The manual is part of the product and contains important information on operation and
service. The manual is written for all employees who assemble, install, startup, and
service the product.
The manual must be accessible and legible. Make sure that persons responsible for the
system and its operation, as well as persons who work independently on the unit, have
read through the manual carefully and understood it. If you are unclear about any of the
information in this documentation, or if you require further information, contact SEWEURODRIVE.
1.2Structure of the safety notes
The safety notes in this manual are structured as follows:
PictogramSIGNAL WORD
Type and source of danger.
Possible consequence(s) if the safety notes are disregarded.
•Measure(s) to prevent the danger.
PictogramSignal wordMeaningConsequences if
disregarded
Example:
General danger
Specific danger,
e.g. electric shock
DANGERImminent dangerSevere or fatal injuries
WARNINGPossible dangerous situationSevere or fatal injuries
CAUTIONPossible dangerous situationMinor injuries
NOTICEPossible damage to propertyDamage to the drive system or its
environment
TIPUseful information or tip.
Simplifies the handling of the
drive system.
6
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
A requirement of fault-free operation and fulfillment of any rights to claim under limited
warranty is that you adhere to the information in the manual. Therefore, read the manual
before you start operating the device!
1.4Exclusion of liability
You must comply with the information in the manual and the documentation of the units
connected to the fieldbus gateway to ensure safe operation and to achieve the specified
product characteristics and performance features. SEW-EURODRIVE assumes no
liability for injury to persons or damage to equipment or property resulting from nonobservance of the operating instructions. In such cases, any liability for defects is
excluded.
•Installation and startup only by trained personnel observing the relevant accident
prevention regulations and the following documents:
– "MOVIDRIVE
– "MOVITRAC
– "MOVIAXIS
•Read through these documents carefully before you commence installation and
startup of the UFF41B fieldbus gateway.
•As a prerequisite to fault-free operation and fulfillment of warranty claims, you must
adhere to the information in the documentation.
2.2General safety notes for bus systems
This communication system lets you adjust inverters and servo inverters to a variety of
different applications. As with all bus systems, there is a danger of invisible, external (as
far as the inverter is concerned) modifications to the parameters which give rise to
changes in the unit behavior. This may result in unexpected (not uncontrolled) system
behavior.
®
®
®
" operating instructions
MDX60B/61B" operating instructions
B" operating instructions
2.3Safety functions
The inverters and servo drives are not allowed to perform any safety functions unless
they are subordinate to other safety systems. Use higher-level safety systems to ensure
protection of equipment and personnel.
For safety applications, ensure that the information in the following publications is
observed: "Safe Disconnection for MOVIDRIVE
2.4Hoist applications
MOVIDRIVE® MDX60B/61B, MOVITRAC® B and MOVIAXIS® must not be used as a
safety device in hoist applications.
Use monitoring systems or mechanical protection devices as safety equipment to avoid
possible damage to property or injury to people.
2.5Product names and trademarks
The brands and product names contained within this manual are trademarks or registered trademarks of the titleholders.
®
B / MOVITRAC® B / MOVIAXIS®".
8
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
•Startup the UFF41B fieldbus gateway with the DeviceNet and PROFIBUS DP-V1
•Configure the DeviceNet master with EDS files.
•Configure the PROFIBUS DP-V1 master using GSD files.
3.2Characteristics
The powerful, universal fieldbus interfaces of the UFF41B option enable you to use the
option to connect to higher-level automation systems via DeviceNet and PROFIBUS
DP-V1.
and to the MOVIAXIS
fieldbus systems.
®
®
servo inverter.
®
B, MOVITRAC® B and MOVIAXIS® for gateway operation.
B, MOVITRAC® B inverters
3.2.1Process data exchange
The UFF41B fieldbus gateway allows for digital access to most parameters and functions via the DeviceNet and PROFIBUS interfaces. Control is performed via fast, cyclic
process data. Via this process data channel, you can enter setpoints and trigger various
control functions, such as enable, normal stop, rapid stop, etc. At the same time you can
also use this channel to read back actual values, such as actual speed, current, unit
status, error number or reference signals. In DeviceNet operation, process data are
exchanged with polled I/O and bit-strobe I/O. In PROFIBUS operation, they are exchanged via I/O data in the master.
