Rudd RAPL-042JEZ Installation Manual

0 (0)
Rudd RAPL-042JEZ Installation  Manual

FORM NO. A11-195

Supersedes Form No. A11-195

CONDENSING UNITS

RAPLJEZ

e a r t h f r i e n d l y r e f r i g e r a n t

14 SEER Models

Efficiencies up to 16.00 SEER Nominal Sizes 11/2 to 5 Tons [5.28 kW] to [17.6 kW]

Seven Models

Cooling Capacities 18,200 to 59,500 BTU/HR [5.33 kW] to [17.44 kW]

Equipped with

Comfort Control System

Increased Reliability

On-Board Diagnostics

Fault Recall

Active Protection

The Rheem Prestige Series™ High Efficiency RAPLJEZ Condensing Units were designed with performance in mind. These units offer comfort, energy conservation and dependability for single, multi-family and light commercial applications.

These units also contain the most advanced alternate refrigerant which contains no chlorofluorocarbons (CFCs), or hydrochlorofluorocarbons (HCFCs), or other compounds that may leak from airconditioning systems and potentially harm the protective ozone layer of the Earth’s atmosphere.

The Rheem Prestige Series™ RAPLJEZ Condensing Units are the result of an ongoing development program for improved efficiencies. These units are flexible enough to achieve up to 16.00 SEER in specific match-ups, continuing a tradition of high efficiency.

The Comfort Control System™ provides on-board diagnostics and fault history for condensing units with single-phase compressors by detecting system and electrical problems without adding sensors. It can also communicate “fault codes” to enabled “L terminal” thermostats. The integrated diagnostics with Active Protection™ prevents compressor operation when potentially harmful conditions are detected.

7-Segment LED Display is exclusive only to Rheem products. The information-display quickly and accurately shows technicians the source of malfunctions.

Features a five-year conditional unit replacement warranty when properly installed with a new Rheem Prestige Series™ Air Handler or Rheem Indoor Coil with a Prestige Series™ Gas Furnace. See product warranty card for additional information.

Compressor sound blanket is standard to provide quiet operation.

Attractive, louvered wrap-around jacket protects the coil from yard hazards and weather extremes. Top grille is steel reinforced for extra strength. Cabinet is powder painted for allweather protection.

Air is discharged upward away from bushes and shrubs. The discharge pattern of the top grille provides minimum air restriction.

Combination Grille/Motor Mount secures the motor to the underside of the discharge grille. The grille protects the motor windings and bearings from rain and snow.

Removable top grille provides access to the condenser fan motor and condenser coil.

Single speed 8-pole fan motor designed for low speed, quiet, energy-saving operation.

All models meet or exceed a 1000-hour salt spray test per ASTM B117 Standard Practice for Operating Salt Spray Testing Apparatus.

14 SEER MODELS

(IN CERTAIN MATCHED SYSTEMS)

All controls and compressor are accessible for servicing by removal of the service panel.

FEATURES & BENEFITS OF THE COMFORT CONTROL SYSTEM

The Rheem exclusive 7-Segment LED Display easily shows system operating status codes and

diagnostic codes.

A Sealed Switch replaces the standard

contactor and features optical control and latching mechanism. The sealed switch prevents infiltration of

insects and dust. A minimal switching arc, by the optical control, offers greater reliability. The latching mechanism consumes less power while reducing chatter.

The Status Indication and System Diagnostics feature thermostat communication capability, built-in diagnostics, high & low voltage monitoring and high & low pressure switch monitoring. The thermostat communication capability alerts the homeowner to any necessary service requirements. Faster, more accurate service is provided by the built-in diagnostics, by providing the HVAC professional with

dependable information. With the high and low voltage monitoring feature, the control provides alerts for out-of- range conditions. In addition, high and low pressure-switch monitoring prevents the system from operating outside of its normal parameters.

