PowerFlex 700S Adjustable Frequency Drive - Phase II Control
Frames 1…6
0.75…132 kW (1…200 Hp)
Introduction
This document explains the 5 primary steps for mechanical installation and for
connecting incoming power, the motor, and basic I/O to the PowerFlex® 700S
adjustable frequency AC drive with Phase II control.
The information provided is intended for qualified installers only.
The Additional Resources section on page 5
Automation publications that provide detailed drive information from wiring
and grounding recommendations to troubleshooting and repair.
ATTENTION: This product contains a 3V Lithium battery if the DriveLogix
Controller option board is installed. Perchlorate Material - special handling may
apply.
See www.dtsc.ca.gov/hazardouswaste/perchlorate
is a directory of Rockwell
Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
2Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
4Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
PowerFlex 700S Drives with Phase II Control
Programming Manual, publication 20D-PM001
PowerFlex 7-Class HIM (DPI) Quick Reference,
publication 20HIM-QR001
PowerFlex 700S Drives with Phase II Control Reference
Manual, publication PFLEX-RM003
DriveLogix5730 Controller for PowerFlex 700S Drives
with Phase II Control User Manual,
publication 20D-UM003
DriveGuard® Safe-Off Option for PowerFlex 700S
Drives with Phase II Control, publication 20D-UM007
Wiring and Grounding Guidelines for Pulse Width
Modulated (PWM) AC Drives,
publication DRIVES-IN001
PowerFlex AC Drives in Common Bus Configurations,
publication DRIVES-AT002
Safety Guidelines for the Ap plication, Installation and
Maintenance of Solid State Control,
publication SGI-1.1
A Global Reference Guide for Reading Schematic
Diagrams, publication 100-2.10
Guarding Against Electrostatic Damage,
publication 8000-4.5.2
Product Certifications website, http://www.ab.com
Provides the following detailed information:
• Drive start-up instructions
• Parameters and programming
• Faults, alarms, and troubleshooting
• Human Interface Module (HIM) Operation Instructions
Provides a quick reference guide for using the PowerFlex 7Class HIM.
Provides detailed control functions and application
programming examples.
Provides instructions for developing DriveLogix controller
projects.
Provides information and instructions for properly planning
for and installing the DriveGuard Safe Torque Off option board.
Provides basic information needed to properly wire and
ground PWM AC drives.
Provides basic information needed to properly wire and
ground PWM AC drives using a common DC bus.
Provides general guidelines for the application, installation,
and maintenance of solid-state control.
Provides a simple cross-reference of common schematic/
wiring diagram symbols used throughout various parts of the
world.
Provides practices for guarding against Electrostatic damage
(ESD)
Provides declarations of conformity, certificates, and other
certification details.
You can view or download publications at
http://www.rockwellautomation.com/literature/
. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
Rockwell Automation Publication 20D-IN024C-EN-P - July 20135
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Step 1: Read the General
Precautions
ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or
implement the installation, startup and subsequent maintenance of the system. Failure to comply may result in personal injury
and/or equipment damage.
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before per forming any
work on the drive. Measure the DC bus voltage at the +DC and –DC terminals of the Power Terminal Block (refer to page 40
location). The voltage must be zero.
ATTENTION: Hazard of personal injury or equipment damage exists when using bipolar input sources. Noise and drift in sensitive
input circuits can cause unpredictable changes in motor speed and direction. Use speed command parameters to help reduce input
source sensitivity.
ATTENTION: Risk of injury or equipment damage exists. DPI or SCANport host products must not be directly connected together
via 1202 cables. Unpredictable behavior can result if two or more devices are connected in this manner.
Qualified Personnel
Personal Safety
for
ATTENTION: The drive start/stop/enable control circuitry includes solid state components. If hazards due to accidental contact
with moving machinery or unintentional flow of liquid, gas or solids exists, an additional hardwired stop circuit may be required to
remove the AC line to the drive. An auxiliary braking method may be required.
ATTENTION: Hazard of personal injury or equipment damage due to unexpected machine operation exists if the drive is
configured to automatically issue a Start or Run command. Do not use these functions without considering applicable local,
national and international codes, standards, regulations or industry guidelines.
ATTENTION: Parameters 365 [Encdr0 Loss Cnfg] - 394 [VoltFdbkLossCnfg] let you determine the action of the drive in response to
operating anomalies. Precautions should be taken to be sure that the settings of these parameters do not create hazards of
personal injury or equipment damage.
ATTENTION: Parameters 383 [SL CommLoss Data] - 392 [NetLoss DPI Cnfg] let you determine the action of the drive if
communications are disrupted. You can set these parameters so the drive continues to run. Precautions should be taken to ensure
the settings of these parameters do not create hazards of personal injury or equipment damage.
ATTENTION: This product contains a 3V Lithium battery if the DriveLogix Controller option board is installed. Perchlorate Material special handling may apply.
See www.dtsc.ca.gov/hazardouswaste/perchlorate
6Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Product Safety
ATTENTION: An incorrectly applied or installed drive can result in component damage or a reduction in product life. Wiring or
application errors such as under sizing the motor, incorrect or inadequate AC supply, or excessive surrounding air temperatures may
result in malfunction of the system.
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are
required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are
not followed. If you are not familiar with static control procedures, reference Guarding Against Electrostatic Damage, publication
8000-4.5.2 or any other applicable ESD protection handbook.
ATTENTION: Configuring an analog input for 0-20 mA operation and driving it from a voltage source could cause component
damage. Verify proper configuration prior to applying input signals.
ATTENTION: A contactor or other device that routinely disconnects and reapplies the AC line to the drive to start and stop the
motor can cause drive hardware damage. The drive is designed to use control input signals that will start and stop the motor. If an
input device is used, operation must not exceed one cycle per minute or drive damage will occur.
Class 1 LED Product
ATTENTION: Hazard of permanent eye damage exists when using optical transmission equipment. This product emits intense
light and invisible radiation. Do not look into module ports or fiber optic cable connectors.
Rockwell Automation Publication 20D-IN024C-EN-P - July 20137
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Step 2: Prepare for
Catalog Number Explanation
Installation
Position
1-345-7891011121314151617
20DD 2P1 A 0 E Y N A N A N E
abcdefghijklm
a
Drive
CodeType
20DPowerFlex 700S
b
Voltage Rating
CodeVoltagePh.Prechg.
B §
240V AC
C §
400V AC
D §
480V AC
E ♣ §
F
H
J
K
M
N
P
R
T
W
♣ Note: CE Certication testing has not been
performed on 600V class drives, Frames 1…4.
Frames 5 & 6 only.
Frames 5 & 6 only.
§ For DC input on Frames 1…4, use the
corresponding AC input code B, C, D, or E.