3.2.2Parameter access
In DeviceNet operation, the parameters of the inverter are set solely via explicit
messages.
In PROFIBUS operation, the PROFIBUS DP-V1 parameter mechanisms lets you
access any device information.
10
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
Using a fieldbus system requires additional monitoring functions, for example, time
monitoring of the fieldbus (fieldbus timeout) or rapid stop concepts. You can determine,
for instance, which fault responses should be triggered in the event of a bus error. The
parameters for the fault response can be set in the servo inverter / inverter. A rapid stop
is useful for many applications. This is why the fieldbus gateway will stop the lower-level
drives in the event of a fieldbus timeout. As the range of functions for the control terminals is also guaranteed in fieldbus mode, you can continue to implement rapid stop
concepts using the servo inverters/inverters connected to the fieldbus gateway.
Introduction
Characteristics
3
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
Voltage supply, system bus and fieldbus interfaces as well as the engineering interface
are located at different potential levels (see chapter 13.1).
Assembly and Installation Instructions
Voltage supply
4
4.2.1Voltage supply in the MOVIAXIS
®
master module
TIP
The MOVIAXIS® master module MXM provides additional connections that are
described in the following section.
Functional description of the terminals, X5a/X5b (MOVIAXIS
MOVIAXIS® master
module MXM
1
X5b
2
3
4
1
X5a
2
3
4
59233AXX
•The terminals X5a and X5b are connected in parallel. In this way, the voltage supply
of the MOVIAXIS
below to X5a. With connection to X5a, further modules can be connected via X5b
(e.g. supply module, axis module). The voltage supply for the brake (X5a/b:3, 4) is
fed through the MOVIAXIS
•The UFF41B fieldbus gateway can be supplied from the MOVIAXIS
power supply (MXS) or from an external voltage source. To do so, connect X5
between the individual units.
•If the UFF41B fieldbus gateway is connected with DC 24 V from the MOVIAXIS
switched-mode power supply, the functioning of the option is maintained after disconnection from the power supply. This is the case if the DC link voltage is maintained or an external DC 24 V supply is present from the MOVIAXIS
power supply.
DesignationTerminalFunction
X5b connectorX5b:1
Terminal X5aX5a:1
®
master module can be provided from the right to X5b or from
X5b:2
X5b:3
X5b:4
X5a:2
X5a:3
X5a:4
®
master module.
®
master module)
DC 24 V
DGND
DC 24 V
BGND
DC 24 V
DGND
DC 24 V
BGND
Voltage supply for control electronics
E
Reference potential for control
electronics
B
Voltage supply for brake
Reference potential for brake
connection
Voltage supply for control electronics
E
Reference potential for control
electronics
B
Voltage supply for brake
Reference potential for brake
connection
®
switched-mode
®
switched-mode
®
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
System bus CAN 1 high
System bus CAN 1 low
Reference potential control/CAN1
-
Reference potential for UFF41B
Voltage supply for controller
Designation
LEDH1
Connector X24:
RJ10 socket
DesignationTerminalFunction
Connector X26:
CAN 1 and voltage supply
(plug-in terminal)
Connection of CAN 1 system bus / voltage supply (terminal X26)
The connections for CAN 1 (X26:1/2/3 and connector X33) are connected in parallel.
The UFF41B fieldbus gateway is supplied with voltage in the UOH21B gateway housing
via X26:6/7.
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
4.3.1Functional description of the terminals, DIP switch es and LEDs of the UFF41B option
Connectors, LEDs and DIP switches in the upper part of the UFF41B fieldbus gateway
allow for connection to the fieldbus systems DeviceNet (see section "Connecting the
UFF41B fieldbus gateway to a DeviceNet network") and PROFIBUS-DP (see section
"Connecting the UFF41B fieldbus gateway to a PROFIBUS network").
