Siemens 7SR11 Argus, 7SR12 Argus User Manual

Answers for energy
7SR11 and 7SR12 Argus
Overcurrent Relays
Protection
Devices
Siemens Protection Devices Limited 2
The 7SR11 & 7SR12 are overcurrent protection relays developed to enhance the Argus family of products by providing a familiar product using the latest generation of hardware technology. The 7SR11 overcurrent and earth fault relays and the 7SR12 directional relays are available in single and four pole variants. Housed in a 4U high, size E4 case, these relays provide protection, monitoring, instrumentation and metering with integrated input and output logic, data logging & fault reports. Communication access to the relay functionality is via a front USB port for local PC connection or rear electrical RS485 port for remote connection.
Protection
37 Undercurrent 46BC Broken Conductor / Load Unbalance 46NPS Negative Phase Sequence Overcurrent 49 Thermal Overload 50 Instantaneous Overcurrent 50G/N/SEF Instantaneous Earth Fault 50BF Circuit Breaker Fail 51 Time Delayed Overcurrent 51G/N/SEF Time Delayed Measured/Derived/Sensitive Earth
Fault 64H High Impedance REF 27/59 Under/Over Voltage 47 Negative Phase Sequence Voltage 51V Voltage Controlled Overcurrent 59N Neutral Voltage Displacement 67/50 Directional Instantaneous Overcurrent 67/50G/N Directional Instantaneous Earth Fault 67/51 Directional Time Delayed Overcurrent 67/51G/N Directional Time Delayed Earth Fault 81HBL2 Inrush Detector
Supervision
60CTS CT Supervision 74T/CCS Trip & Close Circuit Supervision 60VTS VT Supervision
Control
79 Auto Reclose 86 Lockout CB Control
Features
Cold Load Settings Four Settings Groups Password Protection – 2 levels User Programmable Logic Self Monitoring Circuit Breaker Trip and Maintenance Counter Tri p Tim ers
20 Character x 4 Line Backlit LCD Menu Navigation Keys 9 User Programmable Tri-colour LEDs User Language Configuration
Primary/Secondary Current Phases and Earth Direction Primary/Secondary Line and Phase Voltages Apparent Power and Power Factor Real and Reactive Power W Hr & VAr Hr Forward and Reverse Historical Demand Record Positive Phase Sequence (PPS) Voltage & Current Negative Phase Sequence (NPS) Voltage & Current Zero Phase Sequence (ZPS) Voltage
1 CT 3 Binary Inputs 5 Binary Outputs 4 CT 3 Binary Inputs 5 Binary Outputs 4 CT 6 Binary Inputs 8 Binary Outputs 1 CT 3 VT 3 Binary Inputs 5 Binary Outputs 4 CT 3 VT 3 Binary Inputs 5 Binary Outputs 4 CT 3 VT 6 Binary Inputs 8 Binary Outputs
Front USB port + Rear RS485 port Protocols - IEC60870-5-103, DNP3.0 or Modbus RTU Event Records – User Configurable Fault Records Waveform Records Measurands Commands Time Synchronism Viewing and Changing Settings
7SR11 and 7SR12 Argus
Overcurrent Relays
Description
User Interface
Data Storage and Communication
Hardware
Monitoring Functions
Function Overview
Siemens Protection Devices Limited 3
The Argus is a numerical overcurrent protection relay intended for use on distribution and industrial networks. It provides a highly comprehensive functional software package with a range of integral application functions aimed at reducing installation, wiring and engineering time. An extensive range of metered values can be viewed on the front LCD or at a remote point via the communication channel. The integrated control feature allows operation of a single circuit breaker and monitoring of its trip and close circuits.
