SEW Eurodrive UFP11A User Manual

PROFIBUS DP-V1 UFP11A Fieldbus Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Edition
02/2004
Manual
11254416 / EN
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
1 System Overview ..........................................................................4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
2 Unit Design ....................................................................................5
2.1 Front view .............................................................................5
3 Installation and Operation without PC........................................6
3.1 Installation notes ...................................................................6
3.2 Setting the inverter parameters............................................. 9
3.3 Autosetup............................................................................10
3.4 Project planning of the fieldbus master............................... 12
3.5 Starting the inverters...........................................................13
4 Installation and Operation with PC............................................14
4.1 Installation notes .................................................................14
4.2 Setting the inverter parameters........................................... 17
4.3 Startup software..................................................................17
4.4 Starting the inverters...........................................................18
5 PROFIBUS interface....................................................................19
5.1 Startup up PROFIBUS DP master ......................................19
5.2 Configuration of the PROFIBUS DP interface.....................19
5.3 Ident number.......................................................................25
5.4 Inverter control ....................................................................25
6 DP-V1 Functions..........................................................................27
6.1 Introduction to PROFIBUS DP-V1 ......................................27
6.2 Features of SEW drive inverters .........................................29
6.3 Structure of the DP-V1 parameter channel......................... 30
6.4 Project planning for a C1 master.........................................46
6.5 Appendix .............................................................................47
7 Error Responses .........................................................................54
7.1 Fieldbus timeout.................................................................. 54
7.2 SBUS timeout .....................................................................54
7.3 Device errors....................................................................... 54
8 LEDs.............................................................................................55
8.1 RUN ....................................................................................55
8.2 BUS-FAULT ........................................................................55
8.3 SYS-FAULT ........................................................................56
8.4 USER ..................................................................................56
9 DIP Switches................................................................................57
9.1 Setting the station address .................................................57
10 Operating the Interface...............................................................58
11 Appendix......................................................................................61
11.1 List of errors ........................................................................61
11.2 Technical data.....................................................................62
11.3 Dimension sheet .................................................................63
12 Index.............................................................................................64
Manual – PROFIBUS UFP11A Fieldbus Interface
1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
System Overview
1 System Overview
Handbuch
The UFP11A PROFIBUS DP-V1 fieldbus interface is used for connecting inverters with the PROFIBUS DP-V1. Several inverters can be connected to the UFP11A PROFIBUS DP-V1 interface via the SBus. The UFP11A PROFIBUS interface establishes the connection between PROFIBUS DP-VI and SBus.
C1-Master
UFP
PROFIBUS DP-V1
C2-Master
C2-Master
MOVITRAC
Figure 1: System overview DP-V1 master – UFP – inverter
®
07
53453AXX
Manual – PROFIBUS UFP11A Fieldbus Interface
2Unit Design
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
2.1 Front view
Unit Design
Front view
2
Figure 2: Arrangement of LEDs, connectors and DIP switches
X1 SBus and 24 V connector X2 Diagnostic interface X3 PROFIBUS S1 DIP switch RUN Operating status BUS-F Bus fault SYS-F System fault USER Expert mode
Manual – PROFIBUS UFP11A Fieldbus Interface
04888AXX
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation without PC
Installation notes
3 Installation and Operation without PC
3.1 Installation notes
Installation
Pin assignment
The unit can be installed directly onto the wall of a control cabinet by using the pre­installed DIN rail mounting or the four drilled holes on the back of the housing. Basically, there are no restrictions regarding the spatial arrangement of the units to be connected (e.g. MOVITRAC
®
07). The maximum line length and the fact that the gateway must be installed at the end or the beginning of the system bus (SBus) must be taken into consideration. For this reason, we recommend you take the spatial aspects into account.
The UFP must have additional HF-compliant grounding if the DIN rail mounting option is used with SBus cables of more than 1 m in length.
The UFP11A fieldbus interface is connected to the PROFIBUS network by means of a 9-pin sub D connector in accordance with EN 50170. The T-bus connection must be implemented with an appropriately designed plug.