Front view
UFF41B fieldbus
gateway
64418AXX
LED
Designation
DIP switch
Terminal
LEDLED 1
LED 2
LED 3
LED 4
LED 5
Terminal X35:
USB connection
X35:1
X35:2
X35:3
X35:4
Terminal X36:
X36
Connection of an
EtherCAT based
system bus (RJ45 socket)
Terminal X37:
X37Ethernet for engineering
Ethernet connection
(RJ45 socket)
Terminal X32:
System bus CAN 2
(electrically isolated)
X32:1
X32:2
X32:3
(plug-in terminals)
Terminal X33:
System bus CAN 1
(plug-in terminals)
X33:1
X33:2
X33:3
DIP switchS1
Memory cardM1
ButtonT1
CAN 1 status
CAN 2 status
Program status
Gateway status
Gateway error
USB+5 V
USBUSB+
DGND
Standard Ethernet
assignment
BZG_CAN 2
CAN 2H
CAN 2L
DGND
CAN 1H
CAN 1L
To p
Bottom
Function
Status of CAN 1 system bus
Status of CAN 2 system bus
Status of gateway program
Status of gateway firmware
Status of gateway error (see section "Error
messages of the fieldbus gateway")
DC 5 V voltage supply
Signal USBSignal USB+
Reference potential
plus
System bus SBUS
(in preparation)
Reference potential for system bus CAN 2
System bus CAN 2 high
System bus CAN 2 low
Reference potential for system bus CAN 1
System bus CAN 1 high
System bus CAN 1 low
Default IP address (192.168.10.4)
IP parameter from SD memory card
Memory for firmware, gateway application, gateway configuration, and inverter parameters
For Bootloader update
(see section "SD memory card OMG4.B")
16
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
4.3.2Connecting CAN 1 system bus (terminal X33) / CAN 2 (terminal X32 )
Do not connect more than 64 units to the CAN 1 or CAN 2 system bus. The system bus
supports the address range 0 to 63.
TIPS
•The CAN 1 system bus is not electrically isolated. Therefore, it is recommended to
use the CAN 1 (X33 or X26 with UFF41B/UOH21B) interface to connect inverters
via the system bus in the control cabinet. Set the P881 SBus address parameter in
increasing order to values 1 - 16 if the slave unit is connected to CAN 1 or the fieldbus gateway.
•The CAN 2 system bus is electrically isolated. Therefore, preferably use interface
CAN 2 (X32) for connecting field units or units in other control cabinets. Set the
P881 SBus address parameter in increasing order to values 17 - 34 if the unit is
connected to CAN 2 or the fieldbus gateway.
4
The CAN system bus supports transmission systems compliant with ISO 11898. For
detailed information on the CAN system bus, refer to the "MOVIDRIVE
®
Communication
and Fieldbus Device Profile" manual. You can order this manual from SEWEURODRIVE.
®
Wiring diagram for MOVIDRIVE
B, MOVITRAC® B on CAN 1 system bus
64714AXX
Cable specification•Use a 2 x 2-core twisted and shielded copper cable (data transmission cable with
braided copper shield). Clamping without conductor end sleeves is possible in accordance with IEC 60999. The cable must meet the following specifications:
2
– Cable cross-section 0.2 to 1.0 mm
(AWG 24 - AWG 18)
– Cable resistance 120 Ω at 1 MHz
Cable length•The permitted total cable length depends on the baud rate setting of the system bus:
– Capacitance per unit length ≤ 40 pF/m at 1 kHz
Suitable cables include CAN bus or DeviceNet cables.
– 125 kBaud→ 500 m
– 250 kBaud→ 250 m
– 500 kBaud→ 100 m
– 1000 kBaud→ 40 m
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
•Switch on the system bus terminating resistor at the start and end of the CAN system
bus connection (MOVIDRIVE
S1 = ON). For all other devices, switch off the terminating resistor (MOVIDRIVE
DIP switch S12 = OFF; MOVITRAC
way is, for example, located at the end of the CAN 2 system bus, you have to connect
a terminating resistor of 120 Ω between pins X32:2 and X32:3 (for CAN 1: Terminating resistor betwee
n pins X33:2 and X33:3).
®
B, DIP switch S12 = ON; MOVITRAC® B, DIP switch
®
B, DIP switch S1 = OFF). If the fieldbus gate-
®
B,
CAUTION
•There must not be any potential displacement between the units connected via the
CAN 2 system bus.