FUNCTION
FUNCTIONAL
REQUIREMENT
7SR1101-1*A12-**A0
7SR1101-3*A12-**A0
7SR1102-1*A12-**A0
7SR1102-3*A12-**A0
7SR1204-2*A12-**A0
7SR1204-4*A12-**A0
7SR1205-2*A12-**A0
7SR1205-4*A12-**A0
27 Undervoltage ■■■
37 Undercurrent ■■
46BC Broken Conductor / Load Unbalance ■■
46NPS
Negative Phase Sequence Overcurrent
■■
47 Negative Phase Sequence Voltage ■■■
49 Thermal Overload ■■
50 Instantaneous Overcurrent ■■
50G Measured Instantaneous Earth Fault ■■■■
50SEF
Measured Instantaneous Sensitive Earth Fault
■■■
50N Derived Instantaneous Earth Fault ■■
50BF CB Failure ■■■■■■■
51 Time Delayed Overcurrent
■■
51G Measured Time Delayed Earth Fault ■■■■
51SEF
Measured Time Delayed Sensitive Earth Fault
■■■
51N Derived Time Delayed Earth Fault ■■
59 Overvoltage ■■■
59N Neutral Voltage Displacement ■■■
64H
High Impedance Restricted Earth Fault
■■■■■■■
67 Directional Overcurrent ■■■
67G Directional Measured Earth Fault ■■
67SEF Directional Sensitive Earth Fault ■■
67N Directional Derived Earth Fault ■■
CONTROL / MONITOR
51c Cold Load - Phase Only ■■ ■■
60CTS CT Supervision ■■ ■■
60VTS VT Supervision ■■■■
74T/CCS Trip & Close Circuit Supervision ■■■■■■■■
79 Autorec lose □□ □□
86 Lockout ■■■■■■■■
Key - ■ - Included as standard
- Ordering option
Fig 1. Single Pole Overcurrent Relay
7SR11
37
(x2)
49
50
(x2)51(x2)
50G (x2)
51G (x2)
50 BF
50N (x2)
51N (x2)
46 BC
46 NPS (x2)
81
HBL2
37
(x2)
49
50
(x2)
50 BF
81
HBL2
37
(x2)
49
50
(x2)
50 BF
81
HBL2
74
T/CCS
51
(x2)
51
(x2)
81
HBL2
N
81
HBL2
G
I
4
(IG/ISEF)
IL1
(IA)
IL2
(IB)
IL3
(IC)
60
CTS
60
CTS
60
CTS
50 SEF (x2)
51 SEF (x2)
64H
50 BF
79
Optional
51c
51c
51c
Fig 2. Four Pole Overcurrent Relay
Application 7SR11 Functional Diagrams
Function Matrix
Siemens Protection Devices Limited 4
VL1
VL2
VL3
67/ 50 G (x4)
67/ 51 G (x4)
64 H
74 T/
CCS
81H
BL 2
67/ 50 SE F(x2)
67/ 51 S E F(x2)
59 N (x2)
47
(x2)
27 59
(x 4)
27 59
(x 4)
27 59
(x 4)
7SR12
37
(x2)
I1
(I
G/ISEF)
Fig 3. Single Pole Directional Relay
7SR12
64H
46 BC
46 NPS (x2)
37
(x2)
49
50 BF
VL1
VL2
VL3
IL1
37
(x2)
49
50 BF
IL2
37
(x2)
49
50 BF
IL3
60
CTS60VTS
I4
74
T/CCS
67/ 50
(x4)
67/ 51
(x4)
67/ 50N (x4)
67/
50 (x4)
67/
50 (x4)
67/ 51
(x4)
67/ 51
(x4)
67/ 51N (x4)
67/ 50G (x4)
67/ 51G (x4)
27 59
(x4)
27 59
(x4)
27 59
(x4)
59N
47
79
Optional
50 BF
50 BF
37
81HBL
2
81HBL
2
81HBL
2
51V
51V
51V
67/
50SEF(
x2)
67/
51SEF(
x2)
81HBL
2
51c
51c
51c
Fig 4. Four Pole Directional Overcurrent Relay
Notes
1. Items shown dotted are only available in some models; please refer to the Ordering Information Section.
2. The use of some functions are mutually exclusive
27/59 Under/Over Voltage
Each element has settings for pickup level, drop-off level and Definite Time Lag (DTL) delays. Operates if voltage exceeds setting for duration of delay.