[2]
[1]
RxD/TxD-P (B/ )B
RxD/TxD-N (A/ )A CNTR-P
DGND (M5V)
VP (P5V) DGND (M5V)
3
8 4
5 6 9
[3]
Fieldbus connector
Figure 3: Assignment of 9-pin sub D connector X3 according to EN 50170 ([1] = 9-pin sub D
connector; [2] = twisted signal lines; [3] = conductive connection between connector housing and shielding)
01222DXX
The fieldbus interface is generally connected to the PROFIBUS system using a shielded twisted-pair cable. The shielding of the PROFIBUS cable must be attached to both sides, for example on the connector housing. Observe the maximum supported transmission rate when selecting the bus connector.
The twisted-pair cable is connected to the PROFIBUS connector via pin 8 (A/A 3 (B/B
). Communication takes place via these two contacts. The RS-485 signals A/A
) and pin
and B/B must be contacted in the same way for all PROFIBUS stations. Otherwise, no communication is possible via the bus medium.
The PROFIBUS interface sends a TTL control signal for a repeater or fiber optic adapter (reference = pin 9) via pin 4 (CNTR-P).
Manual – PROFIBUS UFP11A Fieldbus Interface
System bus connection
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation without PC
Installation notes
3
Figure 4: System bus connection
UFP
GND = System bus reference SC11 = System bus high SC12 = System bus low
Please note:
Use a 2-core twisted and shielded copper cable (data transmission cable with
braided copper shield). Connect the shield with a wide-area contact at the electronics terminal of MOVITRAC The cable must meet the following specifications (CAN bus or DeviceNet cables are suitable, for example):
– Core cross section 0.75 mm
– Cable resistance 120 Ω at 1 MHz – Capacitance per unit length 40 pF/m (12 pF/ft) at 1 kHz
The approved total cable length depends on the specified SBus baud rate:
– 250 kbaud: 160 m (528 ft) – 500 kbaud: 80 m (264 ft) – 1000 kbaud: 40 m (132 ft)
MOVITRAC® 07
GND = System bus reference SC22 = System bus low, outgoing SC21 = System bus high, outgoing SC12 = System bus low, incoming SC11 = System bus high, incoming S12 = System bus terminating resistor
®
07 or UFP11A and also connect the shield ends to GND.
2
(AWG18)
04848AXX
Manual – PROFIBUS UFP11A Fieldbus Interface
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation without PC
Installation notes
Connect the system bus terminating resistor (S12 = ON) at the end of the system bus
connection. Disconnect the terminating resistor at the other devices (S12 = OFF). The UFP11A gateway must always be connected either at the beginning or the end of the system bus connection and feature a permanently installed terminating resistor.
There must not be any difference of potential between the units connected with the
SBus. Take suitable measures to avoid a difference of potential, such as connecting the unit ground connectors using a separate line.
Point-to-point wiring is not permitted.
24 V connection
Shielding and routing of bus cables
An external 24 V voltage supply must be connected to terminals X1:4 and X1:5.
The PROFIBUS interface supports the RS-485 communications protocol and requires cable type A specified for PROFIBUS in accordance with EN 50170 as shielded twisted­pair cable for the physical connection.
Correct shielding of the bus cable attenuates electrical interference that may occur in industrial environments. The following measures ensure the best possible shielding:
Tighten the mounting screws on the connectors, modules and equipotential bonding
conductors by hand.
Use only connectors with metal housing or plated housing.
Connect the shielding in the connector with the greatest possible surface area.
Attach the shielding of the bus line on both sides.
Do not route signal and bus cables parallel to power cables (motor leads). They must
be routed in separate cable ducts.
Use metallic, grounded cable racks in industrial environments.
Route the signal cable and the corresponding equipotential bonding in close
proximity using the shortest way possible.
Avoid using plug connectors to extend bus cables.
Route the bus cables closely along existing grounding surfaces.
In case of fluctuations in the earth potential, a compensating current may flow via the bilaterally connected shield that is also connected to the protective earth (PE). Make sure you supply adequate equipotential bonding according to relevant VDE regulations in such a case.
Manual – PROFIBUS UFP11A Fieldbus Interface
Installation and Operation without PC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Setting the inverter parameters
3
Bus termination
A bus termination is not provided on the UFP electronics. If the UFP module is used as the first or last device of the PROFIBUS line, the bus termination has to be external. We recommend PROFIBUS connectors with integrated bus termination that open the continuing bus in case the bus termination is connected.
