SEW Eurodrive UFI11A User Manual

Page 1
INTERBUS UFI11A Fieldbus Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Edition
06/2002
Manual
1052 5114 / EN
Page 2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Page 3
1 Overview of the System.................................................................................... 4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
2 Unit Structure ....................................................................................................5
2.1 Front view ................................................................................................. 5
3 Installation and Operation with Autosetup.....................................................6
3.1 Installation notes ....................................................................................... 6
3.2 Setting the inverter parameters............................................................... 10
3.3 Autosetup................................................................................................ 10
3.4 Configuring the fieldbus master .............................................................. 11
3.5 Starting the inverters............................................................................... 12
4 Installation and Operation with a PC............................................................. 13
4.1 Installation notes ..................................................................................... 13
4.2 PC connection......................................................................................... 17
4.3 Setting the inverter parameters............................................................... 17
4.4 Startup software...................................................................................... 17
4.5 Configuring the fieldbus master .............................................................. 18
4.6 Starting the inverters............................................................................... 19
5 INTERBUS Interface........................................................................................20
5.1 Startup of the INTERBUS master ........................................................... 20
5.2 Configuring the INTERBUS interface...................................................... 28
5.3 Examples of DIP switch settings for process data and
PCP communication in Autosetup mode................................................. 31
5.4 Control via INTERBUS............................................................................ 34
5.5 PCP interface.......................................................................................... 35
5.6 Return codes for parameter setting......................................................... 44
5.7 Autosetup................................................................................................ 46
6 Error Response ...............................................................................................48
6.1 Fieldbus timeout...................................................................................... 48
6.2 SBus timeout........................................................................................... 48
6.3 Unit errors ............................................................................................... 48
7 Diagnostic LEDs.............................................................................................. 49
7.1 States of the LEDs UL, RC, BA, TR and RD........................................... 49
8 DIP Switches.................................................................................................... 51
9 Application examples .....................................................................................52
9.1 Control via process data ......................................................................... 52
9.2 Parameter setting via the PCP interface................................................. 52
9.3 Representation of the coding examples.................................................. 53
9.4 Sequence of a parameter setting process .............................................. 53
9.5 Reading of an UFI parameter.................................................................. 54
9.6 Writing of UFI11A or drive parameters via object 8288 .......................... 55
9.7 Reading of UFI11A or drive parameters via object 8288 ........................ 56
10 Parameter List ................................................................................................. 58
11 List of Errors....................................................................................................59
12 Technical Data................................................................................................. 61
13 Dimensions...................................................................................................... 62
14 Index................................................................................................................. 63
Manual – Fieldbus Interface INTERBUS UFI11A
Page 4
1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Overview of the System
1 Overview of the System
The UFI11A INTERBUS fieldbus interface serves as a gateway for connecting one or more MOVIDRIVE, MOVIDRIVEcompact or MOVITRAC 07 inverters to INTERBUS. Se­veral inverters can be connected to the INTERBUS UFI11A interface via the SBus. The INTERBUS UFI11A interface provides the translation between the INTERBUS and the SBus.
Copying data
Fig. 1: Overview of the system: INTERBUS master – UFI11A – inverter
The UFI11A settings can be copied with the UBP11A parameter module from UFI11A to UFI11A. For safety reasons, all inverters connected to the UFI11A must be turned off when writing data.
Manual – Fieldbus Interface INTERBUS UFI11A
05373AXX
Page 5
2Unit Structure
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
2.1 Front view
Unit Structure
2
Fig. 2: Arrangement of LEDs, connectors and DIP switches
X1 SBus and 24 V connection X2 Diagnostic interface X3 INTERBUS remote in (incoming remote bus) X4 INTERBUS remote out (outgoing remote bus) S1 DIP switches UL Logic voltage RC Incoming remote bus OK BA Bus mode active RD Outgoing remote bus switched off TR Parameter data exchange via PCP channel SYS-F System fault USER Expert mode
Manual – Fieldbus Interface INTERBUS UFI11A
05405AXX
Page 6
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with Autosetup
3 Installation and Operation with Autosetup
3.1 Installation notes
Mounting
Pin assignment
The unit can be mounted using the integrated DIN rail mounting option or directly onto a switch cabinet wall using the four holes integrated into the back wall of the housing. In the latter case, the two retaining screws for the DIN rail mounting must be removed. Basically, there are no restrictions regarding positioning in relation to the inverters to be connected (e.g. MOVITRAC length and the fact that the UFI11A must be the first or last node on the system bus (SBus).
The UFI11A must have additional HF-compliant grounding if the DIN rail mounting opti­on is used in conjunction with SBus cables more than 1 m in length.
The UFI11A fieldbus interface is equipped with a 9-pin sub D male connector for the in­coming bus signal and a 9-pin sub D female connector for the outgoing bus signal ac­cording to EN 50170.
®
07). In laying out the system, consider the maximum cable
Fig. 3: Pinout of the 9-pin sub D male connector X3 to EN 50170 ([1] = 9-pin sub D male
connector; [2] = Signal lines twisted pair; [3] = Conductive connection between the connector housing and the shield)
Manual – Fieldbus Interface INTERBUS UFI11A
05406AXX
Page 7
Installation and Operation with Autosetup
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
3
Fig. 4: Pinout of the 9-pin sub D female connector X4 to EN 50170 ([1] = 9-pin sub D female
connector; [2] = Signal lines twisted pair; [3] = Conductive connection between the connector housing and the shield; [4] = Jumper)
As a rule, the fieldbus interface is connected to the INTERBUS system using a twisted, shielded cable. The shield of the INTERBUS cable must be connected on both ends, for example on the plug housing. Note the maximum supported transmission rate when you are selecting the bus connector.
The cable is connected to the INTERBUS plug using pins 6 and 1 (/DO and DO) and pins 7 and 2 (/DI and DI). Communication takes place via these contacts. The RS-485 signals /DO and DO as well as /DI and DI must have the same contacts on all INTER­BUS stations. Otherwise, communication via the bus will not function.
05374AXX
Manual – Fieldbus Interface INTERBUS UFI11A
Page 8
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with Autosetup
Connection
Fig. 5: System bus connection
UFI11A
COM = RS-485 reference /DO = Data out inverted DO = Data out /DI = Data in inverted DI = Data in GND = System bus reference SC11 = System bus high SC12 = System bus low
Notes on SBus configuration:
• Use a twisted and shielded copper cable (data transmission cable with braided cop-
• The permitted total cable length depends on the baud rate setting of the SBus:
05375AXX
MOVITRAC® 07
GND = System bus reference SC22 = System bus outgoing low SC21 = System bus outgoing high SC12 = System bus incoming low SC11 = System bus incoming high S12 = System bus terminating resistor
per shield). Connect the shield at both ends to the electronics shield clamp of MOVI-
®
07 or the UFI11A and ensure a large area of contact between the shield and
TRAC clamp. Also connect the ends of the shield to GND. The cable must meet the follo­wing specifications (CAN bus or DeviceNet cables are suitable, for example):
2
–Conductor cross section 0.75 mm
(AWG18)
–Cable resistance 120 at 1 MHz –Capacitance per unit length 40 pF/m (12 pF/ft) at 1 kHz
–250 kbaud: 160 m (528 ft) –500 kbaud: 80 m (264 ft) –1000 kbaud: 40 m (132 ft)
Manual – Fieldbus Interface INTERBUS UFI11A
Page 9
Installation and Operation with Autosetup
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
• Switch on the system bus terminating resistor (S1 2 = ON) of the node end of the sys­tem bus. Switch off the terminating resistor on the other units (S12 = OFF). The UFI11A fieldbus interface must always be the first or last node on the system bus. It has an integrated terminating resistor.
• There must not be any potential difference between the units connected to the SBus. Take suitable measures such as connecting each unit’s ground lug to a central grounding point in the cabinet to avoid potential differences.
• Point-to-point cabling is not permitted.
3
24 V connection
Shielding and routing of the bus cables
An external 24 VDC voltage supply must be connected to terminals X1:4 and X1:5.
The voltage range for the 24 VDC voltage supply is 18 – 30 V. The current consumption of the UFI11A fieldbus interface is 300 mA.
The INTERBUS interface supports RS-485 transmission technology and requires the cable type specified as the physical medium for INTERBUS. This cable must be a shiel­ded, twisted-pair cable with 3 x 2 cores.
Having the bus cable correctly shielded eliminates parasitic interference which can oc­cur in an industrial environment. The following measures ensure the best possible shiel­ding:
• Finter-tighten the retaining screws of plugs, modules and equipotential bonding con­ductors.
• Use only connectors with a metal housing or a metallized housing.
• Maximize the contact area between the shield and the connector housing.
• Shield the bus cable on both ends.
• Do not route the signal and bus cables in parallel with the power cables (motor leads); use separate cable ducts if possible.
• Only use grounded-metal cable trays in industrial environments.
• Join the signal cables and the associated equipotential bonding together at closely spaced intervals by the shortest route.
• Avoid using plug connectors to extend bus cables.
• Route the bus cables closely adjacent to available grounding surfaces.
In the event of fluctuations in the ground potential, a compensating current may flow along the shield which is connected at both ends and to the ground potential (PE). In this case, make adequate provision for equipotential bonding in accordance with the rele­vant VDE regulations.
Manual – Fieldbus Interface INTERBUS UFI11A
Page 10
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with Autosetup
3.2 Setting the inverter parameters
The settings can be entered using the inverter control panel. Refer to the inverter ope­rating instructions for more information.
• Switch on the voltage supply for the UFI11A and all connected inverters.
• Set an individual SBus address (P813) on the inverters. Recommendation: Assign the addresses starting from address 1 and working in ascending order according to the arrangement of inverters in the switch cabinet. Do not assign address 0 since this is used by the UFI11A.
• Check the SBus baud rate (P816, factory setting = 500 kbaud).