•There must not be any potential displacement between the units connected via the
CAN 1 system bus.
•Take suitable measures to avoid potential displacement, such as connecting the
unit ground connectors using a separate cable.
18
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
Terminal X36 is intended for connecting a system bus based on EtherCAT (SBUS
4.3.4Ethernet interface terminal (terminal X37)
You can connect an engineering PC to the Ethernet interface (terminal X37).
UFF41B
X35
342
1
Version
X36
S1
X37
1
1
XML4
2
2
X32X33
3
3
1
1
2
2
3
3
L1L2L3L5
plus
).
64420AXX
The Ethernet interface (X37) supports auto crossing auto negotiation for baud rate and
duplex mode. The IP parameters are defined depending on DIP switch S1 (see section
"DIP switches S1 default IP address").
In addition to the engineering access via terminal X37, there is another engineering
access via PROFIBUS (see section "Operation of MOVITOOLS
®
MotionStudio").
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
4.3.5Pin assignment X37 (Ethernet for engineering)
Use prefabricated, shielded RJ45 plug connectors compliant with IEC 11801 edition 2.0,
category 5.
Figure 1: Pin assignment of an RJ45 plug connector
A = Front view
B = View from back
[1] Pin 1 TX+ Transmit Plus
[2] Pin 2 TX- Transmit Minus
[3] Pin 3 RX+ Receive Plus
[6] Pin 6 RX- Receive Minus
Connecting UFF41B fieldbus gateway to Ethernet
To connect UFF41B to the Ethernet, connect the Ethernet interface X37 (RJ45 plug
connector) to the other network stations using a category 5, class D twisted-pair cable
in accordance with IEC 11801 edition 2.0. The interface supports auto crossing and high
auto negotiation for baud rate and duplex mode.
TIP
According to IEC 802.3, the maximum cable length for 10/100 MBaud Ethernet
(10BaseT / 100BaseT), e.g. between two network stations, is 100 m.
54174AXX
22
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
The LED L1 indicates the status of the CAN 1 system bus.
Status of the L1
LED
OrangeThe CAN 1 system bus is initialized.
GreenThe CAN 1 system bus is initialized.
Flashing green
(0.5 Hz)
Flashing green
(1 Hz)
RedThe CAN 1 system bus is off (BUS-
Flashing red
(1 Hz)
DiagnosticsRemedy
The CAN 1 system bus is currently in
SCOM suspend mode.
The CAN 1 system bus is currently in
SCOM On mode.
OFF).
Warning on the CAN 1 system bus.1. Check and correct the cabling of the
-
1. Check and correct the cabling of the
CAN 1 system bus.
2. Check and correct the baud rate set
for the CAN 1 system bus.
3. Check and correct the terminating
resistors of the CAN 1 system bus.
CAN 1 system bus.
2. Check and correct the baud rate set
for the CAN 1 system bus.
The LED L2 indicates the status of the CAN 2 system bus.
Status of the L2
LED
OrangeThe CAN 2 system bus is initialized.-
GreenThe CAN 2 system bus is initialized.-
Flashing green
(0.5 Hz)
Flashing green
(1 Hz)
RedThe CAN 2 system bus is off (BUS-
Flashing red
(1 Hz)
DiagnosticsRemedy
The CAN 2 system bus is currently in
SCOM suspend mode.
The CAN 2 system bus is currently in
SCOM On mode.
OFF).
Warning on the CAN 2 system bus.1. Check and correct the cabling of the
-
-
1. Check and correct the cabling of the
CAN 2 system bus.
2. Check and correct the baud rate set
for the CAN 2 system bus.
3. Check and correct the terminating
resistors of the CAN 2 system bus.
CAN 2 system bus.
2. Check and correct the baud rate set
for the CAN 2 system bus.
LED L3 (program
status)
LED L3 indicates the status of the gateway program.
Status of L3DiagnosticsRemedy
GreenGateway program is running.-
OffNo gateway program is loaded.Load a gateway program into the controller.
