Schneider Electric MicroLogic User Manual

MicroLogic™ 5 and 6 Electronic Trip
r c i Mcigolo
E 2
.5
r I
%
A
03
>
0
3
>
0
11
>
.
9
2 9 .
3 9 .
4 9 .
5 9 .
1
89
.
7 9 .
6
9 .
Ir
)
o Ix(
5.
1
2
5.
2
3
4
0
1
8
6
5
d
s
I
)
r
I x (
Units—User Guide
Unidades de disparo electrónico MicroLogic™ 5 y 6—Guía de usuario
MC
Déclencheurs électroniques MicroLogic
5
et 6—Guide de l’utilisateur
48940-312-01 Rev. 05, 01/2020
Retain for future use. / Conservar para uso futuro. / À conserver pour usage ultérieur.
MicroLogic™ 5 and 6 Electronic Trip Units—
r c i Mcigolo
E 2
.5
r
I
%
A
03
>
0
3
>
0
11
>
.
9
2
9
.
3
9
.
4 9 .
5 9 .
1
89
.
7 9 .
69
.
Ir
)
o Ix(
5.
1
2
5.
2
3
4
0
1
8
6
5
d
s
I
)
r
I x (
User Guide
for PowerPact™ H-, J-, and L-Frame Circuit Breakers Instruction Bulletin
48940-312-01 Rev. 05, 01/2020
Retain for future use.
ENGLISH
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
DANGER
WARNING
CAUTION
NOTICE
Hazard Categories and Special Symbols
ENGLISH
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
ANSI
IEC
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, can result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, can result in minor or moderate injury.
NOTICE is used to address practices not related to physical injury. The safety alert symbol is not used with this signal word.
Please Note
FCC Notice
2-EN
NOTE: Provides additional information to clarify or simplify a procedure.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. This Class A digital apparatus complies with Canadian ICES-003.
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Table of Contents MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
Table of Contents
SECTION 1:GENERAL INFORMATION ........................................................................................................ 7
Introduction ...................................................................................................... 7
In Rating ........................................................................................................... 8
Control Power .................................................................................................. 9
Backlighting ...................................................................................................... 9
Trip Unit Installation ......................................................................................... 9
Trip Unit Sealing ............................................................................................ 10
MicroLogic Trip Unit Layout ........................................................................... 11
Trip Unit Face .......................................................................................... 11
Navigation Principles ..................................................................................... 13
Lock/Unlock the Settings ......................................................................... 13
Trip Unit Modes ....................................................................................... 13
Mode Selection ........................................................................................ 14
Readout Mode ............................................................................................... 14
ENGLISH
Energy Meter Readout (MicroLogic E) ........................................................... 19
Protection Function Readout ................................................................... 22
Neutral Status Readout Mode ................................................................. 22
Setting Mode .................................................................................................. 23
Setting Using a Dial ................................................................................. 23
Setting Using the Keypad ........................................................................ 23
Presetting a Protection Function .............................................................. 27
Setting a Protection Function ................................................................... 28
SECTION 2:ELECTRICAL DISTRIBUTION PROTECTION .................................................................. 29
Protection Functions ...................................................................................... 29
Setting the Protection .............................................................................. 29
Reflex Tripping ......................................................................................... 29
Selective Coordination ................................................................................... 30
Mission Critical Circuit Breakers .................................................................... 30
Long-Time Protection ..................................................................................... 31
Setting the Long-Time Protection ............................................................ 31
Ir Pickup Setting Values ........................................................................... 31
tr Time Delay Setting Values ................................................................... 32
Thermal Image ......................................................................................... 32
Conductor Heat Rise and Tripping Curves .............................................. 33
Thermal Memory ...................................................................................... 33
Short-Time Protection .................................................................................... 33
Setting the Short-Time Protection ............................................................ 34
Isd Pickup Setting Values ........................................................................ 34
tsd Time Delay Setting Values ................................................................. 34
I2t ON/OFF .............................................................................................. 34
Instantaneous Protection ............................................................................... 35
Setting the Instantaneous Protection ....................................................... 35
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
3-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Table of Contents
Ii Pickup Setting Values ........................................................................... 36
ENGLISH
Ground-Fault Protection ................................................................................. 36
Setting the Ground-Fault Protection ........................................................ 36
Ig Pickup Setting Values .......................................................................... 37
tg Time Delay Setting Values ................................................................... 37
I2t ON/OFF Function ............................................................................... 37
Ground-Fault Protection Test ................................................................... 37
Neutral Protection .......................................................................................... 38
Operation ................................................................................................. 38
Setting the Neutral Protection .................................................................. 39
Neutral Protection Setting Value .............................................................. 39
Selection of the ENCT Option .................................................................. 39
Zone Selective Interlocking (ZSI) ................................................................... 41
Example of ZSI Operation ....................................................................... 41
ZSI Wiring ................................................................................................ 41
ZSI Connection ........................................................................................ 42
Testing the ZSI ........................................................................................ 43
SECTION 3:METERING FUNCTION .......................................................................................................... 44
Real-Time Measurements .............................................................................. 44
Instantaneous Values .............................................................................. 44
Measuring the Neutral Current ................................................................. 44
Measuring the Phase-to-Neutral Voltages ............................................... 44
Calculating the Average Current and Average Voltage ........................... 45
Measuring the Current and Voltage Phase Unbalances .......................... 45
Maximum/Minimum Values ...................................................................... 46
Resetting Maximum/Minimum Values ...................................................... 46
Calculating Demand Values (MicroLogic E) .................................................. 47
Demand Value Models ............................................................................ 47
Metering Window ..................................................................................... 47
Fixed Metering Window .......................................................................... 47
Sliding Metering Window ......................................................................... 48
Synchronized Metering Window .............................................................. 48
Quadratic Demand Value (Thermal Image) ............................................. 48
Arithmetic Demand Value ........................................................................ 48
Peak Demand Value ................................................................................ 48
Resetting Peak Demand Values .............................................................. 49
Power Metering (MicroLogic E) ...................................................................... 49
