AutoMax™ Network Communication Option Board
For Use With
FlexPak™ 3000 DC Drives and
WebPak™ 3000 DC Drives
M/N 915FK0101
Instruction Manual
D2-3318-5
The information in this manual is subject to change without notice.
Trademarks not belonging to Rockwell Automation are property of their
respective companies.
Throughout this manual, the following notes are used to alert you to safety considerations:
ATTENTION: Identifies information about practices or circumstances that can lead to personal
injury or death, property damage, or economic loss.
!
Important: Identifies information that is critical for successful application and understanding of the product.
The thick black bar shown in the outside margin of this page will be used throughout this instruction manual to
identify new or revised text or figures.
ATTENTION: Only qualified electrical personnel familiar with the construction and operation of
this equipment and the hazards involved should install, adjust, operate, or service this equipment.
!
Read and understand this manual and other applicable manuals in their entirety before
proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
ATTENTION: Do not install modification kits with power applied to the drive. Disconnect and lock
out incoming power before attempting such installation or removal. Failure to observe this
precaution could result in severe bodily injury or loss of life.
ATTENTION: The user must provide an external, hardwired emergency stop circuit outside of the
drive circuitry. This circuit must disable the system in case of improper operation. Uncontrolled
machine operation may result if this procedure is not followed. Failure to observe this precaution
could result in bodily injury.
ATTENTION: The drive contains ESD- (Electrostatic Discharge) sensitive parts and assemblies.
Static control precautions are required when installing, testing, servicing, or repairing the drive.
Erratic machine operation and damage to, or destruction of, equipment can result if this procedure
is not followed. Failure to observe this precaution can result in bodily injury.
ATTENTION: The user is responsible for conforming with all applicable local, national, and
international codes. Failure to observe this precaution could result in damage to, or destruction
of, the equipment.
Microsoft and Windows are trademarks of Microsoft Corporation.ReSource, FlexPak, WebPak, WebPakCS, AutoMax, and Reliance are trademarks of Rockwell Automation.
Table 7.10 – Original Register Map, Drop_2: Master Write Registers, FULL
Connection. Tunable Data (Drive Input Data) ..................................... 7-13
Table 7.11 – Original Register Map, Drop_3: Master Read Registers, FULL
Connection. Runtime Signal Data (Drive Output Data)....................... 7-15
Table 7.12 – Original Register Map, Drop_3: Master Write Registers, FULL
Connection. Tunable/Configurable Data (Drive Input Data) ............... 7-16
List of Tables
VII
VIII
AutoMax Network Communication Option Board
CHAPTER 1
This manual describes the AutoMax™ Network Communication Option Board
(M/N 915FK0101). This board enables a FlexPak™ 3000 or a WebPak™ 3000 DC
drive to be operated and monitored over the AutoMax network.
For normal operation, the drive can be completely controlled using the AutoMax
Network Option board. This allows use of only a network interface connection,
hardwired emergency stop, and three-phase input and output power wiring. Drive
control (such as start, stop, and reset), reference changes, parameter modification,
and drive monitoring can all be performed over the AutoMax network.
1.1Before You Start
In this manual, parameters are shown by the parameter name used on the OIM,
followed by the parameter number in parentheses. For example, the parameter to set
acceleration time, parameter P.001, is shown as
1.2Where to Find Additional Information
ACCELERATIONTIME (P.001).
Introduction
You must be familiar with the instruction manuals that describe your system. This can
include, but is not limited to:
• FlexPak 3000 DC Drive Hardware Reference manual, D2-3404.
• FlexPak 3000 DC Drive Software Reference manual, D2-3405.
• WebPak 3000 DC Drive Hardware Reference manal, D2-3443.
• WebPak 3000 DC Drive Software Reference manual, D2-3444.
• ReSource AutoMax Programming Executive Instruction manual (various part
numbers).
• Control and Configuration Software manual, D2-3348.
• WebPakCS Software manual, D2-3447.
1.3Getting Assistance from Reliance Electric
If you have any questions or problems with the products described in this instruction
manual, contact your local Reliance Electric sales office. For technical assistance, call
1-800-726-8112.
Introduction
1-1
1.4Related Hardware and Software
When the Network Option board is installed in a FlexPak 3000 or WebPak 3000 drive,
the drive can be used with the hardware and software listed in table 1.1.
Table 1.1 – Hardware and Software Options Available for the Network Option Board (Purchased Separately)
Option NameModel #Description
75 Ohm Terminating Load45C71A terminating load is required at both ends of an AutoMax
network coaxial cable system.
AutoMax Processor57C430A
55C431
57C435
AutoMax Programming
Executive
Communications
Passive Tap
Control and Configuration
Software
(FlexPak Drives Only)
WebPakCS Software
(WebPak 3000 Drives Only)
AutoMax Network
Communications Module
Network Drop Cable57C381Cable that connects all network drops and the passive taps.
ReSource™ Interface
Cable
VariousIncludes the tools required for programming in Enhanced BASIC,
Control Block, and Ladder Logic/PC languages.
57C380Required at each network drop for connection to coaxial cabling.
2CS3000Windows-based software that enables you to connect any
personal computer running Microsoft Windows version 3.1 or
later to a FlexPak 3000 drive. Enables you to create, store,
upload, and download drive configurations.
?
57C404
57C404A
57C404B
61C127Cable that connects a personal computer to the AutoMax
Windows-based software that enables you to connect any
personal computer running Microsoft Windows version 9x or
later (including NT) and Internet Explorer version 5.0 or later to a
WebPak 3000 drive. Enables you to create, store, upload, and
download drive configurations.
The master drop (and all AutoMax rack slave drops) on the
AutoMax network must contain a Network Communications
module.
Processor module
1.5AutoMax Network Option Board Description
1-2
The AutoMax Network Option board makes the FlexPak 3000 or WebPak 3000 drive a
slave drop on the AutoMax network. It is a printed circuit board assembly that mounts
inside the drive and connects to the drive’s Regulator board through a ribbon cable.
The Network Option board is powered from the standard drive power supply.
The Network Option board has a 9-pin D-shell connector that connects to a network
drop cable (M/N 57C381). The network drop cable is then connected to a passive tap
on the AutoMax network.
The board contains its own microprocessor. The microprocessor connects to one port
of the board’s dual-port memory. The other port interfaces with the drive’s Regulator
board.
AutoMax Network Communication Option Board
The AutoMax Network Communication Option board is shown in figure 1.1.
9-Pin
D-Shell
Connector
Ribbon Cable
Connector
Pin 1
Figure 1.1 – AutoMax Network Communication Option Board
Introduction
1-3
1-4
AutoMax Network Communication Option Board
CHAPTER 2
This section describes how to install the Network Option board in the FlexPak 3000 or
WebPak 3000 drive and connect the drive to an AutoMax network.
2.1Installing the Network Option Board
ATTENTION: Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
!
should install, adjust, operate, or service this equipment. Read and
understand this manual and other applicable manuals in their entirety
before proceeding. Failure to observe this precaution could result in
severe bodily injury or loss of life.
ATTENTION:
local, national, and international codes. Wiring practices, grounding,
disconnects, and overcurrent protection are particularly impor tant. Failure
to observe this precaution could result in severe bodily injury or loss of life.
ATTENTION: Do not install modification boards with power applied to
the drive. Disconnect and lock out incoming power before attempting
such installation. Failure to observe this precaution could result in severe
bodily injury or loss of life.
The user is responsible for conforming with all applicable
Installation
To install the Network Option board:
Step 1.Turn off, lock out, and tag all incoming power to the drive.
Step 2.Loosen the two (2) captive screws on the drive cover. Remove the cover.
Step 3.Loosen the captive screw on the carrier. Swing open the carrier. See figure 2.1.
Loosen Captive Screw
and Swing Carrier Open
Figure 2.1 – Removing Drive Cover
Installation
2-1
Step 4.Remove the screws that attach the carrier shield to the carrier. See
figure 2.2.
Carrier Shield
Figure 2.2 – Removing the Carrier Shield
Step 5.Remove the connector that attaches the shield ground wire to the drive
power supply. Set the shield aside. See figure 2.3.
Ground Wire
Power Supply
Figure 2.3 – Removing Shield Ground Wire
Step 6.Position the Network Option board over the standoffs. Refer to figure 2.4.
2-2
Step 7.Secure the Network Option board using three captive screws on the board.
Step 8.Plug the option board ribbon cable into the Network Option board.
AutoMax Network Communication Option Board
Attach Network board to
carrier’s molded standoffs
using captive screws
(qty. 3)
Plug option board ribbon
cable into Network board
Figure 2.4 – Installing the Network Communication Option Board
Step 9.Re-attach the carrier shield ground wire to the drive power supply.
Step 10. Re-attach the carrier shield to the carrier.
Step 11. Close the carrier and fasten it with the captive screw.
Step 12. Re-install the drive cover.
2.2Connecting the Drive to an AutoMax Network
ATTENTION: AutoMax networks with more than 5 drops might produce
communication errors if 10-foot drop cables are used. Wherever possible,
!
3-foot drop cables or, if necessary, 5-foot drop cables should be used.
Failure to observe this precaution could result in damage to, or
destruction of, equipment.
Installation
See figure 2.5 for cabling and termination connections.
Refer to the Network Communications Module instruction manual (J2-3001) for a
detailed description of how to add a drop to the network.
Step 1.Stop any application tasks that are running.
Step 2.Use the Network Drop Cable (M/N 57C381) to connect to the
Communications Passive Tap (M/N57C380).
Step 3.If the drop is at the end of the coaxial cable system, it must be terminated.
Terminate by connecting a 75-Ohm Terminating Load (M/N 45C71) to the
remaining BNC connector on the passive tap.
Step 4.Remove the lockout and tag. Apply power to the drive. If a problem is
detected during diagnostics, a fault or alarm will occur. See your drive
software manual for information on faults and alarms.
2-3
Drop Cable
(M/N 57C381)
BNC Connector
FlexPak 3000
FlexPak 3000
or
WebPak 3000
Drive
WebPak 3000
Drive
To DriveTo Drive
Drop Cable
(M/N 57C381)
BNC Connector
or
Drop Cable
(M/N 57C381)
75 Ohm
Terminating Load
Passive Tap
(M/N 57C380)
Figure 2.5 – Connecting a Drive to the AutoMax Network
Coaxial
Cable
Passive Tap
(M/N 57C380)
Coaxial
Cable
75 Ohm
Terminating Load
Passive Tap
(M/N 57C380)
2-4
AutoMax Network Communication Option Board
CHAPTER 3
Drive Configuration
This section describes how to configure a FlexPak 3000 or WebPak 3000 drive for use
with an AutoMax network.
3.1Setting Up the Drive for Network Communication
The drive becomes active on the AutoMax network after you complete the following
steps:
Step 1.Connect the Network Option board to the network using a passive tap. See
section 2.2.
Step 2.Apply power to the drive.
Step 3.Assign a valid AutoMax network drop number to the drive using parameter
NETWDROPNUMBER (P.900). You must set this parameter through the drive
keypad (
WebPakCS). This drop number is the base drop the drive will occupy. In this
manual, the base drop number is called Drop_1.
When
the network.
FlexPak 3000 drives
sequential network drops, including Drop_1. Subsequent drops are called
Drop_2, Drop_3, and Drop_4 in this manual. Your application might use
different drop numbers.
WebPak 3000 drives:
sequential network drops, including Drop_1. Subsequent drops are called
Drop_2 and Drop_3 in this manual. Your application might use different drop
numbers.
Step 4.Set the network connection type using NETWCONNECTTYPE (P.910). This
defines the scope of data that will be communicated. It also determines the
level of control that the master has with the connected drive. You can select
one of two connection types:
• BASIC: Only essential drive data (reference, sequencing, basic tuning, and
• FULL: The entire set of drive data that has been assigned network
OIM or DCM) or using drive configuration software (CS3000 or
NETW DROP NUMBER
feedback data) are transferred over the network. This allows a higher
density network with moderate functionality. Select this connection type if
you do not need to completely configure the drive over the network. When
BASIC is selected, the drive occupies a single network drop.
registers is transferred over the network. Select this connection type if
your application must be able to configure the drive over the network and
have access to most parameters, operating variables, and diagnostic
information.
The large amount of data transferred in the full connection type requires
that the drive occupy multiple network drops, thus decreasing the
potential number of devices on the network.
(P.900) is set, you can set other parameters over
: For
FULL
connections, the drive occupies four
For
FULL
connections, the drive occupies three
Drive Configuration
3-1
FlexPak 3000 drives:
sequential network drops.