600V AC
690V AC
540V DC
650V DC
810V DC
932V DC
325V DC
540V DC
650V DC
810V DC
932V DC
3 (6 pulse)
3 (6 pulse)
3 (6 pulse)
3 (6 pulse)
3 (6 pulse)
_
_
_
_
_
_
_
_
_
c1
ND Rating
208/240V, 60Hz Input
Code
4P2
6P8
9P6
015
022
028
042
052
070
080
104
130
154
192
260
208V
Amps
17.5
25.3
32.2
48.3
78.2
120
130
177
221
260
4.8
7.8
240V
Amps
4.2
6.8
11
56
92
9.6
15.3
22
28
42
52
70
80
104
130
154
192
260
Hp
1.0
2.0
3.0
5.0
7.5
10
15
20
25
30
40
50
60
75
100
_
_
_
_
_
N
N
N
N
Y
Y
Y
Y
Y
Frame
1
1
1
1
1
2
3
3
4
4
5
5
6
6
6
c2
ND Rating
400V, 50 Hz Input
CodeAmpskW
2P1
3P5
5P0
8P7
011
015
022
030
037
043
056
072
085
105
125
170
205
260
2.1
3.5
5.0
8.7
11.5
15.4
22
30
37
43
56
72
85
105
125
170
205
260
0.75
1.5
2.2
4.0
5.5
7.5
18.5
110
132
c3
ND Rating
480V, 60 Hz Input
CodeAmpsHp
2P1
3P4
5P0
8P0
011
014
022
027
034
040
052
065
077
096
125
156
180
248
2.1
3.4
5
8
11
14
22
27
34
40
52
65
77
96
125
156
180
248
1.0
2.0
3.0
5.0
7.5
100
125
150
200
Frame
1
1
1
1
1
1
11
15
22
30
37
45
55
55
90
10
15
20
25
30
40
50
60
75
1
2
2
3
3
3
4
5
5
6
6
6
Frame
1
1
1
1
1
1
1
2
2
3
3
3
4
5
5
6
6
6
CodeAmpsHp
1P7
2P7
3P9
6P1
9P0
011
017
022
027
032
041
052
062
077
099
125
144
♣ Note: CE Certication testing has not been
performed on 600V class drives Frames 1…4.
CodeAmpskW
052
060
082
098
119
142
Code
A
CodeOperator Interface
0Blank Cover
3Full Numeric LCD
c4
ND Rating
600V, 60 Hz Input
1.7
2.7
3.9
6.1
9
11
17
22
27
32
41
52
62
77
99
125
144
c5
ND Rating
690V, 50 Hz Input
52
60
82
98
119
142
d
Enclosure
Description
IP20, NEMA Type 1
with Conformal Coat
e
HIM
♣
0
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
45
55
75
90
110
132
Frame
1
1
1
1
1
1
1
2
2
3
3
3
4
5
5
6
6
Frame
5
5
5
5
6
6
8Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Feedback
CodeOption
N
Standard (Incremental Encoder)
A
Resolver
B
Stegmann Hi-Resolution Encoder
C
Multi-Device Interface
E
2nd Encoder
S
Safe-O (w/2nd Encoder)
Expanded cassette required.
One encoder interface included with base drive.
m
Additional Cong.
CodeDescription
EPhase II Control
KPhase II DriveLogix5730
L
Phase II DriveLogix5730
w/EtherNet/IP
This is an embedded EtherNet/IP option that is
only available with DriveLogix5730.
T
Stegmann Hi-Res Enc. (w/2nd Encoder)
U
Stegmann Hi-Res Enc. (w/Safe-O)
Documentation
CodeDocuments
NNo Documentation
g
Brake
Codew/Brake IGBT ‡
seYY
oNN
‡ Brake IGBT is standard on Frames 1…3 and
optional on Frames 4…9 ONLY.
h
Brake Resistor
Codew/Resistor
YYe s
oNN
Not available for Frame 3 drives or larger.
English ManualE
j
Comm Slot
CodeVersion
NNone
CDPI ControlNet (Coax)
DDPI DeviceNet
EDPI EtherNet/IP
1DriveLogix ControlNet (Coax)
2
DriveLogix ControlNet Redundant
(Coax)
3DriveLogix ControlNet (Fiber)
4
DriveLogix ControlNet Redundant
(Fiber)
5DriveLogix DeviceNet (Open Conn.)
6DriveLogix EtherNet/IP
i
Emission
Code
CE Filter ♣
CM Choke
A
♣ Note: CE Certication testing has not been
performed on 600V class drives Frames 1…4.
Ye sYe s
du/dt Filter
No
k
Control Options
CodeCassette
A
Phase II Contol available only.
B
C
D
G
H
Logix Expansion Synchlink
NoExpanded
Slim
No
NoExpandedYes
YesExpandedNo
YesExpandedYes
NoN/A
SlimYesN/A
Frames 1...9 only.
Catalog Number Explanation, Continued
Rockwell Automation Publication 20D-IN024C-EN-P - July 20139
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Compliance with the Low Voltage (LV) Directive and Electromagnetic
Compatibility (EMC) Directive has been demonstrated using harmonized
European Norm (EN) standards published in the Official Journal of the
European Communities. PowerFlex drives comply with the EN standards listed
below when installed according to the PowerFlex 700S AC Drives Phase II
Control User and Reference Manuals.
CE Declarations of Conformity are available online at:
• EN 61800-5-1 Adjustable speed electrical power drive systems –
Part 5-1: Safety requirements – Electrical, thermal and energy.
EMC Directive (2004/108/EC)
• EN 61800-3 Adjustable Speed Electrical Power Drive Systems Part 3: EMC Product Standard Including Specific Test Methods.
12Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
General Considerations
• If the adhesive label is removed from the top of the drive, the drive must be
installed in an enclosure with side openings less than 12.5 mm (0.5 in.) and
top openings less than 1.0 mm (0.04 in.) to maintain compliance with the
LV Directive.
• The motor cable should be kept as short as possible to avoid
electromagnetic emission as well as capacitive currents.
• Use of line filters in ungrounded systems is not recommended.
• PowerFlex drives may cause radio frequency interference if used in a
residential or domestic environment. The installer is required to take
measures to prevent interference, in addition to the essential requirements
for CE compliance provided in this section, if necessary.
• Conformity of the drive with CE EMC requirements does not guarantee
an entire machine or installation complies with CE EMC requirements.
Many factors can influence total machine/installation compliance.
• PowerFlex drives can generate conducted low frequency disturbances
(harmonic emissions) on the AC supply system.
• More information regarding harmonic emissions can be found in the
PowerFlex 700S AC Drives Phase II Control, Reference Manual,
publication PFLEX-RM003
• When operated on a public supply system, it is the responsibility of the
installer or user to be sure, by consultation with the distribution network
operator and Rockwell Automation, if necessary, that applicable
requirements have been met.
.
Essential Requirements for CE Compliance
Conditions 1…6 listed below must be satisfied for PowerFlex 700S Phase II
drives to meet the requirements of EN61800-3.
1. Standard PowerFlex 700S CE compatible drive.
2. Review important precautions/attentions statements throughout this
document before installing drive.
3. Grounding as described in Grounding Requirements on page 25
4. Output power, control (I/O) and signal wiring must be braided, shield
cable with a coverage of 75% or better, metal conduit or have shielding/
cover with equivalent attenuation.
5. All shielded cables should terminate with proper shielded connector.
Frames Second EnvironmentFirst Environment Restricted Distribution
Restrict Motor Cable to 30 m (98 ft)Restrict Motor Cable to 150 m (492 ft)
Any Drive and OptionAny Drive and OptionExternal Filter Required
1…6√√√
(1) External filters for First Environment installations and increasing motor cable lengths in Second Environment installations are
available. Roxburgh models KMFA (RF3 for UL installations) and MIF or Schaffner FN3258 and FN258 models are recommended.