Principle of Power Metering ..................................................................... 49
Calculation Based on Neutral Conductor ................................................. 50
Distributed Neutral ................................................................................... 50
Power Sign and Operating Quadrant ....................................................... 51
Power Supply ........................................................................................... 51
Power Calculation Algorithm .................................................................... 51
Energy Metering (MicroLogic E) .................................................................... 53
Principle of Energy Calculation ................................................................ 53
Partial Energy Meters .............................................................................. 53
Energy Meters ......................................................................................... 54
Selecting Energy Calculation ................................................................... 54
Resetting Energy Meters ......................................................................... 54
4-EN
Harmonic Currents ......................................................................................... 55
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Table of Contents MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
Origin and Effects of Harmonics .............................................................. 55
Definition of a Harmonic .......................................................................... 55
RMS Currents and Voltages .................................................................... 56
Acceptable Harmonic Levels ................................................................... 56
Metering Energy Quality Indicators (MicroLogic E) ........................................ 58
Current THD ............................................................................................ 58
Voltage THD ............................................................................................ 59
Distortion Power D ................................................................................... 59
Power Factor PF and Cos φ Measurement (MicroLogic E) ........................... 60
Power Factor PF ...................................................................................... 60
Cos φ ....................................................................................................... 60
Power Factor PF and Cos φ When
Harmonic Currents are Present ............................................................... 60
Sign for the Power Factor PF and Cos φ ................................................. 61
Managing the Power Factor PF and Cos φ:
Minimum and Maximum Values ......................................................................62
Monitoring the Cos φ and Power Factor PF Indicators ............................ 62
Selecting the Sign Convention for the
Cos φ and Power Factor PF .................................................................... 63
Measurements ............................................................................................... 63
Accuracy .................................................................................................. 63
Real-Time Measurements .............................................................................. 64
SECTION 4:ALARMS .......................................................................................................... 68
Alarms Associated with Measurements ......................................................... 68
Alarm Setup ............................................................................................. 68
Alarm Priority Level .................................................................................. 68
Alarm Activation Conditions ..................................................................... 69
Overvalue Condition ................................................................................ 69
Undervalue Condition .............................................................................. 69
Equality Condition .................................................................................... 70
Management of Time Delays (Overvalue or Undervalue Conditions) ..... 70
ENGLISH
Alarms on a Trip, Failure, and Maintenance Event ........................................ 71
Alarm Setup ............................................................................................. 71
Alarm Priority Level .................................................................................. 71
Tables of Alarms ............................................................................................ 72
Operation of SDx Module Outputs Assigned to Alarms ................................. 75
SDx Module Output Operating Modes ..................................................... 75
Acknowledgment of Latching Mode ......................................................... 76
SECTION 5:REMOTE SETTING UTILITY (RSU) SOFTWARE ............................................................ 78
Function Setting ............................................................................................. 78
Using the RSU Software .......................................................................... 78
User Profiles ............................................................................................ 79
Offline Mode ............................................................................................ 79
Online Mode ............................................................................................ 79
Software Configuration Tabs ................................................................... 80
Saving and Printing .................................................................................. 81
Protection Functions ...................................................................................... 81
Setting the Protection Functions .............................................................. 81
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
5-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Table of Contents
Presetting the Protection Functions by a Dial .......................................... 81
ENGLISH
Metering Setup ............................................................................................... 82
Alarm Setup ................................................................................................... 84
Setting the SDx Module Output Functions ..................................................... 85
SECTION 6:MICROLOGIC TRIP UNIT INDICATORS ............................................................................ 87
LED Indication ................................................................................................ 87
Local Indicator ......................................................................................... 87
Operation of the Ready LED .................................................................... 87
Operation of Pre-Alarm and Alarm LEDs
(Electrical Distribution Protection) ............................................................ 88
Indication on the MicroLogic Display ............................................................. 88
Stacking Screens ..................................................................................... 88
Indication Screens Cause and Response ...................................................... 89
Values According to IEC Convention ....................................................... 91
Setting the Cos φ Alarms According to IEEE Convention ....................... 92
Setting the SDx Outputs .......................................................................... 93
Acknowledging the Out1 Screen ............................................................. 93
SECTION 7:THE COMMUNICATION NETWORK .................................................................................... 94
Circuit Breaker Communication ..................................................................... 94
Remote Readout of the Circuit Breaker Status ........................................ 94
Remote Readout of the Measurements ................................................... 94
Remote Readout of the Operating Assistance Information ...................... 94
Circuit Breaker Remote Control ............................................................... 95
History and Time-Stamped Information ......................................................... 95
History ...................................................................................................... 95
Time-Stamped Information ...................................................................... 95
Maintenance Indicators .................................................................................. 95
BSCM Counters ....................................................................................... 95
MicroLogic Trip Unit Counters ................................................................. 95
6-EN
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Section 1—General Information MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
200
175
125
150
100
80
70
250
225
8
6
4
5
3 2
1.5
12
10
Ii
45
40
30
35
25 20
15
60
50
10
8
4
6
3
1.5
15
12
Ii (x In)
2
5.3 A
Micrologic
Ir tr Isd tsd Ii(xIn)
Ii (x In)
225
125
2
3
4
6
5
8 10
12
150
175
200
250
300 350
400
1.5
Ir (A)
Section 1— General Information
Introduction
MicroLogic 5 and 6 electronic trip units provide:
Adjustable tripping functions on electronic trip circuit breakers
Protection for the electrical distribution system or specific applications
Metering of instantaneous and demand values
Kilowatt-hour metering
Operating information (such as peak demand values, customized alarms, or operation counters)
Communication
ENGLISH
MicroLogic 5.2 A trip unit
Front faces of MicroLogic trip unit
The product name specifies the protection provided by the trip unit.