WebPak 3000 drives:
sequential network drops using indirect registers in Drop_2 and Drop_3 (see
section 7.1 for information about using indirect registers).
Step 5.Apply power to the AutoMax rack.
Serial communication is now established and information can be exchanged with the
network master. The drive transfers output data whenever this connection is made. To
transfer input data, you must complete the steps in the next section.
When
When
FULL
is selected, the drive will occupy four
FULL
is selected, the drive will occupy three
3.2Selecting a Network Reference Source
AMXNETWREFSELECT (P.911) specifies the source of the speed/torque reference
when
CONTROLSOURCESELECT (P.000) is set to NETWORK. You can select either:
• DIRECT: The reference is from register 33 in the drive’s Drop_1 register map. See
table 5.4 (FlexPak 3000 original map), table 6.4 (FlexPak 3000 alternate map), or
table 7.5 (WebPak 3000 map).
• BROADCAST n: The reference is from one of the eight network broadcast data
registers (network drop area 0, registers 32 to 39). The specific broadcast register
(1 to 8) is assigned using a register in the drive’s Drop_1 register map. See
register 30 in table 5.3 (FlexPak 3000 original map), register 63 in table 6.6 (FlexPak
3000 alternate map), or register 30 in table 7.4 (WebPak 3000 map). See the
Network Communications Module instruction manual (J2-3001) for information on
broadcast data registers.
3.3How the Drive Responds to a Loss of Network
Communication
The Network Option board attempts to remain active on the network at all times,
regardless of the control source setting.
At power up, the drive delays for approximately 10 seconds before indicating a loss of
network communication.
If communication is interrupted:
• The Network Option board immediately notifies the drive Regulator.
• The Network Option board tries to re-establish communication with the network
master.
• For FlexPak 3000 drives, if CONTROLSOURCESELECT (P.000) is set to NETWORK, the
drive reacts to a network communication loss as specified by
SELECT (P.901).
• For WebPak 3000 drives, a fault is generated when network communication is lost if
CONTROLSOURCESELECT (P.000) is set to NETWORK.
• If the drive includes an OIM, the NETWORK indicator above the CONTROLSOURCE
SELECT key blinks to indicate that network communication is inactive.
NETWCOMMLOSS
3-2
AutoMax Network Communication Option Board
3.3.1 Setting NETW COMM LOSS SELECT (P.901)
(FlexPak 3000 Drives Only)
ATTENTION: NETWCOMMLOSSSELECT (P.901) allows you to configure
the drive to continue to run of a loss of network communication occurs.
!
NETWCOMMLOSSSELECT (P.901) is not used in WebPak 3000 drives. For
WebPak 3000 drives, a fault is generated when network communication is lost if
CONTROLSOURCESELECT (P.000) is set to NETWORK. This causes the drive to coast/DB
stop. The drive cannot be restarted until the fault is cleared.
You must provide some form of hardwired stop in case of communication
loss, since stopping the drive over the network might not be possible.
Failure to observe this precaution could result in bodily injury or damage
to, or destruction of, equipment.
For FlexPak 3000 drives,
responds to network communication loss when
to network. Alarms do not cause the drive to stop. Therefore, some form of hardwired
stop must be available in case of communication loss since stopping the drive over the
network might not be possible.
You can set
TRMBLKREF (2), or USETRMBLKCNTL (3).
P.901 = FAULT (0)
When
lost, the following occurs:
NETWCOMMLOSSSELECT (P.901) to FAULT (0), USELASTREF (1), USE
NETWCOMMLOSSSELECT (P.901) is set to FAU LT and network communication is
NETWCOMMLOSSSELECT (P.901) defines how the drive
CONTROLSOURCESELECT (P.000) is set
• The drive latches a fault condition and performs a coast/DB stop.
• A NETWORKCOMMUNICATIONLOSS fault is generated.
When network communication is re-established, you must reset the fault before the
drive can be re-started. See the drive software manual for information on resetting
faults.
ATTENTION: The drive is not equipped with a coast-stop pushbutton.
You must install a hardwired operator-accesible pushbutton that provides
!
a positive interrupt and shuts down the drive. Failure to observe this
precaution could result in bodily injury.
ATTENTION:
MAP SEL
NETWORK
SPD LOOP PI RESET
these values are appropriate for your application before changing the
control source. Failure to observe this precaution could result in severe
bodily injury or loss of life.
If you are using the alternate register map (
(P.914) set to
, the parameters
ALTERNATE
are reset to their default values (0 for each). Ensure
) and you change the control source from
SPD LOOP PI INIT SEL, SPD LOOP PI INIT VAL
NETW REGISTER
, and
Drive Configuration
3-3
P.901 = USE LAST REF (1)
NETWCOMMLOSSSELECT (P.901) is set to USELASTREF and network
When
communication is lost, the following occurs:
• The drive continues to run, using the last reference received from the network
master.
• A NETWORKCOMMUNICATIONTIMEOUT alarm (A00004) is generated.
• An entry is made into the drive’s alarm log for each active-to-inactive transition of
network communication status.
• If network communication is re-established and the drive is still running, the drive
will again follow the reference and sequencing control inputs supplied by the
network master.
You can stop the drive using the hardwired stop input or the
However, you cannot restart the drive until network communication is re-established or
CONTROLSOURCESELECT (P.000) is changed.
P.901 = USE TRMBLK REF (2)
NETWCOMMLOSSSELECT (P.901) is set to USETERMBLKREF (2) and network
When
communication is lost, the following occurs:
OIMSTOP/RESET key.
• The drive continues to run, using the auto reference value selected by AUTO
REFERENCESELECT (P.103)
(or Regulator board terminals 19 and 20?)
• A NETWORKCOMMUNICATIONTIMEOUT alarm (A000014) is generated.
• If network communication is re-established and the drive is still running, the drive
will again follow the reference and sequencing control inputs supplied by the
network master.
You can stop the drive using the hardwired stop input, the
hardwired stop input (coast/DB stop, Regulator board terminal 8). However, you
cannot restart the drive until network communication is re-established or
SOURCESELECT (P.000) is changed.
P.901 = USE TRMBLK CNTL (3)
NETWCOMMLOSSSELECT (P.901) is set to USETRMBLKCNTL (3), and network
When
communication is lost, the following occurs:
OIMSTOP/RESET key, or the
CONTROL
3-4
• The drive continues to run using the Regulator board terminal strip as the source for
all control (run, jog, stop, fault reset, direction, and OCL enable) and speed (auto)
reference signals.
• A NETWORKCOMMUNICATIONTIMEOUT alarm (A000014) is generated.
• The Speed Loop PI Reset and Underwind/Overwind bits cannot be changed while
operating in this mode. They will remain at the last values received from the
network.
If network communication is re-established and the drive is still running, the drive will
again frollow the reference and sequencing control inputs supplied by the network
master.
AutoMax Network Communication Option Board
CHAPTER 4
Programming
This section describes the organization of data in the AutoMax Network
Communication Option board and how the network accesses the data.
4.1Selecting a Register Map (FlexPak 3000 Drives Only)
There are two register maps available for the FlexPak 3000 drive: original and
alternate.
The original register map allows you to use programs developed for versions earlier
than 4.0 of the FlexPak 3000 drive. Register assignments for the original register map
are listed in chapter 5.
The alternate register map is similar to the original register map, except that the most
commonly accessed data is in the base drop area (Drop_1). The alternate register
map also includes functions that were added in regulator software version
FlexPak 3000 DC Drive Software Reference Manual
the
details on the new version
map are listed in chapter 6.
4.2
features. Register assignments for the alternate register
, manual number D2-3405, for
4.2
. See
Important: When a version
existing AutoMax network that uses the ALTERNATE register map, you
may need to reprogram the master task so that it writes valid data in the
registers that are now being used (where previously they were marked as
reserved).
The register map is selected using the
4.2
Regulator board is used as a replacement in an
NETWREGISTERMAPSEL (P.914) parameter.
4.2How the Control Source Selection Affects Data
Transfers
You can use the keypad to change parameter values when CONTROLSOURCESELECT
(P.000) is set to
overwritten when the next network update occurs.
You cannot transfer data using the CS3000
SOURCESELECT (P.000) is set to NETWORK.
NETWORK. However, changes made through the keypad might be
OR WebPakCS software while CONTROL
4.3About Network Transfer Rates
To transfer data, the Network Option board must be communicating with the master.
To transfer input data, the Network Option board must be communicating with the
master and
CONTROLSOURCESELECT (P.000) must be set to NETWORK.
Programming
Data transfer rates between the Network Option board and Regulator board depend
on the type of data being transferred.
4-1
Data can be input or output data.
Input data is one of three types:
• Control/Reference: Data that require the fastest update rates, including data such
as the sequencing inputs (Stop, Run, Jog, Fwd/Rev) and speed/torque reference.
These inputs are transferred every speed loop scan period. An exception to this
occurs if the drive is configured to get its torque reference from the network. If the
torque reference is from the network, the drive reads the
CML reference from the
Network Option board every current minor loop scan.
•
Tunable:
TIME
Data that can be changed while the drive is running, such as
ACCELERATION
(P.001). Tunable inputs are transferred approximately every 600 msec while the
drive is running or stopped.
• Configurable: Data that cannot be changed while the drive is running, such as
CONTROLSOURCESELECT (P.000). Configurable inputs are transferred from the
Network Option board to the Regulator board approximately every 600 msec when
the drive is stopped. Values sent from the network master while the drive is running
are stored in Network Option board memory but are not scanned into Regulator
board memory until the drive is stopped.
Output data is one of two types:
• Runtime Signal: Data such as the selected speed reference value, drive status
(such as ready or running), drive fault flags, the state of terminal strip digital inputs,
and motor status values (
speed loop scan period.
RPM, VOLTS, AMPS). This information is transferred every
• Tunable, Configurable, and Status: All other information provided by the drive.
This typically includes all stored drive parameter values. Tunable, configurable, and
status data are transferred approximately every 600 msec.
Output data is transferred from the Regulator board to the Network Option board
regardless of the status of AutoMax network communication (active or inactive) or the
selected drive control source (
For FlexPak 3000 drives, the speed loop scan period is 10 msec when
SELECT (P.200) is set to ARMATUREVOLT. It is 5 msec when FEEDBACKSELECT (P.200) is
set to any other value.
For WebPak 3000 drives, the speed loop scan period is 10 msec.
KEYPAD, TERMBLK, or NETWORK).
FEEDBACK
4-2
AutoMax Network Communication Option Board
4.3.1 I/O Update Enable Logic Summary
The logic strings shown in figure 4.1 summarize the output and input enable logic
described in this chapter.
Outputs
Updated
CONTROL SOURCE
NETW COMM STATUS
(P.908) = ACTIVE
SELECT = NETWORK
Tune/Config
Input Enable
Running
Jogging
Figure 4.1 – I/O Update Enable Logic Strings
Control/Reference
Inputs Read
Tu na b le
Inputs Read
Configurable
Inputs Read
4.4Setting Up Data Types That Can Be Transferred
You must enable the transfer of tunable and configurable inputs from the Network
Option board to the Regulator board. Until you enable transfer, only control/reference
data are read by the Regulator board.
To enable transfer of tunable and configurable data, set the network-master-controlled
Tune/Config Input Enable bit (Drop_1, register 32, bit 14) to 1.
For example, the master application program would typically:
1. Initialize the tunable and configurable input data in the dual-port memory of the
master’s Network module
2. Delay for an appropriate amount of time to ensure data have been transferred to
the drive
3. Set the Tune/Config Input Enable bit to 1.
If you only want to transfer control/reference data, leave the Tune/Config Input Enable
bit at 0 (off). This forces you to configure the drive through another source, such as the
OIM, CS3000 software, or WebPakCS software, but allows you to control the drive
(including
RUN, JOG, STOP, RESET, and the reference) from the network master.
Programming
4-3
4.5Tune/Config Update Synchronization Flag
This flag allows the network master application program to track when the drive has
updated tunable and configurable inputs. By toggling the tune/config update
synchronization flag in the master and monitoring the copied value from the drive, the
master’s program can determine when the drive has read in that data. This feature has
no effect on drive operation.
The drive regulator copies the tune/config update synchronization flag bit to its
corresponding loopback bit after it has read in and processed all tunable input
registers. Configurable inputs are only read in by the drive while it is not running. This
will not affect copying the synchronization flag to the loopback bit, since tunable inputs
will still be transferred.
When using WebPak 3000 indirect parameters, use the tune/config update
synchronization flag with the network synchronization flag as described in section 7.1.