3.2 Setting the inverter parameters
The settings can be entered via the inverter keypad. Refer to the operating instructions of the inverter for details.
Connect the voltage supply for the UFx and all connected inverters.
Set an individual SBus address (P813) at the inverters. Recommendation: Address
setting beginning with address 1 in ascending order based on the arrangement of inverters in the control cabinet. Address 0 should not be assigned because it is used by the UFx.
Verify the SBus baud rate (P816, factory setting = 500 kbaud).
Set the setpoint source (P100) to SBus (value 10).
Set the control source (P101) to SBus (value 3).
Set the terminal assignment of the binary inputs. For MOVITRAC
recommended for P60-. This corresponds to the following assignment:
– DI01 CW/Stop (wired to 24 V, both directions of rotation enabled) – DI02 CCW/Stop (no function) – DI03 F.Setp. toggle(not wired) – DI04 n11/n21 (not wired) – DI05 n12/n22 (not wired) – If you use a MOVIDRIVE
are not used to "No function."
Important: For MOVITRAC
PC, if necessary. The default value is 0, which means timeout monitoring is deactivated. Set P815 to the value 1 s.
®
07, the value 0 is
®
unit as inverter, you must program the terminals that
®
07, P815 SBus timeout interval can only be adjusted via
Manual – PROFIBUS UFP11A Fieldbus Interface
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
3.3 Autosetup
Installation and Operation without PC
Autosetup
The Autosetup function allows startup of the UFx to be performed without a PC. Activate the function via the Autosetup DIP switch. Switching on the Autosetup DIP switch causes the function to be performed once.
in ON position.
again. First, the UFx searches the lower-level SBUS for drive inverters. This process is indicated by the SYS-FAULT LED flashing briefly. For this purpose, different SBus addresses must be set for the drive inverters (P813). We recommend assigning the addresses beginning with address 1 in ascending order based on the arrangement of inverters in the control cabinet. The process image on the fieldbus side is expanded by three words for each detected drive inverter. If no inverter is detected, the SYS-FAULT LED remains lit. A total of up to eight drive inverters is taken into account. The figure shows the process image for three drive inverters with three words each of process output data and process input data. After the search is complete, the UFx cyclically exchanges three process data words with each connected drive inverter. The process output data are fetched from the fieldbus, divided into blocks of three and transmitted. The drive inverters read the process input data, put them together and send them to the fieldbus master.
Important: If you change the process data assignment of the drive inverters connected to the UFP, you have to activate Autosetup again because the UFP saves these values only once during Autosetup. At the same time, the process data assignments of the connected drive inverters may not be changed dynamically after Autosetup.
The function can be reactivated by turning the DIP switch off and back on
The Autosetup DIP switch must then remain
10
Manual – PROFIBUS UFP11A Fieldbus Interface
Installation and Operation without PC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Autosetup
3
Figure 5: Data exchange DP-V1 master – UFP – inverter
Manual – PROFIBUS UFP11A Fieldbus Interface
04843AXX
11
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation without PC
Project planning of the fieldbus master
3.4 Project planning of the fieldbus master
Set an individual PROFIBUS address using the DIP switches of the UFP for project
planning. The PROFIBUS address is set in binary form. A change of the PROFIBUS address only becomes effective after switching the UFP off and on again.
X = on
1 2 3 4 5 6 7 8 9 10
2 2 2 2 2 2 2 AS F1 F2
0 1 2 3 4 5 6
1: x 0 = +0 2: x 0 = +0 4: x 1 = +4 8: x 0 = +0
16: x 0 = +0 32: x 0 = +0 64: x 0 = +0
= 4
Figure 6: Setting the PROFIBUS station address
50341AXX
The fieldbus master is configured using the GSD file (see appendix). The UFP is
addressed under the specified PROFIBUS address. The number of process data words the fieldbus master uses to address the UFP depends on the number of connected inverters. The process data width for an inverter is three words. If more than one inverter is present, three words should be planned for each inverter. For example, you have to configure nine words for three MOVITRAC
®
07 inverters.