MicroLogic 6.2 A-W
Type of Protection
0—Molded case switch (L-frame circuit breaker only) 1—Magnetic only motor circuit protection (L-frame circuit breaker only) 2—Standard motor circuit protection 3—Standard UL protection (LI or LSI), no display 5—Selective protection (LSI), with display 6—Selective protection plus ground-fault protection for equipment (LSIG), with display
Frame Size
2—150/250 A 3—400/600 A
Type of Measurement
A—Provides protection plus ammeter measurements E—Provides protection plus energy measurements S—Provides LSI protection with fixed long time delay and fixed short time delay W—Mission Critical (Selective)
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
7-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Section 1—General Information
I
s
d(
x
I
r)
8
6
2
3
4
5
7
1
01 .
5
Micrologic
5.2E
A
I
r tr
I
sd ts
d
l
i
(x
l
n
)
N
1
/
A
2
/
B
3
/
C
OK
M
ode
30
Ready
>
1
5
A
Alarm
%
I
r
>9
0
>
1
0
5
36
2
8
1
8
2
0
2
3
2
5
3
2
4
0
I
r
(
A
)
Mic
I
s
d(
x
1
.
5
0
1
2
3
4
5
9
8
7
6
0
1
2
3
4
5
9
8
7
6
3.
2
Micr
o
lo
g
ic
5.1
2
5 .2
3
4
0 1
8
6
5
.9
2 9 .
3 9 .
4
9 .
5 9 .
1
89
.
7 9 .
69
.
0 0
1
0 1 1
5 2 1
0
4 1
0 6 1
0 5
2
52
2
0 02
5 7
1
I
r
d s
I
dsI
) r
I x (
I
r
) o I
x(
o
I
) A
(
r I
%
A
0 3 >
0
3>
0
1 1 >
In=250A
MicroLogic trip units can be configured to communicate with other devices. For
ENGLISH
information on the UTA Tester and Modbus™ Interface Module (IFM), see the product catalog and the circuit breaker user guide.
Modbus™ Interface Module (IFM)
UTA Tester
Front Display Module (FDM121)
PowerPact™ H-frame circuit breaker equipped with a MicroLogic trip unit, BSCM, and NSX Cord
For complete information on available circuit breaker models, frame sizes, interrupting ratings, and trip units, see the product catalog.
This manual describes operation of the MicroLogic 5 and 6 trip units.
In Rating
For additional information see the following user guides available on the Schneider Electric™ website:
Bulletin 48940-310-01: MicroLogic™ 1, 2, and 3 Electronic Trip Units—User
Guide.
Bulletin DOCA0088EN: FDM121—Display for LV Circuit Breaker —User Guide
Bulletin DOCA0037EN: FDM128—Display For 8 LV Devices—User Guide
To access the website go to:
http://www.schneider-electric.com
For application assistance, please call 1-888-778-2733.
The trip unit In value (A) is visible on the front face of the circuit breaker when the trip unit is installed. The trip unit In rating (in amperes) is the trip unit maximum value.
A
For MCP versions, the Full Load Amp (FLA) range is displayed
Example:
250 A trip unit
Sensor rating I
8-EN
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
= 250 A
n
Section 1—General Information MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
Control Power
The current through the circuit breaker provides power to operate the MicroLogic trip unit, maintaining protection if the trip unit is not externally powered.
Backlighting
An optional external 24 Vdc power supply for the MicroLogic trip unit is available for:
Modifying the setting values when the circuit breaker is open
Displaying measurements when the circuit breaker is closed but current through the circuit breaker is low (15–50 A depending on the rating
Continuing to display the reason for the trip and the breaking current when the circuit breaker is open
Without the optional external 24 Vdc power supply, the MicroLogic trip unit only functions when the circuit breaker is closed. When the circuit breaker is open or the current through the circuit breaker is low, the MicroLogic trip unit has no power and the display switches off.
The external 24 Vdc power supply is available to the trip unit when it is connected to another module in the ULP system (Modbus Interface Module (IFM), Front Display Module (FDM121), or UTA Tester).
When the MicroLogic trip unit is not connected to a ULP module, it can be connected directly to an external 24 Vdc power supply using the optional 24 Vdc supply terminal block.
When the MicroLogic trip unit is powered by an external 24 Vdc power supply, the trip unit display has white backlighting that is:
ENGLISH
Trip Unit Installation
Low intensity continuously
High intensity for 1 minute after pressing one of the keypad buttons
The display backlighting is:
Deactivated if the temperature exceeds 149°F (65°C)
Reactivated once the temperature drops back below 140°F (60°C)
On trip units powered by the pocket tester, the display unit is not backlit.
The trip unit is designed for ease of field installation and replacement (for circuit breakers which offer this capability):
No connections to make
Installable with a standard Torx T25 driver
A mechanical cap ensures trip unit compatibility
Torque limiting screws ensure secure mounting
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
9-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Section 1—General Information
ENGLISH
For installation information, see the instruction bulletin shipped with the Field­Installable Trip Unit (FITU).
NOTE: After installation, the screw heads are accessible so the trip unit can be removed if necessary.
Trip Unit Sealing
The transparent cover on MicroLogic trip units is sealable.
A sealed cover prevents modification of the protection settings.
A sealed cover prevents access to the test port.