STANDARD FEATURES

RAPLJEZ Condensing Units

1.This unit contains a special scroll compressor that is designed specifically to operate with R-410A refrigerants and polyolester (POE) oils. The compressor is hermetically sealed and incorporates internal high temperature motor overload protection and durable insulation on the motor windings. It is externally mounted on rubber grommets to reduce vibration and noise.

2.Scroll compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor windings. It is externally mounted on rubber grommets to reduce vibration and noise.

3.Compressors have an internal pressure relief assembly to protect against excessive pressure differential.

4.All refrigerant connections are on the exterior of the unit, located close to the ground for neat appearing installations.

5.Cabinet is constructed of powder painted galvanized steel. The full wrap-around louvered grille protects the coil from damage.

6.Enhanced compressor sound blanket is standard.

7.Copper tube—aluminum fin coils are used on all models.

8.The control box is located in the top corner of the cabinet providing for easy access through a service panel.

9.Service valves are standard on all models.

10.Field connections for power and control wiring are kept separate.

11.Every unit is factory charged and run-tested.

12.Separate compressor compartment for easy service access.

13.Drawn, painted base pan for extra corrosion resistance and sound reduction.

14.The RAPLJEZ has a 10 year limited compressor warranty, plus a 5 year conditional unit replacement warranty. See General Terms of Limited Warranty for more details.

15.Hard Start Kits—Standard on all JEZ models.

16.Control Box Cover.

17.Automatic reset high and low pressure controls are standard on all JEZ models.

18.Liquid line filter drier is standard on all models (shipped – not installed).

The fault recall feature will allow for the last six fault-codes to be displayed, and will retain these codes even if power failure occurs.

Built-in short-cycle protection allows the compressor to restart easily without oil removal.

A 30-second minimum run-time for every compressor call enables the oil return to the compressor.

Active Protection monitors the system to prevent nuisance lockouts and prevents compressor operation when potentially harmful conditions are detected.

The compressor and fan are controlled independently, which reduces the starting load and light dimming.

A push-button is offered to operate the compressor and fan for 5 seconds to allow for an operation check.

In order to save time and money, replacement automo-

tive fuses can be utilized instead of replacing the entire control board.

SCROLL® COMPRESSOR

The scroll compressor is the key to efficiency for this Rheem model. It’s the latest in high-efficiency compressor technology. The advanced scroll compressor

offers low noise and vibration characteristics and features tolerance to liquid refrigerant and system contamination. The scroll compressor also has low start torque, eliminating start problems in the field. And its unique design enables the RAPLJEZ condensing units to perform efficiently, quietly and dependably.

2 Rheem Heating, Cooling and Water Heating

Model Number Identification

R

A

P

L

A*

 

J

E

Z

018

 

 

 

 

 

 

VARIATIONS

 

 

 

 

RHEEM

REMOTE

P = 14 SEER

DESIGN

 

A = STANDARD

ELECTRICAL

VARIATIONS

COOLING

 

COOLING

 

 

CONDENSING

 

SERIES

 

CAPACITY

 

DESIGNATION

EQUIPPED WITH

CONNECTION

 

UNIT

 

 

 

 

 

 

FITTING

 

 

L = R-410A

018 = 18,000 BTU/HR

[5.28 kW]

J = 208/230V-1-60

THE COMFORT

 

 

 

 

 

 

 

 

 

(RAPL MODELS ONLY)

 

CONTROL SYSTEM

Z = SWEAT

 

 

 

 

024

= 24,000 BTU/HR

[7.03 kW]

 

 

W/SCROLL

 

 

 

 

030

= 30,000 BTU/HR

[8.79 kW]

 

 

 

 

 

 

 

036

= 36,000 BTU/HR [10.55 kW]

 

 

 

 

 

 

 

042

= 42,000 BTU/HR [12.31 kW]

 

 

 

 

 

 

 

048

= 48,000 BTU/HR [14.07 kW]

 

 

 

 

 

 

 

060

= 60,000 BTU/HR [17.58 kW]

 

 

 

Field Installed Accessories

Low Ambient Control—Cycles outdoor fan to maintain adequate condensing pressures assuring liquid refrigerant flow to the coil. Allows indoor cooling with outdoor temperatures down to 0°F [–17.8°C]. (Model No. RXAD-A08)

It is recommended that this control be installed in units to be operated at outdoor ambient temperatures under 70°F [21°C].