To use the synchronization flag, the tune/config input enable bit must be set to 1.
To determine when changes to tunable and configurable data in the drive have been
completed, the master:
1. Modifies the tunable and configurable register data in the appropriate network
registers.
2. Sets the tune/config input enable flag.
3. Toggles the tune/config update synchronization flag.
4. Monitors the tune/config update synchronization flag loopback bit until it equals
the value written in item 3, above.
The tune/config update synchronization flag is defined in the first drop of the drive
network drop connection. Therefore, it can only be used to indicate when data for the
first drop has been read in and processed by the drive.
Table 4.1 – Synchronization Flag Register Locations (Alternate and Original Register Maps)
FlagDropRegisterBit
Tune/Config Update Synchronization Flag Loopback
(Master Read) Bit
Tune/Config Update Synchronization Flag (Master
Write)
Tune/Config Input Enable BitDrop_13214
Alternative Synchronization Methods
The tune/config update synchronization flag applies only to Drop_1. To determine if
the drive received data written to other drops, you must use other methods.
One method is to program a delay after writing to the network master’s memory.
Calculate the delay as needed for the number of drops on the network, adding
600 msec for processing time. See your AutoMax documentation for information on
calculating the delay.
Drop_107
Drop_13215
4-4
AutoMax Network Communication Option Board
Note that this method assumes that all requirements have been met for the drive to
obtain its inputs from the network (see figure 4.1).
4.6Monitoring Unacceptable Parameter Values
The parameter processing error status flag (FlexPak drives: Drop_1, register 0, bit 12;
WebPak drives: Drop_1, register 0, bit 13) allows the network master to monitor
parameter values that are unacceptable to the drive.
When this flag is set to 1, one or more parameters sent to the drive were rejected.
When this flag is set to 0, all parameters sent to the drive were accepted.
Note that the Tune/Config Inputs Enable bit (Drop_1, register 32, bit 14) must be set
to 1 before the drive will read or process any tune/config parameters. The parameter
processing error flag is updated approximately every 600 msec.
More information on parameter processing errors is available when using the
FlexPak 3000 alternate register map (see section 6.2) or the WebPak 3000 register
map (see section 7.1).
4.7Timing Requirements
The amount of time required by the network master to transmit data to the drive
depends on the number of active drops on the network. This time is referred to as the
“data update time.” Refer to I/M J2-3001 for details on calculating this time.
Tunable and configurable drive input register values must be maintained by the
network master’s application program for the data update time plus at least 600 msec
to assure that they are read by the drive.
Most of the control/reference data types do not have this 600 msec requirement
because they are read by the drive every 5 or 10 msec.
To start the drive, the Run and Jog inputs must be set to 0 for at least 20 msec, then
set to 1 for at least 20 msec (a 0-to-1 transition). The drive might delay the start for up
to 100 msec after receiving the 0-to-1 transition because of variable processing
delays.
For the following actions, the inputs must be set to 0 for at least 600 msec, then set to
1 for at least 600 msec (a 0-to-1 transition):
• Fault log clear
• Alarm log clear
• Alarm reset
• Memory save
Programming
To reset faults, the inputs must be set to 0 for at least 10 msec, then set to 1 for at
least 10 msec (a 0-to-1 transition).
4-5
4.8Drive Ready Status Bit
The Drive Ready status bit (Drop_1, register 0, bit 0) indicates that a 0-to-1 transition
on the Run or Jog input will start the drive.
FlexPak 3000 drives: The Drive Ready bit is
conditions are met, and
OFF (0) if any one of these conditions is not met:
ON (1) when all of the following
• No drive faults are active (Drop_1, register 0, bit 2 = 0)
• Network stop input is de-asserted (Drop_1, register 32, bit 1 = 1)
• Front-panel STOP/RESET button is not pressed
• Coast/DB Stop terminal strip input is closed (Drop_1, register 0, bit 10 = 1)
• Customer Interlock terminal strip input is closed (Drop_1, register 0, bit 11 = 1)
• A download from the serial port (using the CS3000 software) is not in progress
WebPak 3000 drives: The Drive Ready bit is on (1) when all of the following
conditions are met, and off (0) if any one of these conditions is not met:
•
•
4.9Display of Parameter Values Over the
AutoMax Network
The display of parameter values on the network will be different than the display when
on the
OIM, DCM, or when using CS3000 or WebPakCS software.
Examples of these differences are shown in table 4.2. Refer to the register maps in
chapters 5 and 6 for detail on the scaling parameter for transfer over the AutoMax
network.
Front Panel Display (OIM or DCM)
Values with a decimal
point
Parameters with text
choices
Speed/voltage loop
and current minor loop
parameters
*
For speed parameters, a value of 4095 corresponds to TOPSPEED (P.011). For load parameters, 4095 corresponds to MAXIMUMCURRENT
(P.007).
4-6
(Does this table need to be revised for WebPak?)
Table 4.2 – Front Panel Display Compared to Network Displays
Network Value
Set
MOTORRATEDARMAMPS (P.008) to
27.3 amps.
TRIMMODESELECT (P.110) choices are
NOTRIM, INCREMENTAL, or
PROPORTIONAL.
TOPSPEED (P.011) = 1750 RPM. On the
front panel, you read
FEEDBACK (P.296) = 1000 RPM.
SPDLOOP
2340
AutoMax Network Communication Option Board
Register Map Table
Listing ExampleDescriptionExample
273amps * 10
0, 1, 20 =
NOTRIM
1 = INCREMENTAL
2 = PROPORTIONAL
4095 1000×
⎛⎞
-------------------- ------------ -
=
⎝⎠
1750
4095 at
(P.011)
TOPSPEED
*
4.10 Parameters That Are Not Accessible Over the
AutoMax Network
These FlexPak 3000 parameters are not accessible over the AutoMax network at
any time.
This section lists the original register map, which allows you to use programs
developed for versions earlier than 4.0 of the FlexPak 3000 drive. It also offers a
different set of options in Drop_1 than the alternate register map.
Brief descriptions of parameters are in the register map tables. For detailed parameter
descriptions, refer to the
5.1Accessing the Original Register Map
To access the original register map, set NETWREGISTERMAPSEL (P.914) to ORIGINAL.
FlexPak 3000 DC Drive Software Reference Manual
.
Some parameters are not available and others are mapped differently when
REGISTER MAP SEL
correct mappings if you switch from the alternate register map to the original register map.
(P.914) is set to
ALTERNATE
. Make sure your application uses the
NETW
5.2Finding Data in the Original Register Map Tables
The original register map shown in tables 5.2 through 5.18 describes the registers and
bits used by the FlexPak 3000 drive on the AutoMax network when
MAPSEL (P.914) is set to ORIGINAL.
There are no write registers for control/reference data for Drop_2, Drop_3, and Drop_4.
Table 5.1 – Location of Information in the Original Register Map Tables
Drop_#Master…Data TypeTablePage
1ReadRuntime Signal5.25-2
Tunable, Configurable, and Status5.35-4
WriteControl/Reference5.45-6
Tunable5.55-7
Configurable5.65-8
2ReadRuntime Signal5.75-8
Tunable, Configurable, and Status5.85-8
WriteTunable5.95-9
Configurable5.105-10
3ReadRuntime Signal5.115-11
Tunable, Configurable, and Status5.125-12
WriteTunable5.135-12
Configurable5.145-13
4ReadRuntime Signal5.155-14
Tunable, Configurable, and Status5.165-15
WriteTunable5.175-16
Configurable5.185-17
NETWREGISTER
FlexPak 3000 Drives: Original Register Map
5-1
5-2
AutoMax Network Communication Option Board
Table 5.2 – FlexPak 3000 Original Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
0Drive status word 1Bit-packed word containing information on the present status of the drive
7Tune/config update synch. flag loopback (master read)
8Alarm active
9In current limit
10Coast/DB interlock0=open; 1=closed
11Customer interlock0=open; 1=closed
12Parameter processing error0=no errors; 1=one or more errors
13Terminal strip forward/reverse input state (terminal 5)
14Terminal strip auto/manual input state (terminal 6)
15Terminal strip fault/alarm reset input state (terminal 10)
1
2
3
4
5
6Average
7Network Output Register 1Value of the parameter selected by
8Network Output Register 2Value of the parameter selected by NETWOUTREG 2
9Network Output Register 3Value of the parameter selected by
10 to 15Tunable, Configurable and Status DataSee table 5.3 on page 5-4.
Runtime signal data are updated by the regulator every 5 msec, unless
SPDSOURCESELECTOUT (P.193)Selected speed/voltage loop reference value4095 at TOPSPEED (P.011)
SPDLOOPREFERENCE (P.295)Final speed/voltage loop reference value4095 at TOPSPEED (P.011)
SPDLOOPFEEDBACK (P.296)Final speed/voltage loop feedback value after all scaling 4095 at TOPSPEED (P.011)
SPDLOOPOUTPUT (P.299)Speed loop PI block output value4095 at MAXIMUMCURRENT (P.007
ARMATUREVOLTAGE (P.289)Armature voltage feedback value4095 at MOTORRATEDARMVOLTS (P.009)
CML feedbackCML feedback average over eight CML scans4095 at MAXIMUMCURRENT (P.007)
NETWOUTREG 1
SELECT (P.902)
If no valid parameter value selected,
0=motor speed in RPM
If no valid parameter value selected,
SELECT (P.903)
NETWOUTREG 3
SELECT (P.904)
FEEDBACKSELECT (P.200) is set to ARMATUREVOLT, in which case the update time is 10 msec.
0=armature voltage in volts
If no valid parameter value selected,
0=armature current in amps*10 or amps
FlexPak 3000 Drives: Original Register Map
Table 5.2 – FlexPak 3000 Original Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
16ANALOGAUTOREFERENCE (P.188)The analog reference value in auto mode after all scaling 4095 at TOPSPEED (P.011)
17
18
19
20
21
22
23
Runtime signal data are updated by the regulator every 5 msec, unless FEEDBACKSELECT (P.200) is set to ARMATUREVOLT, in which case the update time is 10 msec.
ANALOGMANTRIMREF (P.194)Analog manual trim reference input value4095 at TOPSPEED (P.011)
ANLGIN 1 (P.492)I/O Exp. kit analog input 1 after gain and zero applied4095 at full scale
ANLGIN 2 (P.493)I/O Exp. kit analog input 2 after gain and zero applied4095 at full scale
FREQIN (P.491)I/O Expansion kit frequency input value after all scaling4095 at full scale
OCLOUTPUT (P.848)Outer control loop output valueRPM
FIELDFEEDBACK (P.589)Motor field current feedback value after scaling and gain 4095 at MOTORHOTFLDAMPS (P.510)
ACLINEVOLTAGE (P.392)Measured AC line RMS voltagevolts RMS
5-3
5-4
AutoMax Network Communication Option Board
Table 5.3 – FlexPak 3000 Original Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Tunable, Configurable, and Status Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
10Fault latch bits word 1Bit-packed word indicating latched faults
0
1
2
3
4
5
6
7Reserved
8
9
10
11OPENARMATURE (F00007)
12
13
14
15
11Reserved
12First faultFault code of the first fault since the last fault reset
13Alarm latch bits wordBit-packed word containing latched alarm bits
0
1
2
3 to 15Reserved
14Last alarmAlarm code of the most recent alarm
15
CONTROLSOURCESELECT (P.000)Selected source for drive control signals
16ACCELERATIONTIME (P.001)Min. time to accelerate from zero to TOPSPEED (P.011)seconds * 10
17
DECELERATIONTIME (P.002)Min. time to decelerate from TOPSPEED (P.011) to zeroseconds * 10
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.