Flashing orange
(1 Hz)
Program has stopped.Bootloader update required (see section
"SD memory card type OMG4.B")
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
LED L4 indicates the firmware status of the fieldbus gateway.
Status of the L4 LED DiagnosticsRemedy
Flashing green
(1 Hz)
Red•No SD card plugged in.
Flashing orange
(1 Hz)
The firmware of the fieldbus gateway
is running properly.
•File system of the SC card corrupt
Program has stopped.Bootloader update required (see section
-
"SD memory card type OMG4.B")
LED L5 (user)LED L5 is lit up red if the gateway program has detected an error and if this error can
only be eliminated after diagnostics with MOVITOOLS
®
MotionStudio.
4.5DIP switch S1 default IP address
With DIP switch S1, you can set a default IP address for the Ethernet connection (X37).
The set IP address is applied in the next boot process.
S1 switch settingMeaning
TopIP p a r a m e t e r :
BottomThe IP parameters defined on the memory card of the UFF41B gateway are used.
•IP address: 192.168.10.4
•Subnet mask: 255.255.255.0
•Standard gateway: 1.0.0.0
The IP parameters for engineering interface X37 are entered in the file "...\System\NetConfig.cfg" in section "Ethernet 2". You can adjust the file using a text
editor (e.g. Notepad).
4.5.1TCP / IP addressing and subnetworks
IntroductionThe settings for the address of the IP protocol are made using the following parameters:
•MAC address
•IP address
•Subnet mask
•Standard gateway
The addressing mechanisms and subdivision of the IP networks into sub-networks are
explained in this chapter to help you set the parameters correctly.
MAC addressThe MAC address (Media Access Controller) is the basis for all address settings. The
MAC address is a worldwide unique 6-byte value (48 bits) assigned to the Ethernet
device. SEW Ethernet devices have the MAC address 00-0F-69-xx-xx-xx. The MAC
address is difficult to handle for larger networks. This is why freely assignable IP
addresses are used.
IP addressThe IP address is a 32 bit value that uniquely identifies a station in the network. An IP
address is represented by four decimal numbers separated by decimal points.
Example: 192.168.10.4
24
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
Each decimal number stands for one byte (= 8 bits) of the address and can also be
represented using binary code (see following table).
Byte 1Byte 2Byte 3Byte 4
11000000.10101000.00001010.00000100
The IP address comprises a network address and a station address (see following
table).
Network addressStation address
192.168.104
The part of the IP address that denotes the network and the part that identifies the
station is determined by the network class and the subnetwork mask.
Station addresses cannot consist of only zeros or ones (binary) because they represent
the network itself or a broadcast address.
Network classesThe first byte of the IP address determines the network class and as such represents
the division into network addresses and station addresses.
This rough division is not sufficient for a number of networks. They also use an explicit,
adjustable subnetwork mask.
A subnetwork mask is used to divide the network classes into even finer sections. The
subnetwork mask is represented by four decimal numbers separated by decimal points,
in the same way as the IP address.
Example: 255.255.255.128
Each decimal number stands for one byte (= 8 bits) of the subnetwork mask and can
also be represented using binary code (see following table).
Byte 1Byte 2Byte 3Byte 4
11111111.11111111.11111111.1 0000000
If you compare the IP addresses with the subnetwork masks, you see that in the binary
representation of the subnetwork mask all ones determine the network address and all
the zeros determine the station address (see following table).
Byte 1Byte 2Byte 3Byte 4
IP address
Subnet mask
decimal192.168..10.129
binary11000000.10101000.00001010.10000001
decimal255.255.255.128
binary11111111.11111111.11111111.10000000
The class C network with the address 192.168.10. is further subdivided into
255.255.255.128 using the subnetwork mask. Two networks are created with the
address 192.168.10.0 and 192.168.10.128.
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
Standard gatewayThe standard gateway is also addressed via a 32-bit address. The 32-bit address is rep-
Assembly and Installation Instructions
SD memory card type OMG4.B
The following station addresses are permitted in the two networks:
•192.168.10.1 - 192.168.10.126
•192.168.10.129 - 192.168.10.254
The network stations use a logical AND operation for the IP address and the subnetwork
mask to determine whether there is a communication partner in the same network or in
another network. If the communication partner is in a different network, the standard
gateway is addressed for passing on the data.
resented by four decimal numbers separated by decimal points.