The protection settings and measurements can still be read on the keypad.
10-EN
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Section 1—General Information MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
Ii (x In)
35
15
2
3
4
8
6
10 12
15
20
25
30 40
45 50
60
1.5
225
200
175
5
4 3 2
1.5
6
8 10
12
250
Ir (A)
125
150
100
80
70
Ii (x In)
Micrologic
5.2 A
MicroLogic Trip Unit Layout
Trip Unit Face
Use the display screen and keypad on the trip unit to set the trip unit options and check system measurements. See “Navigation Principles” on page 13 for more information.
ENGLISH
A
B
C
D
E
A. Indication LEDs: shows the trip unit operational state
vary in meaning depending on the trip unit type.
1. Ready LED (green): Blinks slowly when the electronic trip unit is ready to provide protection.
2. Overload pre-alarm LED (orange): Lights when the load exceeds 90% of the I
3. Overload alarm LED (red): Lights when the load exceeds 105% of the I
1
2
3
B. Test Port
Use the test port for:
— connecting a pocket tester for local testing of the MicroLogic trip unit — connecting the UTA tester for testing, setting the MicroLogic trip unit, and
for installation diagnostics.
C. Dials and Microswitch
A. Indication LEDs B. Test port C. Dials for presetting protection
functions and microswitch for locking
protection setting D. LCD display E. Navigation keypad
setting.
r
setting.
r
A
B
A. Pickup (Ir) preset dial (distribution trip unit only)
Sets the maximum continuous current level of the circuit breaker. If current exceeds this value, circuit breaker trips after the preset time delay.
B. Instantaneous (I
) preset dial (distribution trip unit only)
i
Sets the instantaneous trip pickup value setting for the phases and for the neutral (trip unit with ENCT option and neutral protection active).
C. Microswitch to lock/unlock the protection settings
C
The trip unit face has two dials for presetting protection functions and a microswitch for locking/unlocking the protection settings. For distribution trip units, the dials are for setting long-time and instantaneous protection.
Long-time protection:
protects equipment against overloads
is standard on distribution trip units
uses true rms measurement
Instantaneous protection:
protects equipment against fault currents
is standard on distribution trip units
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
11-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Section 1—General Information
OK
has pickup value setting for the phases and for the neutral (trip unit with ENCT
ENGLISH
option and neutral protection active)
uses true rms measurement
Trip units are shipped with the long-time pickup switch set at the maximum setting and all other trip unit switches set at their lowest settings. All advanced protection settings are turned “off.”
D. LCD display
1. Five pictograms: Metering, Readout, Protection, Setting, Lock. How pictograms are combined defines the mode
2. Up arrow points to protection function currently being set
3. List of protection functions according to the MicroLogic trip unit type
4. Value of the measured quantity
5. Unit of the measured quantity
6. Navigation arrows
7. Down arrow(s) point to the selected phase(s), neutral, or the ground
8. Phases (1/A, 2/B, 3/C), neutral (N) and ground
An LCD display provides information necessary to use the trip unit. The list of protection functions varies according to the MicroLogic trip unit type.
On MicroLogic trip units powered by an external 24 Vdc power supply, the trip unit display has white backlighting that is:
low intensity continuously
high intensity for 1 minute after pressing any of the keys on the keypad
deactivated if the temperature exceeds 149°F (65°C)
reactivated once the temperature drops back below 140°F (60°C)
NOTE: On trip units powered by the pocket tester, the display unit is not backlit.
E. Navigation keypad Use the 5-button keypad for navigation.
Button Description
Mode
Mode: Selecting the mode
Scroll: Scrolling navigation
Back: Navigation back (metering) or - (setting the protection functions)
Forward: Navigation forward (metering) or + (setting the protection functions)
OK: Confirmation
Screensaver The screensaver displays the instantaneous current passing through the most
heavily loaded phase (Instantaneous measurement readout mode).
The MicroLogic display automatically reverts to a screensaver:
12-EN
In padlock locked mode, 20 seconds after the last action on the keypad
In padlock unlocked mode, 5 minutes after the last action on the keypad or dials
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Section 1—General Information MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
Navigation Principles
Lock/Unlock the Settings
Table 1 – Protection Settings
Display Description
Padlock locked. The protection settings are locked.
Padlock unlocked. The protection settings are unlocked.
The protection settings are locked when the transparent cover is closed and sealed to prevent access to the adjustment dials and the locking/unlocking microswitch.
A pictogram on the display indicates whether the protection settings are locked:
To unlock the protection settings:
1. Open the transparent cover
2. Press the lock/unlock microswitch or turn either adjustment dial
To lock the protection settings, press the lock/unlock microswitch again.
The protection settings also lock automatically five minutes after pressing a button on the keypad or turning one of the dials on the MicroLogic trip unit.
ENGLISH
Trip Unit Modes
Information displays on the MicroLogic trip unit are based on its mode. The modes available depend on:
Whether the settings are locked
The trip unit version
A combination of pictograms define the mode:
Metering
Readout
Protection
Setting
Lock
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
13-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Section 1—General Information
Table 2 – Possible Modes
ENGLISH
Pictograms Mode Accessible
Instantaneous measurement readout
or
Kilowatt hour meter readout and reset
Mode Selection
Readout Mode
Max Reset? OK
or
Max Reset? OK
Select mode by successive presses on the button:
Peak demand readout and reset
Protection function readout
Protection function setting
Neutral status readout
Neutral status setting
Mode
The modes scroll cyclically.
Press the lock/unlock microswitch to switch between readout mode and setting mode.
NOTE: When the Readout icon is visible, protection settings cannot be altered.
Press the button successively to scroll through the metering screens.