Thermostats

Compressor Crankcase Heater (CCH)—While scroll compressors usually do not require crankcase heaters, there are instances when a heater should be added. Refrigerant migration during the off cycle can result in a noisy start up. Add a crankcase heater to minimize refrigeration migration, and to help eliminate any start up noise or bearing “wash out.”

[ ] Designates Metric Conversions

Rheem Heating, Cooling and Water Heating

3

Performance Data @ ARI Standard Conditions—Cooling: RAPLJEZ

 

 

Model Numbers

80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air

 

 

 

 

Outdoor

 

 

95°F [35°C] DB Outdoor Air

 

 

 

Sound

 

 

 

 

 

 

 

 

Indoor

 

Unit

Indoor

Total

 

Net

Net

 

 

 

Rating

 

 

 

 

 

CFM [L/s]

 

RAPL-

Coil and/or

Capacity

 

Sensible

Latent

EER

 

SEER

dB

 

 

 

 

 

 

Air Handler

BTU/H [kW]

 

BTU/H [kW]

BTU/H [kW]

 

 

 

 

 

 

 

RCFL-H*2417A*+RXMD-C04

19,100 [5.6]

 

13,700 [4.0]

5,400 [1.6]

12.00

 

14.00

74

600 [283]

 

 

RCFL-A*2414B*+RXMD-C04

19,100 [5.6]

 

13,700 [4.0]

5,400 [1.6]

12.00

 

14.00

74

600 [283]

 

 

RCFL-A*2417B* (RGFD-06?MCK?)

19,500 [5.7]

 

14,000 [4.1]

5,500 [1.6]

13.15

 

15.50

74

600 [283]

 

 

RCFL-A*2417B* (RGFD-07?MCK?)

19,500 [5.7]

 

14,000 [4.1]

5,500 [1.6]

13.20

 

15.50

74

600 [283]

 

 

RCFL-A*2417B* (RGGD-06?MCK?)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.35

 

15.50

74

600 [283]

 

 

RCFL-A*2417B* (RGGD-07?MCK?)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.25

 

15.50

74

625 [295]

 

 

RCFL-A*2417B* (RGLR-07?AMK?)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.40

 

15.50

74

600 [283]

 

 

RCFL-A*2417B* (RGPR-05?BMK?)

19,500 [5.7]

 

14,000 [4.1]

5,500 [1.6]

13.10

 

15.00

74

600 [283]

 

 

RCFL-A*2417B* (RGPR-07?AMK?)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.30

 

15.50

74

600 [283]

 

 

RCFL-A*2417B*+RXMD-C04

19,100 [5.6]

 

13,700 [4.0]

5,400 [1.6]

12.00

 

14.00

74

600 [283]

 

 

RCFL-H*2414A*+RXMD-C04

19,100 [5.6]

 

13,700 [4.0]

5,400 [1.6]

12.00

 

14.00

74

600 [283]

 

 

RCFL-H*2417A* (RGFD-06?MCK?)

19,500 [5.7]

 

14,000 [4.1]

5,500 [1.6]

13.15

 

15.50

74

600 [283]

 

 

RCFL-H*2417A* (RGFD-07?MCK?)