ACLINESYNCHRONIZATIONFAULT (F00010)
FIELDCURRENTLOSS (F00004)
SUSTAINEDOVERLOAD (F00005)
SELFTUNINGFAULT (F00060 to F000099)
MOTORTHERMOSTATTRIP (F00008)
CONTROLLERTHERMOSTATTRIP (F00009)
BLOWERMOTORSTARTEROPEN (F00006)
IET (OVERCURRENT) (F00001)
OVERSPEED (F00003) / ARMATUREOVERVOLTAGE
(F00012)
SCR N
or
MULTIPLE SCRS NOT OPERATING
TACHOMETERLOSS (F00002)
OIMCOMMUNICATIONSTIMEOUT (F00011)
NETWORKCOMMUNICATIONTIMEOUT (F00013)
REVERS EDTACHLEADS (F00014)
MOTORBRUSHWEARLOW (A00001)
ACLINEVOLTAGELOW (A00002)
ACLINEVOLTAGEHIGH (A00003)
(F00030–F00042)
0=
TERMBLK
; 1=
KEYPAD
; 2=
SERIAL
; 3=
NETWORK
FlexPak 3000 Drives: Original Register Map
Table 5.3 – FlexPak 3000 Original Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Tunable, Configurable, and Status Data (Drive Output Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
18MINIMUMSPEED (P.003)Lowest operating speedRPM
19
20
21
22
23
24
25
26
27
280
29NETWCOMMLOSSSELECT (P.901)How the drive responds to network communication loss0=FAUL T; 1 = USELASTREF; 2=USE TRMBLK
30AMXNETWREFSELECT (P.911)AutoMax network reference selection0=DIRECT; 1 to 8 = BROADCAST 1 to 8
31
MAXIMUMSPEED (P.004)Highest operating speedRPM
POSITIVECURRENTLIM (P.005)Highest amount of current for the forward bridge% of MOTORRATEDARMAMPS (P.008)
NEGATIVECURRENTLIM (P.006)Highest amount of current for reverse bridge% of MOTORRATEDAR MAMPS (P.008)
TRIMRANGE (P.109)Amount the trim reference will affect the drive reference %
SPDLOOPPIPROPGAIN (P.211)Speed loop PI proportional gaingain * 100
SPDLOOPPILEADFREQ (P.212)Speed loop PI block lead break frequencyradians/second * 100
CMLPILEADFREQUENCY (P.302) CMLPI lead break frequencyradians/second
CMLREFRATELIMIT (P.303)
JOGSPEED 1 (P.012)Operating speed while joggingRPM
STOPMODESELECT (P.114)Selects how drive responds to a normal stop command0=RAMP; 1= COAST/DB; 2 = CURRENTLIMIT
CURRENTCOMPOUNDING (P.209) Sets the level of current compounding%
NETWCOMMLOSSSELECT
(P.901)
Min. time for
CML
ref. to go from zero to
MAXIMUM CURRENT
milliseconds
How the drive responds to network communication loss0=FAUL T; 1=USELASTREF; 2=USETRMBLKREF,
USETRMBLKCNTL
3=
0=motor speed in
RPM
0=armature voltage in volts
NETWOUTREG 3 SELECT (P.904) Number of the parameter readable in Drop_1, register 9 If no valid parameter value selected, this is set to
0=armature current in amps*10 or amps
Tunable data are read by the regulator approximately every 600 msec while Tune/Config Input Enable bit=1
5-7
5-8
AutoMax Network Communication Option Board
Table 5.6 – FlexPak 3000 Original Register Map, Drop_1: Master Write Registers, BASIC and FULL Connections. Configurable Data (Drive Input Data)
Register Parameter Name (Number)DescriptionSettings
61FEEDBACKSELECT (P.200)Type of feedback for speed/voltage loop feedback0= ARMATUREVOLT; 1=DCTACH ; 2 = PULSETACH; 3=ACTACH
62NETWCONNECTTYPE (P.910)AutoMax network connection type0= BASIC; 1 = FULL
63AMXNETWREFSELECT (P.911)AutoMax network reference selection0=DIRECT; n=BROADCAST n (n=1 to 8)
Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit= 1 and the drive is not running or jogging
Table 5.7 – FlexPak 3000 Original Register Map, Drop_2: Master Read Registers, FULL Connection. Runtime Signal Data (Drive Output Data)
RegisterParameter Name (Number)DescriptionSettings
0ANALOGAUTOREFERENCE (P.188)The analog reference value in auto mode after all scaling 4095 at TOPSPEED (P.011)
1Reserved
2
ANALOGMANTRIMREF (P.194)Analog manual trim reference input value4095 at TOPSPEED (P.011)
3 to 10Reserved
Runtime signal data are updated by the regulator every 5 msec, unless
Table 5.8 – FlexPak 3000 Original Register Map, Drop_2: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data)
FEEDBACKSELECT (P.200) is set to ARMATUREVOLT, in which case the update time is 10 msec.
RegisterBitParameter Name (Number)DescriptionSettings
19ANLGAUTOGAINADJ (P.101)Scales analog auto reference signalgain * 1000
20
21
22
OCLOUTPUT (P.848)Outer control loop output valueRPM
TOPSPEED (P.011)Highest running speed of motorRPM
JOGSPEED 1 (P.012)Operating speed while joggingRPM
JOGACCEL/DECELTIME (P.013)Minimum time in which jog reference can change from
TOPSPEED (P.011) and from TOPSPEED to zero
zero to
S-CURVEROUNDING (P.014)Amount of smoothing of speed/voltage loop reference%
REVERS EDISABLE (P.015)Prevents speed/voltage loop ref. from going negative0=OFF (bipolar ref); 1= ON (positive ref)
ANLGAUTOSIGNALTYPE (P.100)Type of signal applied to analog auto reference input
ANLGAUTOZEROADJ (P.102)Offset removed from analog auto reference signal
AUTOREFERENCESELECT (P.103)Selects the type of auto reference0= ANALOG; 1 = FREQUENCYIN
ANLGMANREFGAINADJ (P.104)Scales the analog manual reference gaingain * 1000
seconds * 10
0=0-10V; 1=±10V; 2=4-20mA; 3=10-50mA
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.
FlexPak 3000 Drives: Original Register Map
Table 5.8 – FlexPak 3000 Original Register Map, Drop_2: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
23ANLGMANREFZEROADJ (P.105)Offset removed from the analog manual reference signal
62REVERS EDISABLE (P.015)Prevents speed/voltage loop ref. from going negative0=OFF (bipolar ref); 1= ON (positive ref)
63
ANLGAUTOSIGNALTYPE (P.100)Type of signal applied to analog auto reference input
0=0-10V; 1=±10V; 2=4-20mA; 3=10-50mA
Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit=1 and the drive is not running or jogging.
Table 5.11 – FlexPak 3000 Original Register Map, Drop_3: Master Read Registers, FULL Connection. Runtime Signal Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
0ANALOGTACHFEEDBACK (P.291)Analog tachometer feedback signal after all scaling4095 at TOPSPEED (P.011)
1
2
3
4
5
6 to 11Reserved
Runtime signal data are updated by the regulator every 5 msec, unless
PULSETACHFEEDBACK (P.292)Pulse encoder feedback signal after all scaling4095 at TOPSPEED (P.011)
SPDLOOPERROR (P.297)Speed loop error
CMLREFERENCE (P.396)Amplitude and rate limited value of selected CML ref.4095 at MAXIMUMCURRENT (P.007)
FIELDREFERENCE (P.590)Field current reference4095 at MOTORHOTFLDAMPS (P.510)
FIELDFEEDBACK (P.589)Motor field current feedback value after scaling and gain 4095 at MOTORHOTFLDAMPS (P.510)
FEEDBACKSELECT (P.200) is set to ARMATUREVOLT, in which case the update time is 10 msec.
5-11
Table 5.12 – FlexPak 3000 Original Register Map, Drop_3: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
12MAXIMUMCURRENT (P.007)Highest amount of current, either positive or negative% of MOTORRATEDARMAMPS (P.008)
13
14
15
16ANALOGTACHGAINADJ (P.201)Scales analog tachometer feedback signalgain * 1000
MOTORRATEDARMAMPS (P.008)Rated armature current from motor nameplateamps * 10
MOTORRATEDARMVOLTS (P.009)Rated armature voltage from motor nameplatevolts DC
FEEDBACKSELECT (P.200)Type of feedback for speed/voltage loop feedback0 = ARMATUREVOLT; 1=DCTACH; 2= PULSE
TACH; 3=ACTACH
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.
5-12
Table 5.12 – FlexPak 3000 Original Register Map, Drop_3: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
17ANALOGTACHZEROADJ (P.202)Removes offset from analog tachometer feedback signal
18
19
20
21
22
23
24
25
26
27
28
29
30
31
ANLGTACHVOLTS/1000 (P.203)Analog tach scaling from tach nameplate in V/1000RPMvolts * 10
ARMVOLTAGE GAINADJ (P.204)Scales the armature voltage signalgain * 1000
ARMVOLTAGE ZEROADJ (P.205)Offset removed from armature voltage feedback
IRCOMPENSATION (P.206)Armature voltage loss compensation%
PULSETACHPPR (P.207)Pulses per revolution from the pulse encoder nameplate
PULSETACHQUADRATURE (P.208)Enables or disables pulse encoder quadrature0=OFF; 1=ON (quad decode)
CURRENTCOMPOUNDING (P.209)Sets the level of current compounding%
SPDLEADLAGRATIO (P.213)Low & high break frequency ratio of feedback lead/lag
SPDLEADLAGLOWFREQ (P.214)Low break frequency of speed feedback lead/lag blockradians/second * 100
SPDLOOPLAGFREQ (P.215)Lag break frequency of speed loop forward path lagradians/second * 100
48SPDLOOPLAGBYPASS (P.217)Speed/voltage loop lag block bypass0= OFF (not bypassed); 1=ON (bypassed)
49
CMLFEEDBACKGAINADJ (P.300)Current minor loop feedback gain adjustgain * 1000
50 to 53Reserved
Tunable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit = 1.
Table 5.14 – FlexPak 3000 Original Register Map, Drop_3: Master Write Registers, FULL Connection. Configurable Data (Drive Input Data)
radians/second * 100
5-13
RegisterBitParameter Name (Number)DescriptionSettings
54AUTOREFERENCESELECT (P.103)Selects the type of auto reference0= ANALOG; 1 = FREQUENCYIN
55MOTORHOTFLDAMPS (P.510)Rated hot field amps from motor nameplateamps * 100
56
57
58MAXIMUMCURRENT (P.007)Highest amount of current, either positive or negative% of MOTORRATEDARMAMPS (P.008)
59
60
61
62
63
Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit=1 and the drive is not running or jogging.
FIELDLOSSTHRESHOLD (P.512)Field current level at which a field loss fault is generated % of MOTORHOTFLDAMPS (P.510)
FIELDAUTOWEAKEN (P.517)Enables or disables automatic field weakening0=DISABLED; 1=ENABLED
MOTORRATEDARMAMPS (P.008)Rated armature current from motor nameplateamps * 10
MOTORRATEDARMVOLTS (P.009)Rated armature voltage from motor nameplatevolts DC
ANLGTACHVOLTS/1000 (P.203)Analog tachometer scaling from tachometer nameplate
in volts per 1000
PULSETACHPPR (P.207)Pulses per revolution from pulse encoder nameplate
PULSETACHQUADRATURE (P.208)Enables or disables pulse encoder quadrature0=OFF; 1=ON (quad decode)
RPM
volts * 10
5-14
AutoMax Network Communication Option Board
Table 5.15 – FlexPak 3000 Original Register Map, Drop_4: Master Read Registers, FULL Connection. Runtime Signal Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
0I/O Expansion kit digital inputs
Bit-packed word that indicates the state of these inputs
0I/O Expansion kit digital input 1 (Preset speed select 1)*
1I/O Expansion kit digital input 2 (Preset speed select 2)*
2I/O Expansion kit digital input 3 (mop decrement)*
3I/O Expansion kit digital input 4 (mop increment)*
4I/O Expansion kit digital input 5 (ocl enable)*
1
2
3
ANLGIN 1 (P.492)I/O Exp. kit analog input 1 after gain and zero applied4095 at full scale
ANLGIN 2 (P.493)I/O Exp. kit analog input 2 after gain and zero applied4095=full scale
FREQIN (P.491)I/O Expansion kit frequency input value after all scaling4095 = full scale
4 to 20Reserved
Runtime signal data are updated by the regulator every 5 msec, unless
*
The I/O Expansion kit digital inputs do not have fixed functions when CONTROLSOURCESELECT (P.000) is set to NETWORK. Therefore, they do not select preset speeds,
change the
MOP setpoint, or enable or disable the OCL.
Table 5.16 – FlexPak 3000 Original Register Map, Drop_4: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data)
FEEDBACKSELECT (P.200) is set to ARMATUREVOLT , in which case the update time is 10 msec.
*
RegisterBitParameter Name (Number)DescriptionSettings
21Level Detector OutputsBit-packed word indicating state of level detector outputs
0Level detector 1 output
1Level detector 2 output
Tunable, configurable and status data are updated by the regulator approximately every 600 msec.
