Thermostat TC-5242 |
2 |
|
|
|
|
Specifications |
|
|
|
Type |
Low limit, single pole thermostat |
Adjusting |
Screwdriver slot, adjusting knob on differential or range screw when required. |
Contact Action |
Open on rise, close on rise, SPDT, as required. |
Electrical Contacts |
Two single pole circuit. Main circuit opens on temperature fall and simultane- |
|
ously the auxiliary or alarm contacts close. |
Contact Unit |
Snap-acting high contact force right up to contact break point, no bounce, |
|
Beryllium copper conductor leaves with Silver-Cadmium Oxide contacts. |
Contact Ratings |
Main circuit contacts 16.0 Amps @ 120 vac, 600 V Max. |
|
Auxiliary circuit contacts 6.0 Amps @ 120 vac, 600 V Max. |
Temperature Range |
Adjustable range of 15° F to 55° F ( -9° C to 13° C).Low limit stop factory set |
|
and sealed at 35° F (2° C). |
Max Overrun Temp |
400° F (204° C). |
on Bulb |
|
Finish |
Gray baked enamel. |
Case Material |
0.062” (1.6 mm) cold rolled steel. |
Cover Material |
0.028” (0.7mm) cold rolled steel. |
Element |
20 Feet of 1/8 O.D. Tubing responds to lowest temperature along any one |
|
foot portion. |
Differential |
Lockout type, requires manual reset after cutout. |
Mounting |
May be mounted in any position, two mounting holes provided in back of the |
|
case (mounting bracket included). |
Shipping Weight |
2.5 lb (1.1 kg) with knob |
Dimensions |
4” L x 3-1/4” H x 2” D ( 1016 mm L x 826 mm H x 508 mm D) |
Notice: This product contains toluene, safely sealed inside of bulb. Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control containing toulene in a sealed tube.
<![if ! IE]><![endif]>© 2010 Schneider Electric. All rights reserved.
Schneider Electric
F-27615-2 |
August 2010 ao |