19,500 [5.7]

 

14,000 [4.1]

5,500 [1.6]

13.20

 

15.50

74

600 [283]

 

 

RCFL-H*2417A* (RGGD-06?MCK?)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.35

 

15.50

74

600 [283]

 

 

RCFL-H*2417A* (RGGD-07?MCK?)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.25

 

15.50

74

625 [295]

 

 

RCFL-H*2417A* (RGJD-06?MCK?)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.35

 

15.50

74

600 [283]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RCFL-H*2417A* (RGJD-07?MCK?)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.25

 

15.50

74

625 [295]

 

 

RCFL-H*2417A* (RGLR-07?AMK?)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.40

 

15.50

74

600 [283]

 

 

RCFL-H*2417A* (RGPR-05?BMK?)

19,500 [5.7]

 

14,000 [4.1]

5,500 [1.6]

13.10

 

15.00

74

600 [283]

 

 

RCFL-H*2417A* (RGPR-07?AMK?)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.30

 

15.50

74

600 [283]

 

 

17AHBL24HM (RCHL-24A2)

18,700 [5.5]

 

12,700 [3.7]

6,000 [1.8]

12.75

 

14.50

74

650 [307]

 

 

RBHK-17 (RCHL-24A2)

18,300 [5.4]

 

12,700 [3.7]

5,600 [1.6]

12.65

 

15.00

74

600 [283]

 

018JEZ

RBHP-17 (RCHL-24A2)

18,700 [5.5]

 

12,700 [3.7]

6,000 [1.8]

12.75

 

14.50

74

650 [307]

 

RCHL-24A2 (RGFD-06?MCK?)

18,200 [5.3]

 

12,650 [3.7]

5,550 [1.6]

12.40

 

14.50

74

600 [283]

 

 

 

 

 

 

RCHL-24A2 (RGFD-07?MCK?)

18,200 [5.3]

 

12,650 [3.7]

5,550 [1.6]

12.40

 

14.50

74

600 [283]

 

 

RCHL-24A2 (RGGD-06?MCK?)

18,200 [5.3]

 

12,700 [3.7]

5,500 [1.6]

12.55

 

14.50

74

600 [283]

 

 

RCHL-24A2 (RGGD-07?MCK?)

18,200 [5.3]

 

12,650 [3.7]

5,550 [1.6]

12.50

 

14.50

74

625 [295]

 

 

RCHL-24A2 (RGJD-06?MCK?)

18,200 [5.3]

 

12,700 [3.7]

5,500 [1.6]

12.55

 

14.50

74

600 [283]

 

 

RCHL-24A2 (RGJD-07?MCK?)

18,200 [5.3]

 

12,650 [3.7]

5,550 [1.6]

12.50

 

14.50

74

625 [295]

 

 

RCHL-24A2 (RGLR-07?AMK?)

18,200 [5.3]

 

12,700 [3.7]

5,500 [1.6]

12.60

 

14.50

74

600 [283]

 

 

RCHL-24A2 (RGPR-05?BMK?)

18,200 [5.3]

 

12,600 [3.7]

5,600 [1.6]

12.30

 

14.50

74

600 [283]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RCHL-24A2 (RGPR-07?AMK?)

18,200 [5.3]

 

12,650 [3.7]

5,550 [1.6]

12.55

 

14.50

74

600 [283]

 

 

RCHL-24A2+RXMD-C04

17,700 [5.2]

 

12,150 [3.6]

5,550 [1.6]

11.05

 

13.00

74

600 [283]

 

 

RCQD-2417A*

19,300 [5.7]

 

14,150 [4.1]

5,150 [1.5]

11.90

 

14.00

74

600 [283]

 

 

RCQD-2417A* (RGFD-06?MCK?)

19,600 [5.7]

 

14,350 [4.2]

5,250 [1.5]

13.20

 

15.50

74

600 [283]

 

 

RCQD-2417A* (RGFD-07?MCK?)

19,600 [5.7]

 

14,350 [4.2]

5,250 [1.5]

13.25

 

15.50

74

600 [283]

 

 

RCQD-2417A* (RGPL-05?BMK?)

19,600 [5.7]

 

14,350 [4.2]

5,250 [1.5]

13.15

 

15.50

74

600 [283]

 

 

RCQD-2417A* (RGPL-07?BRK?)

