Schneider Electric Altivar61 User Manual

Page 1
Altivar 61
Variable speed drives for synchronous motors and asynchronous motors
Installation Manual
03/2011
0.75 kW (1 HP) ... 75 kW (100 HP) / 380 - 480 V
2.2 kW (3 HP) ... 7.5 kW (10 HP) / 500 - 600 V
2.2 kW (3 HP) ... 90 kW (100 HP) / 500 - 690 V
1760643
www.schneider-electric.com
Page 2
Page 3

Contents

Important information __________________________________________________________________________________________ 4 Before you begin______________________________________________________________________________________________ 5 Steps for setting up the drive ____________________________________________________________________________________ 6 Preliminary recommendations ___________________________________________________________________________________ 7 Drive ratings _________________________________________________________________________________________________ 9 Dimensions and weights_______________________________________________________________________________________ 12 Mounting and temperature conditions ____________________________________________________________________________ 13 Mounting in a wall-mounted or floor-standing enclosure ______________________________________________________________ 16 Installing the graphic display terminal_____________________________________________________________________________ 18 Position of the charging LED ___________________________________________________________________________________ 19 Installing option cards_________________________________________________________________________________________ 20 Installing the EMC plates ______________________________________________________________________________________ 22 Wiring precautions ___________________________________________________________________________________________ 23 Power terminals _____________________________________________________________________________________________ 25 Control terminals_____________________________________________________________________________________________ 27 Option terminals _____________________________________________________________________________________________ 29 Connection diagrams _________________________________________________________________________________________ 34 Use on IT system and “corner grounded” system____________________________________________________________________ 43 Electromagnetic compatibility, wiring _____________________________________________________________________________ 45
1760643 03/2011 3
Page 4

Important information

The addition of this symbol to a “Danger” or “Warning” safety label indicates that there is an electrical risk that will result in injury if the instructions are not followed.
This is a safety warning symbol. It warns you of the potential risk of injury. You must comply with all safety messages that
follow this symbol in order to avoid the risk of injury or death.
PLEASE NOTE
Please read these instructions carefully and examine the equipment in order to familiarize yourself with the device before installing, operating or carrying out any maintenance work on it.
The following special messages that you will come across in this document or on the device are designed to warn you about potential risks or draw your attention to information that will clarify or simplify a procedure.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or equipment damage.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death, serious injury or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in injury or equipment damage.
PLEASE NOTE:
Only qualified personnel are authorized to carry out maintenance work on electrical equipment. Schneider Electric accepts no responsibility for the consequences of using this device. This document does not constitute an instruction manual for inexperienced personnel. © 2006 Schneider Electric. All rights reserved.
4 1760643 03/2011
Page 5

Before you begin

Read and observe these instructions before performing any procedure on this drive.
DANGER
RISK OF ELECTRIC SHOCK
• Read and understand this manual before installing or operating the Altivar 61 drive. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical standards in force concerning protective grounding of all equipment.
• Many parts in this variable speed drive, including printed wiring boards, operate at line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA and PB or across the DC bus capacitors.
• Install and close all the covers before applying power or starting and stopping the drive.
• Before servicing the variable speed drive
- Disconnect all power.
- Place a “DO NOT TURN ON” label on the variable speed drive disconnect.
- Lock the disconnect in the open position.
• Disconnect all power including external control power that may be present before servicing the drive. WAIT 15 MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement procedure on page 19
to verify that the DC voltage is less than 45 V. The drive LEDs are not accurate indicators of the absence of DC bus voltage.
Failure to follow these instructions will result in death or serious injury.
CAUTION
IMPROPER DRIVE OPERATION
• If the drive is not turned on for a long period, the performance of its electrolytic capacitors will be reduced.
• If it is stopped for a prolonged period, turn the drive on at least every two years for at least 5 hours to restore the performance of the capacitors, then check its operation. It is recommended that the drive is not connected directly to the line voltage. The voltage should be increased gradually using an adjustable AC source.
Failure to follow these instructions can result in injury and/or equipment damage.
1760643 03/2011 5
Page 6

Steps for setting up the drive

b 1 Receive and inspect the drive controller
v Check that the catalog number printed on the label is the same
as that on the purchase order
v Remove the Altivar from its packaging and check that it has not
been damaged in transit
Steps 1 to 4 must be performed with the power off.
b 2 Check the line voltage
v Check that the line voltage is compatible with the voltage
range of the drive (see pages 9 and 10)
b 3 Mount the drive
v Mount the drive in accordance with the instructions
in this document
v Install any internal and external options
b 4 Wire the drive
v Connect the motor, ensuring that its
connections correspond to the voltage
v Connect the line supply, after making sure that
the power is off
v Connect the control v Connect the speed reference
PROGRAMMING
v 5 Please refer to the
Programming Manual
INSTALLATION
6 1760643 03/2011
Page 7

Preliminary recommendations

45° max.
Handling/Storage
To protect the drive prior to installation, handle and store the device in its packaging. Ensure that the ambient conditions are acceptable.
WARNING
DAMAGED PACKAGING
If the packaging appears damaged, it can be dangerous to open it or handle it. Take precautions against all risks when performing this operation.
Failure to follow this instruction can result in death or serious injury.
WARNING
DAMAGED EQUIPMENT
Do not operate or install any drive that appears damaged.
Failure to follow this instruction can result in death or serious injury.
Handling on installation
ALTIVAR 61 drives up to ratings ATV61HD15M3X, ATV61HD18N4 and ATV61HU75S6X can be removed from their packaging and installed without a handling device.
A hoist must be used for higher ratings and for ATV61H drives all have lifting lugs. Follow the recommendations on the next page.
pppY drives; for this reason, these
1760643 03/2011 7
Page 8
Preliminary recommendations
Read and observe the instructions in the Programming Manual.
CAUTION
INCOMPATIBLE LINE VOLTAGE
Before turning on and configuring the drive, ensure that the line voltage is compatible with the supply voltage range shown on the drive nameplate. The drive may be damaged if the line voltage is not compatible.
Failure to follow this instruction can result in injury and/or equipment damage.
DANGER
UNINTENDED EQUIPMENT OPERATION
• Before turning on and configuring the Altivar 61, check that the PWR (POWER REMOVAL) input is deactivated (at state 0)
in order to prevent unintended operation.
• Before turning on the drive, or when exiting the configuration menus, check that the inputs assigned to the run command
are deactivated (at state 0) since they can cause the motor to start immediately.
Failure to follow these instructions will result in death or serious injury.
Precautions
If the safety of personnel requires the prohibition of unwanted or unintended operation, electronic locking is performed by the Altivar 61's Power Removal function. This function requires the use of connection diagrams conforming to category 3 of standard EN 954-1, ISO 13849-1 and safety integrity level 2 according to IEC/EN 61508. The Power Removal function takes priority over any run command.
8 1760643 03/2011
Page 9