Refer to http://www.deltron-emcon.com
below.
(1)
and http://www.mtecorp.com (USA) or http://www.schaffner.com, respectively.
.
Rockwell Automation Publication 20D-IN024C-EN-P - July 201313
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
IMPORTANT
Common Bus and Precharge Considerations
The following notes must be read and understood. Also refer to Selecting/
Verifying Fan Voltage (Frames 5 and 6 Only) on page 34
Blocks on page 41
for additional common bus information.
1. If drives without internal precharge are used (frames 5 and 6 only), then:
a. precharge capability must be provided in the system to guard against
possible damage, and
b. disconnect switches Must Not be used between the input of the drive
and a common DC bus without the use of an external precharge device.
2. If drives with internal precharge (frames 1…6) are used with a disconnect
switch to the common bus, then an auxiliary contact on the disconnect
must be connected to a digital input of the drive. The corresponding input
(parameter 361…366) must be set to option 30, “Precharge Enable.” This
provides the proper precharge interlock, guarding against possible damage
to the drive when connected to a common DC bus.
Refer to PowerFlex AC Drives in Common Bus Configurations, publication
DRIVES-AT002
, for more information.
through Power Terminal
Operating Conditions and Temperatures
PowerFlex 700S frame 1…6 drives are designed to operate at 0…40 °C (32…104
°F) ambient. To operate most frame 1…4 drives in installations between 41 and
50 ° C (105.8 and 122 °F), you must remove the top adhesive label from the
drive. Frames 5 and 6 do not have an adhesive label. See Ta b l e 8
page 15
below for more information.
Removing the adhesive label from the top of frame 1…4 drives changes the
NEMA/UL enclosure rating from Type 1 to Type Open.
Table 8 - Enclosure Types and Acceptable Surrounding Air Temperature
Enclosure TypeTemperature RatingDrive
IP20, NEMA/UL Type 1
(with Top Label)
IP20, NEMA/UL Type Open
(Top Label Removed)
IP00, NEMA/UL Type Open
(Top Label and Vent Plate Removed)
Flange Mount
Front (Inside Encl.) - IP00, NEMA/UL Type Open
Back/Heat Sink - IP54, NEMA/UL
Typ e 12
Stand-Alone/Wall Mount - IP54, NEMA/UL Type 12 0…40 °C (32…104 °F)Frames 5 and 6
(1) Frames 5 and 6 do not have a label.
(2) To remove the vent plate, lift the top edge of the plate away from the chassis and ro tate the plate out from the back plate. Refer to
Figure 3
(3) Refer to the Fusing and Circuit Breakers tables on page 44, for exceptions.
(1)
(1)
(2)
on page 17 for location of vent plate.
0…40 °C (32…104 °F)Frame 1…4, All Ratings
0…50 °C (32…122 °F)Frames 5 and 6, Most Ratings
0…50 °C (32…122 °F)Most Ratings
0…45 °C (32…113 °F)20DC072 and 20DE062 Only
0…50 °C (32…122 °F)20DC072 Only
Frames 5 a nd 6
0…55 °C (32…131 °F)
0…40 °C (32…104 °F)
and Figure 1 on
(3)
(2)
14Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
IMPORTANT
With Ad hesive
Label Removed
Adhesive LabelWith Adhesive Label
Left in Place
Air flow through the drive
must not be impeded.
PowerFlex 700S drives must be mounted in a clean, dry location. Contaminants
such as oils, corrosive vapors and abrasive debris must be kept out of the
enclosure. These enclosures are intended for indoor use primarily to provide a
degree of protection against contact with enclosed equipment. These
enclosures offer no protection against airborne contaminants.
Minimum Mounting Clearances
Specified vertical clearance requirements are intended to be from the drive to the
closest object that can restrict airflow through the drive heat sink and chassis. The
drive must be mounted in a vertical orientation as shown, and must make full
contact with the mounting surface. Do not use standoffs or spacers. In addition,
inlet air temperature must not exceed the product specification. See Ta b l e 8
page 14
(1) Refer to Drive Rating to Frame Size Cross References on page 10 for frame information.
(2) Junction Box can be removed if drive is mounted in a cabinet.
Rockwell Automation Publication 20D-IN024C-EN-P - July 201321
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Step 3: Lift and Mount the
Drive
Drive Weights
Table 9 - Approximate Drive Weights
Frame SizeDrive RatingDrive Weight
kWHpkg (lb)
10.75…111…107.0 (15.5)
27.5…18.510…2512.5 (27.6)
311…3715…5018.6 (40.9)
425…6018.5…5524.5 (54.0)
540…10030…9037.2 (82.0)
660…20045…13271.5 (157.5)
(1) Weights include HIM, DriveLogix controller with ControlNet daughtercard, Hi-Resolution Encoder Option, and 20-COMM-C
Contro lNet adapt er.
(2) Add an additional 3.6 kg (8.0 lb) for 200 Hp drives.
(1)
(2)
Attaching the Lifting Hardware
All lifting equipment and lifting components (hooks, bolts, lifts, slings, chains,
and so forth) must be properly sized and rated to safely lift and hold the weight of
the drive while mounting. See Figure 8
page 24
for lifting instructions.
and Figure 9 on page 23, and Figure 10 on
ATTENTION: To guard against possible personal injury and/or equipment
damage…
• Inspect all lifting hardware for proper attachment before lifting drive.
• Do not allow any part of the drive or lifting mechanism to make contact with
electrically charged conductors or components.
• Do not subject the drive to high rates of acceleration or deceleration while
transporting to the mounting location or when lifting.
• Do not allow personnel or their limbs directly underneath the drive when it is
being lifted and mounted.
22Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
Figure 8 - Lifting Frame 4 Drives
S
>
1
/
2 A
A
< 45°
S
>
1
/
2 A
A
< 45°
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Figure 9 - Lifting Frame 5 Drives
Rockwell Automation Publication 20D-IN024C-EN-P - July 201323
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
>
1
/
2 A
A
< 45°
Figure 10 - Lifting Frame 6 Drives
24Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
U (T1)
V (T2)
W (T3)
R (L1)
S (L2)
T (L3)
PE
SHLD
Step 4: Power Wiring
ATTENTION: National Codes and standards (NEC, VDE, BSI and so forth) and
local codes outline provisions for safely installing electrical equipment.
Installation must comply with specifications regarding wire types, conductor
sizes, branch circuit protection and disconnect devices. Failure to do so may
result in personal injury and/or equipment damage.
Grounding Requirements
The drive Safety Ground-PE must be connected to system ground. Ground
impedance must conform to the requirements of national and local industrial
safety regulations and/or electrical codes. The integrity of all ground connections
should be periodically checked.
Figure 11 - Typical Grounding
Shield Termination - SHLD
The Shield terminal (see page 39) provides a grounding point for the motor cable
shield. It must be connected to an earth ground by a separate continuous lead.
The motor cable shield should be connected to this terminal on the drive and the
motor frame. Use a shield terminating or EMI clamp to connect shield to this
terminal.
Rockwell Automation Publication 20D-IN024C-EN-P - July 201325
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Unbalanced, Ungrounded or Resistive Grounded Distribution
Systems
If phase to ground voltage will exceed 125% of normal or the supply system is
ungrounded, refer to Wiring and Grounding Guidelines for Pulse Width
Modulated (PWM) AC Drives, publication DRIVES-IN001
information.