19,700 [5.8]

 

14,450 [4.2]

5,250 [1.5]

13.35

 

16.00

74

600 [283]

 

 

RCQD-2417A* (RGPR-05?BMK?)

19,600 [5.7]

 

14,350 [4.2]

5,250 [1.5]

13.15

 

15.50

74

600 [283]

 

 

RCQD-2417A* (RGPR-07?AMK?)

19,700 [5.8]

 

14,450 [4.2]

5,250 [1.5]

13.35

 

16.00

74

600 [283]

 

 

17AHSL18AU (RCSL-A*2417A*)

19,300 [5.7]

 

13,850 [4.1]

5,450 [1.6]

12.35

 

14.00

74

600 [283]

 

 

17AHLL24HM (RCSL-H*2417A*)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.20

 

15.50

74

600 [283]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17AHSL18HM (RCSL-H*2417A*)

19,300 [5.7]

 

13,850 [4.1]

5,450 [1.6]

12.35

 

14.00

74

600 [283]

 

024JEZ

RHKL-HM2417 (RCSL-H*2417A*)

19,900 [5.8]

 

14,250 [4.2]

5,650 [1.7]

13.45

 

15.50

74

650 [307]

 

 

RHLL-HM2417 (RCSL-H*2417A*)

19,600 [5.7]

 

14,050 [4.1]

5,550 [1.6]

13.20

 

15.50

74

600 [283]

 

 

RHSL-HM1817 (RCSL-H*2417A*)

19,300 [5.7]

 

13,850 [4.1]

5,450 [1.6]

12.35

 

14.00

74

600 [283]

 

 

RCFL-H*2417A*

24,000 [7.0]

 

17,400 [5.1]

6,600 [1.9]

12.05

 

14.00

72

800 [378]

 

 

RCFL-A*2414B*

24,000 [7.0]

 

17,400 [5.1]

6,600 [1.9]

12.05

 

14.00

72

800 [378]

 

 

RCFL-A*2417B*

24,000 [7.0]

 

17,400 [5.1]

6,600 [1.9]

12.05

 

14.00

72

800 [378]

 

 

RCFL-A*2417B* (RGFD-06?MCK?)

24,400 [7.1]

 

17,650 [5.2]

6,750 [2.0]

12.85

 

15.00

72

800 [378]

 

024JEZ

RCFL-A*2417B* (RGFD-07?MCK?)

24,400 [7.1]

 

17,700 [5.2]

6,700 [2.0]

12.95

 

15.00

72

800 [378]

 

RCFL-A*2417B* (RGGD-06?MCK?)

24,400 [7.1]

 

17,750 [5.2]

6,650 [1.9]

13.15

 

15.50

72

800 [378]

 

 

 

 

 

 

RCFL-A*2417B* (RGGD-07?MCK?)

24,400 [7.1]

 

17,750 [5.2]

6,650 [1.9]

13.05

 

15.00

72

800 [378]

 

 

RCFL-A*2417B* (RGLR-07?AMK?)

24,600 [7.2]

 

17,800 [5.2]

6,800 [2.0]

13.35

 

15.50

72

800 [378]

 

 

RCFL-A*2417B* (RGPR-05?BMK?)

24,400 [7.1]

 

17,700 [5.2]

6,700 [2.0]

12.95

 

15.00

72

775 [366]

 

 

RCFL-A*2417B* (RGPR-07?AMK?)

24,600 [7.2]

 

17,800 [5.2]

6,800 [2.0]

13.25

 

15.50

72

800 [378]

Highest sales volume tested combination required by D.O.E. test procedures.

