Metered Rack PDU
Overview
The Ameri can P ower Con versi on (A PC
Rack Power Distribution Unit (PDU) distributes
power to devices in the rac k. It has a sensor that
measures the current tha t it and its attached dev ices
use. It can be monitored t hrough Web, Telnet,
SNMP, SSH, or InfraStruXure Central interfaces.
Outlets. The Rack PDU has twenty-four
(24) NEMA 5-20 outlets.
Digita l di sp la y. The int er f a ce u s es a dig i ta l
display that s hows a ggregat e curre nt being u sed by
the Rack PDU.
Power cord. The 10-foot (3.05-meter) power cord
terminates with a NEMA L5-30 connector.
AP7832
®
) Metered
Specifications
Electrical
Input connector NEMA L5-30 plug
Output connectors (24) NEMA 5-20 outlets
Nominal input voltage 120 VAC
Accepta ble input volt age ± 10% of nominal vol tage
Input frequency 50/60 Hz
Physical
Dimensio ns (H × W × D) 63.75 x 2.19 x 1.73in
Shipping dimensions
(H × W × D) 84.00 x 6.00 x 5.00in
Weight 12.50 lb (5.67 kg)
Shipping weight 14.50 lb (6.58 kg)
(161.92 x 5.56 x 4.39 cm)
(213.36 x 15.24 x 12.7 cm)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
Temperature
Operating
Storage
Humidity
Operating
Storage
15,000 ft (4500 m)
50,000 ft (15 000 m )
23 to 115° F (– 5 to 45° C)
–13 to 149° F (–25 to 65° C)
5–95% RH Non-condensing
5–95% RH Non-condensing
Compliance
EMC verification FCC Class A
ICES-003 Class A
Safety verificat ion UL, cUL 60950
Customer support and warranty information is available at the APC Web site,
www.apc.com.
© 2008 American Power Conversion. All rights reserved. All APC trademarks
are property of American Power Conversion. Other trademarks are property
of their respective owners.
990-1896B