Mode
Scrolling is cyclical.
14-EN
Use the , and navigation buttons to select the metering screen for each of the phases:
The down indication arrow indicates the phase relating to the measurement value displayed.
N 1/A 2/B 3/
Indicating arrows on two phases indicates that phase-to-phase value is being measured:
N 1/A 2/B 3/
Indicating arrows on three phases indicates total power is being measured:
N 1/A 2/B 3/
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Section 1—General Information MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
Figure 1 – Readout Screen
Up arrow indicates function being measured.
Ir tr Isd tsd Ii (x
A
200
N 1/A 2/B 3/
Possible to press
button
the
Possible to press
button
the
ENGLISH
Use to select measurement readout mode
Use to select phase screen is measuring
Down arrow indicates phase being measured.
Use to select measurement to display
Table 3 – Metering Screens
Trip Unit Mode Order Screen Description Unit Arrows
MicroLogic A (Ammeter)
or
Max Reset? OK
or
Max Reset? OK
Readout as instantaneous rms value of the:
1
Three phase currents I
2 Ground-fault current (MicroLogic 6) % I 3 Neutral current IN (with ENCT option) A
Readout and resetting of the:
4
Maximum I
currents
Maximum ground-fault current
5
6
(MicroLogic 6 trip unit)
Maximum I
(with ENCT option)
i max
max for the neutral current
N
, IB, and IC A
A
for the three phase
The down arrow indicates the conductor (phase, neutral, or ground) corresponding to the value shown.
g
N 1/A 2/B 3/
The down arrow indicates the conductor
A
(phase, neutral, or ground) corresponding to the value shown.
% I
g
N 1/A 2/B 3/
A
Continued on next page
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
15-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Section 1—General Information
Table 3 – Metering Screens (continued)
ENGLISH
Trip Unit Mode Order Screen Description Unit Arrows
MicroLogic E (Energy)
or
Max Reset? OK
or
Max Reset? OK
Readout as instantaneous rms value of the:
1
Three phase currents A, B, and C A
Ground-fault current (MicroLogic 6 trip
2
unit)
3 Neutral current IN (with ENCT option) A
Readout as instantaneous rms value of the:
Phase-to-phase voltages V
4
VCA
Phase-to-neutral voltages V
, VBC, and
AB
, VBN,
AN
and VCN (with ENVT option)
5 Readout of the total active power P
Readout of the total apparent power S
6
the three phase conductors.
7 Readout of the total reactive power Q
Readout and resetting of the active energy
8
meter E
Readout and resetting of the apparent
9
energy meter E
Readout and resetting of the reactive
10
energy meter E
p
s
q
kW
tot
in
tot
kvar
tot
The down arrow indicates the conductor (phase, neutral, or ground) corresponding to the value shown.
% I
g
N 1/A 2/B 3/
The down arrow indicates the conductor (phase, neutral, or ground) corresponding
V
to the value shown.
N 1/A 2/B 3/
kVA
kWh,
MWh kVAh, MVAh kvarh, Mvarh
or
Max Reset? OK
or
Max Reset? OK
11 Readout of the phase rotation
Readout and resetting of the:
12
Maximum I
Maximum ground-fault current
13
14
(MicroLogic 6 trip unit)
Maximum I
(with ENCT option)
for the 3 phase currents
i max
for the neutral current
N max
% I
Readout and resetting of the:
Maximum V
15
Maximum V
phase voltages
for the three phase-to-
ij max
for the three phase-
iN max
to-neutral voltages (with ENVT option)
Readout and resetting of the maximum
16
P
of the active power
max
Readout and resetting of the maximum
17
S
of the apparent power kVA
max
Readout and resetting of the maximum
18
of the reactive power kvar
Q
max
kW
kVA
kvar
A
The down arrow indicates the conductor (phase, neutral, or ground) corresponding to the value shown.
g
N 1/A 2/B 3/
A
The down arrows indicate the phases between which the maximum V
V
N was measured.
N 1/A 2/B 3/
The down arrows indicate the three phase conductors.
N 1/A 2/B 3/
Continued on next page
L-L or L-
max
16-EN
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Section 1—General Information MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
Table 3 – Metering Screens (continued)
Trip Unit Mode Order Screen Description Unit Arrows
MicroLogic 5 LSI: Protection Function Readout Screens
I
—Long-time protection pickup value for
r
1
the phases
)—Long-time protection pickup value
I
r(IN
for the neutral (trip unit with ENCT option
2
and neutral protection active)
—Long-time protection time delay value
t
r
4
5
6
)
(at 6 I
r
—Short-time protection pickup value for
I
sd
the phases
) —Short-time protection pickup value
I
sd(IN
for the neutral (trip unit with ENCT option and neutral protection active)
—Short-time protection time delay value
t
sd
The time delay is for the I2t inverse time curve protection:
7
ON: I
OFF: I
I setting for the phases and for the neutral
8
(trip unit with ENCT option and neutral
2
t function active
2
t function not active
—Instantaneous protection pickup value
i
protection active).
Neutral status (with ENCT option):
9
N—Neutral protection active
noN—Neutral protection not active
The up arrow indicates the I
Ir tr Isd tsd Ii (x In)
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
The up arrow indicates the I
Ir tr Isd tsd Ii (x In)
A
The down arrow indicates the neutral.
N 1/A 2/B 3/
The up arrow indicates the t
s
Ir tr Isd tsd Ii (x In)
The up arrow indicates the I
Ir tr Isd tsd Ii (x In)
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
The up arrow indicates the I
Ir tr Isd tsd Ii (x In)
A
The down arrow indicates the neutral.