Example: 192.168.10.1
The standard gateway establishes a connection to other networks. In this way, a network station that wants to address another station can use a logical AND operation with
the IP address and the subnetwork mask to decide whether the desired station is located
in the same network. If this is not the case, the station addresses the standard gateway
(router), which must be part of the actual network. The standard gateway then takes on
the job of transmitting the data packages.
4.6SD memory card type OMG4.B
The SD memory card type OMG4.B is required for operating the UFF41B fieldbus gate-
Bootloader
update
way and contains the firmware, the gateway program, and the gateway configuration.
With a MOVIAXIS
terization in case an axis needs to be replaced.
The SD memory card type OMG4.B is included in the scope of delivery of the UFF41B
fieldbus gateway.
Only use type OMG4.B memory cards in a UFF41B fieldbus gateway.
When the LEDs L3 and L4 flash orange at a 1 Hz frequency after power-on, a bootloader
update is required. Proceed as follows:
•Do not switch off the power supply during the entire process.
•Press the reset button T1 on the front of the UFF41B fieldbus gateway for 3 seconds.
When the bootloader update starts, only LED 4 is flashing.
•The bootloader update has been successful when L4 flashes green.
®
axis module, it is also used for data backup and automatic parame-
26
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
Connecting the UFF41B fieldbus gateway to a DeviceNet network
4.7Connecting the UFF41B fieldbus gateway to a DeviceNet network
The following sections describes the terminals, DIP switches, and LEDs relevant for
DeviceNet fieldbus operation.
4
Front view
UFF41B fieldbus
gateway
64775AXX
LED
Designation
DIP switch
Terminal
LEDLED 18
LED 17
LED 16
LED 15
LED 14
LED 13
LED 12
LED 11
Terminal X30D:
DeviceNet
(plug-in terminals)
X30D:1
X30D:2
X30D:3
X30D:4
X30D:5
DIP switch S2
S2To p
Switching between PROFIBUS
and DeviceNet
For operation via DeviceNet:
DIP switch
for setting
the MAC ID and the baud rate
Terminal X38:
CAN for safety-relevant
communication
0
2
1
2
2
2
3
2
4
2
5
2
6
2
7
2
X38:1
X38:2
X38:3
(plug-in terminals)
Mod/Net
Polled I/O
Bit-strobe I/O
BUSFAULT
-
-
VCAN_L
DRAIN
CAN_H
V+
Bottom
Function
LEDs 17 and 18 are reserved for PROFIBUS.
LED 18 is lit orange: UFF41B option is being
initialized
The two-color LEDs 13 to 16 indicate the current
status of the fieldbus interface and the DeviceNet
system.
Reserved
Reserved
0V24
CAN_L
DRAIN
CAN_H
24 V
Fieldbus interface PROFIBUS (X30P) active
Fieldbus interface DeviceNet (X30D) active
The DIP switches 20 - 25 are used to set the
MAC ID (Media Access Control Identifier). The
MAC ID represents the node address (address
range 0 - 63)
Baud rate setting
Baud rate setting
Reserved
Reserved
Reserved
4.7.1Pin assignment X30D (DeviceNet)
The assignment of connecting terminals is described in the DeviceNet specification
(Volume I, Appendix A).
DFD11B
UFF41B
1
2
3
4
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
5
X30D
The UFF41B option is opto-decoupled on the driver side in accordance with the
DeviceNet specification (Volume I, Chapter 9). This means the CAN bus driver must be
powered with 24 V voltage via the bus cable. The cable to be used is also described in
the DeviceNet specification (Volume I, Appendix B). The connection must be made
according to the color code specified in the following table.
Connecting the UFF41B fieldbus gateway to a DeviceNet network
Pin no. SignalMeaningColor coding
1V-0V24BK
2CAN_LCAN_LBU
3DRAINDRAINblank
4CAN_HCAN_HWH
5V+24 VRD
UFF41B and
DeviceNet
connection
According to the DeviceNet specification, a linear bus structure without or with very short
droplines is required.