FlexPak 3000 Drives: Original Register Map
Table 5.16 – FlexPak 3000 Original Register Map, Drop_4: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
22Stop cause wordBit-packed word indicating why the drive stopped
0Stop asserted or Run de-asserted (negated)
1Jog de-asserted for less than 1 second
2Internal stop request
3Current limit stop
4Ramp stop
5Coast/DB stop
6Fault stop or self-tuning complete
7Customer interlock opened
8Coast/DB interlock opened
9Main contactor opened
10 – 15Reserved
23
24
25PLLMAXIMUMERROR (P.308)Max. allowed change in line period per AC line cycleµsec
26
27ENHANCEDFLDVOLTADJ (P.500)Adjusts the field output voltage
28
29
30
31
NOMINALACLINEFREQ (P.306)Nominal AC line frequencyHz
NOMINALACLINEVOLTS (P.307)Nominal AC line RMS voltagevolts RMS
ACLINEVOLTAGE (P.392)Measured AC line RMS voltagevolts RMS
FIELDECONOMYDELAY (P.501)Time between stopping and entering field economyminutes
FIELDECONOMYACTIVE (P.599)Indicates the present state of field economy0=OFF; 1=ON (field economy active)
NOMINALACLINEFREQ (P.306)Nominal AC line frequencyHz
NOMINALACLINEVOLTS (P.307)Nominal AC line RMS voltagevolts RMS
5-18
AutoMax Network Communication Option Board
CHAPTER 6
FlexPak 3000 Drives:
Alternate Register Map
This section lists the alternate register map, which enables you to access most of the
FlexPak 3000 original register map functions plus some additional functions. The
alternate register map is organized so that commonly used functions are available in
Drop_1. It also offers a different set of options in Drop_1 than the original register
map.
The additional functions that are available through the alternate register map are:
• Winding functions: SPEEDFEEDBACKGAIN (Drop_1, register 38) and UNDERWIND
ENABLE (Drop_1, register 32, bit 5) enable you to set up under- or overwinding and
set the gain of the speed loop feedback path for winding applications.
• Access to the speed loop PI reset and initial value. These parameters are SPDLOOP
PIINITSEL (Drop_2, register 32), SPDLOOPPIINITVAL (Drop_1, register 39), and SPD
LOOPPIRESET (Drop_1, register 32, bit 6).
ATTENTION: If you are using the alternate register map (NETWREGISTER
MAPSEL (P.914) set to ALTERNATE) and you change the control source
NETWORK, the parameters SPDLOOPPIINITSEL, SPDLOOPPIINITVAL,
!
from
and
SPDLOOPPIRESET are reset to their default values (0 for each). Make
sure these values are appropriate for your application before changing
the control source. Failure to observe this precaution could result in
severe bodily injury or loss of life.
• Process Error Parameter Number (Drop_1, register 27)
• NEGCURLIMINVEN (P.226) (Drop_3, register 53, bit 0)
• OCLPROPTRIMSELECT (P.813) (Drop_3, register 53, bit 1)
• OCLTYPE3 POSNREGEN (P.814) (Drop_3, register 53, bit 2)
• PHASELOSSDETECTEN (P.609) (Drop_3, register 53, bit 3)
• STOPDECELSELECT (P.122) (Drop_3, register 53, bit 4)
• CMLREFLIMITSELECT (P.311) (Drop_3, register 53, bit 6
• DIGIN 0 SELECT (P.428) (Drop_4, register 47)
Brief descriptions of parameters are in the register map tables. For detailed parameter
descriptions, refer to the
FlexPak 3000 Drives: Alternate Register Map
FlexPak 3000 DC Drive Software Reference Manual
.
6-1
6.1Accessing the Alternate Register Map
To access the alternate register map, set
NETW REGISTER MAP SEL
Some parameters are not available and others are mapped differently when
REGISTER MAP SEL
(P.914) is set to
ALTERNATE
. Make sure your application uses the
correct mappings if you switch from the original register map to the alternate register map.
Important: When a version
4.2
Regulator board is used as a replacement in an
existing AutoMax network that uses the ALTERNATE register map, you
may need to reprogram the master task so that it writes valid data in the
registers that are now being used (where previously they were marked as
reserved).
6.2Diagnosing Processing Errors
In the alternate map, Drop_1, register 27, the number of the parameter that caused a
processing error (indicated by alternal map, register 0, bit 10) is now recorded. If there
are no processing errors, the value will be set to -1.
Because some parameters are processed in groups, it is not possible to always report
the specific parameter that is out of range. Instead, the first parameter number of the
group that conains the error is reported (see table 6.1). For example, if
TIME (P.115) was set out of range by the Network Option board, Drop_1, register 27
would contain the value 14 (
handled on an individual basis by the parameter processing routines so the parameter
causing the processing error is reported by number directly. This feature is available
only with the alternate register map. Also listed in the table are possible non-user
paramter numbers (≥ 25000) that can cause parameter processing errors.
S-CURVEROUNDING). Parameters not listed in table 6.1are
(P.914) to
MOPACCEL
ALTERNATE
NETW
.
Be aware that certain parameters are used as limits for other parameters (for example,
TOPSPEED (P.011) determines the maximum limit for MAXIMUMSPEED (P.004). The
FlexPak 3000 Software Reference
(D2-3405) describes the relationships between all
user parameters. It is also possible (but very unlikely) to get a processing error
reported for a non-user parameter number not listed below. If this occurs, the
Regulator board is suspect. Cycle power, and if another non-user parameter number
processing error occurs, replace the Regulator board.
6-2
AutoMax Network Communication Option Board
Table 6.1 – Error Processing Parameters Reported by Group
Number
Reported
004004
005005
211211
213
424
427
510
514
519
Parameter
NumberParameter Name
MAXIMUMSPEED
003
012
017
117
118
119
113
006
212
213
214
424
423
427
426
510
516
514
515
519
520
MINIMUM
JOG
JOGSPEED 2
PRESETSPEED 1
PRESETSPEED 2
PRESETSPEED 3
STOPSPEEDTHRESHOLD
POSITIVECURRENTLIMIT
NEGATIVE
SPDLOOPPIPROPGAIN
SPD
SPDLEADLAGRATIO
SPD
FREQINFULLSCALE
FREQ
FREQOUTFULLSCALE
FREQ
MOTORHOTFLDAMPS
FLD
FIELDPIPROPGAIN
FIELD
FLDWEAKENPROPGAIN
FLD
SPEED
SPEED 1
CURRENTLIMIT
LOOPPILEADFREQ
LEADLAGLOWFREQ
INZERO
OUTZERO
FEEDBACKGAINADJ
PILEADFREQ
WEAKENLEADGAIN
Number
Reported
Parameter
NumberParameter Name
014014
803803
807807
808808
900900
902902
2520025200
26015
001
018
013
115
120
802
806
809
910
903
904
S-CURVEROUNDING
ACCELERATION
DECELERATION
STOPDECELTIME
RAMP
ACCEL/DECELTIME
JOG
ACCELTIME
MOP
DECELTIME
MOP
OCLREFROUNDING
REFRAMPTIME
OCL
OCLLEADLAGRATIO
LEADLAGLOWREQ
OCL
OCLPIPROPGAIN
PILEADFREQ
OCL
NETWDROPNUMBER
CONNECTTYPE
NETW
NETWOUTREG 1 SELECT
NETW
OUTREG 2 SELECTOUTREG 3 SELECT
NETW
TIMETIME
Trending Aquisition Rate
(set by CS3000)
SPDLOOPPIINITSEL
(alternate, Drop_2, reg
32)
FlexPak 3000 Drives: Alternate Register Map
6-3
6.3Finding Data in the Alternate Register Map Tables
The alternate register maps in table 6.3 through table 6.18 describe the registers and
bits used by the FlexPak 3000 drive on the AutoMax network when
MAPSEL (P.914) is set to ALTERNATE.
Drop_2, Drop_3, and Drop_4 do not have master write registers for control/reference
data. Drop_4 does not have a master read register for runtime signal data.
Table 6.2 – Location of Information in the FlexPak 3000 Alternate Register Map Tables
Drop_#Master…Data TypeTablePage
1ReadRuntime Signal6.36-5
Tunable, Configurable, and Status6.46-7
WriteControl/Reference6.56-9
Tunable6.66-10
Configurable6.76-10
2ReadRuntime Signal6.86-11
Tunable, Configurable, and Status6.96-11
WriteTunable6.106-12
Configurable6.116-13
3ReadRuntime Signal6.126-14
Tunable, Configurable, and Status6.136-14
WriteTunable6.146-15
Configurable6.156-16
4ReadTunable, Configurable, and Status6.166-17
WriteTunable6.176-18
Configurable6.186-18
NETWREGISTER
6-4
AutoMax Network Communication Option Board
FlexPak 3000 Drives: Alternate Register Map
Table 6.3 – FlexPak 3000 Alternate Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
0Drive status word 1Bit-packed word containing information on the present status of the drive
7Tune/config update synch flag loopback (master read)
8Alarm active
9In current limit
10Parameter processing error
11Level detector 1 output
12Level detector 2 output
13–15Reserved
1Drive status word 2Bit-packed word containing information on the present status of the drive
0FN/DB status
1Customer interlock0=open; 1=closed
2Terminal strip run
3Terminal strip forward/reverse
4Terminal strip jog
5Terminal strip stop
6Coast/DB interlock0=open; 1=closed
7Terminal strip fault reset
8I/O Expansion kit digital input 1 (Preset speed select 1)
9I/O Expansion kit digital input 2 (Preset speed select 2)
10I/O Expansion kit digital input 3 (MOP decrement)
11I/O Expansion kit digital input 4 (MOP increment)
12I/O Expansion kit digital input 5 (OCL enable)
6-5
Runtime signal data are updated by the regulator every 5 msec, unless FEEDBACKSELECT (P.200) is set to ARMATUREVOLT, in which case the update time is 10 msec.
*
*
*
*
*
6-6
AutoMax Network Communication Option Board
Table 6.3 – FlexPak 3000 Alternate Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
1 (con’t.)13Terminal strip auto/manual
14Digital input 0
15Motor thermostat
2
3
4
5
6Average
7Network Output Register 1Value of the parameter selected by
8Network Output Register 2Value of the parameter selected by NETWOUTREG 2
9Network Output Register 3Value of the parameter selected by
10 to 15Tunable, Configurable and Status DataSee table 6.4 on page 6-7.
16
17
18
19
20
21
22 FIELDFEEDBACK (P.589)Motor field current feedback value after scaling and gain 4095 at MOTORHOTFLDAMPS (P.510)
23
Runtime signal data are updated by the regulator every 5 msec, unless FEEDBACKSELECT (P.200) is set to ARMATUREVOLT, in which case the update time is 10 msec.
*
The I/O Expansion kit digital inputs do not have fixed functions when CONTROLSOURCESELECT (P.000) is set to NETWORK. Therefore, they do not select preset speeds, change the MOP
setpoint, or enable or disable the
SPDLOOPREFERENCE (P.295)Final speed/voltage loop reference value4095 at TOPSPEED (P.011)
SPDLOOPFEEDBACK (P.296)Final speed/voltage loop feedback value after all scaling 4095 at TOPSPEED (P.011)
SPDLOOPOUTPUT (P.299)Speed loop PI block output value4095 at MAXIMUMCURRENT (P.007)
ARMATUREVOLTAGE (P.289)Armature voltage feedback value4095 at MOTORRATEDARMVOLTS (P.009)
CML feedbackCurrent minor loop feedback average over 8 CML scans4095 at MAXIMUMCURRENT (P.007)
NETWOUTREG 1
SELECT (P.902)
If no valid parameter value selected,
0=motor speed in RPM
If no valid parameter value selected,
SELECT (P.903)
NETWOUTREG 3
SELECT (P.904)
ANALOGAUTOREFERENCE (P.188)Analog reference value in auto mode after all scaling4095 at TOPSPEED (P.011)
ANALOGMANTRIMREF (P.194)Analog manual trim reference input value4095 at TOPSPEED (P.011)
ANLGIN 1 (P.492)I/O Exp. kit analog input 1 after gain and zero applied4095 at full scale
ANLGIN 2 (P.493)I/O Exp. kit analog input 2 after gain and zero applied4095 at full scale
FREQIN (P.491)I/O Expansion kit frequency input value after all scaling4095 at full scale
OCLOUTPUT (P.848)Outer control loop output valueRPM
ACLINEVOLTAGE (P.392)Measured AC line RMS voltagevolts RMS
OCL.