Example for STEP 7:
– Install the GDS file in the STEP 7 software. – In HW config of the hardware catalog, insert the UFP at the PROFIBUS. – Select the setting suitable for your application from the presented process data
configurations, for example "9PD", meaning nine process data words for three
inverters. – Save the configuration. – Expand your application program by the data exchange with the UFP. For this
purpose, use the system functions of S7 for consistent data exchange (SFC14
and SFC15). – The BUS-FAULT LED of the UFP should be extinguished after saving the project,
loading it in the DP-V1 master and starting the DP-V1 master. If this is not the
case, check the connections and terminating resistors of the PROFIBUS and the
project planning, especially the PROFIBUS address in STEP 7.
12
Manual – PROFIBUS UFP11A Fieldbus Interface
3.5 Starting the inverters
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
You can operate up to eight inverters on the PROFIBUS using one UFP. The DP master and the UFP exchange the setpoints and actual values of all inverters connected to the UFP in coherent data packages. It is important for you to know which inverter is located at which position of the data package (process image). Figure 5 shows the relationship.
The inverters are enabled by writing the value 0006h to the corresponding control word 1. The speed setpoint can be specified with the following word. It is scaled with
0.2 1/min per digit.
For more information on the unit profile of MOVITRAC 07 Communication" manual.
Installation and Operation without PC
Starting the inverters
®
07, refer to the "MOVITRAC
3
®
Manual – PROFIBUS UFP11A Fieldbus Interface
13
4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with PC
Installation notes
4 Installation and Operation with PC
4.1 Installation notes
Installation
Pin assignment
The unit can be installed directly onto the wall of a control cabinet by using the pre­installed DIN rail mounting or the four drilled holes on the back of the housing. Basically, there are no restrictions regarding the spatial arrangement of the units to be connected (e.g. MOVITRAC
®
07). The maximum line length and the fact that the gateway must be installed at the end or the beginning of the system bus (SBus) must be taken into consideration. For this reason, we recommend you take the spatial aspects into account.
The UFP must have additional HF-compliant grounding if the DIN rail mounting option is used with SBus cables of more than 1 m in length.
The UFP11A fieldbus interface is connected to the PROFIBUS network by means of a 9-pin sub D connector in accordance with EN 50170. The T-bus connection must be implemented with an appropriately designed plug.
[2]
[1]
RxD/TxD-P (B/ )B
RxD/TxD-N (A/ )A CNTR-P
DGND (M5V)
VP (P5V) DGND (M5V)
3
8 4
5 6 9
[3]
Fieldbus connector
Figure 7: Assignment of 9-pin sub D connector X3 according to EN 50170 ([1] = 9-pin sub D
connector; [2] = twisted signal lines; [3] = conductive connection between connector housing and shielding)
01222DXX
The fieldbus interface is generally connected to the PROFIBUS system using a shielded twisted-pair cable. The shielding of the PROFIBUS cable must be attached to both sides, for example on the connector housing. Observe the maximum supported transmission rate when selecting the bus connector.
The twisted-pair cable is connected to the PROFIBUS connector via pin 8 (A/A 3 (B/B
). Communication takes place via these two contacts. The RS-485 signals A/A
) and pin
and B/B must be contacted in the same way for all PROFIBUS stations. Otherwise, no communication is possible via the bus medium.
The PROFIBUS interface sends a TTL control signal for a repeater or fiber optic adapter (reference = pin 9) via pin 4 (CNTR-P).
14
Manual – PROFIBUS UFP11A Fieldbus Interface
System bus connection
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with PC
Installation notes
4
Figure 8: System bus connection
UFP
GND = System bus reference SC11 = System bus high SC12 = System bus low
Please note:
Use a 2-core twisted and shielded copper cable (data transmission cable with
braided copper shield). Connect the shield with a wide-area contact at the electronics terminal of MOVITRAC The cable must meet the following specifications (CAN bus or DeviceNet cables are suitable, for example):
– Core cross section 0.75 mm
– Cable resistance 120 Ω at 1 MHz – Capacitance per unit length 40 pF/m (12 pF/ft) at 1 kHz
The approved total cable length depends on the specified SBus baud rate:
– 250 kbaud: 160 m (528 ft) – 500 kbaud: 80 m (264 ft) – 1000 kbaud: 40 m (132 ft)
MOVITRAC® 07
GND = System bus reference SC22 = System bus low, outgoing SC21 = System bus high, outgoing SC12 = System bus low, incoming SC11 = System bus high, incoming S12 = System bus terminating resistor
®
07 or UFP11A and also connect the shield ends to GND.