• Set the Setpoint source (P100) to SBus (value 10).
• Set the Control signal source (P101) to SBus (value 3).
• Set the terminal assignment of the binary inputs. The value 0 is recommended for P60- in MOVITRAC
–DI01 CW/STOP (applied to 24 V, enable CW direction of rotation) –DI02 CCW/STOP (applied to 24 V, enable CCW direction of rotation) –DI03 FIX SETPT SW.OV(not connected) –DI04 n11/n21 (not connected) –DI05 n12/n22 (not connected) –Program the unused terminals to "NO FUNCTION" if you are using a MOVIDRIVE
or MOVIDRIVE compact.
• Important: If you need to set P815 SBus timeout delay for MOVITRAC only possible using a PC. The default value is 0, which means timeout monitoring is switched off. Set P815 to the value 1 s.
3.3 Autosetup
Switch on the Autosetup function using the DIP switch on the UFI11A. The function is active for as long as the SYS-FLT LED is flashing briefly with a long interval between flashes. The LED stays off after the scanning process if at least one inverter has been detected. ted by switching the DIP switch off and on again. The SYS-FLT LED remains on follo­wing Autosetup if no inverter is detected. In this case, check the cabling of the SBus, the terminating resistors of the SBus, the voltage supply to the inverters and the SBus address settings (P813).
The Autosetup DIP switch must stay switched on.
®
07. This corresponds to the following assignment:
Autosetup can be reactiva-
®
07, this is
®
10
Manual – Fieldbus Interface INTERBUS UFI11A
Page 11
Installation and Operation with Autosetup
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
3.4 Configuration of the fieldbus master
You will find detailed information in the section "INTERBUS interface."
• Set the required process data length via DIP switches 1 ... 5. You will need three pro­cess data words for each drive inverter connected to the UFI11A. That means you will have to set 9 words in case you are operating three MOVITRAC change in the DIP switch settings will become active after turning the UFI11A off and on again.
• Start the "CMD Tool" project planning software for your INTERBUS interface.
• Enter the bus setup via "Configuration frame / Read in" or "Read in configuration frame."
• Assign program addresses of the control program to the INTERBUS process data of the inverters. This assignment takes place via the context menu "Process data" or "Process data manager."
• Enhance the control program by the data exchange with the UFI11A.
®
07 units. A
3
Manual – Fieldbus Interface INTERBUS UFI11A
11
Page 12
3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with Autosetup
3.5 Starting the inverters
You can operate up to eight inverters on the INTERBUS via one UFI11A. The INTER­BUS master and the UFI11A will exchange setpoints and actual values of all inverters connected to the UFI11A in contiguous data packages. It is important for you to know where a particular inverter is located in the data package (process image). The relation­ship is shown in the following illustration:
Fig. 6: Data exchange INTERBUS master – UFI11A – inverter
You can enable the inverter by writing the value 0006h in the corresponding control word. You can enter the speed setpoint in the following word; it is scaled with 0.2 1/min per digit.
12
05431AXX
Manual – Fieldbus Interface INTERBUS UFI11A
Page 13
Installation and Operation with a PC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
4 Installation and Operation with a PC
4.1 Installation notes
Mounting
Pin assignment
The unit can be mounted using the integrated DIN rail mounting option or directly onto a switch cabinet wall using the four holes integrated into the back wall of the housing. In the latter case, the two retaining screws for the DIN rail mounting must be removed. Basically, there are no restrictions regarding positioning in relation to the inverters to be connected (e.g. MOVITRAC length and the fact that the UFI11A must be the first or last node on the system bus (SBus).
The UFI11A must have additional HF-compliant grounding if the DIN rail mounting opti­on is used in conjunction with SBus cables more than 1 m in length.
The UFI11A fieldbus interface is equipped with a 9-pin sub D male connector for the in­coming bus signal and a 9-pin sub D female connector for the outgoing bus signal.
®
07). In laying out the system, consider the maximum cable
4
Fig. 7: Pinout of the 9-pin sub D male connector X3 to EN 50170 ([1] = 9-pin sub D male
connector; [2] = Signal lines twisted pair; [3] = Conductive connection between the connector housing and the shield)
Manual – Fieldbus Interface INTERBUS UFI11A
05406AXX
13
Page 14
4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with a PC
Fig. 8: Pinout of the 9-pin sub D female connector X4 to EN 50170 ([1] = 9-pin sub D female
connector; [2] = Signal lines twisted pair; [3] = Conductive connection between the connector housing and the shield; [4] = Jumper)
As a rule, the fieldbus interface is connected to the INTERBUS system using a twisted, shielded cable. The shield of the INTERBUS cable must be connected on both ends, for example on the plug housing. Note the maximum supported transmission rate when you are selecting the bus connector.
The cable is connected to the INTERBUS plug using pins 6 and 1 (/DO and DO) and pins 7 and 2 (/DI and DI). Communication takes place via these contacts. The RS-485 signals /DO and DO as well as /DI and DI must have the same contacts on all INTER­BUS stations. Otherwise, communication via the bus will not function.
05374AXX
14
Manual – Fieldbus Interface INTERBUS UFI11A
Page 15
Connection
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with a PC
4
Fig. 9: System bus connection
UFI11A
COM = RS-485 reference /DO = Data out inverted DO = Data out /DI = Data in inverted DI = Data in GND = System bus reference SC11 = System bus high SC12 = System bus low
Notes on SBus configuration:
• Use a twisted and shielded copper cable (data transmission cable with braided cop-
• The permitted total cable length depends on the baud rate setting of the SBus:
05375AXX
MOVITRAC® 07
GND = System bus reference SC22 = System bus outgoing low SC21 = System bus outgoing high SC12 = System bus incoming low SC11 = System bus incoming high S12 = System bus terminating resistor
per shield). Connect the shield at both ends to the electronics shield clamp of MOVI-
®
07 or the UFI11A and ensure a large area of contact between the shield and
TRAC clamp. Also connect the ends of the shield to GND. The cable must meet the follo­wing specifications (CAN bus or DeviceNet cables are suitable):
2
–Conductor cross section 0.75 mm
(AWG18)
–Cable resistance 120 at 1 MHz –Capacitance per unit length 40 pF/m (12 pF/ft) at 1 kHz
–250 kbaud: 160 m (528 ft) –500 kbaud: 80 m (264 ft) –1000 kbaud: 40 m (132 ft)
Manual – Fieldbus Interface INTERBUS UFI11A
15
Page 16
4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with a PC
• Switch on the system bus terminating resistor (S1 2 = ON) of the node end of the sys­tem bus. Switch off the terminating resistor on the other units (S12 = OFF). The UFI11A fieldbus interface must always be the first or last node on the system bus. It has an integrated terminating resistor.
• There must not be any potential difference between the units connected to the SBus. Take suitable measures such as connecting each unit’s ground lug to a central grounding point in the cabinet to avoid potential differences.
• Point-to-point cabling is not permitted.
24 V connection
Shielding and routing of the bus cables
An external 24 VDC voltage supply must be connected to terminals X1:4 and X1:5.
The voltage range for the 24 VDC voltage supply is 18 – 30 V. The current consumption of the UFI11A fieldbus interface is 300 mA.
The INTERBUS interface supports RS-485 transmission technology and requires the cable type specified as the physical medium for INTERBUS. This cable must be a shiel­ded, twisted-pair cable with 3 x 2 cores.
Having the bus cable correctly shielded eliminates parasitic interference which can oc­cur in an industrial environment. The following measures ensure the best possible shiel­ding:
• Finter-tighten the retaining screws of plugs, modules and equipotential bonding con­ductors.
• Use only connectors with a metal housing or a metallized housing.
• Maximize the contact area between the shield and the connector housing.
• Shield the bus cable on both ends.
• Do not route the signal and bus cables in parallel with the power cables (motor leads); use separate cable ducts if possible.
• Only use grounded-metal cable trays in industrial environments.
• Join the signal cables and the associated equipotential bonding together at closely spaced intervals by the shortest route.
• Avoid using plug connectors to extend bus cables.
• Route the bus cables closely adjacent to available grounding surfaces.
In the event of fluctuations in the ground potential, a compensating current may flow along the shield which is connected at both ends and to the ground potential (PE). In this case, make adequate provision for equipotential bonding in accordance with the rele­vant VDE regulations.
16
Manual – Fieldbus Interface INTERBUS UFI11A
Page 17
Installation and Operation with a PC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
4.2 PC connection
The UFI11A is equipped with a 4-pole RJ12 socket on the front. The option UWS21A with item no. 8230773 establishes the connection to a COM interface on your PC. Con­nect the desired COM of the PC with the UWS21A via the enclosed serial cable. The UWS21A will be connected with the UFI11A via the enclosed RJ11 cable.
4.3 Setting the inverter parameters
The settings can be entered using the inverter control panel. Refer to the inverter ope­rating instructions for more information.
• Switch on the voltage supply for the UFI11A and all connected inverters.
• Set an individual SBus address (P813) on the inverters. Recommendation: Assign the addresses starting from address 1 and working in ascending order according to the arrangement of inverters in the switch cabinet. Do not assign address 0 since this is used by the UFI11A.
4.4 Startup software
• Install the MOVITOOLS software package as of version 2.70 on your PC.
• Start the software. Select the COM to which the UFI11A has been connected and press the "Update“ button. The UFI11A should appear at address 0 and the connec­ted inverters on the following addresses. In case you do not see an entry in the win­dow, please check the COM interface and the connection via the UWS21. If you only see the UFI11A as an entry in the window, please check the SBus cabling and the terminating resistors.
• Select the UFI11A and start the UFx Configurator.
• Select the menu item "New configuration of fieldbus node.“
• Select your project path and name. Press the "Next" button.
• Press the "Update“ button. You should now see all inverters connected to the UFI11A. You can customize the configuration with the "Insert“, "Edit“ and "Delete“ buttons. Press the "Next" button.