37 Undercurrent
Each element has settings for pickup level and Definite Time Lag (DTL) delays. Operates if current falls below setting for duration of delay.
46BC Phase Unbalance/Broken Conductor
Element has settings for pickup level and DTL delay. With the circuit breaker closed, if the NPS:PPS current ratio is above setting this could be due to a broken conductor.
46NPS Negative Phase Sequence Overcurrent
Each element has user settings for pickup level and IDMTL or DTL delay, operates if NPS current exceeds setting and delay. NPS current elements can be used to detect unbalances on the system or remote earth faults when a delta-star transformer is in circuit.
47 Negative Phase Sequence Voltage
Each element has settings for pickup level and Definite Time Lag (DTL) delays. Operates if NPS voltage exceeds setting for duration of delay.
49 Thermal Overload
The thermal algorithm calculates the thermal states from the measured currents and can be applied to lines, cables and transformers. Alarm outputs are given for thermal overload and thermal capacity.
50BF Circuit Breaker Fail
The circuit breaker fail function may be triggered from an internal trip signal or from a binary input. Line currents and earth currents are monitored following a trip signal and an output is issued if any current is still detected, above setting, after a specified time interval. Alternatively, if the trip is from a mechanical protection the circuit breaker position can be used to determine a failure. A second time delay is available to enable another stage to be utilized if required. An input is also available to bypass the time delays when the circuit breaker is known to be faulty.
Description of Functionality 7SR12 Functional Diagrams
Siemens Protection Devices Limited 5
50/51 Phase Fault
50 INST/DTL and 51 IDMTL/DTL elements provide overcurrent protection, each with independent settings for pickup current, time-multiplier (51) and time-delays. User can select IEC or ANSI time current characteristics. The IDMT stage has a user programmable reset characteristic, either DTL or shaped current ~ time reset characteristic, to improve grading with electromechanical protection.
50G/51G/50N/51N Earth Fault/Sensitive Earth Fault
Two earth fault measurement modes are available. One mode directly measures the earth current from an independent CT, or the residual connection of the 3 line CTs. This input can be ordered as either earth fault or sensitive earth fault (50G/51G). The second mode derives the earth current internally from the 3 phase CT inputs to give earth fault (50N/51N). 50 INST/DTL and 51 IDMTL/DTL elements provide overcurrent protection, each with independent settings for pickup current, time-multiplier (51) and time-delays. User can select IEC or ANSI time current characteristics. The IDMT stage has a user programmable reset characteristic either DTL or shaped current ~ time reset characteristic to improve grading with electromechanical protection.
0.1
1
10
100
1000
110100
Current (m ultiples of setting)
Time (sec)
2 3 4 5 6 8 20 30 40 50 60 80
Long Time Inverse
Normal Inverse
Very Inverse
Extremely Inverse
Fig 5. IEC Overcurrent Curves
0.1
1
10
100
1000
110100
Current (multipl e s of setting)
Time (sec)
2 3 4 5 6 8 20 30 40 50 60 80
Moderately Inverse
Extremely Inverse
Very Inverse
Fig 6. ANSI Overcurrent Curves
51V Voltage Controlled Overcurrent
Each phase shaped overcurrent element can be independently controlled by the level of measured input voltage. For applied voltages above setting the 51-n element operates in accordance with its current setting but for voltages below the setting a multiplier is applied to reduce the 51-n pick up current setting.
59N Neutral Overvoltage
Neutral overvoltage can be used to detect earth faults in high impedance earthed or isolated systems. Operates if the neutral voltage exceeds setting for duration of delay.