2
(AWG18)
04848AXX
Manual – PROFIBUS UFP11A Fieldbus Interface
15
4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with PC
Installation notes
Connect the system bus terminating resistor (S12 = ON) at the end of the system bus
connection. Disconnect the terminating resistor at the other devices (S12 = OFF). The UFP11A gateway must always be connected either at the beginning or the end of the system bus connection and feature a permanently installed terminating resistor.
There must not be any difference of potential between the units connected with the
SBus. Take suitable measures to avoid a difference of potential, such as connecting the unit ground connectors using a separate line.
Point-to-point wiring is not permitted.
24 V connection
Shielding and routing of bus cables
An external 24 V voltage supply must be connected to terminals X1:4 and X1:5.
The PROFIBUS interface supports the RS-485 communications protocol and requires cable type A specified for PROFIBUS in accordance with EN 50170 as shielded twisted­pair cable for the physical connection.
Correct shielding of the bus cable attenuates electrical interference that may occur in industrial environments. The following measures ensure the best possible shielding:
Tighten the mounting screws on the connectors, modules and equipotential bonding
conductors by hand.
Use only connectors with metal housing or plated housing.
Connect the shielding in the connector with the greatest possible surface area.
Attach the shielding of the bus line on both sides.
Do not route signal and bus cables parallel to power cables (motor leads). They must
be routed in separate cable ducts.
Use metallic, grounded cable racks in industrial environments.
Route the signal cable and the corresponding equipotential bonding in close
proximity using the shortest way possible.
Avoid using plug connectors to extend bus cables.
Route the bus cables closely along existing grounding surfaces.
16
In case of fluctuations in the earth potential, a compensating current may flow via the bilaterally connected shield that is also connected to the protective earth (PE). Make sure you supply adequate equipotential bonding according to relevant VDE regulations in such a case.
Manual – PROFIBUS UFP11A Fieldbus Interface
Installation and Operation with PC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Setting the inverter parameters
4
Bus termination
A bus termination is not provided on the UFP electronics. If the UFP module is used as the first or last device of the PROFIBUS line, the bus termination has to be external. We recommend PROFIBUS connectors with integrated bus termination that open the continuing bus in case the bus termination is connected.
4.2 Setting the inverter parameters
The settings can be entered via the inverter keypad. Refer to the operating instructions of the inverter for details.
Connect the voltage supply for the UFx and all connected inverters.
Set an individual SBus address (P813) at the inverters. Recommendation: Address
setting beginning with address 1 in ascending order based on the arrangement of inverters in the control cabinet. Address 0 should not be assigned because it is used by the UFx.
4.3 Startup software
Install the MOVITOOLS software package version 2.70 or higher on your PC.
Start the software. Select the COM to which the UFP is connected and press the
"Update" button. The UFP should appear at address 0 and the connected inverters at the following addresses. If the window does not show an entry, check the COM interface and the connection via UWS21. If the UFP is the only entry in the window, check the SBus cabling and the terminating resistors.
Select UFx and call up the startup software for the fieldbus gateway (UFx
configurator).
Select the "Reconfigure fieldbus node" menu item.
Select your project path and project name. Press the "Next" button.
Press the "Update" button. All inverters connected to the UFP should be displayed
now. The configuration can be customized using the "Insert," "Change" and "Delete" buttons. Press the "Next" button.
Press the "Autoconfiguration" button. The process image for the UFP will now appear
in your controller. The process data width is shown at the bottom. This value is important for the project planning of the fieldbus master. Press the "Next" button.
Save the project data and press the "Download" button. The Autosetup DIP switch
must be in OFF position for this purpose.