• Press the "Autoconfiguration“ button. You will now see the process image for the UFI11A in your control. The process data length is displayed at the bottom. This va­lue is important for the configuration of the fieldbus master. Press the "Next" button."
• Save the project data and press the "Download“ button. If you experience problems with the download, you have probably set the DIP switch to AUTOSETUP. You need to turn off the autosetup feature when configuring with a PC.
4
Manual – Fieldbus Interface INTERBUS UFI11A
17
Page 18
4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Installation and Operation with a PC
• You can see the data being exchanged between fieldbus master and UFI11A with the process data monitor.
• You will have to enable the unit via the terminals to control the inverter via fieldbus. You have already connected the terminals. Select the first inverter with address 1 in the window "Connected units" to check the pinout and start "Shell." Make the follo­wing settings for the pinout of the MOVITRAC
• Repeat this step for all inverters listed in the window "Connected units."
4.5 Configuration of the fieldbus master
You will find detailed information in the section "INTERBUS interface."
• Set the required process data length via DIP switches 1 ... 5. You will need three pro­cess data words for each drive inverter connected to the UFI11A. That means you will have to set 9 words in case you are operating three MOVITRAC change in the DIP switch settings will become active after turning the UFI11A off and on again.
®
07:
®
07 units. A
• Start the "CMD Tool" project planning software for your INTERBUS interface.
• Enter the bus setup via "Configuration frame / Read in" or "Read in configuration frame."
• Assign program addresses of the control program to the INTERBUS process data of the inverters. This assignment takes place via the context menu "Process data" or "Process data manager."
• Enhance the control program by the data exchange with the UFI11A.
18
Manual – Fieldbus Interface INTERBUS UFI11A
Page 19
4.6 Starting the inverters
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
You can operate up to eight inverters on the INTERBUS via one UFI11A. The INTER­BUS master and the UFI11A will exchange setpoints and actual values of all inverters connected to the UFI11A in contiguous data packages. It is important for you to know where a particular inverter is located in the data package (process image). The relation­ship can be seen in the process data monitor of the UFx Configurator.
You can enable the inverter by writing the value 0006h in the corresponding control word. You can enter the speed setpoint in the following word; it is scaled with 0.2 1/min per digit.
Installation and Operation with a PC
4
Manual – Fieldbus Interface INTERBUS UFI11A
19
Page 20
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
5 INTERBUS Interface
5.1 Startup of the INTERBUS master
Project planning of the UFI11A in the INTERBUS interface module with the "CMD Tool" (CMD = Configuration-Monitoring-Diagnostics) project planning software takes place in two steps. In the first step, you will set up the bus structure. The second step involves a station description and address entry of process data.
Configuring the bus structure
Fig. 10: Project planning example for 3PD + 2PCP
The following illustrations show the CMD Tool settings for a UFI11A configured with 3PD + 2PCP according to Fig. 10 on the input/output addresses 144...149 of the control.
Off-line configuration: Insert with ID code
You can configure the bus structure with the CMD Tool on-line or off-line. In the off-ine status, the drive inverter will be configured with the menu item "Edit / Insert with ID code" in the CMD tool. In this mode, you will have to enter the ID code, process data channel and device type according to Fig. 11.
Fig. 11: Off-line configuration with the CMD Tool
05654AXX
05653AXX
20
Manual – Fieldbus Interface INTERBUS UFI11A
Page 21
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Not all combinations are available. You will find the valid settings in the following table. The insert with ID Code has to correspond to the setting of DIP switches 6 and 7. The process data channel setting has to correspond to the setting of DIP switches 1-5. Any conflicting settings will prevent operation of the INTERBUS. See also the section on con­figuration of the Interbus interface via DIP switches.“
5
ID Code 3 dez (03 hex) No parameter channel PCP
Process data channel:
ID Code 227 dez (E3 hex) Parameter channel PCP: 1 word
Process data channel:
Program setting Function
16 Bit 1 process data word (1 PD)
32 Bit 2 process Data Words (2 PD)
48 Bit 3 process data words (3 PD)
64 Bit 4 process data words (4 PD)
80 Bit 5 process data words (5 PD)
96 Bit 6 process data words (6 PD)
112 Bit 7 process data words (7 PD)
128 Bit 8 process data words (8 PD)
144 Bit 9 process data words (9 PD)
160 Bit 10 process data words (10 PD)
192 Bit 12 process data words (12 PD)
224 Bit 14 process data words (14 PD)
256 Bit 16 process data words (16 PD)
384 Bit 24 process data words (24 PD)
16 Bit 1 process data word (Param + 1 PD)
32 Bit 2 process data words (Param + 2 PD)
48 Bit 3 process data words (Param + 3 PD)
64 Bit 4 process data words (Param + 4 PD)
80 Bit 5 process data words (Param + 5 PD)
96 Bit 6 process data words (Param + 6 PD)
112 Bit 7 process data words (Param + 7 PD)
128 Bit 8 process data words (Param + 8 PD)
144 Bit 9 process data words (Param + 9 PD)
176 Bit 11 process data words (Param + 11PD)
218 Bit 13 process data words (Param + 13 PD)
240 Bit 15 process data words (Param + 15 PD)
368 Bit 23 process data words (Param + 23 PD)
Manual – Fieldbus Interface INTERBUS UFI11A
21
Page 22
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
ID Code 224 dez (E0 hex) Parameter channel PCP: 2 words
Process data channel:
ID Code 225 dez (E1 hex) Parameter channel PCP: 4 words
Process data channel:
Program setting Function
16 Bit 1 process data word (Param + 1 PD)
32 Bit 2 process data words (Param + 2 PD)
48 Bit 3 process data words (Param + 3 PD)
64 Bit 4 process data words (Param + 4 PD)
80 Bit 5 process data words (Param + 5 PD)
96 Bit 6 process data words (Param + 6 PD)
112 Bit 7 process data words (Param + 7 PD)
128 Bit 8 process data words (Param + 8 PD)
160 Bit 10 process data words (Param + 10 PD)
192 Bit 12 process data words (Param + 12 PD)
224 Bit 14 process data words (Param + 14 PD)
352 Bit 22 process data words (Param + 22 PD)
384 Bit 24 process data words (Param + 24 PD)
16 Bit 1 process data word (Param + 1 PD)
32 Bit 2 process data words (Param + 2 PD)
48 Bit 3 process data words (Param + 3 PD)
64 Bit 4 process data words (Param + 4 PD)
80 Bit 5 process data words (Param + 5 PD)
96 Bit 6 process data words (Param + 6 PD)
128 Bit 8 process data words (Param + 8 PD)
160 Bit 10 process data words (Param + 10 PD)
192 Bit 12 process data words (Param + 12 PD)
320 Bit 20 process data words (Param + 20 PD)
352 Bit 22 process data words (Param + 22 PD)
On-line configuration: Configuration frame / Read in
You can initially install the INTERBUS system completely and then set the DIP switches of the UFI11A. The entire bus structure (configuration frame) can then be read in via the CMD Tool. All stations will be automatically identified with their set data length.
22
Manual – Fieldbus Interface INTERBUS UFI11A
Page 23
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5
Insert device description
You can create an individual device description for the UFI11A in the INTERBUS system to clearly identify and describe the INTERBUS stations. The following entries are of im­portance in this instance:
In the fields "Manufacturer Name" and "Device Type" you must enter the
– Manufacturer Name: SEW-EURODRIVE
– Device Type: UFI
so that the drive can be configured via the INTERBUS interface module (Fig. 12) with a management PC from the management level.
Fig. 12: Device description for UFI
05655AXX
Select "Remote Bus" as interface type.
Manual – Fieldbus Interface INTERBUS UFI11A
23
Page 24
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
As of CMD Tool version 4.50, you can copy your own ICO files in the directory ".\IBSCMD\Pict32\" (Fig. 13) for easier identification of the drive inverter. You will find the "INTERBUS description files for CMD Tool" under "Software / Movitrac" on the SEW homepage.
Fig. 13: Linking device description with ICO files
03716AXX
24
Manual – Fieldbus Interface INTERBUS UFI11A
Page 25
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5
Parameter channel
Assigning pro­cess data
The following settings of the parameter channel will become necessary if you want to use the PCP channel for configuring the UFI11A or a drive inverter connected to the UFI11A:
• Message Lengths / Transmit / Receive: 243 bytes each
• Supported Parameter Channel Services (Standard): Read / Write
Fig. 14: Setting the parameter channel (PCP)
You assign the INTERBUS process data of the drive inverters to the program addresses of the control system with the context menu "Process Data."
03717AXX
Fig. 15: Assignment of INTERBUS process data and PLC program addresses
Manual – Fieldbus Interface INTERBUS UFI11A
05657AXX
25
Page 26
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
Testing the PCP connection
You can use the MONITOR mode of the CMD Tool to test the PCP connection to the UFI. The following illustrations demonstrate the PCP test. You are basically establishing a PCP connection with this method and read the parameter list (object directory) stored in the device. Change the CMD Tool to the "Monitoring" operating state.
Fig. 16: Change the CMD Tool to the "MONITO-
RING“ operating state
Click on the UFI to which you would like to establish a PCP connection. Open the con­text menu with the right mouse button and select the menu item "Device Parameteriza­tion".
05658AXX
Fig. 17: Testing the PCP device parameterization
26
Manual – Fieldbus Interface INTERBUS UFI11A
Page 27
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Activate the menu item "Device / Read Parameter List" in the window "Device Parame­terization.“
5
Fig. 18: Window for device parameterization via CMD Tool
The configuration of the PCP channel is correct if the device parameters are now read in. You can cancel the read-in process. If you receive an error message instead of the progression bar, check the PCP configuration and assignment of the CRs. You may want to format the parameterization memory of the interface module once again and wri­te the current project once again into the parameterization memory. Repeat the configu­ration of the interface module and the sequence for testing the PCP connection.
