MINOTAUR MSR17T SAFETY RELAYS
ATTENTION: To prevent electrical shocks, disconnect power
source before servicing.
IMPORTANT: Save these instructions for future use.
General
The safety relay by itself can not provide safety. The
safety relay requires proper component application
and
maintenance. The application must anticipate
failures by using system safety risk assessment. This
product must
accordance with the manufacturer’s instructions as
well as applicable standards.
Mounting
The units must be mounted on a 35 mm DIN rail.
Construction
The relay has (4) groups of terminals:
1. Power Terminals:
(+B1 -B2) for 24V DC
2. Input Terminals:
The E-Stop and Gate interlock operator: Ch 1 (S10 &
S11), Ch 2 (S21 & B2) (Fig. 1, 2)
Start button: S10, S33 (Fig. 1, 2)
*3. Safety Output Terminals:
13-14, 23-24
These are monitored outputs. These outputs are
voltage free.
**4. Auxiliary Terminals:
33-34 (K1 Aux.), 43-44 (K2 Aux.)
be installed and maintained in
Applications: E-Stop, Gate Interlock, Expanders
and Auxiliary Relays, Automatic Start
E-Stop (Fig. 1)
a) Use an E-Stop button conforming to EN 418. It must have (2)
Normally Closed (N.C.) contact blocks. The contact blocks
must conform to EN 60947-5-1 positive-opening operation.
b) Use a start/reset momentary pushbutton with (1) Normally
Open (N.O.) contact block.
k1
k2
MSR17T
INSTRUCTION SHEET
Attaching Auxiliary Relays (Fig. 4
The auxiliary relays must be of the "positively-guided /
Direct Drive
auxiliary relays may be monitored by connecting
N.C. contacts in series to the reset circuit.
TM
"
style conforming to EN 50205. The
k1
MSR17T
k2
)
ATTENTION:
Protection of Safety Circuits.
To avoid contact welding, a fuse (5A quick or 1.6A
*
slow) must be connected externally.
The auxiliary terminals are NOT monitored
**
and must not be used as safety outputs. These
may be used for data and signaling.
Wiring:
Use 0,2-2,5 mm2 (24-14 AWG) Cu only. Typical
screwdriver needed is a flat blade 3 mm (.125 in.) wide
Tighten screws to 0.5-0.8 Nm
LEDs: Run & Fault Conditions (Fig. 1-4)
POWER LED
CH 1 LED
CH 2 LED
K1 LED
K2 LED
CONDITION
ACTION
(5-7 lb.in.).
Refer to
Guardmaster catalogue
Refer to
Guardmaster catalogue
Refer to
Guardmaster catalogue
Refer to
Guardmaster catalogue
l
l
l
l
l
proper
running
conditions
none replace
l
l
l
l
l
channel 1
contacts
may be open
channel 1
contact
block
,
channel 2
contacts
may be open
replace
channel 2
contact
block
Gate Interlock (Fig. 2)
.
Attaching an Expander (Fig. 3)
The expander can be used with E-Stop and Gate Interlock Control.
l
l
l
l
l
Drg No: 23963 / Issue No: 1 (Ref. 40063-239-01 (A))
MSR17T
k1
MSR17T
k2
l
l
l
l
start/reset actuator
contacts may be
welded
replace reset
contacts
Fig. 1
Fig. 2
S3
MSR19E
S4
Fig. 3
Automatic Start
ATTENTION:
Unexpected/unintended start-up may occur
after power supply interruption.
Autostart is not allowed for E-Stops per
EN 292-2, 954-1, 60204-1 and 418.
MSR17T
Single Channel E-Stop (Fig. 6
MSR17T
Maintenance
The relay and its application must be inspected
periodically based on environmental and
operating conditions. Causes of contamination
must be eliminated. Worn and broken assemblies
must be replaced. Fasteners must be securely
re-tightened. Unit has no customer serviceable
parts. Fault c
restoring power.
control system under controlled conditions.
onditions must be corrected before
STOP ACTUATEDSTOP RESET
l
l l
l
l
l
l
l
l l
safety
contacts
may be
welded
replace
safety
relay
l
waiting for
l
start/reset signal
expander or aux.
l
contacts may be
welded
replace expander
or aux. relay
l
l
l
ll
l
input short
or no power
after clearing
short, power
must be off 20 sec.
to reset fuse
l l l
l
l
l
l
input
circuit is
open
reset
E-stop or
gate
Fig. 4
Fig. 5
)
Fig. 6
After maintenance, test the
l
l
l
l
l
ll
channel 1
contacts
may be
welded
replace
channel 1
contact
block
channel 2
contacts
may be
welded
replace
channel 2
contact
block