Drive ratings

Single-phase supply voltage: 200…240 V 50/60 Hz
Three-phase motor 200...240 V
Motor Line supply (input) Drive (output) Altivar 61
Power indicated on plate (1)
kW HP A A kA kVA A A A
0.37 0.5 6.9 5.8 5 1.4 9.6 3 3.6 ATV61H075M3
0.75 1 12 9.9 5 2.4 9.6 4.8 5.7 ATV61HU15M3
1.5 2 18.2 15.7 5 3.7 9.6 8 9.6 ATV61HU22M3
2.2 3 25.9 22.1 5 5.3 9.6 11.0 13.2 ATV61HU30M3 3 - 25.9 22 5 5.3 9.6 13.7 16.4 ATV61HU40M3(6) 4 5 34.9 29.9 22 7 9.6 17.5 21 ATV61HU55M3(6)
5.5 7.5 47.3 40.1 22 9.5 23.4 27.5 33 ATV61HU75M3(6)
Max. line current (2) Max. at 200 V at 240 V
prospective line Isc
Apparent power
Max. inrush current (3)
Three-phase supply voltage: 200…240 V 50/60 Hz
Three-phase motor 200...240 V
Max. available nominal current In (1)
Max. transient current (1) for 60 s
Catalog number (4)(5)
Motor Line supply (input) Drive (output) Altivar 61
Power indicated on plate (1)
kW HP A A kA kVA A A A
0.75 1 6.1 5.3 5 2.2 9.6 4.8 5.7 ATV61H075M3
1.5 2 11.3 9.6 5 4 9.6 8 9.6 ATV61HU15M3
2.2 315 12.8 5 5.3 9.6 11 13.2 ATV61HU22M3 3 - 19.3 16.4 5 6.8 9.6 13.7 16.4 ATV61HU30M3 4 5 25.8 22.9 5 9.2 9.6 17.5 21 ATV61HU40M3
5.5 7.5 35 30.8 22 12.4 23.4 27.5 33 ATV61HU55M3
7.5 10 45 39.4 22 15.9 23.4 33 39.6 ATV61HU75M3 11 15 53.3 45.8 22 18.8 93.6 54 64.8 ATV61HD11M3X 15 20 71.7 61.6 22 25.1 93.6 66 79.2 ATV61HD15M3X
18.5 25 77 69 22 27.7 100 75 90 ATV61HD18M3X 22 30 88 80 22 32 100 88 105.6 ATV61HD22M3X 30 40 124 110 22 42.4 250 120 144 ATV61HD30M3X 37 50 141 127 22 51 250 144 173 ATV61HD37M3X 45 60 167 147 22 65 250 176 211 ATV61HD45M3X
(1)These power ratings and currents are given for an ambient temperature of 50°C (122°F) at the factory-set switching frequency, used
in continuous operation (factory-set switching frequency of 4 kHz for ATV61H 075M3 to D15M3X and 2.5 kHz for ATV61H D18M3X to D45M3X). Above this factory setting, the drive will reduce the switching frequency automatically in the event of excessive temperature rise. For continuous operation above the factory setting, derating must be applied to the nominal drive current in accordance with the curves
on page 14 (2)Current on a line supply with the “Max. prospective line Isc” indicated and for a drive without any external options. (3)Peak current on power-up for the max. voltage (240 V +10%). (4)ATV61H 075M3 to D45M3X drives are available with or without a graphic display terminal. Catalog numbers for drives without a graphic
display terminal have the letter Z added at the end, e.g.: ATV61H075M3Z. This option is not available for drives which operate in difficult
environmental conditions (5). (5) Drives with the S337 or 337 extension are designed for use in difficult environmental conditions (class 3C2 in accordance with IEC 721-3-3).
They are supplied with a graphic display terminal. (6)A line choke must be used (please refer to the catalog).
Max. line current (2) Max. at 200 V at 240 V
.
prospective line Isc
Apparent power
Max. inrush current (3)
Max. available nominal current In (1)
Max. transient current (1) for 60 s
Catalog number (4)(5)
Inhibit the input phase loss fault (IPL) so that ATV61H 075M3 to U75M3 drives can operate on a single-phase supply (see the Programming Manual). If this fault is set to its factory configuration, the drive will stay locked in fault mode.
1760643 03/2011 9
Page 10
Drive ratings
Three-phase supply voltage: 380…480 V 50/60 Hz
Three-phase motor 380...480 V
Motor Line supply (input) Drive (output) Altivar 61
Power indicated on plate (1)
kW HP A A kA kVA A A A A
0.75 1 3.7 3 5 2.4 19.2 2.3 2.1 2.7 ATV61H075N4
1.5 2 5.8 5.3 5 4.1 19.2 4.1 3.4 4.9 ATV61HU15N4
2.2 3 8.2 7.1 5 5.6 19.2 5.8 4.8 6.9 ATV61HU22N4 3 - 10.7 9 5 7.2 19.2 7.8 6.2 9.3 ATV61HU30N4 4 5 14.1 11.5 5 9.4 19.2 10.5 7.6 12.6 ATV61HU40N4
5.5 7.5 20.3 17 22 13.7 46.7 14.3 11 17.1 ATV61HU55N4
7.5 10 27 22.2 22 18.1 46.7 17.6 14 21.1 ATV61HU75N4 11 15 36.6 30 22 24.5 93.4 27.7 21 33.2 ATV61HD11N4 15 20 48 39 22 32 93.4 33 27 39.6 ATV61HD15N4
18.5 25 45.5 37.5 22 30.5 93.4 41 34 49.2 ATV61HD18N4 22 30 50 42 22 33 75 48 40 57.6 ATV61HD22N) 30 40 66 56 22 44.7 90 66 52 79.2 ATV61HD30N4 37 50 84 69 22 55.7 90 79 65 94.8 ATV61HD37N4 45 60 104 85 22 62.7 200 94 77 112.8 ATV61HD45N4 55 75 120 101 22 81.8 200 116 96 139 ATV61HD55N4 75 100 167 137 22 110 200 160 124 192 ATV61HD75N4
Max. line current (2) Max.
prospective line Isc
at 380 V at 480 V
Apparent power
Max. inrush current (3)
Max. available nominal current In (1)
at 380 V at 460 V
Max. transient current (1) for 60 s
Catalog number (4)(5)
(1)These power ratings and currents are given for an ambient temperature of 50°C (122°F) at the factory-set switching frequency, used
in continuous operation (factory-set switching frequency of 4 kHz for ATV61H 075N4 to D30N4 drives, and 2.5 kHz for ATV61H D37N4
to D75N4).
Above this factory setting, the drive will reduce the switching frequency automatically in the event of excessive temperature rise.
For continuous operation above the factory setting, derating must be applied to the nominal drive current in accordance with the
curves on page 14 (2)Current on a line supply with the “Max. prospective line Isc” indicated and for a drive without any external options. (3)Peak current on power-up for the max. voltage (480 V +10%). (4)ATV61H 075N4 to D75N4 drives are available with or without a graphic display terminal. Catalog numbers for drives without a graphic
display terminal have the letter Z added at the end, e.g.: ATV61H075N4Z. This option is not available for drives which operate in difficult
environmental conditions (5). (5) Drives with the S337 or 337 extension are designed for use in difficult environmental conditions (class 3C2 in accordance with IEC 721-3-3).
They are supplied with a graphic display terminal.
.
10 1760643 03/2011
Page 11
Drive ratings
Three-phase supply voltage: 500…600 V 50/60 Hz
Three-phase motor 500...600 V
Motor Line supply (input) Drive (output) Altivar 61
Power indicated on plate (1)
500 V 575 V at 500 V at 600 V 500 V 575 V kW HP A A kA A A
2.2 37.66.7224.5 3.9 ATV61HU22S6X 3 - 9.9 10 22 5.8 - ATV61HU30S6X 4 5 12.5 10.9 22 7.5 6.1 ATV61HU40S6X
5.5 7.5 16.4 14.2 22 10 9 ATV61HU55S6X
7.5 10 21.4 18.4 22 13.5 11 ATV61HU75S6X
Three-phase supply voltage: 500…690 V 50/60 Hz
Three-phase motor 500...690 V
Motor Line supply (input) Drive (output) Altivar 61
Power indicated on plate (1)
500 V 575 V 690 V at 500 V at 600 V at 690 V 500 V 575 V 690 V kW HP kWAAAkAA A A
2.2 3 35.24.45.2224.5 3.9 4.5 ATV61HU30Y 3 - 46.8- 6.6225.8 - 5.8 ATV61HU40Y 4 5 5.5 8.6 7.2 8.6 22 7.5 6.1 7.5 ATV61HU55Y
5.5 7.5 7.5 11.2 9.5 11.2 22 10 9 10 ATV61HU75Y
7.5 10 11 14.6 12.3 15.5 22 13.5 11 13.5 ATV61HD11Y 11 15 15 19.8 16.7 20.2 22 18.5 17 18.5 ATV61HD15Y 15 20 18.5 24 21 24 22 24 22 24 ATV61HD18Y
18.5 25 22 29 24 27 22 29 27 29 ATV61HD22Y 22 30 30 33 28 34 22 35 32 35 ATV61HD30Y 30 40 37 48 41 41 22 47 41 43 ATV61HD37Y 37 50 45 61 51 55 22 59 52 54 ATV61HD45Y 45 60 55 67 57 63 22 68 62 62 ATV61HD55Y 55 75 75 84 70.5 82 22 85 77 84 ATV61HD75Y 75 100 90 110 92 102 22 104 99 104 ATV61HD90Y
Max. line current (2) Max.
prospective line Isc
Max. line current (2) Max.
Max. available nominal current In (1)
prospective line Isc
Max. available nominal current In (1)
Catalog number
Catalog number
(1)These power ratings and currents are given for an ambient temperature of 50°C (122°F) at the factory-set switching frequency, used
in continuous operation (factory-set switching frequency of 4 kHz for ATV61H U22S6X to U75S6X and ATV61H U30Y to D30Y drives,
and 2.5 kHz for ATV61H D37Y to D90Y).
Above this factory setting, the drive will reduce the switching frequency automatically in the event of excessive temperature rise.
For continuous operation above the factory setting, derating must be applied to the nominal drive current in accordance with the
curves on page 14 (2)Current on a line supply with the “Max. prospective line Isc” indicated and for a drive without any external options.
Note The maximum transient current for 60 s corresponds to 120% of the maximum nominal current In.
1760643 03/2011 11
.
Page 12

Dimensions and weights





2 option cards (1)
1 option card (1)
No option card
c
c1
c2
G
a
=
=
H
h
b
4 x
2 option cards (1)
1 option card (1)
No option card
With graphic display terminal
ATV61H a
mm (in.)
075M3, U15M3, 075N4, U15N4,U22N4
U22M3, U30M3, U40M3, U30N4, U40N4
U55M3, U55N4, U75N4
U75M3, D11N4 U22S6X ... U75S6X
D11M3X, D15M3X, D15N4, D18N4
D18M3X, D22M3X, D22N4, U30Y ... D30Y
D30N4, D37N4
D30M3X, D37M3X, D45M3X
D45N4, D55N4, D75N4, D37Y ... D90Y
130
(5.12)
155
(6.10)
175
(6.89)
210
(8.27)
230
(9.05)
240
(9.45)
240
(9.45)
320
(12.60)
320
(12.60)
Without graphic display terminal
b mm (in.)
230
(9.05)
260
(10.23)
295
(11.61)
295
(11.61)
400
(15.75)
420
(16.54)
550
(21.65)
550
(21.65)
630
(24.80)
c mm (in.)
175
(6.89)
187
(7.36)
187
(7.36)
213
(8.39)
213
(8.39)
236
(9.29)
266
(10.47)
266
(10.47)
290
(11.42)
c1 mm (in.)
198
(7.80)
210
(8.27)
210
(8.27)
236
(9.29)
236
(9.29)
259
(10.20)
289
(11.38)
289
(11.38)
313
(12.32)
c2 mm (in.)
221
(8.70)
233
(9.17)
233
(9.17)
259
(10.20)
259
(10.20)
282
(11.10)
312
(12.28)
312
(12.28)
334
(13.15)
G mm (in.)
113.5 (4.47)
138
(5.43)
158
(6.22)
190
(7.48)
210
(8.26)
206
(8.11)
206
(8.11)
280
(11.02)
280
(11.02)
H mm (in.)
220
(8.66)5(0.20)5(0.20)
249
(9.80)4(0.16)5(0.20)
283
(11.14)6(0.24)5(0.20)
283
(11.14)6(0.24)6(0.24)
386
(15.20)8(0.31)6(0.24)
403
(15.87)11(0.45)6(0.24)
531.5
(20.93)11(0.45)6(0.24)
524
(20.93)20(0.79)9(0.35)
604.5
(23.80)15(0.59)9(0.35)
h mm (in.)
Ø mm (in.)
For
screws
M4 3
M4 4
M4 5.5
M5 7
M5 9
M5 30
M5 37
M8 37
M8 45
Weight
kg
(lb.)
(6.61)
(8.82)
(12.13)
(15.43)
(19.84)
(66.14)
(81.57)
(81.57)
(99.21)
For a drive without a graphic display terminal, dimensions c, c1 and c2 in the table above are reduced by 26 mm (1.01 in.). The other dimensions are unchanged.
(1)For the addition of I/O extension cards, communication cards, or the “Controller Inside” programmable card.
12 1760643 03/2011
Page 13

