Schneider Electric MF41-6043 Series, MS41-6043 Series, MF41-6083 Series, MS41-6083 Series Data Sheet

Product Description

These installation instructions describe the steps for direct-coupled mounting of the 44 lb-in MF41-6043 and MS41-6043, and 88 lb-in MF41-6083 and

MS41-6083 Series Non-Spring Return Rotary Electronic Damper SmartX Actuators.

Product Numbers

Three-position control: MF41-6043, MF41-6083, MF41-6083-502, and MF41-6083-510 Modulating control: MS41-6043, MS41-6083,

MS41-6083-520, MS41-6083-522, and MS41-6083-502

Required Tools

4 mm hex wrench

4 mm (5/32-inch) drill bit and drill

Small flat-blade screwdriver

Marker or pencil

Estimated Installation Time

30 minutes

Warning/Caution Notations

MF41-6043/MS41-6043

MF41-6083/MS41-6083 Series

SmartX Actuators - Electric Dampers Non-Spring Return Rotary 24 Vac – Modulating Control 0 – 10Vdc

90

45

90

Caution: Equipment damage or loss of data may occur if you do not follow a procedure as specified.

Warning: Personal injury may occur if you do not follow a procedure as specified.

Schneider Electric

 

F-27211-3

Sept 2014

2

Actuator Components

Legend a. Actuator

b. Position indicator

c. Anti-rotation bracket

d. Mounting screws for anti-rotation bracket

e. 4 mm hex key

f. Shaft insert for use with 3/8-inch (8-10 mm) shafts

Figure 1. Parts of the Rotary SmartX Actuator.

Warning: Do not open the actuator.

Instructions

Note: Place the actuator on the damper shaft with the front of the actuator accessible. The label is on the front side.

1.Determine whether the damper blades will rotate clockwise or counterclockwise to open. See Figure 3.

2.If the blades will rotate counterclockwise, slide the manual override switch to manual, and move the adjustment lever to the right. Return the switch to automatic. See Figure 2.

Figure 2.

3.To mount a (modulating) MS41-6043 or MS41-6083 Series actuator, set the Dual In-line Package (DIP) switches to the required positions. See Figure 3.

4.To access the DIP switches, raise the tab on the lower left side of the actuator’s face. See Figure 3. The factory setting is clockwise (middle switch), with a direct-acting feedback signal (right switch).

5.Close the tab over the DIP switches.

6.To mount a (3-position) MF41-6043 or MF41-6083 Series actuator for counter-clockwise rotation, follow the Counterclockwise Damper Rotation instructions located in the Wiring Diagrams section when wiring the actuator to the controller.

Schneider Electric

 

F-27211-3

Sept 2014

Schneider Electric MF41-6043 Series, MS41-6043 Series, MF41-6083 Series, MS41-6083 Series Data Sheet

3

Figure 3. Setting the Direction of Rotation.

Note: For DIP switch setting options, see the General Instructions F-27213-1 (MF41-6043/6083) and F-27214-1 (MS41-6043/6083).

Mounting and Installation

The SmartX Actuator comes with a factory installed 1/2-inch shaft guide.

If shaft size is 5/8-inch, skip Figure 5 and proceed with the instructions in Figure 6.

Figure 4.

Removing 1/2-inch Shaft

Guide for 3/8-inch Ø

or 5/8-inch Ø Shaft.

 

f

 

90

 

45

 

90

<![if ! IE]>

<![endif]>PL0028R2

Mounting on

 

 

~ 3/8-inch

 

8...10 mm shafts

1.Remove factory installed 1/2-inch guide.

See Figure 4.

A 3/8-inch shaft adapter is provided in actuator package.

2.Hold the shaft insert so that the raised tabs are inserted last when placing the insert into the back of the actuator.

Proceed to Figure 6, step 2.

Figure 5. 3/8-inch Ø Shaft.

1.Remove factory installed 1/2- inch guide. See Figure 4.

2.Mount actuator to shaft per Figure 6.

Figure 6. 5/8-inch Ø Shaft.