0=armature voltage in volts
If no valid parameter value selected,
0=armature current in amps*10 or amps
FlexPak 3000 Drives: Alternate Register Map
Table 6.4 – FlexPak 3000 Alternate Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Tunable, Configurable, and Status Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
10Fault latch bits word 1Bit-packed word indicating latched faults
0
1
2
3
4
5
6
ACLINESYNCHRONIZATIONFAULT (F00010)
FIELDCURRENTLOSS (F00004)
SUSTAINEDOVERLOAD (F00005)
SELFTUNINGFAULT (F00060 to F000099)
MOTORTHERMOSTATTRIP (F00008)
CONTROLLERTHERMOSTATTRIP (F00009)
BLOWERMOTORSTARTEROPEN (F00006)
7Reserved
8
9
10
IET (OVERCURRENT) (F00001)
OVERSPEED (F00003)/ARMATUREOVERVOLTAGE (F00012)
SCR
# or
MULTIPLE SCRS NOT OPERATING
(F00030–F00042)
11OPENARMATURE (F00007)
12
13
14
15
TACHOMETERLOSS (F00002)
OIMCOMMUNICATIONSTIMEOUT (F00011)
NETWORKCOMMUNICATIONTIMEOUT (F00013)
REVERS EDTACHLEADS (F00014)
11Reserved
12First faultFault code of the first fault since the last fault reset
13Alarm latch bits wordBit-packed word containing latched alarm bits
0
1
2
MOTORBRUSHWEARLOW (A00001)
ACLINEVOLTAGELOW (A00002)
ACLINEVOLTAGEHIGH (A00003)
3 to 15Reserved
14Last alarmAlarm code of the most recent alarm
15
CONTROLSOURCESELECT (P.000)Selected source for drive control signals
0=
TERMBLK
; 1=
KEYPAD
; 2=
SERIAL
; 3=
NETWORK
16 to 23See table 6.3 on page 6-5.
24 to 25Reserved
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.
6-7
6-8
AutoMax Network Communication Option Board
Table 6.4 – FlexPak 3000 Alternate Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Tunable, Configurable, and Status Data (Drive Output Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
26Stop cause word
Bit-packed word indicating why the drive stopped
0Stop asserted or Run de-asserted (negated)
1Jog de-asserted for more than 1 second
2Internal stop request
3Current limit stop
4Ramp stop
5Coast/DB stop
6Fault stop or self-tuning completed
7Customer interlock opened
8Coast/DB interlock opened
9Main contactor opened
10 – 15Reserved
27Process Error Parameter NumberIndicates the parameter number that caused a
REGULATORSWVERSION (P.794)Regulator board software version
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.
*
Before examining this register, check the drive status word (Drop_1, register 0) to determine if the drive is presently running or jogging. If neither of these bits is set to ON (1), then the stop
cause word can be examined to determine why the drive last stopped. If all the defined bits in the stop cause word are false, the drive is either running, jogging, or has not been started since
the last power-up.
*
-1 = No parameter processing error.
FlexPak 3000 Drives: Alternate Register Map
Table 6.5 – FlexPak 3000 Alternate Register Map, Drop_1: Master Write Registers BASIC and FULL Connections. Control/Reference Data (Drive Input Data)
RegisterBitParameter Name (Number)DescriptionSettings
32Sequencing control wordWord containing drive sequencing and control bits
0Run0 to 1 transition to run
1Stop0=stop; 1= not stop
2Fault reset0 to 1 transition to reset
3Jog0 to 1 transition to jog; 0=stop
4Fwd/Rev select0=forward; 1=reverse
5
6SPDLOOPPIRESET
7Outer control loop enable0=hold OCL in reset; 1=OCL enabled
8Fault log clear and reset0 to 1 transition to clear
9Alarm log clear and reset0 to 1 transition to clear
10Alarm reset0 to 1 transition to reset
11Memory save0 to 1 transition to save
12&13Reserved
14Tune/config input enable. What to read from the network. “Read all”
15Tune/config update synchronization flag (master write)
33Network ReferenceSpeed/voltage loop or
34Network Input Register 1Written by network masterRead at
35Network Input Register 2Written by network masterRead at
36Network Input Register 3Written by network masterRead at
37
38
FIELDREFREGISTER (P.513)Reference for the field current loop4095 at MOTORHOTFLDAMPS (P.510)
SPEEDFEEDBACKGAINControls gain of the speed loop feedback pathGain * 1000 (1000 to 32000)
39SPDLOOPPIINITVALInitial value of speed loop PI block. This value is at the PI block
Control/reference data are read by the regulator every 5 msec, unless FEEDBACKSELECT (P.200) is set to ARMATUREVOLT, in which case the update time is 10 msec.
6-9
*
This parameter is network-only. If the control source is changed from NETWORK to something else, this parameter is automatically reset to its default value.
UNDERWINDENABLE0=DISABLED (overwind); 1= ENABLED
(underwind); (Default=0)
*
0=OFF (enable) (default); 1 = ON (reset)
0=read only control/reference inputs;
includes control/reference, tunable, and configurable inputs
CML reference value when CONTROLSOURCE
SELECT (P.000)=NETWORK and AMXNETWREFSELECT (P.911) = 0
output when block is in reset. Block is in reset when drive is stopped
1=read all
4095 at
ARMVOLTS (P.009) or MAXCURRENT (P.007)
(Default = 1000 (1.000))
4095 at MAXIMUMCURRENT (P.007)
(default=0)
TOPSPEED (P.011)/MOTORRATED
OIM or DCM (NETWINREG 1, P.905)
OIM or DCM (NETWINREG 2, P.906)
OIM or DCM (NETWINREG 3, P.907)
*
*
or bit 6 of sequencing control word (Drop_1, register 32) is set to 1.
*
6-10
AutoMax Network Communication Option Board
Table 6.6 – FlexPak 3000 Alternate Register Map, Drop_1: Master Write Registers, BASIC and FULL Connections. Tunable Data (Drive Input Data)
Register Bit Parameter Name (Number)DescriptionSettings
40ACCELERATIONTIME (P.001)Min. time to accelerate from zero to TOPSPEED (P.011)seconds * 10
41
42
43MAXIMUMSPEED (P.004)Highest operating speedRPM
44POSITIVECURRENTLIM (P.005)Highest amount of current for the forward bridge% of MOTORRATEDARMAMPS (P.008)
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59NETWOUTREG 2 SELECT (P.903) Number of the parameter readable in Drop_1, register 8
60NETWOUTREG 3 SELECT (P.904) Number of the parameter readable in Drop_1, register 9 If no valid parameter selected, set to 0=armature current in
DECELERATIONTIME (P.002)Min. time to decelerate from TOPSPEED (P.011) to zeroseconds * 10
MINIMUMSPEED (P.003)Lowest operating speedRPM
NEGATIVECURRENTLIM (P.006)Highest amount of current for reverse bridge% of MOTORRATEDARMAMPS (P.008)
S-CURVEROUNDING (P.014)Smoothing of the speed/voltage loop reference%
TRIMRANGE (P.109)Amount the trim reference will affect the drive reference %
SPDLOOPPIPROPGAIN (P.211)Speed loop PI proportional gaingain * 100
SPDLOOPPILEADFREQ (P.212)Speed loop PI block lead break frequencyradians/second * 100
62REVERSEDISABLE (P.015)Prevents speed/voltage loop ref. from going negative 0 = OFF (bipolar ref); 1= ON (positive ref)
Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit= 1 and the drive is not running or jogging.
*
1; 3=
NETW
ANALOG IN
2
6-14
Table 6.11 – FlexPak 3000 Alternate Register Map, Drop_2: Master Write Registers, FULL Connection. Configurable Data (Drive Input Data) (Continued)
Register Bit Parameter Name (Number)DescriptionSettings
63ANLGAUTOSIGNALTYPE (P.100) Type of signal applied to analog auto reference input 0 = 0–10V; 1= +/– 10 V; 2=4- 20 mA; 3 =10-50mA
Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit= 1 and the drive is not running or jogging.
*
This parameter is network-only. If the control source is changed from NETWORK to something else, this parameter is automatically reset to its default value.
Table 6.12 – FlexPak 3000 Alternate Register Map, Drop_3: Master Read Registers, FULL Connection. Runtime Signal Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
0ANALOGTACHFEEDBACK (P.291)Analog tachometer feedback signal after all scaling4095 at TOPSPEED (P.011)
1
2
3
4
5Reserved
Runtime signal data are updated by the regulator every 5msec, unless
Table 6.13 – FlexPak 3000 Alternate Register Map, Drop_3: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data)
PULSETACHFEEDBACK (P.292)Pulse encoder feedback signal after all scaling4095 at TOPSPEED (P.011)
SPDLOOPERROR (P.297)Speed loop error
CMLREFERENCE (P.396)Amplitude and rate limited value of selected CML ref4095 at MAXIMUMCURRENT (P.007)
FIELDREFERENCE (P.590)Field current reference4095 at MOTORHOTFLDAMPS (P.510)
FEEDBACKSELECT (P.200) is set to ARMATUREVOLT, in which case the update time is 10msec.
AutoMax Network Communication Option Board
RegisterBitParameter Name (Number)DescriptionSettings
NOMINALACLINEFREQ (P.306)Nominal AC line frequencyHz
NOMINALACLINEVOLTS (P.307)Nominal AC line RMS voltagevolts RMS
6-19
6-20
AutoMax Network Communication Option Board
This section lists the WebPak 3000 register map and describes how to use indirect
parameters.
Brief descriptions of parameters are in the register map tables. For detailed parameter
descriptions, refer to the
WebPak 3000 DC Drive Software Reference Manual.
7.1Using Indirect Parameters
In a full connection, the WebPak 3000 drive occupies three sequential network drops.
Drop_2 and Drop_3 contain indirect registers. The indirect registers enable you to
customize the list of input parameters you want the master to write to.
The Drop_2 master write registers (registers 32 to 63) determine the parameters to
which the values in the Drop_3 master write registers are written. Up to 33
user-specified input registers can be accessed at any one time. A value of 0 in any of
the Drop_2 write registers disables the corresponding indirect register in drop 3.
CHAPTER 7
WebPak 3000 Drives:
Register Map
Drop_3, register 31 contains an Indirect Register Status (ISR) word. This output
register indicates the current status of the parameters written to the master write
registers in Drop_2 along with the tune/config update synchronization flag loopback bit
(Drop_3, register 32, bit 15). This network synchronization bit functions the same as
the network synchronization bit in Drop_1 (register 0, bit 15) (described in section 4.5
of this manual).
The ISR word also contains status information about the parameters input to Drop_2.
When all of the parameter numbers have been accepted by the drive, the two status
bits (Drop_3, register 31, bits 13 to14) and the lower six bits are all 0. If the value
entered in Drop_2 is not a valid parameter number, then bit 13 is set. If the value
entered in Drop_2 corresponds to an output parameter, then bit 14 is set. In either
case, the offending register number is placed in the lower six bits (1 to 32). If multiple
errors are present, then the highest numbered register is reported.
Example Using the ISR Word
Assume the master program writes the value 820 (the parameter number for
LOADING) to AutoMax indirect parameter 17 (Drop_2, register 48).
After the drive completes processing, the drive updates the ISR (bits 0 to 14) with the
value 16401 (4011 hexadecimal). Bit 15 equals the value written to the network
synchronization flag (Drop_1, register 0, bit 15).
Since parameter P.820 is an output parameter, bit 14 in the ISR is set. Bits 0 to 6
identify the offending AutoMax indirect register as number 17.
DANCER
WebPak 3000 Drives: Register Map
7-1
When updating the Drop_2 master read registers in the WebPak 3000 drive, the
network synchronization flag must be used with the tune/config input enable flag. If the
updating of the indirect parameter numbers in Drop_2 is not properly synchronized to
the values written in Drop_3, improper values written to parameters may result in
unintended drive operation. The following sections describe the proper sequences for
modifying the Drop_2 and Drop_3 master read values.
7.1.1 Enabling the AutoMax Indirect Parameter Numbers
Step 1.The tune/config input enable flag must have been cleared for a minimum of
600 msec (Drop_1, register 32, bit 14).
Step 2.Modify AutoMax Indirect Register numbers (Drop_2, registers 32 to 63) with
the parameter numbers that you wish to write to in the corresponding
Drop_3 register. Parameter number 0 deactivates that particular indirect
register.
Step 3.Modify the corresponding register values (Drop_3, registers 32 to 63) for the
parameters selected in step 2.
Step 4.Set the tune/config input enable flag (Drop_1, register 32, bit 14).
Step 5.Toggle the tune/config update synchronization flag (Drop_1, register 32, bit
15).
Step 6.Monitor the tune/config update synchronization flag loopback bit in the
Indirect Register Status word (Drop_3, register 32, bit 15) until it equals the
value written in step 4.
7.1.2 Changing the AutoMax Indirect Register Values
Step 1.Modify the desired register values (Drop_3, registers 32 to63).
Step 2.Toggle the tune/config update synchronization flag (Drop_1, register 32, bit
15).