Mounting and temperature conditions

u 100 mm
u 3.94 in.
u 100 mm
u 3.94 in.
u 50 mm u 1.97 in.
u 50 mm u 1.97 in.
u 50 mm u 1.97 in.
u 50 mm u 1.97 in.
Install the drive vertically to ± 10°. Do not place it close to heating elements. Leave sufficient free space to ensure that the air required for cooling purposes can circulate from the bottom to the top of the unit.
Free space in front of the drive: 10 mm (0.39 in.) minimum
When IP20 protection is adequate, it is recommended that the protective cover on the top of the drive is removed as shown below.
Removing the protective cover
ATV61H 075M3 to D15M3X, ATV61H075N4 to D18N4 and ATV61H U22S6X to U75S6X
Two types of mounting are possible:
Type A mounting
Free space
u 50 mm (u 1.97 in.) on each side, with protective cover fitted
ATV61H D18M3X to D45M3X, ATV61H D22N4 to D75N4 and ATV61H U30Y to D90Y
Type B
Drives mounted side by side, with the protective cover removed (the degree of protection becomes IP20)
mounting
Type C
Free space
u 50 mm (u 1.97 in.) on each side, with protective cover removed (the degree of protection becomes IP20)
mounting
1760643 03/2011 13
Page 14
Mounting and temperature conditions
In = 100 %
90 %
80 %
70 %
60 %
50 %
4 kHz 8 kHz 12 kHz 16 kHz
Switching frequency
I/In
40°C (104°F) mounting type A 50°C (122°F) mounting type B
50°C (122°F) mounting type A
60°C (140°F) mounting types A and B
40°C (104°F) mounting type B
In = 100 %
90 %
80 %
70 %
60 %
50 %
4 kHz 8 kHz 12 kHz 16 kHz
Switching frequency
I/In
50°C (122°F) mounting types A and B
60°C (140°F) mounting types A and B
40°C (104°F) mounting types A and B
In = 100 %
90 %
80 %
70 %
60 %
50 %
4 kHz 8 kHz 12 kHz 16 kHz
2,5 kHz
Switching frequency
I/In
40°C (104°F) mounting types A and B
50°C (122°F) mounting types A and B
60°C (140°F) mounting types A and B
Derating curves
Derating curves for the drive current In as a function of the temperature, switching frequency and type of mounting.
ATV61H 075M3 to D15M3X and ATV61H 075N4 to D18N4
ATV61H D22N4 and ATV61H D30N4 (1)
ATV61H D18M3X to D45M3X and ATV61H D37N4 to D75N4 (1)
For intermediate temperatures (e.g. 55°C (131°F)), interpolate between two curves.
(1)Above 50°C (122°F), these drives must be equipped with a control card fan kit. Please refer to the catalog.
14 1760643 03/2011
Page 15
Mounting and temperature conditions
In = 100 %
90 %
80 %
70 %
60 %
50 %
2 kHz
4 kHz 6 kHz
40 %
I/In
40°C (104°F) mounting type A
50°C (122°F) mounting type A
60°C (140°F) mounting types A, B and C
Switching frequency
50°C (122°F) mounting types B and C
I/In
Switching frequency
40°C (104°F) mounting type A
50°C (122°F) mounting type A
60°C (140°F) mounting types A, B and C
50°C (122°F) mounting types B and C
Derating for ATV61HpppS6X
Mounting type A and B:
ATV61H
pppS6X drives can operate with a switching frequency 2,5…6kHz up to 50°C without derating.
Mounting type C:
ATV61H
pppS6X drives can operate with a switching frequency 2,5…6kHz up to 60°C without derating
For operation above 50°C (122°F), power supply voltage must be limited up to 600V+5%.
ATV61H U30Y to D30Y
ATV61H D37Y to D90Y
In = 100 %
90 %
80 %
70 %
60 %
50 %
40 %
2,5 kHz
4,9 kHz
For intermediate temperatures (e.g. 55°C (131°F)), interpolate between two curves.
1760643 03/2011 15
Page 16

Mounting in a wall-mounted or floor-standing enclosure

Follow the mounting precautions on the previous pages. To ensure proper air circulation in the drive:
- Fit ventilation grilles.
- Ensure that the ventilation is adequate: if not, install a forced ventilation unit with a filter.
- Use special IP54 filters.
Dust and damp proof metal wall-mounted or floor-standing enclosure
The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions: dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.
(IP 54 degree of protection)
To avoid hot spots in the drive, add a fan to circulate the air inside the enclosure, catalog number VW3 A9 4
pp (see catalog).

Mounting the drive in the enclosure

Dissipated power
These levels of power dissipation are given for operation at nominal load and for the factory-set switching frequency.
ATV61H Dissipated
power (1)
WWWW
075M3 66 075N4 44 U22S6X 100 U30Y 111 U15M3 101 U15N4 64 U30S6X 118 U40Y 119 U22M3 122 U22N4 87 U40S6X 143 U55Y 136 U30M3 154 U30N4 114 U55S6X 183 U75Y 158 U40M3 191 U40N4 144 U75S6X 244 D11Y 182 U55M3 293 U55N4 178 D15Y 227 U75M3 363 U75N4 217 D18Y 300 D11M3X 566 D11N4 320 D22Y 386 D15M3X 620 D15N4 392 D30Y 463
D18M3X
D22M3X
D30M3X
D37M3X
D45M3X
657
766
980
1154
1366
ATV61H Dissipated
power (1)
ATV61H Dissipated
power (1)
ATV61H Dissipated
power (1)
D18N4 486 D37Y 716 D22N4 574 D45Y 716 D30N4 799 D55Y 911
D37N4
D45N4
D55N4
D75N4
861
1060
1210
1720
D75Y
D90Y
1087
1545
(1)Add 7 W to this value for each option card added
Ensure that the flow of air in the enclosure is at least equal to the value given in the table below for each drive.
ATV61H
075M3, U15M3, 075N4, U15N4, U22N4
U22M3, U30M3, U40M3, U30N4, U40N4
U55M3,
3
m
Flow ratex
/hour
3
ft
/min
ATV61H
17 10 U30Y to
D37Y
56 33 D45Y to
D90Y
112 66
U55N4, U75N4
U75M3,
163 96
D11N4, U22S6X to U75S6X
D11M3X, D15M3X,
252 148
D15N4, D18N4
D18M3X, D22M3X,
203 119
D22N4, D30N4, D37N4
D30M3X, D37M3X, D45M3X,
406 239
D45N4, D55N4, D75N4
16 1760643 03/2011
Flow rate
3
/hour
m
330 194
406 234
3
ft
/min
Page 17
Mounting in a wall-mounted or floor-standing enclosure
Example: ATV61HU55N4

Dust and damp proof flange mounting

This mounting is used to reduce the power dissipated in the enclosure by locating the power section outside the enclosure. This requires the use of a dust and damp proof flange-mounting kit VW3 A9 501...509 (please refer to the catalog). The degree of protection for the drives mounted in this way becomes IP54.
To install the kit on the drive, please refer to the manual supplied with the kit.
Power dissipated inside the enclosure for dust and damp proof flange-mounting
These levels of power dissipation are given for operation at nominal load and for the factory-set switching frequency.
ATV61H
075M3 27 075N4 26 U22S6X 60 U30Y 71 U15M3 30 U15N4 28 U30S6X 70 U40Y 71 U22M3 38 U22N4 30 U40S6X 75 U55Y 73 U30M3 38 U30N4 35 U55S6X 80 U75Y 75 U40M3 41 U40N4 40 U75S6X 85 D11Y 77 U55M3 59 U55N4 50 D15Y 81 U75M3 67 U75N4 55 D18Y 87 D11M3X 80 D11N4 65 D22Y 94 D15M3X 84 D15N4 85 D30Y 100
D18M3X
D22M3X
D30M3X
D37M3X
D45M3X
Dissipated
power (1)
WWWW
114
124
144
161
180
ATV61H
D18N4 86 D37Y 120 D22N4 110 D45Y 120 D30N4 135 D55Y 133
D37N4
D45N4
D55N4
D75N4
Dissipated
power (1)
137
165
178
225
ATV61H Dissipated
power (1)
ATV61H
D75Y
D90Y
Dissipated
power (1)
144
158
(1)Add 7 W to this value for each option card added
1760643 03/2011 17
Page 18