N 1/A 2/B 3/
The up arrow indicates the t
s
Ir tr Isd tsd Ii (x In)
The up arrow indicates the I
Ir tr Isd tsd Ii (x In)
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
Continued on next page
function.
r
function.
r
function.
r
function.
sd
function.
sd
function.
sd
function.
i
ENGLISH
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
17-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Section 1—General Information
Table 3 – Metering Screens (continued)
ENGLISH
Trip Unit Mode Order Screen Description Unit Arrows
function.
r
function.
r
function.
r
sd
sd
sd
function.
g
MicroLogic 6 LSIG: Protection Function Readout Screens
I
—Long-time protection pickup value for
r
1
the phases
I
)—Long-time protection pickup value
r(IN
2
for the neutral (trip unit with ENCT option and neutral protection active)
t
—Long-time protection time delay value
r
4
5
6
)
(at 6 I
r
I
—Short-time protection pickup value for
sd
the phases
)—Short-time protection pickup value
I
sd(IN
for the neutral (trip unit with ENCT option and neutral protection active)
—Short-time protection time delay value
t
sd
The time delay is for the I curve protection:
7
ON: I
OFF: I
I setting for the phases and for the neutral
8
(trip unit with ENCT option and neutral
2
t function active
2
t function not active
—Instantaneous protection pickup value
i
2
t inverse time
protection active).
9 I
—Ground-fault protection pickup value A A
g
The up arrow indicates the I
Ir tr Isd tsd Ii Ig tg
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
The up arrow indicates the I
Ir tr Isd tsd Ii Ig tg
A
The down arrow indicates the neutral.
N 1/A 2/B 3/
The up arrow indicates the t
s
Ir tr Isd tsd Ii Ig tg
The up arrow indicates the I
Ir tr Isd tsd Ii Ig tg
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
The up arrow indicates the I
Ir tr Isd tsd Ii Ig tg
A
The down arrow indicates the neutral.
N 1/A 2/B 3/
The up arrow indicates the t
s
Ir tr Isd tsd Ii Ig tg
The up arrow indicates the Ii function.
Ir tr Isd tsd Ii Ig tg
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
The up arrow indicates the I
Ir tr Isd tsd Ii Ig tg
The down arrows indicate the three phases.
function.
function.
function.
18-EN
N 1/A 2/B 3/
t
—Ground-fault protection time delay
g
value The time delay is for the I
10
curve protection:
ON: I
OFF: I
2
t function active
2
t function not active
2
t inverse time
The up arrow indicates the t
s
Ir tr Isd tsd Ii Ig tg
function.
g
Neutral status (with ENCT option):
11
N—Neutral protection active
noN —Neutral protection not active
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Section 1—General Information MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
Energy Meter Readout (MicroLogic E)
Energy meters change measurement unit automatically:
For active energy, E
, displayed in kWh from 0 to 9999 kWh then in MWh
p
For reactive energy, Eq, displayed in kvarh from 0 to 9999 kvarh then in Mvarh
For apparent energy, E
, displayed in kVAh from 0 to 9999 kVAh then in MVAh
s
When energies are in MWh, Mkvarh, or MVAh, the values display on four digits. The MicroLogic trip unit incorporates the option of full energy meter readout.
NOTE: The energy meter can be reset with the padlock locked or unlocked. Table 4 shows the padlock locked.
Table 4 – Example of Full Energy Readout (MicroLogic E)
Step Readout Value Action Using Display
Reading Full Energy Values
Ir tr Isd tsd Ii (x In)
1
2
Current in most heavily loaded phase
Energy with Reset option showing
Select the readout and reset the energy meter mode (main screen displayed).
Select the E The value displayed is 11.3 MWh (in the
example), which corresponds to 10 MWh +1300 kWh (approximately).
active energy meter.
p
Mode
Ir tr Isd tsd Ii (x In)
N 1/A 2/B 3/
N 1/A 2/B 3/
Reset? OK
229
11.3
ENGLISH
A
MWh
3
4
Specific energy measurement
Energy normal display
Specify the measurement. The value displayed is 1130 kW. (In the example
the full energy meter value is 11300 kWh)
Return to the energy meter normal display. The display reverts automatically after 5
minutes.
Ir tr Isd tsd Ii (x In)
Reset? OK
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In
Reset? OK
N 1/A 2/B 3/
1130
11.3
Continued on next page
kWh
kWh
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
19-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Section 1—General Information
Mode
Mode
Table 4 – Example of Full Energy Readout (MicroLogic E) (continued)
ENGLISH
Resetting Full Energy Readout
Ir tr Isd tsd Ii (x In)
Current in most
1
heavily loaded phase
Energy with
2
Reset option showing
3 Reset option lit
4 OK
Select the measurement readout and reset energy meter mode (main screen displayed).
Select the energy meter to reset.
Enter the reset. The OK pictogram blinks.
Confirm the reset. The confirmation OK displays for 2 seconds.
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
OK
OK
Reset? OK
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
Reset? OK
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
229
1458
1458
A
kWh
kWh
OK
Resetting Peak Demand Values
1 Main screen
Peak demand
2
with Reset option showing
3 Reset option lit
4 OK
Select the Readout and reset peak demand value mode
Select the peak demand to reset.
Enter the reset. The OK pictogram blinks.
Confirm the reset. The confirmation OK display for 2 seconds.
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
OK
OK
Max Reset?
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
Max Reset?
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
Reset? OK
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
N 1/A 2/B 3/
243
435
435
A
V
V
OK
20-EN
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Section 1—General Information MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
OK
OK
Table 5 – Example of Ground-Fault Protection Readout (MicroLogic 6)
Step Readout Value Action Using Display
Reading Measurement Values
Current in most
1
heavily loaded phase
2 Ground-fault current
Select the Instantaneous measurement readout mode (the display is the most heavily loaded phase, in this example Phase B).