 

 

[

] Designates Metric Conversions

4 Rheem Heating, Cooling and Water Heating

Performance Data @ ARI Standard Conditions—Cooling: RAPLJEZ (continued)

 

Model Numbers

80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air

 

 

 

 

Outdoor

 

 

95°F [35°C] DB Outdoor Air

 

 

 

Sound

 

 

 

 

 

 

 

 

Indoor

Unit

Indoor

Total

 

Net

Net

 

 

 

Rating

 

 

 

 

CFM [L/s]

RAPL-

Coil and/or

Capacity

 

Sensible

Latent

EER

 

SEER

dB

 

 

 

 

 

Air Handler

BTU/H [kW]

 

BTU/H [kW]

BTU/H [kW]

 

 

 

 

 

 

 

RCFL-H*2414A*

24,000 [7.0]

 

17,400 [5.1]

6,600 [1.9]

12.05

 

14.00

72

800

[378]

 

RCFL-H*2417A* (RGFD-06?MCK?)

24,400 [7.1]

 

17,650 [5.2]

6,750 [2.0]

12.85

 

15.00

72

800

[378]

 

RCFL-H*2417A* (RGFD-07?MCK?)

24,400 [7.1]

 

17,700 [5.2]

6,700 [2.0]

12.95

 

15.00

72

800

[378]

 

RCFL-H*2417A* (RGGD-06?MCK?)

24,400 [7.1]

 

17,750 [5.2]

6,650 [1.9]

13.15

 

15.50

72

800

[378]

 

RCFL-H*2417A* (RGGD-07?MCK?)

24,400 [7.1]

 

17,750 [5.2]

6,650 [1.9]

13.05

 

15.00

72

800

[378]

 

RCFL-H*2417A* (RGJD-06?MCK?)

24,400 [7.1]

 

17,750 [5.2]

6,650 [1.9]

13.15

 

15.50

72

800

[378]

 

RCFL-H*2417A* (RGJD-07?MCK?)

24,400 [7.1]

 

17,750 [5.2]

6,650 [1.9]

13.05

 

15.00

72

800

[378]

 

RCFL-H*2417A* (RGLR-07?AMK?)

24,600 [7.2]

 

17,800 [5.2]

6,800 [2.0]

13.35

 

15.50

72

800

[378]

 

RCFL-H*2417A* (RGPR-05?BMK?)

24,400 [7.1]

 

17,700 [5.2]

6,700 [2.0]

12.95

 

15.00

72

775

[366]

 

RCFL-H*2417A* (RGPR-07?AMK?)

24,600 [7.2]

 

17,800 [5.2]

6,800 [2.0]

13.25

 

15.50

72

800

[378]

 

RCHL-24A2

22,200 [6.5]

 

15,350 [4.5]

6,850 [2.0]

11.20

 

13.00

72

800

[378]

 

17AHBA24HM (RCHL-24A2)

22,400 [6.6]

 

15,500 [4.5]

6,900 [2.0]

12.20

 

14.50

72

825

[389]

 

 

 

 

 

 

 

 

 

 

 

 

 

17AHBL24HM (RCHL-24A2)

22,600 [6.6]

 

15,850 [4.6]

6,750 [2.0]

12.30

 

14.50

72

800

[378]

 

RBHK-17 (RCHL-24A2)

22,800 [6.7]

 

16,000 [4.7]

6,800 [2.0]

12.65

 

15.00

72

800

[378]

 

RBHP-17 (RCHL-24A2)

22,400 [6.6]

 

15,500 [4.5]

6,900 [2.0]

12.20

 

14.50

72

825

[389]

 

 

 

 

 

 

 

 

 

 

 

 

 

RCHL-24A2 (RGFD-06?MCK?)

22,600 [6.6]

 

15,800 [4.6]

6,800 [2.0]

12.20

 

14.50

72

800

[378]

 

RCHL-24A2 (RGFD-07?MCK?)

22,600 [6.6]

 

15,850 [4.6]

6,750 [2.0]

12.35

 

14.50

72

800

[378]

 

RCHL-24A2 (RGGD-06?MCK?)