Installing the graphic display terminal

Installing the graphic display terminal on the drive
Drives with catalog numbers ending in the letter Z are supplied without a graphic display terminal (VW3 A1 101). This can be ordered separately. It is installed on the drive as shown below.
The graphic display terminal can be connected or disconnected with the power on. Before disconnecting it, drive control via the display terminal must be disabled (refer to the Programming Manual).
18 1760643 03/2011
Page 19

Position of the charging LED

ATV61H 075M3 to D15M3X, ATV61H 075N4 to D18N4 and ATV61H U22S6X to U75S6X
ATV61H D18M3 to D45M3X, ATV61H D22N4 to D75N4 and ATV61H U30Y to D90Y
Red LED indicating that the DC bus is turned on
DANGER
HAZARDOUS VOLTAGE
Read and understand the instructions on page 5 before performing this procedure.
Failure to follow this instruction will result in death or serious injury.
Before working on the drive, turn it off, wait until the red capacitor charging LED has gone out, then measure the DC bus voltage.
Position of the capacitor charging LED
Procedure for measuring the
The DC bus voltage can exceed 1,000 V c. Use a properly rated voltage sensing device when performing this procedure. To measure the DC bus voltage:
1 Disconnect the drive power supply. 2 Wait 15 minutes to allow the DC bus capacitors to discharge. 3 Measure the voltage of the DC bus between the PA/+ and PC/- terminals to check whether the voltage is less than 45 V
for the arrangement of the power terminals.
4 If the DC bus capacitors have not discharged completely, contact your local Schneider Electric representative (do not repair or operate
the drive).
DC bus voltage
c. See page 26
1760643 03/2011 19
Page 20

Installing option cards

3
2
1
• Using a screwdriver, press down on the catch and pull to release the left­hand part of the control front panel
• Do the same on the right-hand side
• Pivot the control front panel and remove it
If an I/O or communication option card or a “Controller Inside” programmable card has already been installed, remove it so you can access the slot for the encoder interface card.
These should ideally be installed once the drive is mounted and before wiring it. Check that the red capacitor charging LED is off. Measure the DC bus voltage in accordance with the procedure indicated on page 19 The option cards are installed under the drive control front panel. If the drive has a graphic display terminal, remove it, then remove the control front panel as indicated below.
.
Removing the control front panel
Installing an encoder interface card
There is a special slot on the drive for adding an encoder interface card.
20 1760643 03/2011
Page 21
Installing option cards
Install an encoder interface card (if used)
(see previous page)
Position the option card on the clasps
Then pivot it until it clicks into place
4
5
6
Replace the control front panel over the option card
(same procedure as for installing the option card, see and )
7
5
6
6
5
7
, and Remove the control front panel
(see previous page)
1
2
3
Installing an I/O extension card, a communication card or a “Controller Inside” programmable card
CAUTION
RISK OF DAMAGE TO THE CONNECTOR
Ensure good positioning of the option card on the clasps to avoid damage to the connector.
Failure to follow these instructions can result in equipment damage.
1760643 03/2011 21
Page 22

Installing the EMC plates

3
4
6
1
5
6
3
4
1
4
2
4
ATV61H 075M3 to D15M3X, ATV61H 075N4 to D18N4 and ATV61H U22S6X to U75S6X
ATV61H D18M3X to D45M3X, ATV61H D22N4 to D75N4 and ATV61H U30Y to D90Y
6
Installing the EMC clamps
Δb
1 - EMC plate for connecting the power cables 2 - EMC plate for connecting the control cables (only for ATV61H 075M3 to D15M3X, ATV61H 075N4 to D18N4 and ATV61H U22S6X to
U75S6X
3 - EMC plate for connecting the I/O option card cables (supplied with the option cards) 4 - M4 screws (supplied) 5 - M8 screws (supplied) 6 - EMC clamps with captive screws (supplied)
ATV61H
075M3 to U40M3, 075N4 to U40N4
U55M3 to D15M3X, U55N4 to D18N4, U22S6X to U75S6X
D18M3X to D45M3X, D22N4 to D75N4, U30Y to D90Y
Δb
mm in.
55 2.17
65 2.56
120 4.72
22 1760643 03/2011
Page 23

Wiring precautions

DANGER
HAZARDOUS VOLTAGE
Connect the device to the protective ground using the grounding point provided, as shown in the figure below. The drive panel must be connected to the protective ground before power is applied.
Failure to follow these instructions will result in death or serious injury.
Drive
Drive
Drive
Power section
The drive must be connected to the protective ground. To comply with current regulations concerning high leakage currents (above 3.5 mA), use at least a 10 mm² (AWG 6) protective conductor or 2 protective conductors with the same cross-section as the power section AC supply conductors.
• Check whether the resistance to the protective ground is one ohm or less. Connect a number of drives to the protective ground as shown in the diagram (see left). Do not lay protective grounding cables in a loop or in series.
WARNING
IMPROPER WIRING PRACTICES
• The ATV61 drive will be damaged if input line voltage is applied to the output terminals (U/T1,V/T2,W/T3).
• Check the power connections before powering up the ATV61 drive.
• If replacing another drive, verify that all wiring connections to the ATV61 drive comply with all wiring instructions in this manual.
Failure to follow these instructions can result in death, serious injury or equipment damage.
When upstream protection by means of a “residual current device” is required by the installation standards, a type A device should be used for single-phase drives and type B for three-phase drives. Choose a suitable model integrating:
• HF current filtering
• A time delay to prevent tripping caused by the load from stray capacitance on power-up. The time delay is not possible for 30 mA devices. In this case, choose devices with immunity against nuisance tripping, for example “residual current devices” with reinforced immunity from
s.i range (Merlin Gerin brand).
the
If the installation includes several drives, provide one residual current device per drive.
WARNING
INADEQUATE OVERCURRENT PROTECTION
• Overcurrent protective devices must be properly coordinated.
• The Canadian Electricity Code and the National Electrical Code require branch circuit protection. Use the fuses recommended on the drive nameplate to achieve published short-circuit current ratings.
• Do not connect the drive to a power feeder whose short-circuit capacity exceeds the drive short-circuit current rating listed on the drive nameplate.
Failure to follow these instructions can result in death, serious injury or equipment damage.
1760643 03/2011 23
Page 24
Wiring recommendations
Keep the power cables separate from circuits in the installation with low-level signals (sensors, PLCs, measuring apparatus, video, telephone).
The motor cables must be at least 0.5 m (20 in.) long.
In certain situations where the motor cables have to be submerged in water, earth leakage currents can cause tripping, requiring the addition of output filters.
Do not use surge arresters or power factor correction capacitors on the variable speed drive output.
CAUTION
IMPROPER USE OF A BRAKING RESISTOR
• Only use the braking resistors recommended in our catalogs.
• Wire the thermal protection contact on the resistor so that the drive power supply is disconnected immediately in the event of a fault (refer to the manual supplied with the resistor).
Failure to follow these instructions can result in injury and/or equipment damage.
Control section
Keep the control circuits away from the power circuits. For control and speed reference circuits, we recommend using shielded twisted cables with a pitch of between 25 and 50 mm (0.98 and 1.97 in.) and connecting the shielding to ground at each end.
If using conduit, do not lay the motor, power supply and control cables in the same conduit. Keep metal conduit containing power supply cables at least 8 cm (3 in.) away from metal conduit containing control cables. Keep non-metal conduits or cable ducts containing power supply cables at least 31 cm (12 in.) away from metal conduits containing control cables. If it is necessary for control and power cables to cross each other, be sure they cross at right angles.
Length of motor cables
ATV61H 0 m
Shielded
075M3 to U75M3 075N4 to D15N4
D11M3X to D45M3X D18N4 to D75N4
U22S6X to U75S6X U30Y to D90Y
With dv/dt filters
With sinus filters
cable Unshielded
cable Shielded
cable Unshielded
cable Shielded
cable
(0 ft)
10 m (32.8 ft)
See catalog
50 m (164 ft)
100 m (328 ft)
150 m (492 ft)
300 m (984 ft)
1000 m
(3280 ft)
Choice of associated components:
Please refer to the catalog.
24 1760643 03/2011
Page 25

Power terminals

Example of ATV61HU22M3
Example of ATV61HD75N4

Access to the power terminals

ATV61H 075M3 to D15M3X and ATV61H 075N4 to D18N4 and ATV61H U22S6X to U75S6X
Unlock the power part access flap and remove it as shown below.
ATV61H D18M3X to D45M3X, ATV61H D22N4 to D75N4 and ATV61H U30Y to D90Y
To access the power terminals, remove the front panel as shown below.
Characteristics and functions of the power terminals
Terminal Function
t
R/L1 S/L2 T/L3
PO DC bus + polarity PA/+ Output to braking resistor (+ polarity) PB Output to braking resistor PC/- DC bus - polarity U/T1
V/T2 W/T3
Protective ground connection terminal Power section AC supply
Outputs to the motor
Only remove the link between PO and PA/+ if a DC choke has been added. The screws on the PO and PA/+ terminals must always be fully tightened as there is a high current flowing in the commoning link.
1760643 03/2011 25
Page 26
Power terminals
PO PA/+ PB PC/-
U/T1 V/T2 W/T3
R/L1 S/L2 T/L3
PO PA/+ PB PC/-
U/T1 V/T2 W/T3
R/L1 S/L2 T/L3
ATV61H 075M3, U15M3, U22M3, U30M3, U40M3,
075N4, U15N4, U22N4, U30N4, U40N4
ATV61H U55M3, U75M3, D11M3X, D15M3X,
U55N4, U75N4, D11N4, D15N4, D18N4, U22S6X, U30S6X, U40S6X, U55S6X, U75S6X
ATV61H D18M3X, D22M3X, D30M3X, D37M3X, D45M3X,
D22N4, D30N4, D37N4, D45N4, D55N4, D75N4
ATV61H
Maximum
wire size
Tightening
torque
mm² AWG Nm
(lb.in)
075M3, U15M3, U22M3, U30M3, U40M3, 075N4, U15N4, U22N4, U30N4, U40N4
68
1.4
(12.3)
ATV61H Maximum
wire size
Tightening
torque
mm² AWG Nm
(lb.in)
U55M3, U55N4, U75N4
68
3
(26.5)
U75M3, D11N4, U22S6X to U75S6X
16 4
3
(26.5)
D11M3X, D15M3X, D15N4, D18N4
25 3
5.4
(47.7)
ATV61H Maximum
wire size
Tightening
torque
mm² AWG Nm
(lb.in)
D18M3X, D22M3X, D22N4, D30N4, D37N4, U30Y to D30Y
50 1/0
12
(106.2)
ATV61H Maximum
wire size
Tightening
torque
mm² kcmils Nm
(lb.in)
D30M3X, D37M3X, D45M3X, D45N4, D55N4, D75N4, D37Y to D90Y
150 300
41
(360)
Arrangement of the power terminals
R/L1 S/L2 T/L3
PO PA/+ PB PC/-
26 1760643 03/2011
U/T1 V/T2 W/T3
Page 27

