - 2 Installation
NOTICE
4. Place the workstation table outs ide the patient environment of safety reasons. Patient environment is determined by IEC 6060 1-1-1 as 1.5 m away from the patient.
Cables 8 m
Cable 1,5 m
Biopsy controller
Stand
Biopsy unit
Min.1,5 m
Cable (workstation table) 2 m
Workstation
CCD camera holder
150
Cable duct
CCD camera
Generator
Fig. 2
OPD00489
There must be enough space around the workst ation table so i t can be safely vertical adjusted.
5. If the workstation table st ands on an uneven floor, it can be adjusted wit h the adjustable screws on the framework.
Opdimar SPB7-230.031.18 Page 2 of 4 Siemens-Elema AB Installation Rev. 01 10.00 SPS-UD Solna, Sweden
Page 9
Installation 2 - 3
CAUTION
Connecting the cables 2
HEWLETT PACKARD
Fig. 3
1. Place the monitor, the keyboard and the mouse on the tabletop. Make sure that all the equipment is within the edge s of the tabletop.
2. Let the cables from the monitor, the keyboard and t he mouse pass through the hole at the back of the tabletop.
2
1
OPD00502
3. Place the computer unit to the r ight on its shelf (1/Fig. 3 ).
4. Mount the MO unit shelf close to the computer unit (2/Fig. 3).
5. Place the MO unit to the right on the shel f (2/Fig. 3).
6. Connect the cables to the computer unit as shown i n the figure below:
Power cord
Keyboard
Monitor
A
Biopsy controller
B
MO unit
Printer (option)
Camera controller
Network
Fig. 4
Connecting a cable to a wrong connector may cause severe dam­age to the equipment.
Siemens-Elema AB SPB7-230.031.18 Page 3 of 4 Opdimar Solna, Sweden Rev . 01 10.00 SPS-UD Installation
Page 10
2 - 4 Installation
Strain relieving the cables 2
To avoid that the cables from the workstation components and from the Mammomat can cause any harm, they must be strain relieved with cable clamps at the back of the MO unit shelf according to the figure below (Fig. 5).
To ensure that the cables have enough length for the vertical adjustment, let th e
workstation table be in its highest possible position when strain relie ving the cables.
Use cable ties to arrange the cables in an organi zed way and make sure that the cables
can run without a risk of getting caught .
1
3
SCSI CONNECTOR
Fig. 5
OPD00503
Keyboard
Printer (option)
Biopsy controller Monitor Camera controller
Printer (Option) 2
If there is a printer (opti on) included in t he Opdimar system the ca ble from the pr inter shall be connected to the computer unit as shown in (Fig. 4) and strain relieved as shown in (Fig. 5).
Functional test 2
Before the installed workstation t able is handed over to the customer, check that the work­station table can be vertically adjuste d between the highest and lowest possi ble posi tions properly and safety.
Opdimar SPB7-230.031.18 Page 4 of 4 Siemens-Elema AB Installation Rev. 01 10.00 SPS-UD Solna, Sweden
Loading...