Step 3.Monitor the tune/config update synchronization flag loopback bit in the
Indirect Register Status word (Drop_3, register 32, bit 15) until it equals the
value written in step 4.
7.1.3 Disabling the AutoMax Indirect Registers
Step 1.Clear the tune/config input enable flag (Drop_1, register 32, bit 14).
Step 2.Toggle the tune/config update synchronization flag (Drop_1, register 32, bit
15).
Step 3.Monitor the tune/config update synchronization flag loopback bit in the
Indirect Register Status word (Drop_3, register 32, bit 15) until it equals the
value written in step 4.
7-2
AutoMax Network Communication Option Board
7.2Diagnosing Processing Errors
In the alternate map, Drop_1, register 27, the number of the parameter that caused a
processing error (indicated by alternate map, register 0, bit 10) is now recorded. If
there are no processing errors, the value will be set to -1.
Because some parameters are processed in groups, it is not possible to always report
the specific parameter that is out of range. Instead, the first parameter number of the
group that contains the error is reported (see table 7.1).
TIME
(P.115) was set out of range by the Network Option board, Drop_1, register
27 would contain the value 14 (
7.1 are handled on an individual basis by the parameter processing routines so the
parameter causing the processing error is reported by number directly. Also listed in
the table are possible non-user parameter numbers (≥ 25000) that can cause
parameter processing errors.
Be aware that certain parameters are used as limits for other parameters (for example,
TOP SPEED
(P.011) determines the maximum limit for
WebPak 3000 Software Reference (D2-3444) describes the relationships between all
user parameters. It is also possible (but very unlikely) to get a processing error
reported for a non-user parameter number not listed below. If this occurs, the
Regulator board is suspect. Cycle power, and if another non-user parameter number
processing error occurs, replace the Regulator board.
Table 7.1 – Error Processing Parameters Reported by Group
S-CURVE ROUNDING
For example, if
).
Parameters not listed in table
MAXIMUM SPEED
MOP ACCEL
(P.004).
The
Number
Reported
004004
005005
213213
014014
424424
427427
510510
514514
Parameter
NumberParameter Name
MAXIMUMSPEED
003
012
113
006
214
001
002
018
013
423
426
516
515
MINIMUM
JOG
STOPSPEEDTHRESHOLD
POSITIVECURRENTLIM
NEGATIVE
SPDLEADLAGRATIO
SPD
S-CURVEROUNDING
ACCELERATION
DECELERATION
RAMP
JOG
FREQINFULLSCALE
FREQ
FREQOUTFULLSCALE
FREQ
MOTORHOTFLDAMPS
FLD
FIELDPIPROPGAIN
FIELD
SPEED
SPEED 1
CURRENTLIM
LEADLAGLOWFREQ
TIMETIME
STOPDECELTIME
ACCEL/DECELTIME
INZERO
OUTZERO
FEEDBACKGAINADJ
PILEADFREQ
Number
Reported
519519
803803
807807
900900
902902
Parameter
NumberParameter Name
FLDWEAKENPROPGAIN
520
802
806
910
903
904
WEAKENLEADFREQ
FLD
OCLREFROUNDING
REFRAMPTIME
OCL
OCLLEADLAGRATIO
OCL
LEADLAGLOWREQ
NETWDROPNUMBER
CONNECTTYPE
NETW
NETWOUTREG 1 SELECT
OUTREG 2 SELECT
NETW
OUTREG 3 SELECT
NETW
2520025200Trending Aquisition Rate
(set by WebPakCS)
26015SPDLOOPPIINITSEL
(alternate, Drop_2,
reg 32)
WebPak 3000 Drives: Register Map
7-3
7.3Finding Data in the Register Map Tables
There are no write registers for control/reference data for Drop_2 and Drop_3.
Table 7.2 – Location of Information in the WebPak Register Map Tables
Drop_#Master…Data TypeTablePage
1ReadRuntime Signal7.37-5
Tunable, Configurable, and Status7.47-7
WriteControl/Reference7.57-8
Tunable7.67-9
Configurable7.77-11
2ReadRuntime Signal7.87-11
Tunable, Configurable, and Status7.97-12
WriteTunable - Indirect Parameters7.107-13
3ReadRuntime Signal7.117-15
WriteTunable/Configurable - Indirect
Parameters
7.117-16
7-4
AutoMax Network Communication Option Board
WebPak 3000 Drives: Register Map
Table 7.3 – WebPak 3000 Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
0Drive status word 1Bit-packed word containing information on the present status of the drive
0Drive ready
1Drive running
2Fault active
3Jogging forward
4Jogging reverse
5Underwind active
6Stopping
7Tension On active
8Stall tension active
9Current mem active
10Current limit
11Alarm active
12Current/speed active
13Processing error
14Tune/cnfg enable
15Network sync
1Drive status word 2Bit-packed word containing information on the present status of the drive
0FN/DB status
1Customer interlock
2TB Section Run
3TB Jog Reverse
4TB Jog Forward
5TB Section Off
6Coast/DB interlock
7TB Fault reset
8TB Diameter Sel A
9TB Diameter Sel B
7-5
10TB Diameter Reset
Runtime signal data are updated by the regulator every 10 msec.
7-6
AutoMax Network Communication Option Board
Table 7.3 – WebPak 3000 Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
11TB Tension On
12TB Current Memory
13TB Underwind
14TB Slack Take Up
15Level Det1 Output
2
3
4
5
6
7Average CML feedbackCML feedback average over eight CML scans4095 at MAXIMUMCURRENT (P.007)
8Network Output Register 1Value of the parameter selected by
9Network Output Register 2Value of the parameter selected by NETWOUTREG 2
10Network Output Register 3Value of the parameter selected by
11 to 16Tunable, Configurable and Status DataSee table 7.4 on page 7-7.
17
18
19TENSIONSETPOINTIN (P.492)Digital value of the tension setpoint input (TB 50, 51)
20
21
22
23
SPDLOOPREFERENCE (P.295)Final speed/voltage loop reference value
SPDLOOPFEEDBACK (P.296)Final speed/voltage loop feedback value after all scaling
SPDLOOPOUTPUT (P.299)Speed loop PI block output value4095 at MAXIMUMCURRENT (P.007)
ARMATUREVOLTAGE (P.289)Armature voltage feedback value4095 at MOTORRATEDARMVOLTS (P.009)
CMLREFERENCE (P.196)Amplitude-and rate-limited value of the selected CML
reference
NETWOUTREG 1
SELECT (P.902)
If no valid parameter value selected,
0=MOTORSPEEDINRPM
If no valid parameter value selected,
SELECT (P.903)
NETWOUTREG 3
SELECT (P.904)
LINESPEED (P.188)Analog reference value output by the drive
DIAMETER/TAPERINTP (P.192)Diameter/taper range input (TB 16, 17, 18) in counts
0=armature voltage in volts
If no valid parameter value selected,
0=armature current in amps*10 or amps
DIAMETER, TAPERRANGE
after gain and zero applied
after gain and zero applied
TENSION/DANCERFDBK (P.493)Digital value of the tension/dancer feedback input (TB
52, 53) after gain and zero applied
FREQIN (P.491)Frequency input value (terminals 39, 40, 41 on I/O
4095 at full scale
Expansion board) after all scaling
OCLOUTPUT (P.848)Outer control loop output valueRPM
OCLPARALLELOUT (P.816)Output of the selected outer control loop for parallel
mode
Runtime signal data are updated by the regulator every 10 msec.
WebPak 3000 Drives: Register Map
Table 7.3 – WebPak 3000 Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
24 FIELDFEEDBACK (P.589)Motor field current feedback value after scaling and gain 4095 at MOTORHOTFLDAMPS (P.510)
25
ACLINEVOLTAGE (P.392)Measured AC line RMS voltageVolts RMS
Runtime signal data are updated by the regulator every 10 msec.
Table 7.4 – WebPak 3000 Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Tunable, Configurable, and Status Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
11Fault latch bits word 1Bit-packed word indicating latched faults
0
1
2
3
4
5
6
7Reserved
8
9
10
11OPENARMATURE (F00007)
12
13
14
15
12Reserved
13First faultFault code of the first fault since the last fault reset
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.
ACLINESYNCHRONIZATIONFAULT (F00010)
FIELDCURRENTLOSS (F00004)
SUSTAINEDOVERLOAD (F00005)
SELFTUNINGFAULT (F00060 to F000099)
MOTORTHERMOSTATTRIP (F00008)
CONTROLLERTHERMOSTATTRIP (F00009)
BLOWERMOTORSTARTEROPEN (F00006)
IET (OVERCURRENT) (F00001)
OVERSPEED (F00003) / ARMATUREOVERVOLTAGE
(F00012)
SCR N OR MULTIPLE SCRS NOT OPERATING
(F00030 to
F00042)
TACHOMETERLOSS (F00002)
OIMCOMMUNICATIONSTIMEOUT (F00011)
NETWORKCOMMUNICATIONTIMEOUT (F00013)
REVERS EDTACHLEADS (F00014)
7-7
7-8
Table 7.4 – WebPak 3000 Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Tunable, Configurable, and Status Data (Drive Output Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
14Alarm latch bits wordBit-packed word containing latched alarm bits
0
1
2
3 to15Reserved
15Last alarmAlarm code of the most recent alarm
16
CONTROLSOURCESELECT (P.000)Selected source for drive control signals
17 to 25Runtime parameters see table 7.2
26Reserved
27Stop cause
28Param Proc Error Number
29
NETWCONNECTTYPE (P.910)AutoMax network connection typeBASIC; FULL
30AMXNETWREFSELECT (P.911)AutoMax network reference selectionDIRECT; BROADCASTN (N=1 TO 8)
31
REGULATORSWVERSION (P.794)Regulator board software version
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.
Table 7.5 – WebPak 3000 Register Map, Drop_1: Master Write Registers, BASIC and FULL Connections. Control/Reference Data (Drive Input Data)
MOTORBRUSHWEARLOW (A00001)
ACLINEVOLTAGELOW (A00002)
ACLINEVOLTAGEHIGH (A00003)
0=
TERMBLK
; 1=
KEYPAD
; 2=
SERIAL
; 3=
NETWORK
AutoMax Network Communication Option Board
RegisterBitParameter Name (Number)DescriptionSettings
32Sequencing control wordWord containing drive sequencing and control bits
0Section run
1Section off
2Fault/alarm reset
3Jog forward
4Jog reverse
5Underwind
6Slack take up
7Tension on
8Diameter reset
Control/reference data are read by the regulator every 10 msec.
WebPak 3000 Drives: Register Map
Table 7.5 – WebPak 3000 Register Map, Drop_1: Master Write Registers, BASIC and FULL Connections. Control/Reference Data (Drive Input Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
9Current memory
10Memory save
11Current/speed
12Diameter sel A
13Diameter sel B
14Tune/config input enable: Determines what is read from
network. “Read all” includes control/reference, tunable,
and configurable inputs
15Network sync
33Network ReferenceSpeed/voltage loop or
CONTROLSOURCESELECT (P.000) is set to NETWORK and
AMXNETWREFSELECT (P.911)= 0
34
35
36
37
38
39
NETWINREG 1Written by network master. Read this value through the
OIM using NETWINREG 1 (P.905)
NETWINREG 2Written by network master. Read this value through the
OIM using NETWINREG 2 (P.906)
NETWINREG 3Written by network master. Read this value through the
OIM using nETWINREG 3 (P.907)
TAPERREGISTER (P.860)Determines amount of taper to apply to the tension
reference when
FIELDREFREGISTER (P.513)Reference for the field current loop4095 at MOTORHOTFLDAMPS (P.510)
POSITIONREFERENCE (P.240)Dancer position reference.-4095 to 4095 COUNTS
TAPERTYPE (P.863) = REGISTER
Control/reference data are read by the regulator every 10 msec.
CML reference value when
READONLYCONTROL/REFERENCEINPUTS
0=
1=READALL
0.000 to 1.000
7-9
7-10
AutoMax Network Communication Option Board
Table 7.6 – WebPak 3000 Register Map, Drop_1: Master Write Registers, BASIC and FULL Connections. Tunable Data (Drive Input Data)
RegisterBitParameter Name (Number)DescriptionSettings
40DIAMETERREGISTER (P.874)Value assigned to NORMROLLDIAMETER (P.131) when
DIAMETERCALCENABLE (P.826) = DISABLE.