Read the value of current in Phase B.
Select the ground-fault current measurement screen (the value is a % of the I
Ground-Fault Protection Test (MicroLogic 6)
setting).
g
Mode
Ir tr Isd tsd Ii Ig tg
N 1/A 2/B 3/
Ir tr Isd tsd Ii Ig tg
OK
N 1/A 2/B 3/
A
229
%
17
ENGLISH
Current in most
1
heavily loaded phase
Peak demand with
2
Reset option showing
3 Reset option lit
4 OK
Access the ground-fault protection test function by pressing OK.
The tESt pictogram appears and the OK pictogram blinks.
Prompt the ground-fault protection test by pressing OK.
The circuit breaker trips. The ground-fault protection trip screen is displayed.
Acknowledge the ground-fault trip screen by pressing OK.
The Reset OK pictogram blinks.
Confirm by pressing OK again The confirmation OK displays for 2 seconds.
Mode
Ir tr Isd tsd Ii Ig tg
OK
N 1/A 2/B 3/
Ir tr Isd tsd Ii Ig tg
Reset? OK
N 1/A 2/B 3/
Ir tr Isd tsd Ii Ig tg
Reset? OK
N 1/A 2/B 3/
Ir tr Isd tsd Ii Ig tg
N 1/A 2/B 3/
tESt
triP
triP
OK
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
21-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Section 1—General Information
Mode
Mode
Protection Function Readout
ENGLISH
Select a protection function using the mode key. This selection is only possible in Readout mode (when the padlock is locked).
Scrolling is cyclical.
The up arrow indicates the selected protection function. (For the neutral protection functions, the down arrow which points to N replaces the up arrow.)
Example: I
Ir tr Isd tsd Ii (x In)
pickup selected
r
Table 6 – Example of Protection Function Readout
Readout
Step
1
2
3
Value
Long-time protection I pickup setting value in amperes.
Long-time protection t time delay setting value in seconds.
The short-time protection I pickup setting value in amperes.
Action Using Display
Select the Protection function readout mode
r
(main screen displayed). The long-time protection I
in amperes.
r
Select the long-time protection tr time delay.
sd
Select the short-time protection I
pickup setting value
r
pickup
sd
Ir tr Isd tsd Ii (x In)
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
110
A
s
8.0
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
A
715
N 1/A 2/B 3/
Neutral Status Readout Mode
NOTE: The Neutral status readout mode is dedicated to this function. Navigation is
therefore limited to the Mode key.
Table 7 – Example of Neutral Status Readout
Readout
Step
1
22-EN
Value
Neutral status is displayed
Action Using Display
Select the Neutral status readout mode. The neutral status value is displayed:
N—Neutral protection active (with ENCT
option declared)
noN—Neutral protection not active (without
ENCT option or with ENCT option not declared)
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Ir tr Isd tsd Ii (x In)
N 1/A 2/B 3/
noN
Section 1—General Information MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
CAUTION
Setting Mode
Setting Using a Dial
Figure 2 – Protection
Switches
150
175
125
100
A
80
70
3
B
2
1.5
Ir (A)
4
Ii (x In)
200
5.2 A
225
250
5
6
8 10
12
Micrologic
HAZARD OF NO PROTECTION OR NUISANCE TRIPPING
Modifying the protection functions must be done only by qualified electrical personnel.
Failure to follow these instructions can result in injury or equipment damage.
The protection function settings can be set:
By a dial and fine-tuned on the keypad for the main protection functions
On the keypad for all protection functions
The up arrow on the display indicates the protection function currently being set.
Use a dial to set (or preset) the Ir (A) and Ii (B) pickups.
Turning a dial results simultaneously in:
Selection of the screen for the protection function assigned to the dial
Unlocking (if necessary) the padlock (the navigation interface is in protection function setting mode)
Setting the protection function assigned to the dial to the value indicated on the dial and on-screen.
ENGLISH
Setting Using the Keypad
Use the keypad to fine-tune the protection function.
The setting value cannot exceed that indicated by the dial.
All the protection function settings are accessible on the keypad.
Press the button successively to scroll through the protection function
Mode
screens. Scrolling is cyclical.
Navigate through the protection function settings with the , and navigation buttons.
Use the button to select the function to set:
— The up arrow indicates the selected function — The down arrow indicates phase. Multiple down arrows indicate all phases
set to the same value (except for the neutral protection setting)
— Scrolling is cyclical
Set the protection functions on the keypad with the and buttons.
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
23-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Section 1—General Information
Figure 3 – Protection Function Screen
ENGLISH
Up arrow indicates selected function.
Ir tr Isd tsd Ii (x
200
N 1/A 2/B 3/
A
Possible to press
button
the
Possible to press
button
the
Confirmation of Setting
Use to select protection function screen
Use to select function to set
Down arrow indicates phase.
Use to select measurement to display
The value of a protection function set on the keypad must be:
1. Entered by pressing the OK key once (the OK pictogram blinks on the display)
2. Then confirmed by pressing the OK key again (the text OK displays for 2 seconds)
NOTE: Setting using a dial does not require any enter/confirm action.
24-EN
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Section 1—General Information MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
Table 8 – List of Protection Function Setting Screens
Trip Unit Mode Screen Description Unit Arrows
I
—Long-time protection pickup setting for the
r
phases Preset by a dial
—Long-time protection time delay setting (at 6 Ir) s
t
r
The up arrow indicates the I
Ir tr Isd tsd Ii (x In)
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
The up arrow indicates the t
Ir tr Isd tsd Ii (x In)
function.
r
function.
r
ENGLISH
MicroLogic 5 LSI
—Short-time protection pickup setting for the
I
sd
phases Preset by a dial
—Short-time protection time delay setting
t
sd
Activation of the I2t inverse time curve short-time protection:
2
ON: I
OFF: I
I
N
t function active
2
t function not active
—Protection pickup setting for the neutral (trip unit with ENCT option and neutral protection active)
—Instantaneous protection pickup value setting
I
i
for the phases and for the neutral (trip unit with ENCT option and neutral protection active).