ATTENTION: PowerFlex 700S drives contain protective MOVs and common
mode capacitors that are referenced to ground. These devices must be
configured according to the recommendations in Ta bl e 10
, for more
on page 27.
RFI Filter Ground
Using an optional RFI filter may result in relatively high ground leakage currents.
Therefore, the filter must only be used in installations with grounded AC supply
systems and be permanently installed and solidly grounded (bonded) to the
building power distribution ground. Be sure that the incoming supply neutral is
solidly connected (bonded) to the same building power distribution ground.
Grounding must not rely on flexible cables and should not include any form of
plug or socket that would permit inadvertent disconnection. Some local codes
may require redundant ground connections. The integrity of all connections
should be periodically checked. Refer to the instructions supplied with the filter.
26Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
IMPORTANT
R/L1
S/L2
T/L3
DC+
DC–
MOV and AC EMI Capacitor Phase to Ground
Common Mode Capacitor Phase to Ground
Jumper Wire
Jumper Wire
Power Jumpers
PowerFlex 700S Phase II drives contain protective MOVs and Common Mode
Capacitors that are referenced to ground (see below). To guard against unstable
operation and/or damage, the drive must be properly configured
Ta b l e 1 0
on page 27.
as shown in
All PowerFlex 700S Phase II drives are shipped with the DC bus common mode
capacitors referenced to ground. The following installation instructions must
be completed before applying power to the drive.
Table 10 - Recommended Power Jumper Configurations
Power S ource Ty pe
Solid Ground
• AC fed, solidly grounded
• DC fed from passive rectifier, which has
an AC source and solid ground
Non-Solid Ground
• AC fed ungrounded
• Impedance grounded
• High resistive ground
• B phase ground
• Regenerative unit such as common DC
bus supply & brake
• DC fed from an active converter
(1) It is highly recommended to accurately determine the power source type and then configure appropriately.
(2) When MOVs are disconnected, the power system must have its own transient protection to verify known and controlled voltages.
Rockwell Automation Publication 20D-IN024C-EN-P - July 201327
(1)
MOV/ Input Filter
(2)
Caps
ConnectedConnected
DisconnectedD isconnected
DC Bus Common
Mode Caps
Benefits Of Correct Configuration on
Power S ource Ty pe
• UL compliance,
• Reduced electrical noise,
• Most stable operation,
• EMC compliance,
• Reduced voltage stress on
components and motor bearings
• Helps avoid severe equipment
damage when ground fault
occurs
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
IMPORTANT
Volt age Co de
Frame
Current Rating
Series
To connect or disconnect these devices, refer to pages 29 through 32.
Common mode capacitors are required to conform with the EMC directive.
Removing these devices will withdraw the associated directive.
In addition, on an ungrounded distribution system where the line-to-ground
voltages on any phase could exceed 125% of the nominal line-to-line voltage, an
isolation transformer should be installed. See Wiring and Grounding Guidelines
for PWM AC Drives, publication DRIVES-IN001
for more information on
impedance grounded and ungrounded systems.
Jumper Installation, Removal and Storage
PowerFlex 700S drives utilize plug-in style jumpers and jumper wires. Most drives
will have a jumper storage area inside the front cover. Extra jumpers or jumpers
that have been removed should be stored in this location for use at a later time.
Insulating Jumper Wires
Some drives utilize nylon screws and spacers to insulate jumper
wires from ground and secure them to the chassis. The
components must be installed as shown.
Drive Identification
Refer to the drive nameplate and locate the “Voltage Code,” “Current Rating,”
“Frame,” and “Series”. Use this information to locate the proper procedure in the
following tables.
Cat No. 20D D xxx x x xxxxxxx
UL TYPE 1/IP20
Normal Duty Power
Heavy Duty Power
Input: 3 Phase, 47-63Hz
AC Voltage Range
Amps
Output: 3 Phase, 0-400 Hz
AC Voltage Range
Base Hz (default)
Continuous Amps
1 Min Overload Amps
3 Sec Overload Amps
Mfd. in 2007 on Aug 1
Made in the USA (TAC 1J)
Rockwell Automation, Mequon WI 53092-4400
400V480V
xxx kW
xxx kW
342-440
0-400
50 Hz
xxx
xxx
xxx
xxx
432-528
xxx kW
xxx kW
xxx
0-460
60 Hz
xxx
xxx
xxx
Frame: 3
Serial Number: xxxxxxx
Series: B
Original Firmware V. x.xxx
U
c
L
®
US
Listed
Ind. Cont
Eq. 966X
N223
28Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
Frame
BR1
BR2
DC+
DC–
PE
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Use 75C Wire Only
#10-#14 AWG
Torque to 7 in-lbs
!
DANGER
PE A
PE B
CM Cap
MOV
BR1 BR2 DC+ DC- U/T1 V/T2 W/T3
SHLDSHLD
PE R/L1 S/L2 T/L3
PE 2
MOV-PE JMPR
PE 1
AUX IN+ AUX OUT–
75C Cu Wire
6 AWG [10MM2] Max.
12 IN. LBS.
1.4 N-M
} TORQUE
WIRE
STRIP
CONTROL
POWER
PE 4
PE 3
MOV
PE_MOV
CM Cap
PE_CAP
1B
Volt age
C
D
E
Factory Default Jumper SettingsPower Source Type
MOV/Input Filter
Current
Rating
Caps
Code
AllPE_B
Installed
Table 11 - Jumper Settings and Locations
DC Bus Common
Mode Caps
PE_A
Installed
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Solid Ground
• Remove the I/O Cassette (refer to the Installation
Instructions for details). Verify that jumpers are
installed at the “PE_A” and “PE_B” locations on
the Power Board.
Non-Solid Ground
• Remove the I/O Cassette (refer to the Installation
Instructions for details). Remove jumpers at the
“PE_A” and “PE_B” locations on the Power Board.
2B
3 & 4 B
AllPE_MOV
C
D
E
AllPE_MOV
C
D
E
Installed
Installed
PE_CAP
Installed
PE-CAP
Installed
Solid Ground
• Verify that jumpers are installed at the “PE_CAP”
and “PE_MOV” locations.
Non-Solid Ground
• Remove jumpers at the “PE_CAP” and “PE_MOV”
locations.
Solid Ground
• Verify that jumpers are installed at the “PE_CAP”
and “PE_MOV” locations.
Non-Solid Ground
• Remove jumpers at the “PE_CAP” and “PE_MOV”
locations.
CM Cap
PE_CAP
SHLD
MOV
PE_MOV
PE CAP
BR1 BR2
75C Cu Wire
6 AWG [10MM2] Max.
12 IN. LBS.
} TORQUE
1.4 N-M
AUX IN
BR1 BR2 DC+ DC- U/T1 V/T2 W/T3 R/L1 S/L2 T/L3
+ –
3 AWG [25MM2] Max.
16 IN. LBS.
1.8 N-M
75C Cu Wire
PE MOV
WIRE
STRIP
POWER
CONTROL
} TORQUE
PE
SHLD
Rockwell Automation Publication 20D-IN024C-EN-P - July 201329
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY
Two green/yellow
wires connected
the Power Terminal
Voltag e
Code
F
W
DC Bus Common
Mode Caps
Green/yellow wire to
to
CM Cap Board is
connected
to ground
Block rail
Solid Ground
1. CM Cap jumper wire should be connected to ground
with a metal screw. Verify. If necessary, remove the
nylon screw/spacer and insert a metal M5 x 8 screw.