Fig. 19: CMD Tool reads in device parameters, indicating that the
PCP communication is ok
03713AXX
03722AXX
Manual – Fieldbus Interface INTERBUS UFI11A
27
Page 28
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
5.2 Configuration of the INTERBUS interface
Under the cover plate, there is a DIP switch for setting the INTERBUS data length of the fieldbus interface. The process data length can be set to a maximum of 24 words using switches S1-1 to S1-5. The PCP length can be set using switches S1-6 and S1-7. PCP is the parameter channel of the INTERBUS and is used for setting the parameters of the UFI11A and the connected inverters.
Fig. 20: UFI11A DIP
switches
The process data channel is the means by which the connected inverters are controlled and their status read. Since all data of the connected inverters are transmitted by the INTERBUS, you will have to enter the sum of the process data lengths of all individual inverters. In Autosetup, this means three words per inverter.
Fig. 21 shows an example setting of six process data words for two inverters. The value of each switch in determining the process data length is shown on the right.
Fig. 21: Process data words
05376AXX
05377AXX
28
Manual – Fieldbus Interface INTERBUS UFI11A
Page 29
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
A maximum of 3PDs can be assigned to one station on the SBus.
The PCP channel can be set to 0, 1, 2, or 4 words. At least one word must be set to enable parameter data to be exchanged. Higher settings increase the transmission speed. Fig. 8 shows the possible settings for the PCP channel.
5
Fig. 22: Possible settings for PCP words
Note that if the total of process data and PCP words exceeds 10 words , you must select a value equal to or greater than your required data length from the following settings:
0 – 10 words set directly, 12 words, 14 words, 16 words, 24 words and 26 words.
Manual – Fieldbus Interface INTERBUS UFI11A
05378AXX
29
Page 30
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
Use the following table for the valid settings. You can also refer to the example settings given below if you are operating the fieldbus interface in Autosetup mode.
Number of process data words 0 PCP words 1 PCP word 2 PCP words 4 PCP words
1 XXXX
2 XXXX
3 XXXX
4 XXXX
5 XXXX
6 XXXX
7 XXX
8 XXXX
9XX
10 X X X
11 X
12 X X X
13 X
14 X X
15 X
16 X
17
18
19
20 X
21
22 XX
23 X
24 X X
De-energize the UFI11A before adjusting the DIP switch settings. The settings of DIP switches S1-1 to S1-7 are only read during the power-up initialization.
The UFI11A signals the "Microprocessor not ready" ID code (38h) if the settings of DIP switches S1-1 to S1-7 are invalid.
30
Manual – Fieldbus Interface INTERBUS UFI11A
Page 31
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5.3 Examples of DIP switch settings for process data and PCP communication in Autosetup mode
1 inverter (3 process data words)
3 process data words are set. 0, 1, 2 and 4 PCP words can be set using DIP switches PCP1 and PCP2.
5
2 inverters (6 process data words)
3 inverters (9 process data words)
6 process data words are set. 0, 1, 2 and 4 PCP words can be set using DIP switches PCP1 and PCP2.
9 process data words are set. 0 and 1 PCP word can be set using DIP switches PCP1 and PCP2.
Manual – Fieldbus Interface INTERBUS UFI11A
31
Page 32
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
4 inverters (12 process data words)
5 inverters (15 process data words)
6 inverters (18 process data words)
12 process data words are set. 0, 2 and 4 PCP words can be set using DIP switches PCP1 and PCP2.
15 process data words are set. Only 1 PCP word can be set using DIP switches PCP1 and PCP2.
20 process data words are set. 4 PCP words must be set using DIP switches PCP1 and PCP2.
32
Manual – Fieldbus Interface INTERBUS UFI11A
Page 33
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5
7 inverters (21 process data words)
8 inverters (24 process data words)
22 process data words are set. 2 and 4 PCP words can be set using DIP switches PCP1 and PCP2.
24 process data words are set. 0 and 2 PCP words can be set using DIP switches PCP1 and PCP2.
Manual – Fieldbus Interface INTERBUS UFI11A
33
Page 34
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
5.4 Control via INTERBUS
Data exchange between the INTERBUS master and the UFI11A takes place using the I/O area. The process data for all inverters connected to the UFI11A are located in a contiguous block in this area.
If there is more than one inverter, the associated process data words are appended at the end (see Fig. 23). The number of process data words per inverter is 3 words with Autosetup.
The inverters are located in ascending (SBus) address sequence with their associated process data lengths in the process image, for example an inverter with address 1 and 3 words, then an inverter with address 2 and 3 words, then an inverter with address 3 and 2 words, etc.
POW318 POW316 POW314 POW312 POW310 POW308
[1]
PIW318 PIW316 PIW314 PIW312 PIW310 PIW308
Fig. 23: Representation of the INTERBUS data in the PLC address area ([1] = PLC address area
/ U/f = Inverter)
PO 3 PO 2 PO 1
PO 3 PO 2 PO 1
UFI
PI 3 PI 2 PI 1 PI 3 PI 2 PI 1
PO 1
PO 2
PO 3
U/f!1 U/f!2
PI 2
PI 1
PI 3
PO 1
PI 1
PO 2
PI 2
PO 3
PI 3
50394AXX
34
Manual – Fieldbus Interface INTERBUS UFI11A
Page 35
5.5 PCP interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
The UFI11A fieldbus interface offers a standardized interface for parameter setting using the "Peripherals Communication Protocol" (PCP). This communications channel gives you full access to the parameters of the UFI11A fieldbus interface and the drive parameters of the inverters connected to the UFI11A.
Overview of basic structure
PCP services
The PCP channel must be set to one, two or four words using the DIP switches on the UFI11A to enable access to the parameter values of the UFI11A fieldbus interface or the inverter. Changing the number of PCP words varies the access speed to parameter va­lues via the PCP channel. The PCP interface is implemented using PCP version 3.0 in the UFI11A.
The UFI11A fieldbus interface supports the PCP services shown in Fig. 10. However, only the following services are relevant for setting parameters:
• Establishing the connection (Initiate)
• Reading of parameter values (Read)
• Writing of parameter values (Write)
• Cancelling the connection (Abort)
INTERBUS Interface
5
Fig. 24: PCP services supported by the UFI11A fieldbus interface
Manual – Fieldbus Interface INTERBUS UFI11A
05389AXX
35
Page 36
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
Establishing the communications link with "Initiate"
Canceling the communications link with "Abort"
Reading parame­ter values with "Read"
Writing parameter values with "Write"
Parameters in the object list
The "Initiate" PCP service establishes a communication link for exchanging parameters between an INTERBUS master and the UFI11A fieldbus interface. The connection is al­ways established from the INTERBUS master. Various arrangements relating to the communication link are checked during establishment of the connection, such as sup­ported PCP services, user data length, etc. The fieldbus interface responds with a posi­tive initiate response if the connection is established successfully. If the connection can not be established, then the arrangements for the communications link on the INTER­BUS master do not match those on the fieldbus interface. The fieldbus interface re­sponds with an initiate error response. In this case, compare the configured communi­cations relationship list in the INTERBUS master with that in the fieldbus interface.
As a rule, an attempt to re-establish an existing communication link leads to an abort. The communication link is then dropped, which means the "Initiate" PCP service must be run a third time in order to re-establish the communication connection.
The "Abort" PCP service cancels an existing communications link between the INTER­BUS master and the fieldbus interface. Abort is an unconfirmed PCP service and can be triggered either from the INTERBUS master or from the fieldbus interface.
The "Read" PCP service gives the INTERBUS master read access to all communication objects (drive parameters) of the fieldbus interface. All drive parameters and their coding are presented in detail in the Fieldbus Unit Profile documentation and the list of MOVID-
®
parameters.
RIVE
The "Write" PCP service gives the INTERBUS master write access to all parameters of the fieldbus interface. The fieldbus interface generates a write error response if incorrect access is made to a parameter (e.g. the value written is too large). Precise information is given relating to the cause of the error.
The "Read" and "Write" PCP services give the INTERBUS master access to all parame­ters defined in the object list of the UFI11A. All the parameters of the fieldbus interface which can be accessed via the bus system are described as communication objects in the static object list of the UFI11A. All objects in the static object list are addressed using indices. The following table shows the structure of the object list of the UFI11A.
36
Manual – Fieldbus Interface INTERBUS UFI11A
Page 37
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
The index range is subdivided into three logical areas. The UFI11A parameters are addressed using indices 8300 – 8313dec. Indices below 8300dec can be used for ac­cessing parameters which are not contained in the object list, or for addressing parame­ters which are found on an inverter connected to the UFI11A.
Parameter index (decimal)
8288 Variable data channel with acyclical routing (UFI11A and parameters of the con-
8296 Download parameter block
8297 Last PCP index
8299 MOVILINK parameter channel acyclical (only UFI11A parameters can be rea-
8300 – 8313 UFI11A parameters
8314 – 9999 Parameters of the UFI11A or of an inverter connected to the UFI11A which can
> 10000 Table, program and variable memory of the UFI11A or an inverter connected to
Name of the communication object
nected inverters can be reached)
ched)
be addressed via object 8288.
the UFI11A. These parameters can be addressed with object 8288.
5
Object description of the UFI11A or drive parameters
The parameters of the connected inverters are described in detail in the SEW document "Parameter List." In addition to the parameter index, additional information about coding, the range of values and the meaning of the parameter data is provided. The object de­scription in the object list is identical for all parameters. Even read-only parameters are given the Read all/Write all attribute in the object list because the inverter undertakes the corresponding check itself and sends back a return code if necessary. The following table shows the object description of all parameters.