Activation of neutral status (trip unit with ENCT option):
N: Neutral protection active
noN: Neutral protection not active
The up arrow indicates the I
Ir tr Isd tsd Ii (x In)
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
The up arrow indicates the t
s
Ir tr Isd tsd Ii (x In)
The down arrow indicates the neutral.
A
N 1/A 2/B 3/
The up arrow indicates the I
Ir tr Isd tsd Ii (x In)
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
Continued on next page
function.
sd
function.
sd
function.
i
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
25-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Section 1—General Information
Table 8 – List of Protection Function Setting Screens (continued)
ENGLISH
Trip Unit Mode Screen Description Unit Arrows
The up arrow indicates the I
—Long-time protection pickup setting for the
I
r
phases Preset by a dial
t—Long-time protection time delay setting s
Ir tr Isd tsd Ii Ig tg
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
The up arrow indicates the t
Ir tr Isd tsd Ii Ig tg
function.
r
function.
r
MicroLogic 6 LSIG:
I
—Short-time protection pickup setting for the
sd
phases
—Short-time protection time delay setting
t
sd
The time delay is for the I
2
t inverse time curve
protection:
2
ON: I
OFF: I
I
N
t function active
2
t function not active
—Protection pickup setting for the neutral (trip unit with ENCT option and neutral protection active)
—Instantaneous protection pickup setting for the
I
i
phases and for the neutral (trip unit with ENCT option and neutral protection active).
I—Ground-fault protection pickup setting Preset by a dial
The up arrow indicates the I
Ir tr Isd tsd Ii Ig tg
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
The up arrow indicates the t
s
Ir tr Isd tsd Ii Ig tg
The down arrow indicates the neutral.
A
N 1/A 2/B 3/
The up arrow indicates the I
Ir tr Isd tsd Ii Ig tg
A
The down arrows indicate the three phases.
N 1/A 2/B 3/
The up arrow indicates the Ig function.
Ir tr Isd tsd Ii Ig tg
A
The down arrows indicate the three phases.
function.
sd
function.
sd
function.
i
26-EN
N 1/A 2/B 3/
t
—Ground-fault protection time delay setting
g
The time delay is for the I2t inverse time curve protection:
2
ON: I
OFF: I
t function active
2
t function not active
The up arrow indicates the t
s
Ir tr Isd tsd Ii Ig tg
function.
g
Activation of neutral status (trip unit with ENCT option):
N—Neutral protection active
noN—Neutral protection not active
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Section 1—General Information MicroLogic™ 5 and 6 Electronic Trip Units—User Guide
Presetting a Protection Function
Table 9 illustrates presetting and setting the long-time protection Ir pickup on a MicroLogic trip unit 5.2 rated 250 A:
Press the button to scroll through the metering screens.
Mode
Press the , and navigation buttons to select the metering screen for each of the phases:
Table 9 – Example of Presetting a Protection Function Using a Dial
Step Action Using Display
Set the Ir dial to the maximum value (the padlock unlocks
1
2
4
automatically). The down arrows indicate all 3 phases (the setting is identical
on each phase).
Turn the I Presetting is complete:
If the pickup setting value is correct (in this case, 175 A), exit
If the pickup setting value is not suitable, fine-tune it on the
Set the exact value required for I (in increments of 1 A).
dial to the setting above the value required.
r
the setting procedure (no enter keystroke is required).
keypad.
on the keypad
r
16
17
14
10
14
10
Ir (A)
16
Ir (A)
25
17
25
20 22
20 22
12
11
12
11
Ir tr Isd tsd Ii (x In)
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
N 1/A 2/B 3/
OK
ENGLISH
A
250
A
175
A
170
Ir tr Isd tsd Ii (x In)
5
6
Enter the reset. The OK pictogram blinks.
Confirm the reset. The confirmation OK displays for 2 seconds.
OK
OK
OK
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
N 1/A 2/B 3/
170
A
OK
© 2011–2020 Schneider Electric All Rights Reserved48940-312-01
27-EN
MicroLogic™ 5 and 6 Electronic Trip Units—User Guide Section 1—General Information
Mode
Setting a Protection Function
ENGLISH
Table 10 illustrates setting the long-time protection tr time delay on a MicroLogic
5.2 trip unit:
Press the button to scroll through the screens.
Mode
Press the , and navigation buttons to select the screen for each of the phases:
Table 10 – Example of Setting a Protection Function Using the Keypad
Step Action Using Display
Ir tr Isd tsd Ii Ig tg
1
2 Select the protection function setting mode.
3 Select the t
If the locked pictogram is displayed, unlock the protection settings.
function: the up arrow moves under tr.
r
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
N 1/A 2/B 3/
A
229
A
170
s
0.5
4 Set the t
5 Enter the setting (the OK pictogram blinks).
6
Confirm the setting. The confirmation OK displays for 2 seconds.
value required on the keypad.
r
Ir tr Isd tsd Ii (x In)
s
OK
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
OK
OK
OK
N 1/A 2/B 3/
Ir tr Isd tsd Ii (x In)
N 1/A 2/B 3/
8.0
s
8.0
OK
28-EN
© 2011–2020 Schneider Electric All Rights Reserved 48940-312-01
Loading...
+ 282 hidden pages