Manual – PROFIBUS UFP11A Fieldbus Interface
17
4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with PC
Starting the inverters
The data exchanged between fieldbus master and the UFP can be viewed with the
process data monitor.
Enabling on the terminal side is required to control the inverters via fieldbus. You
have already wired the terminals. To check the terminal assignment, select the first inverter with address 1 in the "Connected inverters" window and start Shell. For MOVITRAC
Repeat the previous step for all inverters displayed in the "Connected inverters"
window.
®
07, the terminal assignment should be set as follows:
4.4 Starting the inverters
You can operate up to eight inverters on the PROFIBUS using one UFP. The DP master and the UFP exchange the setpoints and actual values of all inverters connected to the UFP in coherent data packages. It is important for you to know which inverter is located at which position of the data package (process image). The process data monitor indicates the relationship in the project planning of the fieldbus gateway (UFx configurator).
The inverters are enabled by writing the value 0006h to the corresponding control word 1. The speed setpoint can be specified with the following word. It is scaled with
0.2 1/min per digit.
For more information on the unit profile of MOVITRAC 07 Communication" manual.
®
07, refer to the "MOVITRAC
®
18
Manual – PROFIBUS UFP11A Fieldbus Interface
5 PROFIBUS interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5.1 Startup up PROFIBUS DP master
Supporting files for UFP are available in the Internet at sew-eurodrive web site.
Observe the notes in the README.TXT file on the GSD disk.
Install the GSD file according to the requirements of the project planning software for
the DP master. After successful installation, the "UFP" device appears in the list of slave stations.
Insert the interface module into the PROFIBUS structure under the name "UFP" and
assign the PROFIBUS address.
Select the process data configuration required for your application (see next section).
Enter the I/O or peripheral addresses for the configured data widths.
Save the configuration.
Expand your application program by the data exchange with the fieldbus interface.
In case of S7, use the system functions for consistent data exchange for this purpose (SFC14 and SFC15).
The BUS-FAULT LED of the fieldbus interface should extinguish after you have
saved the project, loaded it in the DP-V1 master and started the DP-V1 master. If this is not the case, check the connections and terminating resistors of the PROFIBUS and the project planning, especially the PROFIBUS address.
PROFIBUS interface
Startup up PROFIBUS DP master
5
5.2 Configuration of the PROFIBUS DP interface
General information
The inverter must be given a specific DP configuration by the DP master to define type and number of input and output data used for the transmission. You have the opportunity to control the drives via process data and to read or write all parameters of the fieldbus interface via parameter channel.
Manual – PROFIBUS UFP11A Fieldbus Interface
19
5
c
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
PROFIBUS interface
Configuration of the PROFIBUS DP interface
The figure shows a schematic view of the data exchange between automation device 8DP-V1 master), fieldbus interface (DP-V1 slave) and an inverter with process data channel and parameter channel.
C1-Master
Process data configuration
C2-Master
Cyclic OUT Data
Param PD
yclic DPV1
1-Services
Axis = 1
Axis = SBus-Address: 12345678
Param PD
Cyclic IN Data
Axis = 0
Axis = 3
Axis = 0
Axis = 5
Acyclic DPV1
C2-Services
PROFIBUS DPV1
Axis = 8
C2-Master
Acyclic DPV1
C2-Services
53129BXX
Figure 9: Data exchange with parameter data (Param) and process data (PD)
The fieldbus interface allows for different DP configurations for the data exchange between DP master and fieldbus interface. The following table provides additional details on all standard DP configurations of the fieldbus interfaces. The "Process data configuration" column shows the name of the configuration. These texts also appear as a selection list in your project planning software for the DP master. The DP configurations column shows the type of configuration data sent to the fieldbus interface while the link to PROFIBUS DP is being established. The configurations are determined by the default process data width for SEW inverters of three process data words. In the simplest case, the controller transmits three process data words to each inverter connected to the fieldbus interface. The fieldbus interface then distributes these process data words to the individual devices. The parameter channel is used for setting the parameters of the UFP and is not passed on to the connected participants. The fieldbus interface accepts 1 ... 24 process data words with and without parameter channel.
20
Manual – PROFIBUS UFP11A Fieldbus Interface
Loading...
+ 44 hidden pages