Torque to 3.2 N•m (28 lb•in).
2. MOV/Input Filter Cap jumper wires should be
connected to ground with a metal screw. Verify. If
necessary, remove the nylon screw/spacer and insert
a metal M5 x 12 screw.
Non-Solid Ground
1. CM Cap jumper wire should be insulated from ground
with a nylon screw/spacer. Verify. If necessary,
remove the metal screw and insert a M5 x 15 nylon
screw/spacer.
2. MOV/Input Filter Cap jumper wires should be
insulated from ground with a nylon screw/spacer.
Verify. If necessary, remove the metal screw and
insert a
M5 x 20 nylon screw/spacer.
E
077
Two green/yellow
F
082
wires connected
T
098
W
chassis ground
099
Green/yellow wire to
CM Cap Board is
to
connected
to ground
Solid Ground
1. CM Cap jumper wire should be connected to ground
with a metal screw. Verify. If necessary, remove the
nylon screw/spacer and insert a metal M5 x 8 screw.
Torque to 3.2 N•m (28 lb•in).
2. MOV jumper wire should be connected to ground
with metal screws. Verify. If necessary, remove the
nylon screw/spacers and insert metal M5 x 12 screws.
3. Input Filter Cap jumper wire should be connected to
ground with a metal screw. Verify. If necessary,
remove the nylon screw/spacer and insert metal M5
x 8 screw.
Non-Solid Ground
1. CM Cap jumper wire should be insulated from ground
with a nylon screw/spacer. Verify. If necessary,
remove the metal screw and insert a M5 x 15 nylon
screw/spacer.
2. MOV jumper wire should be insulated from ground
with a nylon screw/spacer. Verify. If necessary,
remove the metal screws and insert a M5 x 20 nylon
screw/spacer.
3. Input Filter Cap jumper wire should be insulated from
ground with a nylon screw/spacer. Verify. If
necessary, remove the metal screws and insert a M5 x
15 nylon screw/spacer.
(1) AC input drives only. MOV’s and input filter caps do not exist on DC input drives.
(2) When removing MOV’s, the input filter capacitor must also be removed.
30Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
Frame
CM Cap Older Drives
MOV / Input Filter Cap
MOV
CM Cap - Newer Drives
5 B
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Factory Default Jumper SettingsPower Source Type
MOV/Input Filter
(1) (2)
Current
All,
except
C140
(see
next
page)
Rating
Caps
Two green/yellow
wires connected
the Power Terminal
Block rail
Volt age
Code
C
D
H
J
N
P
R
DC Bus Common
Mode Caps
Green/yellow wire is
to
connected to ground
Solid Ground
1. CM Cap jumper wire should be connected to
ground with a metal screw. Verify.
• Newer Drives - If necessary, remove the nylon
screw/spacer and insert a metal M5 x 8 screw.
Torque to 3.2 N•m (28 lb•in).
• Older Drives - Remove the I/O Cassette (see
Installation Instructions for details). The green/
yellow CM Cap jumper wire is located on the
back of chassis and should be connected to
groun d with a metal screw. If necess ary, rem ove
the insulation from the wire terminal and
connect to chassis with a metal M5 x 12 screw.
Optional
Communications
Module
Torque screw to 3.2 N•m (28 lb•in).
2. MOV/Input Filter Cap jumper wires should be
Non-Solid Ground
1. CM Cap jumper wire should be insulated from
2. MOV/Input Filter Cap jumper wires should be
(1) AC input drives only. MOV’s and input filter caps do not exist on DC input drives.
(2) When removing MOV’s, the input filter capacitor must also be removed.
connected to ground with a metal screw. Verify. If
necessary, remove the nylon screw/spacer and
insert a metal M5 x 12 screw.
ground. Verify.
• Newer Drives - If necessary, remove the metal
screw and insert a M5 x 15 nylon screw/spacer.
• Older Drives - Remove the I/O Cassette (see
Installation Instructions for details). If
necessary, insulate/secure jumper wire to guard
against unintentional contact with chassis or
components.
insulated from ground with a nylon screw/spacer.
Verify. If necessary, remove the metal screw and
insert a M5 x 20 nylon screw/spacer.
POWER TERMINAL RATINGS
WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY
GROUND TERMINAL RATINGS (PE)
WIRE RANGE: 6-1/0 AWG (16-35 MM
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
17
2
)
21
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
2
)
9
INPUT ACOUTPUT
Rockwell Automation Publication 20D-IN024C-EN-P - July 201331
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
DC–DC+BR1BR2
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
PS+
PS–
USE 75 C
COPPER WIRE
ONLYTORQUE52 IN-LB(6 N-M)
UT1VT2W
T3
RL1S
L2
INPUTOUTPUT
T
L3
PE PE
Optional
Communications
Module
PE PE
MOV
Input Filter Cap
CM Cap
DO NOT
REMOVE
MOV
DC–DC+BR1BR2
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
PS+
PS–
USE 75 C
COPPER WIRE
ONLYTORQUE52 IN-LB
(6 N-M)
UT1VT2W
T3
RL1S
L2
INPUTOUTPUT
T
L3
PE PE
Optional
Communications
Module
Input Filter Cap
PE PE
MOV
CM Cap
DO NOT
REMOVE
MOV
Factory Default Jumper SettingsPower Source Type
Frame
6B
MOV/Input Filter
Code
Current
Rating
Caps
Volt age
AllTwo green/yellow
C
D
H
wires connected
Power Terminal
Block “PE”
(1) (2)
DC Bus Common
Mode Caps
Green/yellow wire to
to
CM Cap Board is
connected
Terminal Block “PE”
to Power
J
N
P
R
Solid Ground
1. The green/yellow CM Cap jumper wire should
be connected to “PE.”
2. The MOV/Input Filter Cap jumper wires should
be connected to “PE.”
Non-Solid Ground
1. The green/yellow CM Cap jumper wire should
be insulated from ground. If necessary, remove
the jumper wire from “PE” and insulate/secure
it to guard against unintentional contact with
chassis or components. Important: Do Not
Remove/Disconnect the larger green/
yellow wire.
2. MOV/Input Filter Cap jumper wires should be
insulated from ground. If necessary, remove
the jumper wires from “PE” and individually
insulate/ secure each jumper wire to guard
against unintentional contact with chassis or
components.
E
AllTwo green/yellow
F
T
W
wires connected
Power Terminal
Block “PE” and
chassis
Green/yellow wire to
to
CM Cap Board is
connected
Ter mi nal Bl ock “ PE”
to Power
Solid Ground
1. The green/yellow CM Cap and MOV jumper
wires should be connected to “PE.”
2. The Input Filter Cap jumper wire (top right)
should be connected to chassis ground with a
metal screw. Verify. If necessary, remove the
nylon screw/spacer and insert a metal M5 x 10
screw. Torque to 3.2 N•m (28 lb•in).
Non-Solid Ground
1. The green/yellow CM Cap and MOV jumper
wires should be insulated from ground. If
necessary, remove them from “PE” and
individually insulate/secure each jumper wire
to guard against unintentional contact with
chassis or components. Important: Do Not
Remove/Disconnect the larger green/
yellow wire.
