Compact 1769-IR6 RTD/Resistance Input Module
User Manual
Compact 1769 Expansion I/O Power Supplies
Installation Instructions
Installation Instructions
Compact I/O End Caps/Terminators Installation
Instructions
Hazardous Location Considerations
1769-UM004
1769-IN027
1769-UM005
1769-IN028
1769-IN014
1769-IN015
This product must be installed in an enclosure. This equipment is suitable for use in Class I,
Division 2, Groups A, B, C, D or non-hazardous locations only. The following
ATTENTION statement applies to use in hazardous locations.
ATTENTION
!
EXPLOSION HAZARD
• Substitution of components may impair suitability for Class I,
Division 2.
• Do not replace components or disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.
• Do not connect or disconnect components unless power has been
switched off or the area is known to be non-hazardous.
• All wiring must comply with N.E.C. article 501-4(b).
Overview
The 20D-DL2-CR3 and 20D-DL2-CL3 cables allow you to connect a DriveLogix5730 Phase
II controller to a bank of Compact I/O. A maximum of two banks of I/O can be used a
DriveLogix5730 Phase II controller. Each bank requires its own power supply.
Configurations on page 5.
Publication 20D-IN008B-EN-P - August 2004
See System
4 Compact I/O Cable for DriveLogix™5730 Controller
Cable Types and Length
Cables for Connecting Controllers to I/O Banks
Catalog NumberCable Type
20D-DL2-CL3Controller-to-left bank expansion3.28 ft. (1 m)
20D-DL2-CR3Controller-to-right bank expansion3.28 ft. (1 m)
(1)
Approximate cable length is measured from end-to-end of the cable only.
32 mm
15 mm
(0.59 in.)
18 mm
(0.71 in.)
(1.26 in.)
Length
(1)
118 mm
(4.65 in.)
118 mm
(4.65 in.)
20D-DL2-CL320D-DL2-CR3
Cables for Connecting I/O Banks to I/O Banks
Catalog NumberCable Type
1769-CLL1Left bank-to-left bank expansion1 ft. (305 mm)
1769-CLL3Left bank-to-left bank expansion3.28 ft. (1 m)
1769-CRR1Right bank-to-right bank expansion1 ft. (305 mm)
1769-CRR3Right bank-to-right bank expansion3.28 ft. (1 m)
1769-CRL1Right bank-to-left bank expansion1 ft. (305 mm)
1769-CRL3Right bank-to-left bank expansion3.28 ft. (1 m)
(1)
Approximate cable length is measured from end-to-end of the cable only.
Length
(1)
Publication 20D-IN008B-EN-P - August 2004
System Configurations
Compact I/O Cable for DriveLogix™5730 Controller 5
The following illustration show examples of four valid system setups.
DriveLogix
PowerFlex 700S Drive
I/O Slot Number
DriveLogix
PowerFlex 700S Drive
I/O Slot Number
Bank 1
1769 I/O
20D-DL2-CL3
1
20D-DL2-CL3
Bank 1
1769 Power Supply
Bank 1
1769 I/O
1
1769 I/O
2
1769 I/O
1769 Power Supply
1769-CRL3
1769 End Cap
2
Bank 2
1769 I/O
1769-CRL3
3
1769 I/O
1769 Power Supply
1769 End Cap
4
1769 I/O
1769 End Cap
4
1769 End Cap
2
Bank 2
1769 Power Supply
1769 Power Supply
1769 I/O
3
1769 I/O
1
1769-CRl3
20D-DL2-CR3
I/O Slot Number
1769-CRl3
DriveLogix
PowerFlex 700S Drive
Bank 1
1769 I/O
2
1769 I/O
1769 Power Supply
20D-DL2-CR3
1
I/O Slot Number
Publication 20D-IN008B-EN-P - August 2004
DriveLogix
PowerFlex 700S Drive
1769 I/O
6 Compact I/O Cable for DriveLogix™5730 Controller
Installation
Remove Power
ATTENTION
!
To avoid an electric shock hazard, verify that the voltage on the bus
capacitors has discharged before performing any work on the drive.
Measure the DC bus voltage at the +DC & –DC terminals of the
Power Terminal Block. The voltage must be zero.
HOT surfaces can cause severe burns. Do not touch the heatsink
surface during operation of the drive. After disconnecting power
allow time for cooling.
Remove power before making or breaking cable connections. When
you remove or insert a cable connector with power applied, an
electrical arc may occur. An electrical arc can cause personal injury or
property damage by:
• sending an erroneous signal to your system’s field devices,
causing unintended machine motion
• causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance.
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch bus connector pins or the terminal
block. Follow these guidelines when handling 1769 Compact I/O
components:
• Touch a grounded object to discharge static potential.
• Wear an approved wrist-strap grounding device.
• Do not touch the bus connector or connector pins.
• Do not touch circuit components inside the module.