60CTS CT Supervision
The relay has two methods of CT supervision depending upon the relay model. The 7SR11 monitors each phase current input and operates if any one or two inputs fall below the setting. The 7SR12 considers the presence of negative phase sequence current, without an equivalent level of negative phase sequence voltage, for a user set time as a CT failure. Both element types have user operate and delay settings.
60VTS VT Supervision
The VT supervision uses a combination of negative phase sequence voltage and negative phase sequence current to detect a VT fuse failure. This condition may be alarmed or used to inhibit voltage dependent functions. Element has user operate and delay settings.
Siemens Protection Devices Limited 6
64H Restricted Earth Fault
The measured earth fault input may be used in a 64H high impedance restricted earth fault scheme to provide sensitive high speed unit protection. A calculation is required to determine the values of the external series stabilising resistor and non-linear shunt resistor which can be ordered separately.
67/67N Directional Control
Phase, earth and sensitive earth fault elements can be directionalised. Each element can be user set to Forward, Reverse, or Non-directional. Directional Phase Fault elements are polarised from quadrature voltage. Derived earth fault elements can be user set to be polarised from residual voltage or negative phase sequence voltage. Measured earth fault elements are polarized from Vo.
74T/CCS Trip & Close Circuit Supervision
The trip or close circuit(s) can be monitored via binary inputs. Trip circuit failure raises an HMI alarm and output(s).
81HBL2 Inrush Restraint
Where second harmonic current is detected (i.e. during transformer energisation) user selectable elements can be blocked and an alarm given.
51c Cold Load Pickup
If a circuit breaker is closed onto a ‘cold’ load, i.e. one that has not been powered for a prolonged period, this can impose a higher than normal load-current demand on the system which could exceed normal settings. These conditions can exist for an extended period and must not be interpreted as a fault. To allow optimum setting levels to be applied for normal operation, the cold load pickup feature will apply alternative current settings for a limited period. The feature resets when either the circuit breaker has been closed for a settable period, or if the current has reduced beneath a set level for a user set period.
Standard Version – Plus 79 Auto-Reclose
A high proportion of faults on an overhead line network are transient and can be cleared quickly by high speed tripping followed by an automated circuit breaker reclose sequence.
The function provides independent phase fault and earth fault / sensitive earth fault sequences of up to 5 trip i.e. 4 reclose attempts before lockout. An auto-reclose sequence can be user set to be initiated from internal protection operation or via binary input from an external protection.
Programmable Logic
The user can map binary inputs, protection elements, LEDs and binary outputs together in a logical scheme. Up to 4 logic equations can be defined using standard logic functions e.g. Timers, AND/OR gates, Inverters and Counters to provide the user required functionality. Each logic equation output can be used for alarm & indication and/or tripping.
Virtual Inputs/Outputs
There are 8 virtual inputs/outputs to provide internal logical states to assist in the application of the functions. Each virtual I/O can be assigned in the same way as a physical I/O.
Circuit Breaker Maintenance
Two circuit breaker operations counters are provided to assist with maintenance scheduling. The maintenance counter records the overall number of operations and the delta counter records the number of operations since the last reset. An I
2
t summation counter provides a measure of the contact wear indicating the total energy interrupted by the circuit breaker contacts. Each counter has a user set target operations count which, when reached, can be mapped to raise alarms/ binary outputs. A CB Trip Time meter is also available, which measures the time between the trip being issued and the auxiliary contacts changing state.
Control Mode
The relay has a control menu with access to commonly used command operations. Access to the control commands is restricted by a 4 character control function password. Each command requires a select then execute operation, if the execute operation is not performed within a time window the command is aborted. The following control functions are available: CB Operation Auto Reclose In/Out Auto Reclose Trip & Reclose Auto Reclose Trip & Lockout SEF In/Out Inst Prot In/Out Hot Line Working In/Out
Fig 7. Example of Control Function View
Loading...
+ 14 hidden pages