2. The Input Filter Cap jumper wire (top right)
should be insulated from ground with a nylon
screw/spacer. Verify. If necessary, remove the
metal screw and insert a M5 x 15 nylon screw/
spacer.
(1) AC input drives only. MOV’s and input filter caps do not exist on DC input drives.
(2) When removing MOV’s, the input filter capacitor must also be removed.
32Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
AC Supply Source Considerations
PowerFlex drives are suitable for use on a circuit capable of delivering up to a
maximum of 200,000 rms symmetrical amperes, 600 volts with recommended s/
circuit breakers.
ATTENTION: To guard against personal injury and/or equipment damage
caused by improper fusing or circuit breaker selection, use only the
recommended line s/circuit breakers specified in Fusing and Circuit Breakers on
.
page 44
If a residual current detector (RCD) is used as a system ground fault monitor,
only Type B (adjustable) devices should be used to avoid nuisance tripping.
Input Power Conditioning
Certain events on the power system supplying a drive can cause component
damage or shortened product life. These conditions are divided into two basic
categories:
1. All Drives
• The power system has power factor correction capacitors switched in
and out of the system, either by the user or by the power company.
• The power source has intermittent voltage spikes in excess of 6000
volts. These spikes could be caused by other equipment on the line or by
events such as lightning strikes.
• The power source has frequent interruptions.
2. 5 Hp or Less Drives (in addition to “1” above)
• The nearest supply transformer is larger than 100 kVA or the available
short circuit (fault) current is greater than 100,000 A.
• The impedance in front of the drive is less than 0.5%.
If any or all of these conditions exist, it is recommended that the user install a
minimum amount of impedance between the drive and the source. This
impedance could come from the supply transformer itself, the cable between the
transformer and drive or an additional transformer or reactor. The impedance
can be calculated using the information supplied in Wiring and Grounding
Guidelines for Pulse Width Modulated (PWM) AC Drives, publication
DRIVES-IN001
.
Single-Phase Input Power
The PowerFlex 700S drive is typically used with a three-phase input supply.
Single-phase operation of the drive is not currently rated under the UL508C
listing. Rockwell Automation has verified that single-phase operation with
output current derated by 50% of the three-phase ratings identified in the Fusing
and Circuit Breakers tables on page 44
Rockwell Automation Publication 20D-IN024C-EN-P - July 201333
will meet all safety requirements.
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
IMPORTANT
AC Input Phase Selection (Frames 5 and 6 Only)
ATTENTION: To avoid a shock hazard, be sure that all power to the drive has
been removed before performing the following.
Moving the “Line Type” jumper shown in Figure 12 on page 35 will select single
or three-phase operation. Remove plastic guard to access jumper.
When selecting single-phase operation, input power must be applied to the R
(L1) and S (L2) terminals only.
Selecting/Verifying Fan Voltage (Frames 5 and 6 Only)
ATTENTION: To avoid a shock hazard, be sure that all power to the drive has
been removed before performing the following.
Frames 5 and 6 utilize a transformer to match the input line voltage to the
internal fan voltage. If your line voltage is different than the voltage class specified
on the drive nameplate, it may be necessary to change transformer taps as shown
below. Common bus (DC input) drives require user supplied 120 or 240V AC to
power the cooling fans. The power source is connected between “0 VAC” and the
terminal corresponding to your source voltage (see Figure 12
on page 35).
34Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY
Figure 12 - Phase Selection Jumper and Fan Transformer Locations (Frame 5 shown)
Frame 5 and 6 Transformer Tap Access
The transformer is located behind the power terminal block in the area shown in
Figure 12
release terminal block and change tap:
Rockwell Automation Publication 20D-IN024C-EN-P - July 201335
. Access is gained by releasing the terminal block from the rail. To
1. Locate the small metal tab at the bottom of the end block.
2. Press the tab in and pull the top of the block out. Repeat for next block if
desired.
3. Select appropriate transformer tap.
4. Replace block(s) in reverse order.
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Important Common Bus (DC Input) Application Notes
1. If drives without internal precharge are used (Frames 5 and 6 only), then:
• precharge capability must be provided in the system to guard against
possible damage, and
• disconnect switches Must
and a common DC bus without the use of an external precharge device.
2. If drives with internal precharge (Frames 1…6) are used with a disconnect
switch to the common bus, then an auxiliary contact on the disconnect
must be connected to a digital input of the drive. The corresponding input
(parameters 825…830) must be set to “Precharge Enable”. This provides
the proper precharge interlock, guarding against possible damage to the
drive when connected to a common DC bus.
Not be used between the input of the drive
Auxiliary Control Power Supply
An auxiliary power supply can be used to keep the 700S control assembly
energized when input power is de-energized. This allows the main control board,
DriveLogix controller and any feedback option cards to continue operation.
Refer to Power Terminal Block Specifications on page 39
information. You must set bit 17 “Aux Pwr Sply” of Par 153 [Control Options] to
enable this feature. Refer to the PowerFlex 700S Auxiliary Control Power Supply
(20-24V-AUX1), Installation Instructions, publication 20D-IN021
information.
for connection
, for more
36Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
Accessing the Terminals
=
Proper tightening torque for
reassembly is 0.7 N•m (6 lb•in)
Removing the Cassette
TaskDescription
Open the door of the power structure and disconnect the cables that
connect to the main board. Depress the locking tab on connector
before disconnecting cables.
Loosen the screws on the face of the cassette.
Remove the cassette.
A
B
C
Removing the Side Covers
TaskDescription
Loosen the screws on the face of the front cover and remove the cover.
Loosen the screws on the side of rear cover and remove the cover.
Frames 1…4
Locate the slot in the upper left corner. Slide the locking
tab up and swing the cover open. Special hinges allow
the cover to move away from the drive and lay on top of
an adjacent drive (if present).
Frame 5
Slide the locking tab up, loosen the right-hand cover
screw and remove th e cover.
Frame 6
Loosen the two screws at the bottom of the bottom
cover and carefully slide the cover down and out.
Loosen the two screws at top of the top cover and
remove the cover.
B
C
B
Figure 13 - Opening the Drive Cover
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
(x2)
W/T3
R/L1
L2
BR1
BR2
DC+
DC-
PE
U/T1
V/T2
A
B
A
(x2)
A
(x3)
Rockwell Automation Publication 20D-IN024C-EN-P - July 201337
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
IMPORTANT
SHLD
SHLD
PE
(Frame 3 Shown)
Cable Entry Plate Removal
If additional wiring access is needed, the cable entry plate on frame 1…3 drives
can be removed. Loosen the screws securing the plate to the chassis and slide the
plate down and off the drive.
Removing the cable entry plate on frame 1…3 limits the maximum
surrounding air temperature to 40 °C (104 °F).
Power Wiring Access Panel Removal
ATTENTION: Removing the access panel/cover exposes dangerous voltages on
the terminals and negates the enclosure type rating. Replace the access panel/
cover when service is complete. Failure to comply may result in personal injury
or equipment damage.
FrameRemoval Procedure (Replace when wiring is complete)
1, 2 & 6The access panel is part of the front cover, see Figure 13
3Open front cover and gently tap/slide the access panel down and out.
4Loosen the 4 screws and remove the access panel.
38Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
5Remove the front cover (see Figu re 13
on page 37) and gently tap/slide the access panel up and out.
on page 37.
Power Wire Recommendations
TypeDescriptionMin Insulation
(1)(2)
Power
Standard• Four tinned copper conductors with XLPE insulation.
• Copper braid/aluminum foil combination shield and tinned
copper drain wire.
• PVC jacket.
(1) Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot).
(2) The use of shielded wire for AC input power may not be necessary but is always recommended.
Power Terminal Block Specifications
Refer to illustrations on pages 40 and 41 for terminal block locations.
No. NameFrameDescriptionWire Size Range
MaximumMinimumMaximumRecommended
(10 AWG)
(6 AWG)
(3 AWG)
(6 AWG)
(1/0 AWG)
(1/0 AWG)
(1/0 AWG)
(2/0 AWG)
(1/0 AWG)
(1/0 AWG)
(4/0 AWG)
2
2
2
2
2
2
2
2
2
2
2
(5)
1Power Terminal Block 1Input power and motor connections4.0 mm
2Input power and motor connections10.0 mm
3Input power and motor connections25.0 mm
BR1, BR210.0 mm
4Input power and motor connections35.0 mm
5
(75 HP)
R, S, T, BR1, BR2, DC+, DC-, U, V and W50.0 mm
(3)
PE50.0 mm
5
(100 HP)
R, S, T, DC+, DC-, U, V and W70.0 mm
(3)
BR1, BR250.0 mm
PE50.0 mm
6Input power and motor connections120.0 mm
(1)
0.5 mm
(22 AWG)
0.8 mm
(18 AWG)
2.5 mm
(14 AWG)
0.8 mm
(18 AWG)
10 mm
(8 AWG)
2.5 mm
(14 AWG)
4.0 mm
(12 AWG)
16.0 mm
(6 AWG)
2.5 mm
(14 AWG)
4.0 mm
(12 AWG)
2.5 mm
(14 AWG)
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Rating
600V,
75 °C (167 °F)
Tor queTer mina l Bo lt Size
2
1.7 N•m
(15 lb•in)
2
1.7 N•m
(15 lb•in)
2
3.6 N•m
(32 lb•in)
2
1.7 N•m
(15 lb•in)
2
4.0 N•m
(24 lb•in)
2
See Note
2
2
2
2
2
6 N•m
(52 lb•in)
0.8 N•m
—
(7 lb•in)
1.4 N•m
—
(12 lb•in)
1.8 N•m
—
(16 lb•in)
1.4 N•m
—
(12 lb•in)
4.0 N•m
—
(24 lb•in)
(4)
See Note
(3)
—
—
—
—
—
6 N•m
—
(52 lb•in)
(2)
2SHLD Terminal1-6Terminating point for wiring shields——1.6 N•m
(14 lb•in)
3AUX Terminal Block1-4Auxiliary Control Voltage
(6)
PS+, PS-
5-64.0 mm
4Fan Terminal Block
(Common Bus Only)
(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt to avoid damage to the terminal.
(3) Not all terminals present on all drives.
(4) Refer to the terminal block label inside the drive.
(5) If necessary, two wires can be used in parallel to any of these terminals using two lugs.
(6) Auxiliary power: UL Installation - 300V DC, ±10%, Non UL Installation - 270…600V DC, ±10%. Frame 1…6, 100 W.
5-6User Supplied Fan Voltage
0V AC, 120V AC, 240V AC
1.5 mm
(16 AWG)
(10 AWG)
4.0 mm
(10 AWG)
2
0.2 mm
2
———
(24 AWG)
2
2
0.5 mm
(22 AWG)
0.5 mm
(22 AWG)
2
0.6 N•m
(5.3 lb•in)
2
0.6 N•m
(5.3 lb•in)
Rockwell Automation Publication 20D-IN024C-EN-P - July 201339
1.6 N•m
(14 lb•in)
0.6 N•m
(5.3 lb•in)
0.6 N•m
(5.3 lb•in)
M12
—
M10
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
BR1
BR2
DC+
DC–
PE
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Use 75C Wire Only
#10-#14 AWG
Torque to 7 in-lbs
!
DANGER
BR1 B
SHLDSHLD
V/T2 W/T3 PE R/L1 S/L2 T/L3
AUX IN+ AUX OUT–
Optional
Communications
Module
75C Cu Wire
6 AWG [10MM2] Max.
12 IN. LBS.
1.4 N-M
} TORQUE
WIRE
STRIP
CONTROL
POWER
WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
1
2
Frame 1
Frame 2
Frames 3 & 4
Frame 5
Frame 6
3
Below Wire
Guard
PE
/
3
3
2
2
1
1
1
2
3
2
3
1
4
Figure 14 - Typical Power Terminal Block Locations
PE B
PE A
BR1 BR2
75C Cu Wire
6 AWG [10MM2] Max.
12 IN. LBS.
} TORQUE
1.4 N-M
AUX IN
BR1 BR2 DC+ DC- U/T1 V/T2 W/T3 R/L1 S/L2 T/L3
+ –
SHLD
75C Cu Wire
3 AWG [25MM2] Max.
16 IN. LBS.
1.8 N-M
} TORQUE
PE
WIRE
STRIP
POWER
CONTROL
SHLD
40Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
T
(L3)
S
(L2)
R
(L1)
W
(T3)
V
(T2)
U
(T1)
PEDC–DC+BR2BR1
T
(L3)
S
(L2)
R
(L1)
W
(T3)
V
(T2)
U
(T1)
DC–DC+BR2BR1
T/L3S/L2R/L1PEPEW/T3V/T2U/T1DC–DC+
BR1/
DC+BR2
PS–
PS+
T/L3S/L2R/L1
PEPE
W/T3V/T2U/T1DC–DC+
BR1/
DC+BR2
PS–
PS+
240
VAC
120
VAC
0
VAC
PEPEW/T3V/T2
Precharge Resistor Fuse – FWP-15A14F
(Common Bus Drives w/Precharge Only)
U/T1DC–DC+
BR1*/
DC+
BR2*
PS–
PS+
240
VAC
120
VAC
0
VAC
PE
PE
W/T3V/T2U/T1DC–DC+
BR1*/
DC+
BR2*
PS–
PS+
Precharge Resistor Fuse – FWP-15A14F
(Common Bus Drives w/Precharge Only)
USE 75 C
COPPER WIRE
ONLY
TORQUE
52 IN-LB
(6 N-M)
U
T1
DC–DC+BR1BR2
VT2W
T3
RL1S
L2
INPUTOUTPUT
T
L3
PEPE
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
PS+
PS–
Common Mode Capacitor
& MOV Jumpers
(Green/Yellow Wire)
Input Filter Capacitor
(Green/Yellow Wire)
Frame 1Frame 2
Frame 3
Frame 5 - 75 HP, Normal Duty
480V AC Input
Frame 5 - 100 HP, Normal Duty
480V AC Input
Shaded terminals (BR1 & BR2) are only present on drives ordered with the brake option.
