Schneider Electric MNL-50 Series Data Sheet

Page 1
Page 2
TAC I/A Series
MNL-50 Series Controllers
2
Specifications continued from first page.
Current Ratings
Universal Input
1K ohm Balco Input
-40 to 250 °F (-40 to 121°C) range. TSMN-81011, TS-8000 Series or equivalent.
1K ohm Platinum Input
-40 to 240 °F (-40 to 116 °C) range. TSMN-58011, TS-5800 Series or equivalent.
1k Resistance
0 to 1.5kohms.
10K ohm Thermistor w/ 11K ohm Shunt Resistor
-40 to 250°F (-40 to 121°C) range. TSMN-57011­850, TS-5700-850 Series or equivalent.
10k Resistance
0 to 10.5kohms.
Voltage
0 to 5Vdc.
Current
0 to 20mA requires an external 250ohm shunt resistor.
Digital Input
Dry Contact. Detection of closed switch requires less than 300ohms. Detection of open switch requires more than 1.5Kohms.
FEATURES
• Designed for new or existing system installations, the MN50 controllers provide control for: unit ventilators; heat pumps; fan coils; and packaged rooftops.
• Conforms to the LonMark guidelines.
• HVAC interoperability achieved through use of LonMark HVAC profiles.
• A complete, custom application can be designed for each controller, using WorkPlace Tech Tool.
• Controllers are field programmable, using WorkPlace Tech Tool, but controllers with satellite profiles are especially suited for a broad range of applications, providing solutions for your building control needs.
• Capability to function in standalone mode or as part of a communications network.
• Multiple controllers on a LonWorks FTT network create a complex network of controllers for virtually any building control need.
• Proportional (P), Proportional Plus Integral (PI), and Proportional Plus Integral and Derivative (PID) control for cooling and heating.
• Onboard LED indication without cover removal.
• Plenum-rated enclosure allows direct mounting in plenum.
LonWorks TP/FT-10 Free Topology
COMMUNICATIONS
Lon Works Networks
A LonWorks communications network uses a TP/FT-10 Free Topology configuration. Controllers on a
LonWorks network can communicate with each other in a peer-to-peer fashion. A LonWorks network has a communications speed of 78kbps, using unshielded, twisted-pair cabling, with connections that are not polarity sensitive.
S-Link
The Sensor Link (S-Link) communications wiring provides power and a communication interface for an MN-Sx TAC I/A Series MicroNet sensor. The various MN-Sx sensors can provide room temperature, room humidity, setpoint adjustment, and occupancy override. This connection uses two-wire, unshielded cable and is not polarity sensitive. Maximum wire length allowed between a controller and a TAC I/A Series MicroNet Sensor is 200ft (61m).
Schneider Electric
F-26616-6 Octobe r 2013 tl
© 2013 Schneider Electric. All rights reserve d.
Page 3
TAC I/A Series
MNL-50 Series Controllers
INPUTS FROM MN-SX I/A SERIES MICRONET SENSORS
Inputs Description MN-Sx Sensor
Space Temperature 32 to 122 °F (0 to 50 °C)
Space Humidity 5 to 95% RH, Non-condensing MN-S1HT, MN-S2HT, MN-S3HT, MN-S4HT, MN-S4HT-FCS, and
Adjustable Setpoint 40 to 95 °F (4 to 35°C) MN-S3, MN-S3HT, MN-S4, MN-S4HT, MN-S4-FCS,
Override Pushbutton For standalone occupancy control or remote
status monitoring of local status condition.
Fan Operation and Speed Fan mode selection: On, Speed (Low/Medium/
High), or Auto.
System Mode System mode selection: Heat, Cool, Off, or
Auto.
Emergency Heat Emergency heat mode selection: Enable or
Disable
MN-S1, MN-S1HT, MN-S2, MN-S2HT, MN-S3, MN-S3HT, MN-S4, MN-S4HT, MN-S4-FCS, MN-S4HT-FCS, MN-S5 and MN-S5HT
MN-S5HT
MN-S4HT-FCS, MN-S5, and MN-S5HT
MN-S2, MN-S2HT, MN-S3, MN-S3HT, MN-S4, MN-S4HT, MN-S5, and MN-S5HT
MN-S4, MN-S4HT, MN-S4-FCS, MN-S4HT-FCS, MN-S5, and MN-S5HT
MN-S4, MN-S4HT, MN-S5, and MN-S5HT
MN-S5 and MN-S5HT
MODELS
Part Number Description Inputs/Outputs Profiles
MNL-5Rxx
a
TAC I/A Series MicroNet 50Series controller
1 Digital Input (DI)
1 Universal Input (UI)
3 Digital Outputs (DO)
Heat Pump Fan Coil Packaged Rooftop Satellite
3
a
“xx” denotes
LonMark profile and profile version (F=Fan Coil, H=Heat Pump, R=Rooftop, S=Satellite). Satellite profile is based on Rooftop profile.
Schneider Electric
F-26616-6 Octobe r 2013 tl
© 2013 Schneider Electric. All rights reserve d.
Page 4