Index: 8300 ... 8313
Object code: 7 (simple variable)
Data type index : 10 (octet string)
Length: 4
Local address:
Password:
Access groups:
Access rights: Read all/Write all
Name[16]: -
Extension length: -
Manual – Fieldbus Interface INTERBUS UFI11A
37
Page 38
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
"Variable data channel with acy­clical routing" object
This object enables you to address all the parameters of the UFI11A itself and the con­nected inverters. The object contains a selection option for the subchannel and address information for selecting the target unit. It contains information about the data length and frame type and an acyclical MOVILINK parameter channel. The required service and data value are specified here. The length is fixed at 12 bytes.
Octet 0 1 2 3 4 5 6 7 8 9 10 11
Meaning Subchan-
Fine structure Subchan-
Coarse struc­ture
nel
nel
Routing information MOVILINK parameter channel acyclical
Subad­dress
Subad­dress
Frame type
Frame type
Data
length
Data
length
Admin Re-
served
Admin Re-
served
Index
Index Low
Data MSB
High
Parameter index 4 bytes data
Data Data Data
The subchannel determines to which interface the data will be directed. The setting 0 addresses the parameters of the UFI11A and the subaddress is of no importance. The setting 1 on the subchannel addresses the standard interface (the SBus in case of the UFI11A).
The subaddress byte allows selection of the target unit. If you want to address the pa­rameters of a drive inverter connected to the UFI11A via SBus, you will enter the SBus address of the respective drive inverter.
The frame type must be set to 86hex (only acyclical parameter data). The data length for this frame type is fixed at 8 bytes.
Variable data channel performs a write service
If a write service is performed via the data channel (e.g. write parameter or write para­meter volatile), the UFI11A responds with the current service confirmation when the ser­vice has been performed. The corresponding error code is returned if the write service is not successful.
This method offers the advantage that the write services are processed simply by sen­ding a WRITE "MOVILINK parameter channel" once and evaluating the "write confirma­tion." The following table shows how write services are performed via the variable data channel.
Control (master) UFI11A fieldbus interface
1. Initiate the service coded in the parameter channel by means of a WRITE to the "MOVILINK parameter channel cyclical" object.
WRITE 8288 (parameter channel)
LSB
Service confirmation (OK/error code)
The WRITE service coded in the parameter channel is performed and the service con­firmation is returned directly as the response.
38
Manual – Fieldbus Interface INTERBUS UFI11A
Page 39
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5
Variable data channel performs a read type service
A PCP WRITE service has to be performed before a parameter can be read via the data channel. The PCP WRITE service defines where the UFI11A data should be available. A read service must take place on the variable data channel in order for these data to get to the master. As a result, a PCP WRITE and a PCP READ are always required for performing read services via the variable data channel. The following table shows how read services are performed via the variable data channel.
Control (master) UFI11A fieldbus interface
1. Initiate the service coded in the parameter channel by means of a WRITE to the "MOVILINK parameter channel cyclical" object.
2. READ "MOVILINK parameter channel cyclical" and evaluation of the service confirmation in the para­meter channel.
WRITE 8288 (parameter channel)
OK
READ 8288 (parameter channel)
Data = Parameter channel with result
1. Reception is confirmed immediately, the data channel is evaluated and the reques­ted service performed.
2. Service confirmation is entered in the data channel and can be evaluated by READ access in the master.
The "variable data channel with acyclical routing" object is only handled locally on the fieldbus interface and is defined as in the following table.
Index: 8288
Object code: 11 (string variable)
Data type index : 10 (octet string)
Length: 11
Local address:
Password:
Access groups:
Access rights: Read all/Write all
Name[16]: -
Extension length: -
Manual – Fieldbus Interface INTERBUS UFI11A
39
Page 40
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
"Download para­meter block" object
The "download parameter block" object enables up to 38 drive parameters of the UFI11A or an inverter connected to the UFI11A to be written at the same time with only one write service. This object gives you the opportunity to set the parameters of the in­verter in the startup phase, by calling the write service only once. In general, only a few parameters vary from application to application so that this parameter block with its max. 38 parameters is sufficient for almost all applications. The user data area is defined as 38 x 6 + 2 bytes = 230 bytes (byte format). The following table shows the structure of the "download parameter block" object.
Octet Meaning Note
0 Address Target address: 0 or 254 for the UFI11A or SBus address of the
1 Number of parameters 1 – 38 parameters
2 Index high
3 Index low
4 Data MSB
5Data
6Data
7 Data LSB
8 Index high
223 Data LSB
224 Index high
225 Index low
226 Data MSB
227 Data
228 Data
229 Data LSB
target inverter
1st parameter
2nd parameter... ...
38th parameter
The "download parameter block" object is only handled locally on the fieldbus interface and is defined as in the following table.
Index: 8296
Object code: 7 (simple variable)
Data type index : 10 (octet string)
Length: 230
Local address:
Password:
Access groups:
Access rights: Write all
Name[16]: -
Extension length: -
40
Manual – Fieldbus Interface INTERBUS UFI11A
Page 41
Example
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"Last PCP index" object
INTERBUS Interface
The WRITE service on the "download parameter block" object starts a parameterization mechanism on the UFI11A. This writes all the parameters specified in the user data area of the object one after the other in the UFI11A itself or a connected inverter and therefore sets the parameters of the UFI11A or the inverter. The UFI11A is addressed using address 0. An inverter connected to the UFI11A is addressed using its SBus address. The write service is terminated with a positive write response once the download para­meter block has been processed successfully (i.e. all parameters transferred by the IN­TERBUS fieldbus interface have been written). A negative write response is returned in case of an error. The return code contains more detailed information about the type of error, as well as the number of the parameter (no. 1 – 38) where the error occurred (see example).
Write error response for an error when writing the 11th parameter: Error class: 8 Other Error code: 0 Other Additional code high: 11dec Error when writing parameter 11 Additional code low: 15hex Value too large
Note the following points when using the download parameter block:
• Do not perform a factory setting within the download parameter block!
• All parameters written after the parameter lock has been activated will be rejected.
This object is 4 bytes long and, when read access is executed, it returns the numerical value of the last index which can be addressed directly using the PCP services. PCP accesses to indices greater than this numerical value must be made using the "MOVI­LINK parameter channel with acyclical routing" object. Access is also possible using ob­ject 8299 "MOVILINK parameter channel acyclical" if the parameters of the UFI11A are to be addressed.
Index: 8297
Object code: 7 (simple variable)
Data type index : 10 (octet string)
Length: 4
Local address:
Password:
Access groups:
Access rights: Read all
Name[16]: -
Extension length: -
5
Manual – Fieldbus Interface INTERBUS UFI11A
41
Page 42
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
MOVILINK para­meter channel acyclical
Parameter chan­nel performs a write service
The "MOVILINK parameter channel acyclical" object is 8 bytes long and contains the MOVILINK parameter channel. This object can be used for acyclical parameter acces­ses, i.e. the inverter processes the service coded in the parameter channel every time a WRITE service is received on this object.
The handshake bit is not evaluated! The following table shows the structure of the "MO­VILINK parameter channel acyclical."
Octet 01234567 Meaning Admin Re-
Note Admin Re-
served
served
Index
Index
Data
high
Parameter index 4 bytes data
low
Data Data Data
MSB
LSB
There are two different procedures involved in setting the drive inverter parameters via the acyclical MOVILINK parameter channel:
• Parameter channel performs a write service
• Parameter channel performs a read service
If a write service is performed via the acyclical parameter channel (e.g. write parameter or write parameter volatile), the UFI11A responds with the current service confirmation when the service has been performed. The appropriate error code is returned if the write access is not successful.
This method offers the advantage that the write services are processed simply by sen­ding a WRITE "MOVILINK parameter channel" once and evaluating the "write confirma­tion". The following table shows how write services are performed via the acyclical MO­VILINK parameter channel.
Control (master) UFI11A fieldbus interface
1. Initiate the service coded in the parameter channel by means of a WRITE to the "MOVILINK parameter channel cyclical" object.
WRITE 8299 (parameter channel)
Service confirmation (OK/error code)
The WRITE service coded in the parameter channel is performed and the service con­firmation is returned directly as the response.
42
Manual – Fieldbus Interface INTERBUS UFI11A
Page 43
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5
Parameter chan­nel performs a read type service
A PCP WRITE service must be performed before a parameter can be read via the pa­rameter channel. The PCP WRITE service defines where the UFI11A data should be available. A read service must take place on the acyclical parameter channel in order for these data to get to the master. As a result, a PCP WRITE and a PCP READ are always required for performing read services via the parameter channel. The following table shows how read services are performed via the acyclical MOVILINK parameter channel.
Control (master) UFI11A fieldbus interface
1. Initiate the service coded in the parameter channel by means of a WRITE to the "MOVILINK parameter channel cyclical" object.
2. READ "MOVILINK parameter channel cyclical" and evaluation of the service confirmation in the para­meter channel.
WRITE 8299 (parameter channel)
OK
READ 8299 (parameter channel)
Data = Parameter channel with result
1. Reception is confirmed immediately, the parameter channel is evaluated and the re­quested service performed.
2. Service confirmation is entered in the parameter channel and can be evaluated by READ access in the master.
The acyclical MOVILINK parameter channel is only handled locally on the fieldbus inter­face and is defined as in the following table.
Index: 8299
Object code: 7 (simple variable)
Data type index : 10 (octet string)
Length: 8
Local address:
Password:
Access groups:
Access rights: Read all/Write all
Name[16]: -
Extension length: -
Manual – Fieldbus Interface INTERBUS UFI11A
43
Page 44
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
5.6 Return codes for parameter setting
Different return codes will be sent back to the master used for parameter setting in case of inccorrect parameters. These codes will give the user a detailed insight into the re­ason for an error. The return codes are usually structured according to EN 50170 with the following elements:
•Error class
•Error code
• Additional code
These return codes apply to all communication interfaces of the UFI11A.
Error class
Error code
The element "Error class" classifies the type of error. The following error classes are listed according to EN 50170.