Control terminals

1
2
R1B
R1A
R1C
R2A
R2C
AI1+
+10
AI1-
COM
AI2
COM
AO1
0V
P24
LI1
LI2
LI3
LI4
LI5
LI6
+24
PWR
RJ45
SW1
SW2
Ext
Source
Sink
Int
PTC
LI
Logic input switch
LI6 input switch
RJ45 connector
Factory setting: Source
Factory setting: LI
Access to the control terminals
Removing the terminal card
To access the control terminals, open the cover on the control front panel.
Arrangement of the control terminals
To make it easier to wire the drive control section, the control terminal card can be removed.
• Undo the screw until the spring is fully extended
• Remove the card by sliding it downwards
CAUTION
IMPROPERLY SECURED TERMINAL CARD
When replacing the control terminal card, it is essential to fully tighten the captive screw.
Failure to follow this instruction can result in injury and/or equipment damage.
Note: The ATV61 is supplied with a link between the PWR and +24 terminals.
1760643 03/2011 27
Maximum wire size:
2.5 mm² - AWG 14
Max. tightening torque:
0.6 Nm - 5.3 lb.in
Page 28
Control terminals
Switch SW1 State 0 State 1 Source (factory
setting)
< 5 V
c > 11 V c
Sink Int or Sink Ext > 16 V c < 10 V c
Characteristics and functions of the control terminals
Terminal Function Electrical characteristics R1A
R1B R1C
R2A R2C
Common point C/O contact (R1C) of programmable relay R1
N/O contact of R2 programmable relay
• Minimum switching capacity: 3 mA for 24 V
• Maximum switching capacity on resistive load
5 A for 250 V a or 30 V c
• Maximum switching current on inductive load (cos ϕ = 0.4 L/R = 7 ms):
2 A for 250 V a or 30 V c
• Reaction time: 7 ms ± 0.5 ms
• Service life: 100,000 operations at max. switching power
c
:
+10 + 10 V
AI1+ AI1 -
c power supply for 1 to 10 kΩ
reference potentiometer
•+10 V c (10.5 V ± 0.5 V)
• 10 mA max.
Differential analog input AI1 • -10 to +10 V c (max. safe voltage 24 V)
• Reaction time: 2 ms ± 0.5 ms, 11-bit resolution + 1 sign bit
• Accuracy ± 0.6% for Δθ = 60°C (140°F), linearity ± 0.15% of max. value COM Analog I/O common 0V AI2 Depending on software configuration:
Analog voltage input
or Analog current input
• Analog input 0 to +10 V
or
• Analog input X - Y mA, X and Y being programmable from 0 to 20 mA
• Impedance
• Reaction time: 2 ms ± 0.5 ms
• 11-bit resolution, accuracy ± 0.6% for Δθ = 60°C (140°F), linearity ± 0.15% of max.
COM Analog I/O common 0V AO1 Depending on software configuration:
Analog voltage output or Analog current output or Logic output
• Analog output 0 to +10 V
or
• Analog output X - Y mA, X and Y being programmable from 0 to 20 mA
• Max. load impedance
• 10-bit resolution, reaction time: 2 ms ± 0.5 ms
• Accuracy ± 1% for Δθ = 60°C (140°F), linearity ± 0.2% of max. value
or
• logic output : 0 to +10V or 0 to 20 mA.
P24 Input for external +24 V
c control
power supply
0V Logic input common and 0 V
•+24 V c (min. 19 V, max. 30 V)
• Power 30 Watts
0V
of P24 external power supply
LI1 LI2 LI3
Programmable logic inputs • +24 V
• Impedance 3.5 kΩ
• Reaction time: 2 ms ± 0.5 ms LI4 LI5
impedance
value
c (max. 30 V)
30 kΩ
c (max. safe voltage 24 V),
250 Ω
c, load impedance greater than 50 kΩ
500 Ω
LI6 Depending on the position of switch
SW2:
- Programmable logic input
or
- Input for PTC probes
+24 Logic input power supply Switch SW1 in Source or Sink Int position
PWR Power Removal safety function input
When PWR is not connected to the 24 V, the motor cannot be started (compliance with functional safety standard EN 954-1, ISO 13849-1 and IEC/EN 61508)
28 1760643 03/2011
Switch SW2 on LI (factory setting)
• Same characteristics as logic inputs LI1 to LI5
or Switch SW2 on PTC
• Trip threshold 3 kΩ, reset threshold 1.8 kΩ
• Short-circuit detection threshold < 50Ω
•+24 V
• Max. current available for customers 200 mA
c power supply (min. 21 V, max. 27 V), protected against short-circuits and overloads
Switch SW1 in Sink Ext position
• Input for external +24 V
c power supply (max. 30 V)
•24 V
Impedance 1.5 kΩ
• State 0 if < 2 V, state 1 if > 17 V
c power supply for the logic inputs
• Reaction time: 10 ms
Page 29

Option terminals

R3A
TH1+
SW3
R3C
R3B0V-10
+24
LI7
LI8
LI9
LI10
TH1-
L01
L02
CLO
0V
Ext
Source
Sink
Int
Logic input switch SW3
Factory setting: Source
Switch SW3 State 0 State 1 Source (factory
setting)
< 5 V
c > 11 V c
Sink Int or Sink Ext > 16 V c < 10 V c

Logic I/O option card terminals (VW3 A3 201)

Characteristics and functions of the terminals
Terminal Function Electrical characteristics R3A
R3B R3C
Common point C/O contact R3C of programmable relay R3
• Minimum switching capacity: 3 mA for 24 V
• Maximum switching capacity on resistive load:
5 A for 250 V a or 30 V c
• Maximum switching capacity on inductive load (cos ϕ = 0.4 L/R = 7 ms):
2 A for 250 V a or 30 V c
• Reaction time: 7 ms ± 0.5 ms
• Service life: 100,000 operations
Maximum wire size:
1.5 mm² - AWG 16
Max. tightening torque:
0.25 Nm - 2.21 lb.in
c
-10 -10 V
c power supply for 1 to 10 kΩ
reference potentiometer
•- 10 V c (-10.5 V ± 0.5 V)
• 10 mA max.
+24 Logic input power supply Switch SW3 in Source or Sink Int position
• +24 V
• Max. current available for customers 200 mA (This current corresponds to the total consumption
c power supply (min. 21 V, max. 27 V), protected against short-circuits and overloads
on the control card +24 and the option cards +24)
Switch SW3 in Sink Ext position
c power supply for the logic inputs
LI7 LI8 LI9
• Input for external +24 V
Programmable logic inputs • +24 V
• Impedance 3.5 kΩ
• Reaction time 2 ms ± 0.5 ms
c power supply (max. 30 V)
LI10
0 V 0 V 0 V
TH1+ PTC probe input • Trip threshold 3 kΩ, reset threshold 1.8 kΩ TH1­LO1
LO2
Open collector programmable logic outputs
• Short-circuit detection threshold < 50 Ω
• +24 V
c (max. 30 V)
• Max. current 200 mA for internal power supply and 200 mA for external power supply
• Reaction time: 2 ms ± 0.5 ms CLO Logic output common 0V 0 V 0 V
1760643 03/2011 29
Page 30
Option terminals
R4A
0V
SW4
TH2+
R4B
AO3
R4C
-10
AI3+
AI3-
AI4
COM
AO2
+24
LI11
LI12
LI13
LI14
CLO
0V
LO4 LO3 RP TH2-
Ext
Source
Sink
Int
Logic input switch SW4
Factory setting: Source

Extended I/O option card terminals (VW3 A3 202)

