Rockwell Automation 440R-MSR23M User Manual

PRESSURE SENSITIVE SAFETY MAT MODULE MODUL FÜR DRUCKSENSITIVE-SICHERHEITSSCHALTMATTEN MODULE POUR TAPIS SENSIBLES A LA PRESSION
MINOTAUR
MSR23M
According to EU directive for machines 98/37/EG
According to IEC 204-1, EN 60 204-1, DIN VDE 0113-1, EN 954-1
can also be used for safety edges (4 wire non resistive type)
Safety category 4 according to DIN EN 954-1
Output: 2 N/O + 1N/C contacts
Monitoring of Reset-button function
Manual reset or automatic reset when connecting the supply
voltage, switch S1
LED indicator for state of operation
Indicator for status of switching element
LED indicator for channel 1 and 2
Removable terminal strips
Wire connection: also 2 x 1,5 mm
2
stranded ferruled (isolated), DIN 46 228-4 or 2 x 2,5 mm2 stranded ferruled DIN 46 228-1/-2/-3
Width 22,5 mm
Notes
Monitoring of Reset-button function: Monitoring of Reset-button function is only active when S12 and S22 are switched simultaneously. If the Reset-button is closed before S12, S22 is connected to voltage (also when fault across Reset-Button), the output contacts will not close. A fault across the Reset-button which occurred after activation of the relay, will be detected with the next activation and the output contacts will not close. If a fault occurs after the voltage has been connected to S12, S22, the unit will be activated because this fault is similar to the normal Reset-function. The gold plated contacts of the MSR23M mean that this module is also suitable for switching small loads of 1 mVA - 7 VA, 1 mW - 7 W in the range 0,1 - 60 V, 1 - 300 mA. The contacts also permit the maximum switching current. However since the gold plating will be burnt off at this current level, the device is no longer suitable for switching small loads after this.
Approvals and marking
Control unit for safety mats and safety edges (4 wire non resistive type)
Applications
Indicators
upper LED: ON when supply connected lower LEDs: ON when relay K1 and K2 energized
ET
Circuit diagrams
S33 S34A1
31242313
S21
S1114
S22
32S12
A2
K1
K2
A1 S11
S12
S34
S33
S22
A2 S21
13 3123
14 32
24
S33 S34
31242313
S21
S1114
S22
32
S12
K1
K2
A1
S11
S12
S34
S33
S22
A2 S21
13 3123
14 32
24
A1
A2
Part No. 440R-P23073 - 24V DC supply
Part No. 440R-P23074 - 110V AC supply
Function diagram
Block diagram
118mm
Part No. 440R-P23073 - 24V DC supply
22.5mm
86mm
* Line fault detection at the Reset push button
Power
Reset
Safety input
118mm
Part No. 440R-P23074 - 110V AC supply
45mm
86mm
R
Input circuit
Nominal Voltage U
N
: DC 24 V, AC/DC 24 V
Voltage range DC AC/DC
DC: at 10% residual ripple: 0,9 ... 1,1 U
N
0,95 ... 1,1 U
N
at 48% Rresidual ripple: 0,8 ... 1,1 U
N
0,8 ... 1,1 U
N
AC: 0,8 ... 1,1 U
N
Nominal consumption: DC approx. 2 W Min. Off-time: 1 s Control voltage on S11: approx. DC 23 V at U
N
Cross fault current
between line S11-S12 and line S21-S22 with active safety mat or safety edge start-up: max. 0,4 A for approx. 2 ms continuously DC: approx. 29 mA at U
N
AC: approx. 37 mA at U
N
Control current over S12, S22: 40 mA at U
N
Min. voltage on S12, S22: DC 21 V when relay activated Short-circuit protection: Internal PTC Overvoltage protection: Internal VDR
Output
Contacts
Contacts 2 NO, 1 NC contact
Operate delay typ. at U
N
:
Manual start: 40 ms automatic start: 200 ms
Release delay typ. at U
N
:
Disconnecting the supply: 50 ms Disconnecting S12, S22: 15 ms
Contact type: positive guided Nominal output voltage: AC 250 V
DC: see limit curve for arc-free operation Switching of low loads: ≥100 mV (contact 5 Au) 1 mA
Thermal current I
th
: see current limit curve
on 1 contact path: max. 8 A on more then 1 contact path: max. 7 A per contact path
Unit programming
Technical data
Technical data
Switching capacity
to AC 15: AC 3 A / 230 V EN 60 947-5-1
for NO contacts AC 2 A / 230 V EN 60 947-5-1 for NC contact
Electrical contact life
to AC 15 at 2 A, AC 230 V: 10
5
switching cycles EN 60 947-5-1
Permissible operating frequency: max. 1 200 operating cycles / h Short circuit strength
max. fuse rating: 6 A gL EN 60 947-5-1 line circuit breaker: C 8 A Mechanical life: 10 x 10
6
switching cycles
General data
Operating mode: Continuous operation Temperature range: - 15 ... + 55 C Clearance and creepage distances
Overvoltage category / contamination level: 4 kV / 2 DIN VDE 0110-1 (04.97)
EMC
Electrostatic discharge: 8 kV (air) EN 61 000-4-2 HF irradiation: 10 V / m EN 61 000-4-3 Fast transients: 2 kV EN 61 000-4-4 Surge voltages between wires for power supply: 1 kV EN 61 000-4-5 between wire and ground: 2 kV EN 61 000-4-5 Interference suppression: Limit value class B EN 55 011 Degree of protection: Housing: IP 40 EN 60 529
Terminals: IP 20 EN 60 529
Housing: Thermoplastic with V0 behaviour
according to UL subject 94
Vibration resistance: Amplitude 0,35 mm EN 60 068-2-6
frequency 10 ... 55 Hz
Climate resistance: 15 / 055 / 04 EN 60 068-1 Terminal designation: EN 50 005 Wire connection: 1 x 4 mm
2
solid or
1 x 2,5 mm
2
stranded ferruled (isolated) or 2 x 1,5 mm
2
stranded ferruled (isolated) DIN 46 228-1/-2/-3/-4 or 2 x 2,5 mm
2
stranded ferruled DIN 46 228-1/-2/-3
Wire fixing: Box terminal with wire protection,
removable terminal strips
Mounting: DIN rail EN 50 022 Weight: 220 g
Dimensions
Width x height x depth: 22,5 x 84 x 118 mm
Notes
Connecting the terminal S21 to the protective ground bridges the internal short-circuit protection of Line A2 (-). The short-circuit protection of line A1 (+) remains active. Depending on the operation of the machine, the switch S1 is set to automatic or manual restart.
Drawing shows setting at the state of delivery Disconnect unit before setting
Switch S1 Upper position for Auto reset. Lower position for Manual reset.
Isolate power before removing cover
Screwdriver
S1
Loading...