Class (hex) Designation Meaning
1 vfd-state Status error of the virtual field device
2 application-reference Error in application program
3 definition Definition error
4 resource Resource error
5 service Error during service execution
6 access Access error
7 ov Error in object directory
8 other Other error (see Additional code)
Except for error class 8 = Other error, the error class is generated by the communication software of the fieldbus card in case of communication problems. Return codes genera­ted by the inverter system are all classified as error class 8 = Other error. You will get a more detailed analysis of the error with the element "Additional code."
The element "Error code" gives you more detailed information on the reason for the error within the "Error class" and is generated by the communication software of the fieldbus card in case of communication problems. Error code = 0 (other error code) is the only error code that has been defined for error class 8 = Other error. You will find detailed information for this error in "Additional code."
44
Manual – Fieldbus Interface INTERBUS UFI11A
Page 45
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5
Additional code
Special case "Internal communication error"
The "Additional code" contains all SEW-specific return codes for incorrect parameter setting of the drive inverters. These codes are sent back to the master as "Error class 8 = Other error." Table 2 lists all possible codes for the additional code.
Add. code high (hex)
00 00 No error
00 10 Incorrect parameter index
00 11 Function/parameter not available
00 12 Read access only
00 13 Parameter block is active
00 14 Factory setting is active
00 15 Value too large for parameter
00 16 Value too small for parameter
00 17 No option card available for this function/parameter
00 18 Error in system software
00 19 Parameter access via RS485 process interface on X13 only
00 1A Parameter access via RS485 diagnostics interface only
00 1B Limited-access parameter
00 1C Requires controller inhibit
00 1D Invalid parameter value
00 1E Factory setting has been activated
00 1F Parameter was not saved in EEPROM
00 20 Parameter cannot be changed with enabled output stage
Add. code low (hex)
Meaning
The return code listed in the following table will be generated in case of a communication error between option card and inverter system. The PCP service transmitted via fieldbus may not have been executed and should be repeated. In case this error occurs frequent­ly, the drive inverter will have to be turned off and on again to start a new initialization.
Error class: 6 Access
Error code: 2 Hardware problem
Add. code high: 0 -
Add. code low: 0 -
Code (dez) Meaning
Manual – Fieldbus Interface INTERBUS UFI11A
45
Page 46
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
INTERBUS Interface
Error correction
Extension of the Additional code
Extension of the special return codes
5.7 Autosetup
Repeat the read or write service. If the error occurs once again, turn off the drive inverter completely and turn it on again. Please consult the SEW Electronics Service If this error occurs permanently.
00 23h Parameter may only be changed in IPOS program "Stop"
00 24h Parameter may only be changed with Autosetup turned off
Error class: 06 Access
Error code: 01 Object does not exist
Add. code high: 0 -
Add. code low: 0 -
Remedy: You are trying to exchange parameters with a drive inverter and have not con­figured a parameter channel.
You can start up the UFI11A without a PC with the Autosetup function. It is activated with the Autosetup DIP switch. Turning on the Autosetup DIP switch will execute the function
The DIP switch will have to stay turned on afterwards.
once. cuted once again by turning the switch off and on again. Upon activation of the Autosetup feature, the UFI11A automatically searches for inverters on the lower-level SBus and indicates this activity with a brief blinking of the SYS-FLT LED. Each inverter on the SBus must be assigned a unique SBus address (P813). To avoid confusion with data assignments, it is recommended to assign the addresses from address 1 ans wor­king in ascending order according to the arrangement of inverters in the control cabinet. The process image on the fieldbus side will be extended by three words for each located inverter. The SYS-FLT LED stays on if no inverters are found. A maximum of eight in­verters can be configured. The figure shows the process image for three inverters with three words in the process output data and process input data. Following the search, the UFI11A cyclically exchanges three process data words with each connected inverter. The process output data are collected from the fieldbus, divided into blocks of three and sent. The process input data are read by the inverters, assembled and sent to the field­bus master.
Autosetup has to be executed only once. The detected configuration will be saved in the non-volatile memory. See section "Installation and operation without PC."
Important: Execute Autosetup again in case you change the process data assignment of the inverters connected to the UFI11A, because the UFI11A saves these values once only during Autosetup. Likewise, the process data assignments (P860 ... P865) of the connected inverters must not be altered dynamically either, for example by an IPOS pro­gram, following Autosetup.
Code (dez) Meaning
The function can be exe-
46
Manual – Fieldbus Interface INTERBUS UFI11A
Page 47
INTERBUS Interface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5
Fig. 25: Data exchange INTERBUS master – UFI11A – inverter
Manual – Fieldbus Interface INTERBUS UFI11A
05431AXX
47
Page 48
6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
6 Error Response
6.1 Fieldbus timeout
6.2 SBus timeout
6.3 Unit errors
Error Response
Switching off the fieldbus master or a wire break in the fieldbus cabling leads to a field­bus timeout in the UFI11A. The connected inverters are set to a safe status by zeros being sent on the process output data. This corresponds to a rapid stop on control word
1. The fieldbus timeout error is self-resetting, meaning the inverters will begin receiving
the current process output data from the master immediately after fieldbus communica­tion is re-established. This error response can be deactivated using P831 on the UFI11A.
If one or more inverters on the Sbus can no longer be addressed by the UFI11A, the UFI11A enters error code 91, "System error," in status word 1 of the corresponding in­verter. The SYS-FLT LED lights up and the error is also displayed via the diagnostic in­terface. P815 SBus timeout delay must be set to a value other than 0 on the inverter if it is to stop. The error is self-resetting on the UFI11A, meaning the current process data are exchanged again immediately after communication resumes.
UFI11A fieldbus interfaces detect a range of hardware defects and respond with an in­hibit condition. Refer to the list of errors for the exact error responses and measures to remedy the problem. A hardware defect means error 91 is entered in the process input data of the fieldbus in status word 1 of all inverters. The SYS-FLT LED on the UFI11A then flashes evenly. The exact error code is displayed in the status of the UFI11A using the diagnostic interface of MOVITOOLS.
48
Manual – Fieldbus Interface INTERBUS UFI11A
Page 49
7 Diagnostic LEDs
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
The UFI11A INTERBUS interface has 7 diagnostic LEDs.
• LED "UL" (green) Logic voltage
• LED "RC" (green) Incoming remote bus OK
• LED "BA" (green) Bus mode active
• LED "RD" (yellow) Outgoing remote bus switches off
• LED "TR" (green) Parameter data exchange via PCP channel
• LED "SYS-FAULT"(red) for displaying system errors and operating conditions of the
• LED "USER" (green) for application-specific diagnostics in expert mode
7.1 States of the LEDs UL, RC, BA, TR and RD
LED UL "U-Logic" (green)
LED RC "Cable Check" (green)
LED BA "Bus Active" (green)
LED RD "Remote Bus Disable" (red)
Status Meaning Remedy
on Supply voltage of bus electro-
off Supply voltage of bus electro-
Status Meaning Remedy
on Incoming remote bus connec-
off Incoming remote bus connec-
Status Meaning Remedy
on Data transmission via INTER-
off No data transmission; INTER-
Status Meaning Remedy
on Outgoing remote bus turned off -
off Outgoing remote bus not turned off -
nics is present
nics is missing
tion is ok
tion is faulty
BUS active
BUS has been stopped
UFI11A
-
Check the 24V voltage supply of the UFI11A.
-
Check the incoming remote bus connection.
-
Check the incoming remote bus cable. Use the diagnostics display of the INTERBUS interface module (master) for additional error localization.
Diagnostic LEDs
7
Manual – Fieldbus Interface INTERBUS UFI11A
49
Page 50
7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
LED TR "Trans­mit" (green)
LED TR "Trans­mit" (yellow or red)
LED "SYS­FAULT" (red)
LED "USER" (green)
Diagnostic LEDs
Status Meaning Remedy
The LED TR corresponds in the color green according to the Interbus standard.
off No PCP communication -
green PCP communication active or INTERBUS start (parameter access via
Status Meaning Remedy
The LED TR signals system-internal states with the colors yellow and red that usually do not occur during INTERBUS operation.
off or green
flashing yellow
steady red Incorrect DIP switch configuration selected,
flashing red
Status Meaning
OFF Standard operating status. The UFI11A is exchanging data with the connected inver-
FLASHES 1 x briefly with long pause
FLASHES regularly UFI11A is in error status. If you started the UFI11A using the Autosetup DIP switch,
ON The UFI11A is not exchanging data with the connected inverters. Either is has not
Statuts Meaning
OFF Standard operating status. The "USER“ LED is reserved for expert mode.
INTERBUS PCP channel)
Standard operation (see table for TR = green) -
Inverter is in initialization phase -
no INTERBUS operation possible.
Incorrect DIP switch configuration or defec­tive INTERBUS option card, no INTERBUS operation possible.
ters.
Autosetup has been selected using the DIP switch and the UFI11A is currently set­ting up its configuration. If this status lasts for more than one minute, turn off the Autosetup mode and turn it on again. Replace the module if the behavior persists.
turn the UFI11A off and on again. If the LED is still on, restart Autosetup by turning the DIP switch off and on again. If you started the UFI11A with MOVITOOLS, you will see an error message in the status window. Consult the corresponding error description.
been configured or one or more of the connected inverters are not responding. Reconfigure the UFI11A. If you started up the UFI11A using Autosetup, please switch the Autosetup DIPswitch off and on again. If the LED stays on after Autose­tup, please check the cabling and the terminating resistors of the SBus as well as the inverter voltage supply. If you started up the UFI11A using MOVITOOLS, click the "Update" button in the Movitools Manager. All the inverters should be displayed in the "Connected Inverters" window. If this is not the case, please check the cabling and the terminating resistors of the SBus as well as the inverter voltage supply. Reconfigure the UFI11A with MOVITOOLS if necessary.