Maximum wire size:
1.5 mm² - AWG 16
Max. tightening torque:
0.25 Nm - 2.21 lb.in
Characteristics and functions of the terminals
Terminal Function Electrical characteristics R4A
R4B R4C
-10 -10 V
AI3 + + polarity of the current differential
AI3- - polarity of the current differential
AI4 Depending on software configuration:
COM Analog I/O common 0 V AO2
AO3
Common point C/O contact R4C of programmable relay R4
c power supply for 1 to 10 kΩ
reference potentiometer
analog input AI3
analog input AI3
Analog current input
or Analog voltage input
Depending on software configuration: Analog voltage outputs
or Analog current outputs
• Minimum switching capacity: 3 mA for 24 V
• Maximum switching capacity on resistive load:
5 A for 250 V a or 30 V c
• Maximum switching capacity on inductive load (cos ϕ = 0.4 L/R = 7 ms):
1.5 A for 250 V a
• Reaction time: 10 ms ± 1 ms
• Service life: 100,000 operations
•- 10 V c (-10.5 V ± 0.5 V)
• 10 mA max.
• Analog input X - Y mA, X and Y being programmable from 0 to 20 mA,
impedance 250 Ω
• Reaction time: 5 ms ± 1 ms
• 11-bit resolution + 1 sign bit, accuracy ± 0.6% for Δθ = 60°C (140°F)
• Linearity ± 0.15% of max. value
• Analog input 0 to +10 V
impedance
30 kΩ
or
• Analog input X - Y mA, X and Y being programmable from 0 to 20 mA,
impedance
250 Ω
• Reaction time: 5 ms ± 1 ms
• 11-bit resolution, accuracy ± 0.6% for Δθ = 60°C (140°F), linearity ± 0.15% of max.
value
•0 - 10 V
c or -10/+10 V c bipolar analog output depending on software configuration, load
impedance greater than 50 kΩ
or
• Analog current output X-Y mA, X and Y being programmable from 0 to 20 mA, max.
load impedance 500 Ω
• 10-bit resolution
• Reaction time 5 ms ± 1 ms, accuracy ± 1% for Δθ = 60°C (140°F), linearity ± 0.2%
or 30 V c
c (max. safe voltage 24 V),
c
30 1760643 03/2011
Page 31
Option terminals
Switch SW4 State 0 State 1 Source (factory
setting)
< 5 V
c > 11 V c
Sink Int or Sink Ext > 16 V c < 10 V c
Terminal Function Electrical characteristics +24 Logic input power supply Switch SW4 in Source or Sink Int position
•+24 V
• Max. current available for customers 200 mA (This current corresponds to the total consumption
c output (min. 21 V, max. 27 V), protected against short-circuits and overloads
on the control card +24 and the option cards +24)
Switch SW4 in Sink Ext position
c power supply for the logic inputs
LI11 LI12 LI13
• Input for external +24 V
Programmable logic inputs • +24 V
• Impedance 3.5 kΩ
• Reaction time: 5 ms ± 1 ms
c (max. 30 V)
LI14
0V Logic input common 0 V
TH2 + TH2 -
PTC probe input • Trip threshold 3 kΩ, reset threshold 1.8 kΩ
• Short-circuit detection threshold < 50Ω
RP Frequency input • Frequency range: 030 kHz
• Cyclic ratio: 50% ± 10%
• Maximum sampling time: 5 ms ± 1 ms
• Maximum input voltage 30 V, 15 mA
• Add a resistor if the input voltage is greater than 5 V (510 Ω for 12 V, 910 Ω for 15 V, 1.3 kΩ for 24 V)
• State 0 if < 1.2 V, state 1 if > 3.5 V
LO3 LO4
Open collector programmable logic outputs
•+24 V
• Max. current 20 mA for internal power supply and 200 mA for external power supply
c (max. 30 V)
• Reaction time 5 ms ± 1 ms
CLO Logic output common 0V 0 V 0 V
1760643 03/2011 31
Page 32
Option terminals
VW3 A3 401...407
A A
B
B
0Vs
+Vs
VW3 A3 411
A + A ­B + B ­Z + Z ­P 0 OA + OA ­OB + OB -
OZ + OZ -

Encoder interface card terminals

Maximum wire size:
1.5 mm² - AWG 16
Max. tightening torque:
0.25 Nm - 2.21 lb.in
Characteristics and functions of the terminals
Encoder interface cards with RS422-compatible differential outputs
Terminal Function Electrical characteristics
VW3 A3 401 VW3 A3 402 +Vs Power supply 0Vs
A, /A B, /B
Encoder interface cards with open collector outputs
Terminal Function Electrical characteristics
+Vs Power supply 0Vs
A, /A B, /B
Encoder interface cards with push-pull outputs
Terminal Function Electrical characteristics
+Vs Power supply 0Vs
A, /A B, /B
for encoder
Incremental logic inputs
for encoder
Incremental logic inputs
for encoder
State 0 If < 1.5 V State 1 If > 7.7 V and < 13 V If > 7.7 V and < 16 V If > 11.5 V and < 25 V
Incremental logic inputs
•5 V c (max. 5.5 V) protected against short-circuits
and overloads
• Max. current 200 mA
• Max. resolution: 5,000 points/rev
• Max. frequency: 300 kHz
• Nominal input voltage: 5 V
VW3 A3 403 VW3 A3 404
• 12 V c (max. 13 V) protected against short-circuits
and overloads
• Max. current 175 mA
• Max. resolution: 5,000 points/rev
• Max. frequency: 300 kHz
VW3 A3 405 VW3 A3 406 VW3 A3 407
• 12 V c (max. 13 V) protected
against short-circuits and overloads
• Max. current 175 mA
• Max. resolution: 5,000 points/rev
• Max. frequency: 300 kHz
• 15 V c (max. 16 V) protected
against short-circuits and overloads
• Max. current 175 mA
•15 V c (max. 16 V) protected against short-circuits
and overloads
• Max. current 175 mA
•15 V c (max. 16 V) protected against short-circuits
and overloads
• Max. current 175 mA
• 24 V c (min. 20 V, max. 30 V)
protected against short-circuits and overloads
• Max. current 100 mA
32 1760643 03/2011
Page 33
Option terminals
ON
12345
Encoder interface cards with RS422 compatible differential outputs with encoder emulation
Terminal Function Electrical characteristics
VW3 A3 411 P Encoder power 0
A+, A­B+, B­Z+, Z-
OA+, OA­OB+, OB­OZ+, OZ-
This encoder card has two groups of parameter switches:
• The first is for selecting the supply voltage supplied by the interface card to the encoder: 5 V or 15 V.
• The second is a set of five switches numbered 1 to 5 (see diagram below). The division ratio for the ESIM outputs is selected using switches 1, 2 and 3. Switches 4 and 5 are used to select the input signals for the encoder card. Fault detection will be inhibited for the inputs selected using these switches.
123ESIM outputs 45Encoder inputs
ON ON ON A and B divided by 1 ON ON Encoder A, B and Z ON ON OFF A and B divided by 2 ON OFF Encoder A and B ON OFF ON A and B divided by 4 OFF ON Encoder A and B ON OFF OFF A and B divided by 8 OFF OFF Encoder A OFF ON ON A and B divided by 16 OFF ON OFF A and B divided by 32 OFF OFF ON A and B divided by 64 OFF OFF OFF ESIM disabled
supply
Logic inputs • Max. resolution: 10,000 points/rev
Logic outputs • Selectable ratio: 1, 1/2, 1/4, 1/8, 1/16, 1/32, 1/64
•5 V c (max. 5.5 V) protected against short-circuits
and overloads
• Max. current 200 mA
• Max. frequency: 300 kHz
• Nominal input voltage: 5 V
• Max. frequency: 300 kHz
•15 V c (max. 16 V) protected against short-circuits
and overloads
• Max. current 200 mA

Selecting the encoder

The 8 encoder interface cards available as an option with the ATV61 enable three different encoder technologies to be used.
• Optical incremental encoder with differential outputs compatible with the RS422 standard
• Optical incremental encoder with open collector outputs
• Optical incremental encoder with push-pull outputs
• Incremental encoder with RS422-compatible differential outputs with encoder emulation
The encoder must comply with the following two limits:
• Maximum encoder frequency 300 kHz
• Maximum resolution 5,000 points/revolution
Choose the max. standard resolution within these two limits to obtain optimum accuracy.
1760643 03/2011 33
Page 34

Connection diagrams

Wiring the encoder

Use a shielded cable containing 3 twisted pairs with a pitch of between 25 and 50 mm (0.98 in. and 1.97 in.). Connect the shielding to ground at both ends. The minimum cross-section of the conductors must comply with the table below to limit line voltage drop.
Max. encoder
cable length
10 m
32.8 ft
50 m
164 ft
100 m
328 ft
200 m
656 ft
300 m
984 ft
Max. encoder
cable length
25 m
82 ft
50 m
164 ft
100 m
328 ft
VW3 A3 401...402 VW3 A3 403...407
Max. consumption current of encoder
100 mA 0.2 mm² AWG 24 100 mA 0.2 mm² AWG 24 200 mA 0.2 mm² AWG 24 200 mA 0.2 mm² AWG 24 100 mA 0.5 mm² AWG 20 100 mA 0.5 mm² AWG 20 200 mA 0.75 mm² AWG 18 200 mA 0.75 mm² AWG 18 100 mA 0.75 mm² AWG 18 100 mA 0.75 mm² AWG 18 200 mA 1.5 mm² AWG 15 200 mA 1.5 mm² AWG 16
- - - 100 mA 0.5 mm² AWG 20
- - - 200 mA 1.5 mm² AWG 15
- - - 100 mA 0.75 mm² AWG 18
- - - 200 mA 1.5 mm² AWG 15
Max. consumption current of encoder
100 mA 0.2 mm² AWG 24 0.5 mm² AWG 20 200 mA 0.5 mm² AWG 20 1 mm² AWG 17 100 mA 0.5 mm² AWG 20 0.75 mm² AWG 18 200 mA 0.75 mm² AWG 18 1.5 mm² AWG 15 100 mA 0.75 mm² AWG 18 - ­200 mA 1.5 mm² AWG 15 - -
Minimum cross-section of
conductors
VW3 A3 411
Minimum cross-section of conductors
15 V power supply 5 V power supply
Max. consumption current of encoder
Minimum cross-section of
conductors
34 1760643 03/2011
Page 35
Connection diagrams
ATV61HpppM3
U / T1
V / T2
W / T3
R / L1
M
3 a
S / L2
T / L3
A1
R1A
R1C
R1B
R2A
R2C
(2)
(1)
- KM1
- KM1 A2A1
- S1
- S2
R1CR1A
- KM1
- T1
- Q2
- Q3
- Q2
A1
U1
W1
V1
PWR
+24
P0
PA / +
PB
PC / -
2 a
Braking resistor (if used)
ATV61HpppM3
U / T1
V / T2
W / T3
R / L1
U1
W1
V1
M
3 a
S / L2
T / L3
A1
R1A
R1C
R1B
R2A
R2C
(1)
(2)
P0
PA / +
PB
PC / -
Q1
PWR
+24
2 a
Braking resistor (if used)