41
ACCELERATIONTIME (P.001)Min. time to accelerate from zero to GEARINSPEED
(P.011)
42
DECELERATIONTIME (P.002)Min. time to decelerate from GEARINSPEED (P.011) to
zero
43
44
45
46
47
48
49
50
51
52
53
54
55
MINIMUMSPEED (P.003)Lowest operating speedRPM
MAXIMUMSPEED (P.004)Highest operating speedRPM
POSITIVECURRENTLIM (P.005)Highest amount of current for the forward bridge
NEGATIVECURRENTLIM (P.006)Highest amount of current for reverse bridge
S-CURVEROUNDING (P.014)Amount of smoothing of speed/voltage loop reference0 to 50%
TRIMRANGE (P.109)Amount the trim reference will affect the drive reference0.0 to 100.0%
SPDLOOPPIPROPGAIN (P.211)Speed loop PI proportional gain0.10 to 128.00
SPDLOOPPILEADFREQ (P.212)Speed loop PI block lead break frequency
CMLPIPROPGAIN (P.301)CMLPI proportional gain
CMLPILEADFREQUENCY (P.302) CMLPI lead break frequency0.000 to 4.000
TENPIPROPGAIN (P.841)
TENPILEADFREQ (P.840)
TENSIONPILIMIT (P.853)
Tension loop PI block proportional gain
Tension loop PI block lead frequency
Tension loop pi block high and low limits
56JOGSPEED (P.012)Operating speed while jogging0 to BASESPEED (P.017) in FPM
57
STOPMODESELECT (P.114)Selects how drive responds to a normal stop commandRAMP; COAST/DB; CURRENTLIMIT
58NETWOUTREG 1 SELECT (P.902) Number of the parameter readable in Drop_1, register 7 If no valid parameter value selected, this is set to
59NETWOUTREG 2 SELECT (P.903) Number of the parameter readable in Drop_1, register 8 If no valid parameter value selected, this is set to
60
NETWOUTREG 3 SELECT (P.904) Number of the parameter readable in Drop_1, register 9 If no valid parameter value selected, this is set to
Tunable data are read by the regulator approximately every 600 msec while Tune/Config Input Enable bit=1.
1.000 to 2.000
seconds * 10
seconds * 10
0.001 to 32.767
0.00 to 141.37 radians/second
0 to 4095 COUNTS
0=motor speed in
RPM
0=armature voltage in volts
0=armature current in amps*10 or amps
WebPak 3000 Drives: Register Map
Table 7.7 – WebPak 3000 Register Map, Drop_1: Master Write Registers, BASIC and FULL Connections. Configurable Data (Drive Input Data)
Register Parameter Name (Number)DescriptionSettings
61FEEDBACKSELECT (P.200)Type of feedback for speed/voltage loop feedbackARMATUREVOLT; DCTACH ; ENCODER
62NETWCONNECTTYPE (P.910)AutoMax network connection typeBASIC, FULL
63AMXNETWREFSELECT (P.911)AutoMax network reference selectionDIRECT; BROADCASTN (N=1 to 8)
Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit=1 and the drive is not running or jogging.
Table 7.8 – WebPak 3000 Register Map, Drop_2: Master Read Registers, FULL Connection. Runtime Signal Data (Drive Output Data)
RegisterParameter Name (Number)DescriptionSettings
0ANALOGTACHFEEDBACK (P.291)Analog tachometer feedback input after scaling
1
2CMLERROR (P.398)CML error signal
3
4
5
6
7
8
9
10
11
12
13
14
ANALOGTRIMREF (P.195)Trim reference value when TRIMREFERENCESELECT
(P.108) =
DANCERLOADING (P.820)Rate-limited and scaled value of TENSIONDEMAND (P.844)
ENCODERFEEDBACK (P.292)Digital value from pulse encoder after scaling
FIELDREFERENCE (P.590)Reference to the field regulator PI block as a percentage
of
INSTANTANEOUSINERTIA (P.230)Dynamic load inertial as provided by the inertial
ANALOG
MOTORHOTFLDAMPS (P.510)
compensation task
NORMFIELDREF (P.130)Nominalized reference to the field shaping table
NORMROLLDIAMETER (P.131)Roll diameter normalized at 1.000 at EMPTYCORE
DIAMETER (P.830)
POSITIONVERNIER (P.241)Output of the position major loop
REFERENCERATE (P.866)Rate of change in the speed loop reference.
SPDLOOPERROR (P.297)Speed loop error signal
SPDLOOPLAGOUTPUT (P.298)Output of the lag block following the speed loop PI block
TENSIONDEMAND (P.844)Output of the tension setpoint generator in counts
TENSIONVERNI ER (P.856)Output of the tension major loop in counts
Runtime signal data are updated by the regulator every 10 msec.
7-11
7-12
AutoMax Network Communication Option Board
Table 7.9 – WebPak 3000 Register Map, Drop_2: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
15ACLINEPERIOD (P.393)AC line period as measured by the drive in
microseconds
16
17ARMATUREDELTA (P.399)Armature firing angle in microseconds
18
19
20
21
22
23
24
25
26FIELDDELTA (P.588)Field firing angle indegrees0 to 180 degree
27
28FLDCURRENTREGULATOR (P.586)Indicates if the Field Current Regulator kit is installed
29INERTIACOMPENSATION (P.244)Output of the inertia compensation calculator
30
31
ARMATUREBRIDGEPOL (P.394)Indicates which bridge is currently active.OFF (forward bridge active; ON (reverse
bridge active)
CMLFEEDBACK (P.397)CML feedback signal after scaling
CMLRAMPINPUTTP (P.390)Current reference value to the CML ramp block
CMLSPEEDREFERENCE (P.391)Speed reference value to the current minor loop
CURRENTCOMPOUNDTP (P.293)Trim value that is subracted from the speed reference
based on motor load
DIAMETERANALOG (P.821)Output of the diameter calculator scaled from zero at
empty core to 4095 at full roll diameter
DIAMETERRESETTP (P.829)State of the diameter reset signal
DRAWPERCENTAGEOUT (P.196)Product of the selectrd trim reference value and trim
range value
ENCODERKIT (P.798)Indicates if Pulse Encoder kit is installed and passed
INSTALLED; NOTINSTALLED; FAILEDDIAGS
diagnostics
FIELDECONOMYACTIVE (P.599)State of the field economy functionON; OFF
NOTINSTALLED; 4 AMP, 10 AMP, 20 AMP
and its rating
IRCOMPENSATIONTP (P.290)Level of IR compensation being subtracted from the
measured armature voltage
DIAMETERCALCOUTPUT (P.132)Value of the calculated roll diameter normalized at
1.000 at
EMPTYCOREDIAMETER (P.830)
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.
WebPak 3000 Drives: Register Map
7-13
Table 7.10 – WebPak 3000 Register Map, Drop_2: Master Write Registers, FULL Connection. Tunable Data (Drive Input Data)
RegisterBitParameter Name (Number)DescriptionSettings
32AutoMax Indirect Parameter 1Selects parameter to which the value in the
corresponding Drop 3 register is written
33AutoMax Indirect Parameter 2Selects parameter to which the value in the
corresponding Drop 3 register is written
34AutoMax Indirect Parameter 3Selects parameter to which the value in the
corresponding Drop 3 register is written
35AutoMax Indirect Parameter 4Selects parameter to which the value in the
corresponding Drop 3 register is written
36AutoMax Indirect Parameter 5Selects parameter to which the value in the
corresponding Drop 3 register is written
37AutoMax Indirect Parameter 6Selects parameter to which the value in the
corresponding Drop 3 register is written
38AutoMax Indirect Parameter 7Selects parameter to which the value in the
corresponding Drop 3 register is written
39AutoMax Indirect Parameter 8Selects parameter to which the value in the
corresponding Drop 3 register is written
40AutoMax Indirect Parameter 9Selects parameter to which the value in the
corresponding Drop 3 register is written
41AutoMax Indirect Parameter 10Selects parameter to which the value in the
corresponding Drop 3 register is written
42AutoMax Indirect Parameter 11Selects parameter to which the value in the
corresponding Drop 3 register is written
43AutoMax Indirect Parameter 12Selects parameter to which the value in the
corresponding Drop 3 register is written
44AutoMax Indirect Parameter 13Selects parameter to which the value in the
corresponding Drop 3 register is written
45AutoMax Indirect Parameter 14Selects parameter to which the value in the
corresponding Drop 3 register is written
46AutoMax Indirect Parameter 15Selects parameter to which the value in the
corresponding Drop 3 register is written
47AutoMax Indirect Parameter 16Selects parameter to which the value in the
corresponding Drop 3 register is written
Tunable data are updated by the regulator approximately every 600 msec when Tune/Config Input Enable bit = 1.
Value of 0 disables register 32 in Drop 3
Value of 0 disables register 33 in Drop 3
Value of 0 disables register 34 in Drop 3
Value of 0 disables register 35 in Drop 3
Value of 0 disables register 36 in Drop 3
Value of 0 disables register 37 in Drop 3
Value of 0 disables register 38 in Drop 3
Value of 0 disables register 39 in Drop 3
Value of 0 disables register 40 in Drop 3
Value of 0 disables register 41 in Drop 3
Value of 0 disables register 42 in Drop 3
Value of 0 disables register 43 in Drop 3
Value of 0 disables register 44 in Drop 3
Value of 0 disables register 45 in Drop 3
Value of 0 disables register 46 in Drop 3
Value of 0 disables register 47 in Drop 3
7-14
AutoMax Network Communication Option Board
Table 7.10 – WebPak 3000 Register Map, Drop_2: Master Write Registers, FULL Connection. Tunable Data (Drive Input Data) (Continued)
RegisterBitParameter Name (Number)DescriptionSettings
48AutoMax Indirect Parameter 17Selects parameter to which the value in the
corresponding Drop 3 register is written
49AutoMax Indirect Parameter 18Selects parameter to which the value in the
corresponding Drop 3 register is written
50AutoMax Indirect Parameter 19Selects parameter to which the value in the
corresponding Drop 3 register is written
51AutoMax Indirect Parameter 20Selects parameter to which the value in the
corresponding Drop 3 register is written
52AutoMax Indirect Parameter 21Selects parameter to which the value in the
corresponding Drop 3 register is written
53AutoMax Indirect Parameter 22Selects parameter to which the value in the
corresponding Drop 3 register is written
54AutoMax Indirect Parameter 23Selects parameter to which the value in the
corresponding Drop 3 register is written
55AutoMax Indirect Parameter 24Selects parameter to which the value in the
corresponding Drop 3 register is written
56AutoMax Indirect Parameter 25Selects parameter to which the value in the
corresponding Drop 3 register is written
57AutoMax Indirect Parameter 26Selects parameter to which the value in the
corresponding Drop 3 register is written
58AutoMax Indirect Parameter 27Selects parameter to which the value in the
corresponding Drop 3 register is written
59AutoMax Indirect Parameter 28Selects parameter to which the value in the
corresponding Drop 3 register is written
60AutoMax Indirect Parameter 29Selects parameter to which the value in the
corresponding Drop 3 register is written
61AutoMax Indirect Parameter 30Selects parameter to which the value in the
corresponding Drop 3 register is written
62AutoMax Indirect Parameter 31Selects parameter to which the value in the
corresponding Drop 3 register is written
63AutoMax Indirect Parameter 32Selects parameter to which the value in the
corresponding Drop 3 register is written
Tunable data are updated by the regulator approximately every 600 msec when Tune/Config Input Enable bit = 1.
Value of 0 disables register 48 in Drop 3
Value of 0 disables register 49 in Drop 3
Value of 0 disables register 50 in Drop 3
Value of 0 disables register 51 in Drop 3
Value of 0 disables register 52 in Drop 3
Value of 0 disables register 53 in Drop 3
Value of 0 disables register 54 in Drop 3
Value of 0 disables register 55 in Drop 3
Value of 0 disables register 56 in Drop 3
Value of 0 disables register 57 in Drop 3
Value of 0 disables register 58 in Drop 3
Value of 0 disables register 59 in Drop 3
Value of 0 disables register 60 in Drop 3
Value of 0 disables register 61 in Drop 3
Value of 0 disables register 62 in Drop 3
Value of 0 disables register 63 in Drop 3
WebPak 3000 Drives: Register Map
7-15
Table 7.11 – WebPak 3000 Register Map, Drop_3: Master Read Registers, FULL Connection. Runtime Signal Data (Drive Output Data)
RegisterBitParameter Name (Number)DescriptionSettings
0J11 ANLGTACHVLTSCL (P.792)Position to set J11 jumper16; 31; 62; 126; 250
1
2J15 REGULATORTYPE (P.799)Indicates position of jumper J15SPEED/VOL TAG E; CURRENT/TORQUE