22,800 [6.7]

 

15,950 [4.7]

6,850 [2.0]

12.55

 

14.50

72

800

[378]

 

 

 

 

 

 

 

 

 

 

 

 

 

RCHL-24A2 (RGGD-07?MCK?)

22,800 [6.7]

 

15,900 [4.7]

6,900 [2.0]

12.40

 

14.50

72

800

[378]

024JEZ

RCHL-24A2 (RGJD-06?MCK?)

22,800 [6.7]

 

15,950 [4.7]

6,850 [2.0]

12.55

 

14.50

72

800

[378]

 

RCHL-24A2 (RGJD-07?MCK?)

22,800 [6.7]

 

15,900 [4.7]

6,900 [2.0]

12.40

 

14.50

72

800

[378]

 

RCHL-24A2 (RGLR-07?AMK?)

22,800 [6.7]

 

16,000 [4.7]

6,800 [2.0]

12.70

 

15.00

72

800

[378]

 

RCHL-24A2 (RGPR-05?BMK?)

22,600 [6.6]

 

15,850 [4.6]

6,750 [2.0]

12.30

 

14.50

72

775

[366]

 

RCHL-24A2 (RGPR-07?AMK?)

22,800 [6.7]

 

15,950 [4.7]

6,850 [2.0]

12.60

 

15.00

72

800

[378]

 

RCQD-2417A*

24,200 [7.1]

 

18,000 [5.3]

6,200 [1.8]

12.10

 

14.50

72

800

[378]

 

RCQD-2417A* (RGFD-06?MCK?)

24,200 [7.1]

 

18,000 [5.3]

6,200 [1.8]

12.90

 

15.50

72

800

[378]

 

 

 

 

 

 

 

 

 

 

 

 

 

RCQD-2417A* (RGFD-07?MCK?)

24,200 [7.1]

 

18,000 [5.3]

6,200 [1.8]

13.00

 

15.50

72

800

[378]

 

RCQD-2417A* (RGJD-06?MCK?)

24,400 [7.1]

 

18,150 [5.3]

6,250 [1.8]

13.20

 

16.00

72

800

[378]

 

RCQD-2417A* (RGJD-07?MCK?)

24,400 [7.1]

 

18,200 [5.3]

6,200 [1.8]

13.10

 

15.50

72

800

[378]

 

RCQD-2417A* (RGPL-05?BMK?)

24,200 [7.1]

 

18,000 [5.3]

6,200 [1.8]

13.00

 

15.50

72

775

[366]

 

 

 

 

 

 

 

 

 

 

 

 

 

RCQD-2417A* (RGPL-07?BRK?)

24,400 [7.1]

 

18,150 [5.3]

6,250 [1.8]

13.30

 

16.00

72

800

[378]

 

RCQD-2417A* (RGPR-05?BMK?)

24,200 [7.1]

 

18,000 [5.3]

6,200 [1.8]

13.00

 

15.50

72

775

[366]

030JAZ

RCQD-2417A* (RGPR-07?AMK?)

24,400 [7.1]

 

18,150 [5.3]

6,250 [1.8]

13.30

 

16.00

72

800

[378]

 

17AHSL24AU (RCSL-A*2417A*)

24,200 [7.1]

 

17,550 [5.1]

6,650 [1.9]

12.40

 

14.50

72

800

[378]

 

17AHLL24HM (RCSL-H*2417A*)

24,600 [7.2]

 

17,900 [5.2]

6,700 [2.0]

13.65

 

15.50

72

775

[366]

 

17AHSL24HM (RCSL-H*2417A*)

24,200 [7.1]

 

17,550 [5.1]

6,650 [1.9]

12.40

 

14.50

72

800

[378]

 

RHKL-HM2417 (RCSL-H*2417A*)

24,800 [7.3]

 

17,950 [5.3]

6,850 [2.0]

13.30

 

15.50

72

850

[401]

 

RHLL-HM2417 (RCSL-H*2417A*)