Connection diagrams conforming to standards EN 954-1 category 1, ISO 13849-1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204 1

Single-phase power supply (ATV61H 075M3 to U75M3)
Diagram with line contactor
Diagram with switch disconnect
(1)Line choke, if used (compulsory for ATV61H U40M3 to U75M3 drives) (2) Fault relay contacts for remote signaling of drive status
Inhibit the input phase loss fault (IPL) so that ATV61H 075M3 to U75M3 drives can operate on a single-phase supply (see the Programming Manual). If this fault is set to its factory configuration, the drive will stay locked in fault mode.
Note: Install interference suppressors on all inductive circuits near the drive or connected to the same circuit (relays, contactors, solenoid valves, etc).
Choice of associated components:
Please refer to the catalog.
1760643 03/2011 35
Page 36
Connection diagrams
U / T1
V / T2
W / T3
R / L1
M
3 a
S / L2
T / L3
+24
PWR
A1
R1A
R1C
R1B
R2A
R2C
(2)
- KM1
- KM1 A2A1
- S1
- S2
R1CR1A
- KM1
- T1
- Q2
- Q3
- Q2
A1
U1
W1
V1
(1)
P0
PA / +
PB
PC / -
3 a
ATV61Hppppp
Braking resistor (if used)
U / T1
V / T2
W / T3
R / L1
U1
W1
V1
M
3 a
S / L2
T / L3
PWR
+24
A1
R1A
R1C
R1B
R2A
R2C
(1)
(2)
Q1
P0
PA / +
PB
PC / -
3 a
ATV61Hppppp
Braking resistor (if used)

Connection diagrams conforming to standards EN 954-1 category 1, ISO 13849-1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1

Three-phase power supply
Diagram with line contactor
Diagram with switch disconnect
(1)Line choke (if used) (2) Fault relay contacts for remote signaling of drive status
Note: Install interference suppressors on all inductive circuits near the drive or coupled to the same circuit (relays, contactors, solenoid valves, etc).
Choice of associated components:
Please refer to the catalog.
36 1760643 03/2011
Page 37
Connection diagrams
U / T1
V / T2
W / T3
R / L1
U1
W1
V1
M
3 a
S / L2
T / L3
+24
PWR
A1
R1A
R1C
R1B
LI1
LI6
S2
A1 23 33Y2 13
A2
PE
14 24 34
Y43
Y44
Y1
K2K1
48 V, 115 V, 230 V
K1
K2
T
ESC
XPS AC
S1
F1
LI2
L1(+)
N(-)
P0
PA / +
PB
PC / -
(1)
3 a
(2)
(3)
ATV61Hppppp
Braking resistor (if used)
Logic

Connection diagrams conforming to standards EN 954-1 category 3, ISO 13849-1 and IEC/EN 61508 capacity SIL2, stopping category 0 in accordance with standard IEC/EN 60204-1

This connection diagram is suitable for use with machines with a short freewheel stop time (machines with low inertia or high resistive torque). When the stop request is activated, the motor power supply is cut immediately and it stops in accordance with category 0 of standard IEC/EN 60204-1.
(1)Line choke (if used) (2)It is essential to ground the shielding on the cable connected to the Power Removal input. (3)Use cable ends DZ5CE020 (yellow) on wires connected to PWR and +24 inputs.
- Standard EN 954-1 category 3 and ISO 13849-1 require the use of a dual-contact stop button (S1).
- S1 is used to activate the Power Removal safety function.
- S2 is used to initialize the Preventa module when powering up or after an emergency stop. ESC enables the use of other initialization conditions for the module.
- One Preventa module can be used for the Power Removal safety function on several ATV61 drives.
- A logic output on the Preventa module can be used to indicate reliably that the drive is operating in safe conditions.
Note:
For preventive maintenance, the Power Removal function must be activated at least once a year. The drive power supply must be turned off and then on again before carrying out this preventive maintenance.
The drive logic output signals cannot be considered as safety-type signals. Install interference suppressors on all inductive circuits near the drive or coupled to the same circuit (relays, contactors, solenoid valves, etc).
Choice of associated components:
Please refer to the catalog.
1760643 03/2011 37
Page 38
Connection diagrams
S1
F1
ESC
U / T1
V / T2
W / T3
R / L1
U1
W1
V1
M
3 a
S / L2
T / L3
+24
PWR
A1
R1A
R1C
R1B
LI1
LI6
LI2
S21 S11
A1
A2 PE Y1
13
T
-+
115 V 230 V
2
K2
K1
K3
K4
K1 K2K3
23
24
14 34 42 6858
33 41 57 67
B1 S12 S22
S33
XPS AT
Y2 Y3
K4
K1 K2
K2
K1
1
Y4 Y5
K3
K4
S2
N(-)
L1(+)
(1)
P0
PA / +
PB
PC / -
(2)
(3)
(4)
3 a
ATV61Hppppp
Braking resistor (if used)
Logic

Connection diagram conforming to standards EN 954-1 category 3, ISO 13849-1 and IEC/EN 61508 capacity SIL2, stopping category 1 in accordance with standard IEC/EN 60204-1

This connection diagram is suitable for use with machines with a long freewheel stop time (machines with high inertia or low resistive torque).
When the stop request is activated, deceleration of the motor, controlled by the drive, is requested first. Then, after a time delay corresponding to the deceleration time, the Power Removal safety function is activated.
Example:
- 2-wire control
- LI1 assigned to forward
- LI2 assigned to reverse
(1)In this example, the logic inputs LI (2)Line choke (if used) (3)It is essential to ground the shielding on the cable connected to the Power Removal input. (4)Use cable ends DZ5CE020 (yellow) on wires connected to PWR and +24 inputs.
- Standard EN 954-1 category 3 and ISO 13849-1 require the use of a dual-contact stop button (S1).
- S1 is used to activate the Power Removal safety function.
- S2 is used to initialize the Preventa module when powering up or after an emergency stop. ESC enables the use of other initialization conditions for the module.
- One Preventa module can be used for the Power Removal safety function on several ATV61 drives. In this case the time delay must be set to the longest stopping time.
p are wired as “Source” but can be wired as “Sink Int” or “Sink Ext”.
- A logic output on the Preventa module can be used to indicate reliably that the drive is operating in safe conditions.
Note:
For preventive maintenance, the Power Removal function must be activated at least once a year. The drive power supply must be turned off and then on again before carrying out this preventive maintenance.
The drive logic output signals cannot be considered as safety-type signals. Install interference suppressors on all inductive circuits near the drive or coupled to the same circuit (relays, contactors, solenoid valves, etc).
Choice of associated components:
Please refer to the catalog.
38 1760643 03/2011
Page 39
Connection diagrams
LI1
LI5
+24
0V
A1
ATV61Hppppp
PWR
+10
AI1+
AI2
AI1-
COM
COM
AO1
LI3
LI2
LI6
LI4
Reference potentiometer
0 ± 10 V or X-Y mA
A1
ATV61Hppppp
SW1
Ext
Source
Sink
Int
LI1
LI5
+24
0V
LI3
LI2
LI6
LI4
A1
ATV61Hppppp
SW1
Ext
Source
Sink
Int
LI1
LI5
+24
0V
LI3
LI2
LI6
LI4
+24 V
0 V
24 V c supply
A1
ATV61Hppppp
SW1
Ext
Source
Sink
Int
LI1
LI5
+24
0V
LI3
LI2
LI6
LI4
A1
ATV61Hppppp
SW1
Ext
Source
Sink
Int
LI1
LI5
+24
0V
LI3
LI2
LI6
LI4
+24 V
0 V
24 V c supply

Control connection diagrams

Control card connection diagram
Logic input switch (SW1)
The logic input switch (SW1) is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
• Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
• Set the switch to Sink Int or Sink Ext if using PLC outputs with NPN transistors.
• Switch SW1 set to “Source” position
• Switch SW1 set to “Source” position and use of an external power
supply for the LIs
• Switch SW1 set to “Sink Int” position • Switch SW1 set to “Sink Ext” position
WARNING
UNINTENDED EQUIPMENT OPERATION
When switch SW1 is set to “Sink Int” or “Sink Ext”, the common must never be connected to ground or the protective ground, as there is then a risk of unintended equipment operation on the first insulation fault.
1760643 03/2011 39
Failure to follow this instruction can result in death, serious injury or equipment damage.
Page 40
Connection diagrams
- 10 V
+ 10 V
COM
AI1+
AI1-
A1
ATV61Hppppp
±10 V c supply
+
COM
AI1+
AI1-
A1
ATV61Hppppp
0V
-
Axis control
±10 V
reference
0V
LI6
A1
ATV61Hppppp
PTC
LI
SW2
Motor
A1
ATV61Hppppp
P240V
+24 V
0 V
24 V c supply
Bipolar speed reference
Speed reference using axis control
Switch SW2
The LI6 logic input switch (SW2) makes it possible to use the LI6 input:
- Either as a logic input by setting the switch to LI (factory setting)
- Or for motor protection via PTC probes by setting the switch to PTC
Control power supply via an external source
The control card can be supplied via an external +24 V c supply source
40 1760643 03/2011
Page 41
Connection diagrams
+24
VW3 A3 202
0V
RP
CLO
LO4
LO3
LI11
0V
TH2+
TH2-
AO2
AO3
COM
AI4
AI3-
AI3+
R4A
R4C
R4B
A1
0 ± 10 V or X-Y mA
Motor
0-20 mA 4-20 mA X-Y mA supply
+24
VW3 A3 201
CLO
LO2
LO1
LI7
0V
TH1+
TH1-
R3A
R3C
R3B
A1
Motor