Check the settings of DIP switch S1. Correct the settings of the DIP switches and turn the unit on again.
Check the setting of DIP switch S1. If the set­ting is correct, contact SEW Electronics Ser­vice.
-
50
Manual – Fieldbus Interface INTERBUS UFI11A
Page 51
8 DIP Switches
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
DIP Switches
8
PD1 – PD5
PCP 1, 2
Process data length
Fig. 26: DIP switches
05376AXX
Binary setting of the process data length
The following example shows how the DIP switch settings are determined for a process data length of 17. Divide each required process data length by the number two and make a note of the remainder. The remainder can only be 0 or 1. This corresponds to the setting of the DIP switches.
Table 1: Example for determining the DIP switch settings for process data width 17
Calculation Remainder DIP switch setting Significance
17 ÷ 2 = 8 1 X1 = 20 = ON 1 8 ÷ 2 = 4 0 X2 = 21 = OFF 2 4 ÷ 2 = 2 0 X3 = 22 = OFF 4 2 ÷ 2 = 1 0 X4 = 23 = OFF 8 1 ÷ 2 = 0 1 X5 = 24 = ON 16
You can set the lengths of the PCP channel in words using these two DIP switches. Pos­sible values are 0, 1, 2 and 4 words.
PCP 1 PCP 2
OFF OFF 0
ON OFF 1
OFF ON 2
ON ON 4
Please note that INTERBUS does not support all data lengths which can be set. The to­tal data length of process data and PCP words can be 1 – 10, 12, 14, 16, 24, 26 and 36 words.
If you require a number of words which lies between these settings, the next higher num­ber must be used. For example, 9PD + 4 words PCP results in 14 words.
AUTO SETUP: See Sec. Quickstart without PC
Manual – Fieldbus Interface INTERBUS UFI11A
51
Page 52
9
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Application examples
9 Application examples
This section describes small application examples for the exchange of process data and configuration of the UFI11A or a drive inverter connected to the UFI11A via the PCP in­terface.
9.1 Control via process data
Control of the drive inverters via process data takes place by simple reading/writing of the program addresses to which the INTERBUS process data of the drive inverters have been written. A simple STEP7 program for the Simatic S7 looks as follows:
L W#16#0006 T PAW 144 //write 6hex to PO1 (control word = enable) L 1500 T PAW 146 //write 1500dez to PO2 (speed setpoint = 300 1/min) L W#16#0000 T PAW 148 //write 0hex to PO3 (has no function after factory setting)
You will find additional information concerning control of the drive inverters via the pro­cess data channel, especially coding of the control and status word, in the manual for the fieldbus unit profile of the corresponding drive inverter.
9.2 Parameter setting via the PCP interface
This section describes how you can read or write parameters and IPOS variables via the standardized INTERBUS PCP services "Read" and "Write." The example is valid for all INTERBUS interface modules of generation 4 (G4) and is explained in the PHOENIX nomenclature. The coding examples described in the following sections are represented in the same manner as described in the INTERBUS user manual "Peripherals Commu­nication Protocol (PCP)" published by Phoenix Contact.
Prerequisites
You should have access to the following user manuals:
• INTERBUS user manual "Peripherals Communication Protocol (PCP)", PHOENIX CONTACT, IBS SYS PCP G4 UM
• Manual for the fieldbus unit profile of the drive inverter connected to the UFI11A
52
Manual – Fieldbus Interface INTERBUS UFI11A
Page 53
9.3 Representation of the coding examples
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
All information of a PCP service is represented in a word-by-word manner with one word listed below the other. This means you can consider a word as an PLC word (for examp­le Simatic data word). You will find a coding example for the UFI11A in the right table column.
Select the UFI11A to be configured with the "Communication Reference (CR)." In the following examples, the UFI11A has been assigned the CR = 02 hex in the CMD tool. The index defines the parameter that is to be accessed.
Before you can use the PCP channel of the UFI11A, you will have to configure the de­vice description for the inverter in the CMD Tool.
9.4 Sequence of a parameter setting process
The Peripherals Communication Protocol (PCP) of the INTERBUS standardizes the ac­cess to parameter data of INTERBUS stations and establishes the following sequence:
• Establishing the PCP connection with the "Initiate" service.
• Reading or writing parameters with the "Read" and "Write" services.
• If the communication connection is no longer necessary, it can be disconnected with the "Abort" service (not explained here since it often is not necessary, see PCP ma­nual).
• Initialization of the PCP connection with the "Initiate" service.
Access to the parameters of the Interbus station takes place only after the PCP connec­tion has been established with "Initiate_Request." This step can be established during the initial startup of the system.
Word Meaning Coding (hex)
1 Command_Code = Initiate_Request 00 8B
2 Parameter_Count 00 02
3 - Comm._Reference 00 02
4 Password Access_Groups 00 00
Bits 15 ... 8 7 ... 0
After sending the service, you should receive a confirmation with "Initiate_Confirmation" (see PCP manual in case of a non-confirming message).
Application examples
9
Manual – Fieldbus Interface INTERBUS UFI11A
53
Page 54
9
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Application examples
9.5 Reading of an UFI parameter
You read an UFI11A parameter with the "Read" service. The parameters are typically 4 bytes long (1 double word). This read service accesses only those parameters with in­dices between 8300dez and 8310dez. Parameter access to all other parameters of the UFI11A or a drive inverter connected to the UFI11A takes place via object 8288 "Vari­able data channel with acyclical routing." The access is decribed in the next section.
Example
Reading of index 8301 unit type (Index 8301dez = 206Dhex)
Word Meaning Coding (hex)
1 Command_Code = Read_Request 00 81
2 Parameter_Count 00 03
3 Invoke_ID Comm._Reference 00 02
4 Index 20 6D
5 Subindex - 00 00
Bits 15 ... 8 7 ... 0
After sending the service, you should receive a confirmation with "Read_Confirmation."
Word Meaning Coding (hex)
1 Message_Code = Read_Confirmation (+) 80 81
2 Parameter_Count 00 05
3 Invoke_ID Comm._Reference 00 02
4 Result (+) 00 00
5 - Length 00 04
6 Data [1] Data [2] 00 28
7 Data [3] Data [4] 01 00
Bits 15 ... 8 7 ... 0
The parameter data are displayed as follows in the Motorola format (Simatic format):
Data [1] = High Byte Data [2] = Low Byte Data [3] = High Byte Data [4] = Low Byte
00 hex 28 hex 01 hex 00 hex
00 28 01 00 hex = Identification for UFI11A
You will find additional information on the UFI11A parameters in the section "Parameter List."
54
Manual – Fieldbus Interface INTERBUS UFI11A
Page 55
Application examples
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
9.6 Writing of UFI11A or drive parameters via object 8288
The UFI offers a special parameter access via the object 8288 "variable data channel with acyclical routing" for the universal write access to all data of the UFI or a drive in­verter connected to the UFI (parameters, IPOS variables, IPOS program code, etc.). The following description is the mechanism that can be used to change IPOS variables or other variables via the parameter channel. The "variable data channel with acyclical routing“ is available via index 8288 dez (2060 hex).
Example
Writing the value 74565 of the IPOS variable H0 = Index 11000 dez (2AF8 hex). The value 74565 dez (0001 2345 hex) has to be written to the drive inverter with SBus address 1.
Word Meaning Coding (hex)
1 Command_Code = Write_Request 00 82
2 Parameter_Count 00 09
3 Invoke_ID Comm._Reference 00 02
4 Index = 8288 20 60
5 Subindex Length 00 0C
6 Data[1] = Subkanal Data[2] = Subadresse 01 01
7 Data[3] = Frametyp Data[4] = Datenlänge 86 08
8 Data[5] = Verwaltung Data[6] = Reserviert 32 00
9 Data[7] = Index High Data[8] = Index Low 2A F8
10 Data[9] Data[10] 00 01
11 Data[11] Data[12] 23 45
Bits 15 ... 8 7 ... 0
After sending this service, you will receive the "Write_Confirmation." You can once again use the return codes for the evaluation of a negative message.
9
Manual – Fieldbus Interface INTERBUS UFI11A
55
Page 56
9
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Application examples
9.7 Reading of UFI11A or drive parameters via object 8288
The UFI offers a special parameter access via the object 8288 "variable data channel with acyclical routing" for the universal read access to all data of the UFI or a drive in­verter connected to the UFI (parameters, IPOS variables, IPOS program code, etc.). The following description is the mechanism that can be used to read the IPOS variables or other variables via the parameter channel of a drive inverter connected to the UFI (with SBus address 1). This process requires a two-setp sequence:
• Writing the "variable data channel with acyclical routing“ with the order "Read IPOS variable H0 to sub channel 1, sub address 1“
• Reading of the "variable data channel with acyclical routing“
The "variable data channel with acyclical routing“ is available via index 8288 dez (2060 hex).
Example
Reading the IPOS variable H0 = Index 11000 dez (2AF8 hex) of the drive inverter with SBus address 1.
Word Meaning Coding (hex)
1 Command_Code = Write_Request 00 82
2 Parameter_Count 00 09
3 Invoke_ID Comm._Reference 00 02
4 Index = 8288 20 60
5 Subindex Length 00 0C
6 Data[1] = Subkanal Data[2] = Subadresse 01 01
7 Data[3] = Frametyp Data[4] = Datenlänge 86 08
8 Data[5] = Verwaltung Data[6] = Reserviert 31 00
9 Data[7] = Index High Data[8] = Index Low 2A F8
10 Data[9] Data[10] 00 00
11 Data[11] Data[12] 00 00
Bits 15 ... 8 7 ... 0
After receiving the positive "Write_Confirmation (+)," there will be a read access to the "variable data channel with acyclical routing“ that will read in the data read with the read order defined in the "Write_Request" into the interface module.