24,600 [7.2]

 

17,900 [5.2]

6,700 [2.0]

13.65

 

15.50

72

775

[366]

 

 

 

 

 

 

 

 

 

 

 

 

 

RHSL-HM2417 (RCSL-H*2417A*)

24,200 [7.1]

 

17,550 [5.1]

6,650 [1.9]

12.40

 

14.50

72

800

[378]

 

RCFL-H*3617A*+RXMD-C04

28,400 [8.3]

 

21,050 [6.2]

7,350 [2.2]

12.00

 

14.00

73

950

[448]

 

RCFL-A*3617B* (RGFD-07?MCK?)

29,000 [8.5]

 

21,450 [6.3]

7,550 [2.2]

12.40

 

14.50

73

1,000

[472]

 

RCFL-A*3617B* (RGGD-06?MCK?)

29,000 [8.5]

 

21,450 [6.3]

7,550 [2.2]

12.45

 

14.50

73

1,000

[472]

 

RCFL-A*3617B* (RGPR-05?BMK?)

28,800 [8.4]

 

21,400 [6.3]

7,400 [2.2]

12.30

 

14.50

73

1,000

[472]

 

RCFL-A*3617B* (RGPR-07?AMK?)

29,000 [8.5]

 

21,550 [6.3]

7,450 [2.2]

12.65

 

14.50

73

1,000

[472]

 

RCFL-A*3617B*+RXMD-C04

28,400 [8.3]

 

21,050 [6.2]

7,350 [2.2]

12.00

 

14.00

73

950

[448]

 

RCFL-A*3621B* (RGFD-07?MCK?)

29,000 [8.5]

 

21,450 [6.3]

7,550 [2.2]

12.45

 

14.50

73

1,000

[472]

 

RCFL-A*3621B* (RGGD-06?MCK?)

29,000 [8.5]

 

21,500 [6.3]

7,500 [2.2]

12.50

 

14.50

73

1,000

[472]

030JEZ

RCFL-A*3621B* (RGPR-05?BMK?)

29,000 [8.5]

 

21,450 [6.3]

7,550 [2.2]

12.35

 

14.50

73

1,000

[472]

 

RCFL-A*3621B* (RGPR-07?AMK?)

29,000 [8.5]

 

21,550 [6.3]

7,450 [2.2]

12.70

 

14.50

73

1,000

[472]

 

RCFL-A*3621B* (RGPR-07?BRQ?)

29,400 [8.6]

 

21,700 [6.4]

7,700 [2.3]

13.15

 

15.50

73

1,000

[472]

 

RCFL-A*3621B*+RXMD-C04

28,400 [8.3]

 

21,050 [6.2]

7,350 [2.2]

12.00

 

14.00

73

950

[448]

 

RCFL-H*3617A* (RGFD-07?MCK?)

29,000 [8.5]

 

21,450 [6.3]

7,550 [2.2]

12.40

 

14.50

73

1,000

[472]

 

RCFL-H*3617A* (RGGD-06?MCK?)

29,000 [8.5]

 

21,450 [6.3]

7,550 [2.2]

12.45

 

14.50

73

1,000

[472]

 

RCFL-H*3617A* (RGJD-06?MCK?)

29,000 [8.5]

 

21,450 [6.3]

7,550 [2.2]

12.45

 

14.50

73

1,000

[472]

 

RCFL-H*3617A* (RGPR-05?BMK?)

28,800 [8.4]

 

21,400 [6.3]

7,400 [2.2]

12.30

 

14.50

73

1,000

[472]

 

RCFL-H*3617A* (RGPR-07?AMK?)

29,000 [8.5]

 

21,550 [6.3]

7,450 [2.2]

12.65

 

14.50

73

1,000

[472]

Highest sales volume tested combination required by D.O.E. test procedures.

 

 

[

] Designates Metric Conversions

Rheem Heating, Cooling and Water Heating

5