• If available, use a static-safe workstation.
• When not in use, keep cables in static shield packaging.
Publication 20D-IN008B-EN-P - August 2004
Compact I/O Cable for DriveLogix™5730 Controller 7
What You Need to Do
❐ Step 1: Remove power from drive and Compact I/O
❐ Step 2: Remove the control cassette from the drive and the cover
from the control cassette
❐ Step 3: Install the controller end of the cable
❐ Step 4: Replace the cover and control cassette
❐ Step 5: Connect the Compact I/O end of the cable
Publication 20D-IN008B-EN-P - August 2004
8 Compact I/O Cable for DriveLogix™5730 Controller
Step 1: Removing Power from Drive and Compact I/O
ATTENTION
!
To avoid an electric shock hazard, verify that the voltage on the bus
capacitors has discharged before performing any work on the drive.
Measure the DC bus voltage at the +DC & –DC terminals of the
Power Terminal Block. The voltage must be zero.
Remove power before making or breaking cable connections. When
you remove or insert a cable connector with power applied, an
electrical arc may occur. An electrical arc can cause personal injury or
property damage by:
• sending an erroneous signal to your system’s field devices,
causing unintended machine motion
• causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance.
L1L2L3
I
O
Task Description
Turn off and lock out input power.
A
Wait five minutes.
Verify that there is no voltage at
B
the drive’s input power terminals.
Measure the DC bus voltage at
C
the +DC & -DC terminals on the
Power Terminal Block. The voltage
must be zer o.
Publication 20D-IN008B-EN-P - August 2004
Compact I/O Cable for DriveLogix™5730 Controller 9
Step 2: Removing the Control Cassette from the Drive and the Covers from
the Cassette
B
BR1
B
R
2
D
C
+
D
C
-
PE
U/T1
V/T2
W/T3
R/L1
L2
C
Removing the Side Covers
Task Description
Loosen screws on face of front
A
cover and remove the cover
Loosen screws on side of rear
B
cover and remove the cover
B
A
A
Removing the Cassette
Task Description
Open the door of the power
A
structure and disconnect the
cables that connect to the main
board
Loosen screws on face of cassette
B
Remove the cassette
C
=
Proper tightening
torque for reassembly
is 6 lb.-in.
=
B
Publication 20D-IN008B-EN-P - August 2004
10 Compact I/O Cable for DriveLogix™5730 Controller
Step 3: Installing the Controller End of the Cable
D
A
B
C
A
B
=
Task Description
D
A
B
C
D
E
Remove screws
Install clips on controller end of cable
Plug controller end of cable into mating
connector on the Logix Expansion Board
Install and tighten screws (7-10 lb.-in.)
Route and secure cable
E
E
Use cable tie to anchor cable
to slots on this flange for
Step 4: Replacing the Cover and Control Cassette
The procedure for replacing the cover and control cassette is the reverse of removing these
components.
from the Cassette on page 9.
Refer to Step 2: Removing the Control Cassette from the Drive and the Covers
strain relief
E
E
Publication 20D-IN008B-EN-P - August 2004
Compact I/O Cable for DriveLogix™5730 Controller 11
Step 5: Installing the Compact I/O End of the Cable
ATTENTION
!
TaskDescription
Unlock the Bus Lever on the I/O module accepting the cable cover by pushing
A
the lever back and then right
Align both of the cable cover’s tongues (1) with the grooves (2) on the side of the
B
I/O module
Slide the cable cover back onto the module until the bus connectors (3) are
C
aligned
Lock the Bus Lever on the I/O module by pushing the lever back and then left
D
until locked
On a right-hand cable cover, lock the Bus Lever by pushing the lever back to
E
the left until locked
=
When energized bus connections break in hazardous environments,
resulting sparks can cause explosions.
Risk of personal injury and/or equipment damage exists.
Securely lock the bus connectors (tasks D and E below) to avoid this
hazard.
AD
=
2
3
Left Cover
B
1
C
B
1
E
Right Cover
C
Publication 20D-IN008B-EN-P - August 2004
2
3
TIP
Each I/O bank requires its own power supply. The 1769 cables extend the
1769 communication bus, but do not extend bus power.
Specifications
Approximate Shipping
W
ight (with carton)
e
3-foot cables: 350 g (0.77lbs.)
Storage Temperature-40°C to +85°C (-40°F to +185°F)
Operating Temperature0°C to +60°C (32°F to +140°F)
Operating Humidity5% to 95% non-condensing
Operating Altitude2000 meters (6561 feet)
VibrationOperating: 10 to 500 Hz, 5G, 0.030 inches maximum
Relay Operation: 2G
ShockOperating: 30G panel mounted (20G DIN rail mounted)
Relay Operation: 7.5G panel mounted (5G DIN rail mounted)
Non-Operating: 40G panel mounted (30G DIN rail mounted)