I/O extension card connection diagrams

Connection diagram for extended I/O option card (VW3 A3 202)
Connection diagram for logic I/O option card (VW3 A3 201)
1760643 03/2011 41
Page 42
Connection diagrams
A1
VW3 A3 20p
+24
CLO
LOp
LIp
0V
Ext
Source
Sink
Int
SW3 or SW4
+24V
0V
+24
CLO
LOp
LIp
0V
A1
VW3 A3 20p
Ext
Source
Sink
Int
24 V c supply
SW3 or SW4
A1
+24
CLO
LOp
LIp
0V
VW3 A3 20p
Ext
Source
Sink
Int
SW3 or SW4
+24V
0V
+24
CLO
0V
LOp
LIp
A1
VW3 A3 20p
Ext
Source
Sink
Int
24 V c supply
SW3 or SW4
SW3/SW4 logic I/O switch
• Switch in “Source” position • Switch in “Source” position and use of an external +24 Vc supply
source
• Switch in “Sink Int” position • Switch in “Sink Ext” position
WARNING
UNINTENDED EQUIPMENT OPERATION
When switches SW3 or SW4 are set to “Sink Int” or “Sink Ext”, the common must never be connected to ground or the protective ground, as there is then a risk of unintended equipment operation on the first insulation fault.
Failure to follow this instruction can result in death, serious injury or equipment damage.
42 1760643 03/2011
Page 43
Connection diagrams
F1 F2
F3
U / T1
V / T2
W / T3
U1
W1
V1
M1
3 a
ATV61Hppppp
PO
PC/-
U / T1
V / T2
W / T3
U2
W2
V2
M2
3 a
ATV61Hppppp
PO
PC/-
U / T1
V / T2
W / T3
U3
W3
V3
M3
3 a
ATV61Hppppp
PO
PC/-
1 2
3
R / L1
S / L2
T / L3
R / L1
S / L2
T / L3
R / L1
S / L2
T / L3
3 a
123

Connection of several drives in parallel on the DC bus

Connection in parallel on the DC bus is recommended in applications for which full motor power must be guaranteed.
Each drive uses its own charging circuit
Drives , and must not be more than one size apart when they are connected in this way.
F1, F2, F3: Fast-acting semiconductor fuses for protection on the DC bus side.
1760643 03/2011 43
Page 44

Use on IT system and “corner grounded” system

Normal (filter connected)
IT system (filter disconnected)
ATV61pD22N4
IT system: Isolated or impedance grounded neutral Use a permanent insulation monitor compatible with non-linear loads, such as a Merlin Gerin type XM200 or equivalent. “Corner grounded” system: System with one phase connected to ground
Altivar 61 drives feature built-in RFI filters. When using ATV61H U30Y to D90Y drives on an IT system, the link between these filters and ground must be removed as shown in the following two diagrams. For other catalog numbers, removal of this link is possible but not mandatory:
Remove the jumper located to the left of the power terminals (two jumpers for
CAUTION
RISK OF DAMAGE TO THE DRIVE
On ATV61p075N4 to U40N4 ratings, if the filters are disconnected, the drive's switching frequency must not exceed 4 kHz. Refer to the Programming Manual for the corresponding parameter setting.
Failure to follow these instructions can result in injury and/or equipment damage.
ATV61 pD22N4).
44 1760643 03/2011
Page 45
Use on IT system and “corner grounded” system
Normal (filter connected)
IT system (filter disconnected)
Disconnection of the filter on ATV61H D37Y to D90Y products
WARNING
RISK OF ELECTRIC SHOCK
• ATV61H U30Y to D90Y drives must not be connected to a “corner grounded” system.
•ATV61HpppS6X must not be used with corner grounded systems in case of altitude is higher than 2000m.
Failure to follow this instruction can result in death, serious injury or equipment damage.
1760643 03/2011 45
Page 46

Electromagnetic compatibility, wiring

1
2
5
4
10
3
6
12
7
11
13
8
9

Electromagnetic compatibility

Principle
• Grounds between drive, motor and cable shielding must have “high-frequency” equipotentiality.
• Use of shielded cables with shielding connected to ground at both ends for the motor cables, braking resistor (if used) and control-signal wiring. Metal ducting or conduit can be used for part of the shielding length provided that there is no break in continuity.
• Ensure maximum separation between the power supply cable (line supply) and the motor cable.
Installation diagram
ATV61H 075M3 to D15M3X, ATV61H 075N4 to D18N4 and ATV61H U22S6X to U75S6X
• Attach and ground the shielding of cables 4 and 5 as close as possible to the drive:
- Strip the shielding.
- Use stainless steel metal clamps on the parts from which the shielding has been stripped, to attach them to the metal plate 2. The shielding must be clamped tightly enough to the metal plate to ensure correct contact.
• Install the control EMC plate 11 on the sheet steel grounded plate 2, as shown in the diagram.
• Attach and ground the shielding of cables 7, 12 and 13 as close as possible to the drive:
- Strip the shielding.
- Use stainless steel metal clamps on the parts from which the shielding has been stripped, to attach them to the control EMC flange 9. The shielding must be clamped tightly enough to the metal plate to ensure correct contact.
1 Altivar 61
2 Sheet steel grounded plate supplied with the drive
3 Tapped holes for installing the control EMC plate
4 Shielded cable for motor connection, with shielding connected to ground
at both ends. The shielding must be continuous and intermediate terminals must be in EMC shielded metal boxes.
5 Shielded cable for connecting the braking resistor (if used). The shielding must be continuous and intermediate terminals must be in EMC shielded metal boxes.
6 Non-shielded wires for relay contact output
7 Shielded cables for connecting the Power Removal safety function input.
The shielding must be continuous and intermediate terminals must be in EMC shielded metal boxes.
8 Metal clamps
9 Protective ground connection
10 Unshielded power supply cable or wires
11 Control EMC plate
12 Shielded cables for connecting the control-signal section. For applications
requiring several conductors, use cables with a small cross-section (0.5 mm
2
- AWG 20).
Note:
• If using an additional input filter, it should be installed under the drive and connected directly to the line supply via an unshielded cable.
13 Shielded cables for connecting the encoder The shielding must be continuous and intermediate terminals must be in EMC shielded metal boxes.
Link 10 on the drive is then established via the filter output cable.
• The HF equipotential ground connection between the drive, motor and cable shielding does not remove the need to connect the PE protective conductors (green-yellow) to the appropriate terminals on each unit.
46 1760643 03/2011
Page 47
Electromagnetic compatibility, wiring
1
2
5
3
4
6
7
8
10
11
9
Installation diagram
ATV61H D18M3X to D45M3X, ATV61H D22N4 to D75N4 and ATV61H U30Y to D90Y
Attach and ground the shielding of cables 4 and 5 as close as possible to the drive:
- Strip the shielding.
- Use stainless steel metal clamps on the parts from which the shielding has been stripped, to attach them to the metal plate 2.
The shielding must be clamped tightly enough to the metal plate to ensure correct contact.
• Attach and ground the shielding of cables 6
, 7 and 8 as close as possible to the drive:
- Strip the shielding.
- Use stainless steel metal clamps on the parts from which the shielding has been stripped, to attach them to the drive. The shielding must be clamped tightly enough to the metal plate to ensure correct contact.
1 Altivar 61
2 Sheet steel grounded plate supplied with the drive
3 Metal clamps
4 Shielded cable for motor connection, with shielding connected to ground at
both ends. The shielding must be continuous and intermediate terminals must be in EMC shielded metal boxes.
5 Shielded cable for connecting the braking resistor (if used). The shielding must be continuous and intermediate terminals must be in EMC shielded metal boxes.
6 Shielded cables for connecting the control-signal section. For applications requiring several conductors, use cables with a small cross-section (0.5 mm
2
- AWG 20).
7 Shielded cables for connecting the Power Removal safety function input. The shielding must be continuous and intermediate terminals must be in EMC shielded metal boxes.
8 Shielded cables for connecting the encoder. The shielding must be continuous and intermediate terminals must be in EMC shielded metal boxes.
9 Non-shielded wires for relay contact output
10 Protective ground connection
11 Unshielded power supply cable or wires
Note:
• If using an additional input filter, it should be installed under the drive and connected directly to the line supply via an unshielded cable. Link 4 on the drive is then established via the filter output cable.
• The HF equipotential ground connection between the drive, motor and cable shielding does not remove the need to connect the PE protective conductors (green-yellow) to the appropriate terminals on each unit.
1760643 03/2011 47
Page 48
48 1760643 03/2011
Page 49
ATV61S_installation_manual_EN_1760643_05
1760643 03/2011
Loading...