Word Meaning Coding (hex)
1 Command_Code = Read_Request 00 81
2 Parameter_Count 00 03
3 Invoke_ID Comm._Reference 00 02
4 Index = 8288 20 60
5 Subindex - 00 00
Bits 15 ... 8 7 ... 0
56
Manual – Fieldbus Interface INTERBUS UFI11A
Page 57
Application examples
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
After sending this service, you should receive a positive "Read_Confirmation."
Word Meaning Coding (hex)
1 Command_Code = Read_Confirmation (+) 80 81
2 Parameter_Count 00 09
3 Invoke_ID Comm._Reference 00 02
4 Result (+) 00 00
5 - Length 00 0C
6 Data[1] = Subkanal Data[2] = Subadresse 01 01
7 Data[3] = Frametyp Data[4] = Datenlänge 86 08
8 Data[5] = Verwaltung Data[6] = Reserviert 31 00
9 Data[7] = Index High Data[8] = Index Low 2A F8
10 Data[9] Data[10] 00 01
11 Data[11] Data[12] 23 45
Bits 15 ... 8 7 ... 0
You can use the return codes for the evaluation of negative messages.
Word Meaning Coding (hex)
1 Command_Code = Read_Confirmation 80 81
2 Parameter_Count 00 03
3 Invoke_ID Comm._Reference 00 02
4 Error_Class Error_Code 08 00
5 Additional_Code 00 10
Bits 15 ... 8 7 ... 0
9
Manual – Fieldbus Interface INTERBUS UFI11A
57
Page 58
10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Parameter List
10 Parameter List
Par.
Parameter Index Unit Access Default Meaning / Value range
no.
010 Unit status 8310 RO 0
011 Operating status 8310 RO 0
012 Error status 8310 RO 0
013 Current parameter set 8310 RO 0
015 Operating hours 8328 s RO/N 0
070 Device type 8301 RO 0
076 Firmware basic unit 8300 RO 0
090 PD – configuration 8451 RO 4
091 Fieldbus type 8452 RO 2
092 Baud rate fieldbus 8453 RO 0
093 Fieldbus address 8454 RO 0
094 PO1 setpoint 8455 RO 0
095 PO2 setpoint 8456 RO 0
096 PO3 setpoint 8457 RO 0
097 PI1 actual value 8458 RO 0
098 PI2 actual value 8459 RO 0
099 PI3 actual value 8460 RO 0
802 Factory setting 8594 R/RW 0 0: NO
810 RS485 address 8597 R0 0
812 RS485 timeout delay 8599 s R/RW 1
816 SBUS Baud rate 8603 R/RW 0 0: 125 kBaud
819 Fieldbus timeout delay 8606 s RO 0.630
831 RESPONSE fieldbus timeout 8610 R/RW 10 0: NO RESPONSE
840 Manual reset 8617 R/RW
870 Setpoint description PO1 8304 RO 12 IPOS PO DATA
871 Setpoint description PO2 8305 RO 12 IPOS PO DATA
872 Setpoint description PO3 8306 RO 12 IPOS PO DATA
873 Acutal value description PI1 8307 RO 9 IPOS PI DATA
874 Actual value description PI2 8308 RO 9 IPOS PI DATA
875 Actual value description PI3 8309 RO 9 IPOS PI DATA
1: YES 2: DELIVERY STATUS
1: 250 kBaud 2: 500 kBaud 3: 1000 kBaud
10: PO DATA = 0 / WARN
58
Manual – Fieldbus Interface INTERBUS UFI11A
Page 59
11 List of Errors
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Error
Name Response Cause Action
code
10 IPOS ILLOP IPOS program
17 Stack overflow SBus communi-
18 Stack under-
flow
19 NMI SBus communi-
20 Undefined
opcode
21 Protection
error
22 Illegal word
operand access
23 Illegal instruc-
tion access
24 Illegal exter-
nal bus access
25 EEPROM SBus communi-
28 Fieldbus time-
out
32 IPOS index
overflow
37 Watchdog
error
45 Initialization
error
77 Invalid IPOS
control word
stop
cation stopped
SBus communi­cation stopped
cation stopped
SBus communi­cation stopped
SBus communi­cation stopped
SBus communi­cation stopped
SBus communi­cation stopped
SBus communi­cation stopped
cation stopped
Connected inver­ters stopped (control word = 0)
IPOS program stop
SBus communi­cation stopped
SBus communi­cation stopped
IPOS program stopped
List of Errors
Error in IPOS program, see IPOS variable H469 for more information
Inverter electronics disrupted, pos­sibly due to effect of EMC
""
""
""
""
""
""
""
Error when accessing EEPROM Call up default setting, perform
No master-slave communication took place within the configured response monitoring period.
Basic programming rules violated causing stack overflow in system.
Error in system software procedure Check ground connections and
Error after self-test in reset Ensure DIP switches F1 and F2
Attempt was made to set an invalid automatic mode (via external cont­rol).
Correct the IPOS program, load and reset
Check ground connections and shields; improve them if neces­sary. Contact SEW Service for advice if this reoccurs.
reset and set parameters of UFI11A again. Contact SEW Ser­vice for advice if this reoccurs.
• Check master communication routine
• Extend the fieldbus timeout delay (response monitoring) in the master configuration or turn off monitoring
Check IPOS user program and correct if necessary
shields; improve them if neces­sary. Contact SEW Service for advice if this reoccurs.
are off. Perform reset. Contact SEW Service for advice if problem persists.
Check write values of external control
11
Manual – Fieldbus Interface INTERBUS UFI11A
59
Page 60
11
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Error code
91 System error None Please check the red SYS-FLT LED
97 Copy data SBus communi-
List of Errors
Name Response Cause Action
on the UFI11A. If this LED is on, then one or more stations on the SBus could not be addressed within the timeout delay. If the red SYS­FLT LED is flashing, then the UFI11A itself is in error status. In this instance, error 91 alone was transmitted to the control via the fieldbus.
cation stopped
An error occurred while the data record was being copied. The data are not consistent.
Check the voltage supply and the SBus cabling, check the SBus ter­minating resistors. Check the con­figuration if the UFI11A was configured with the PC. Switch the UFI11A off and on again. Check the error code using the diagnostic interface if the error remains, and take the action described in this table.
Carry out the "delivery condition" factory setting, perform a reset and then try to copy the data again.
60
Manual – Fieldbus Interface INTERBUS UFI11A
Page 61
12 Technical Data
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Part number: 823 898 7
Startup utility: MOVITOOLS V 2.70 or later
Voltage supply: 24 V
Parameter setting and diagnostic interface: RS-485
Parameter setting: Autoconfiguration
Diagnostics: LEDs on the front panel of the unit
Mounting: Screw mounting or support rail
Ambient temperature: -10 °C...+50 °C
Technical Data
, external supply
DC
Using MOVITOOLS from V 2.70 or la­ter
MOVITOOLS
12
SBus
Maximum transmission speed: 1 MBaud
Transfer protocol: MOVILINK
Number of units on SBus: max. 8
Process data words per unit: max. 3 PD
Connection technology: Disconnectable screw terminals
Manual – Fieldbus Interface INTERBUS UFI11A
61
Page 62
13
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
13 Dimensions
Dimensions
Fig. 27: Dimension drawing
62
Manual – Fieldbus Interface INTERBUS UFI11A
05114AXX
Page 63
14 Index
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
A
Abort 36 Additional code 45 Additional codes, extension 46 Address information 38 Application examples 52 Autosetup 46
B
BA 49 Baud rate 8, 15 Bus Active 49 Bus configuration 20 Bus structure 20 Bus termination 9, 16
C
Cable Check 49 CC 49 Communication error 45 Communications link, breaking off 36 Communications link, establishing 36 Configuration 18, 28 Configuration of the fieldbus master 11 Configuring the fieldbus master 11, 18 Connection 7, 8, 14, 15 Connection, breaking off 36 Connection, establishing 36 Control via process data 52
D
Device description 23 Diagnostic interface 5 Diagnostic LEDs 49 Dimension drawing 62 DIP switches 5, 11, 18, 51 Display elements 49 Download parameter block 40
E
Error class 44 Error code 44
F
Fieldbus timeout 48 Front view 5
I
ICO files 24 Initiate 36 Installation notes 6, 13 Internal communication error 45 Inverter parameters 10, 17
L
Last PCP index 41 LED BA 49 LED CC 49 LED RD 49 LED SYS-FAULT 50 LED TR 50 LED UL 49 LEDs 49 List of errors 59
M
MOVILINK parameter channel acyclical 42
O
Object description 37
P
Parameter channel 25 Parameter list 58 Parameter module 4 Parameter setting via the PCP interface 52 Parameter setting, Return codes 44 PC connection 17 PCP configuration 27 PCP connection 26 PCP interface 35 PCP services 35 Pin assignment 6, 13 Process data 25 PROFIBUS address 11, 18 Program addresses 25
R
RD 49 Read 36 Read parameter values 36 Reading of an UFI parameter 54 Reading of UFI11A or drive parameters via object 8288 56 Remote Bus Disable 49 Representation of the coding examples 53 Return codes 44 Return codes, extension 46
S
SBus timeout 48 Sequence of a parameter setting process 53 Setting the inverter parameters 10, 17 Shielding 7, 8, 9, 14, 15, 16 Starting the inverters 12, 19 Startup 10, 17, 20 Subchannel 38 SYS-FAULT 50
Manual – Fieldbus Interface INTERBUS UFI11A
63
Page 64
T
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Technical data 61 TR 50 Transmit 50
U
UL 49 U-Logic 49 Unit errors 48 Unit structure 5 UWS21A 17
V
Variable data channel with acyclical routing object 38
W
Write 35, 36, 38, 42 Write parameter values 35, 36, 38, 42 Writing of UFI11A or drive parameters via object 8288 55
64
Manual – Fieldbus Interface INTERBUS UFI11A
Loading...