The maximum permitted cable length depends on the baud rate setting:
Baud rateMaximum cable length
500 kBaud100 m
250 kBaud250 m
125 kBaud500 m
4.7.2Bus termination
In order to avoid disruptions in the bus system due to reflections, each DeviceNet segment must be terminated with 120 Ω bus terminating resistors at the first and last physical station. Connect the bus terminating resistor between connections 2 and 4 of the
bus plug.
4.7.3Setting the DIP switches
TIP
De-energize the UFF41B fieldbus gateway before you change the DIP switch settings.
The DIP switch settings are adopted during initialization only.
UFF41B
0
2
1
2
2
2
ON
3
2
4
2
5
2
6
2
7
2
64419AXX
20-25 = MAC ID setting
6-27
2
= Baud rate setting
Setting the MAC IDThe MAC ID (Media Access Control Identifier) is set on the UFF41B option using DIP
switches 2
0
- 25 in a binary coded manner. The MAC ID represents the node address
of the UFF41B. The UFF41B supports the address range 0 - 63.
28
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
Connecting the UFF41B fieldbus gateway to a DeviceNet network
4
Setting the baud
rate
The baud rate is set using DIP switches 26 and 27.
DIP switch
6
2
00125 kBaud
10250 kBaud
01500 kBaud
11Invalid
7
2
Baud rate
A maximum of 64 DeviceNet data words can be exchanged between the DeviceNet
module and the UFF41B option. The number is set using the DeviceNet scanner.
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
Connecting the UFF41B fieldbus gateway to a DeviceNet network
4.7.4Status LED in DeviceNet operation
The UFF41B fieldbus gateway has four two-color LEDs for diagnostic of the DeviceNet
system; they indicate the current status of the UFF41B and the DeviceNet system. The
unit status corresponding to the status of the LED is described in chapter "Error
diagnostics".
DesignationAbbreviationComplete LED designation
L16MOD/NETModule/Network status
L15PIOPolled I/O
L14BIOBit-strobe IO
L13BUS FAULTBUS FAULT
LED
LED L16
(Mod/Net)
The function of the L16 LED (Mod/Net = Module/Network Status) described in the
following table is specified in the DeviceNet specification.
Status of the
L16 LED
OffNot switched on/offline•Unit is offline
Flashing green
(1 s cycle)
Lights up green Online, operational mode
Flashing red
(1 s cycle)
Red lightCritical fault or critical link
StatusMeaning
•Unit performs DUP MAC check
•Unit is switched off
Online and in operational
mode
and connected
Minor fault or connection
timeout
failure
•The unit is online and no connection has been
established
•DUP-MAC check performed successfully
•A connection has not yet been established with a
master
•Missing, incorrect or incomplete configuration
•Online
•Connection to a master has been established
•Connection is active (established state)
•A correctable fault has occurred
•Polled I/O and/or bit strobe I/O connections are in the
timeout status
•DUP-MAC check has detected an error
•A correctable fault has occurred
•BusOff
•DUP-MAC check has detected an error
L15 LED (PIO)The L15 (Polled I/O) LED monitors the polled I/O connection.
Status of the
L15 LED
Flashing green
(125 ms cycle)
OffNot switched on / offline
Flashing green
(1 s cycle)
Lights up green Online, operational mode
Flashing red
(1 s cycle)
Red lightCritical fault or critical link
30
StatusMeaning
DUP-MAC checkUnit is performing DUP-MAC check
but not DUP-MAC check
Online and in operational
mode
and connected
Minor fault or connection
timeout
failure
•Unit is offline
•Unit is switched off
•Unit is online
•DUP-MAC check performed successfully
•A polled IO connection is being established with a
master (configuring state)
•Missing, incorrect or incomplete configuration
•Online
•A polled I/O connection has been established
(established state)
•Invalid baud rate set via DIP switches
•A correctable fault has occurred
•Polled I/O connection is in timeout status
•A fault that cannot be remedied has occurred
•BusOff
•DUP-MAC check has detected an error
Manual – Fieldbus Gateway UFF41B DeviceNet and PROFIBUS DP
Loading...
+ 127 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.