Frame 5 - 75 HP, Normal Duty
650V DC Input
Frame 5 - 100 HP, Normal Duty
650V DC Input
Frame 6 - 150 HP, Normal Duty
480 V AC Input
Frame 6 - 150 HP, Normal Duty
650V DC Input
0 VAC240V AC120V AC
Motor
Input AC Line
BR1
BR2
DC+
DC–
PE
U (T1)
V (T2)
W (T3)
R (L1)
S (L2)
T (L3)
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Figure 15 - Power Terminal Blocks
PS+
PS–
22-10
AWG
5.3 IN-LB
WIRE STRIP
(0.6 N-M)
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
DC–DC+BR1BR2
Common Mode Capacitor
& MOV Jumpers
(Green/Yellow Wire)
Input Filter Capacitor
(Green/Yellow Wire)
Precharge Resistor Fuse – FWP-15A14F
(Common Bus Drives w/Precharge Only)
USE 75 C
COPPER WIRE
ONLY
U
TORQUE
52 IN-LB
(6 N-M)
Rockwell Automation Publication 20D-IN024C-EN-P - July 201341
VT2W
T1
OUTPUT
PEPE
T3
22-10 AWG
0 VAC
120 VAC
240 VAC
5.3 IN-LB
(0.6 N-M)
FAN
1-PHASE
INPUT
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Power On
R (L1)
S (L2)
T (L3)
Power SourceDB Resistor Thermostat
Power Off
M
M
(Input Contactor) M
Three-Phase
AC Input
TerminalDescriptionNotes
BR1DC Brake (+)Dynamic Brake Resistor Connection (+)
BR2DC Brake (–)Dynamic Brake Resistor Connection (–)
DC+DC Bus (+)DC Input Power or Dynamic Brake Chopper
DC–DC Bus (–)DC Input Power or Dynamic Brake Chopper
PEPE GroundRefer to Fig ure 14
Motor GroundRefer to Figure 14 on page 40 for location on 3 Frame drives
UU (T1)To motor
VV (T2)To motor
WW (T3)To motor
RR (L1)AC Line Input Power
SS (L2)AC Line Input Power
TT (L3)AC Line Input Power
on page 40 for location on 3 Frame drives
Dynamic Brake Resistor Considerations
ATTENTION: The drive does not offer protection for externally mounted brake
resistors. A risk of fire exists if external braking resistors are not protected.
External resistor packages must be self-protected from over temperature or a
circuit equivalent to the one shown below must be supplied.
Figure 16 - External Brake Resistor Circuitry
42Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Using Input/Output Contactors
It is recommended that the auxiliary relay of the output contactor (when used) be
wired in series with Digital Input 6 and that Digital Input 6 be configured as a
hardware enable input. See Hardware Enable Circuitry on page 54
information.
ATTENTION: A contactor or other device that routinely disconnects and
reapplies the AC line to the drive to start and stop the motor can cause drive
hardware damage. The drive is designed to use control input signals that start
and stop the motor. If an input device is used occasionally, an auxiliary contact
on that device should also be wired to a digital input programmed as a “Enable”
function. The input device must not exceed one operation per minute or drive
damage will occur.
ATTENTION: The drive start/stop control circuitry includes solid state
components. If hazards due to accidental contact with moving machinery or
unintentional flow of liquid, gas or solids exist, an additional hard-wired stop
circuit may be required to remove the AC line to the drive. When the AC line is
removed, any inherent regenerative braking effect that might be present is lost
- the motor coasts to a stop. An auxiliary braking method may be required.
for more
ATTENTION: To guard against drive damage when using output contactors, the
following information must be read and understood. One or more output
contactors can be installed between the drive and motor(s) for the purpose of
disconnecting or isolating certain motors/loads. If a contactor is opened while
the drive is operating, power is removed from the respective motor, but the
drive continues to produce voltage at the output terminals. In addition,
reconnecting a motor to an active drive (by closing the contactor) could produce
excessive current that may cause the drive to fault. If any of these conditions are
determined to be undesirable or unsafe, wire an auxiliary contact on the output
contactor to a drive digital input programmed as “Enable.” This causes the drive
to execute a coast-to-stop (cease output) whenever an output contactor is
opened.
Using PowerFlex 700S Drives with Regenerative Power Units
If a Regenerative unit (that is, 1336 REGEN) is used as a bus supply or a brake,
the common mode capacitors should be disconnected (see Power Jumpers on
page 27
for details).
Rockwell Automation Publication 20D-IN024C-EN-P - July 201343
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Regenerative Unit to Drive Connections
Regenerative Brake Mode
Frame(s) Terminals
1336 REGENPowerFlex 700S
1…4DC+ & DC-BR1 & DC5 & 6DC+ & DC-DC+ & DC-
Regenerative Bus Supply Mode
Frame(s) Terminals
1336 REGENPowerFlex 700S
1…4DC+ & DC-DC+ & DC5 & 6DC+ & DC-DC+ & DC- of Common
Bus Drives
Electronic Motor Overload Protection
Provides class 10 motor overload protection according to NEC article 430 and
motor over-temperature protection according to NEC article 430.126 (A)(2).
UL 508C File E59272.
Short Circuit Current Rating
Maximum short circuit current rating: 200,000 Amps symmetrical.
Branch Circuit Short Circuit Protection
Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the
National Electrical Code and any additional local codes, or the equivalent.
Fusing and Circuit Breakers
The tables on the following pages provide recommended AC line input and
circuit breaker information. See Fusing and Circuit Breakers below for UL and
IEC requirements. Sizes listed are the recommended sizes based on 40 °C (104
°F) and the U.S. NEC. Other country, state, or local codes can require different
ratings. Tables with DC link recommendations for DC input drives are also
provided.
Fusing
The recommend types are listed below. If available current ratings do not match
those listed in the tables provided, chose the next higher rating.
• IEC – BS88 (British Standard) Parts 1 & 2, EN60269-1, Parts 1 & 2
type gG or equivalent should be used.
• UL – UL Class CC, T, RK1, J, or L should be used.
(1)
,
44Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Circuit Breakers
The “non-” listings in the following tables include inverse time circuit breakers,
instantaneous trip circuit breakers (motor circuit protectors) and 140M selfprotected combination motor controllers. If one of these is chosen as the desired
protection method, the following requirements apply:
• IEC – Both types of circuit breakers and 140M self-protected
combination motor controllers are acceptable for IEC installations.
• UL - Only inverse time circuit breakers and the specified 140M selfprotected combination motor controllers are acceptable for UL
installations.
(1) Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC,
BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH.
Table 12 - 208 Volt AC Input Frames 1…6 Drive Protection Devices
(1) Minimum protection device size is the lowest rated device that supplies maximum protection with out nuisance tripping.
(2) Maximum protection device size is the hig hest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Maximum allowable rating by US NEC. Exac t size must be chosen for each installation.
(5) Motor Circuit Protector - instantaneo us trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(6) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground
systems.
(8) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Applic ation Ratings
(9) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in t his column. Application specific thermal
considerations may require a larger enclosure.
kW RatingInput
NDHDAmps kVAMin
Frame
–2284.730.5125200125350300150––––
–3011335.3125225125400300150––––
–3714150.9200300200500450250––––
–4516760.1225350225500500250––––
–5519971.7225450225600600400––––
Ratings
Dual Element
Time Delay Fuse
(1)
Max
Non-Time Delay
Fuse
(2)
Min
Circuit
Breaker
(1)
(2)
Max
Max
Motor
(3)
Circuit
Protector
(4)
Max
(5)
140M Motor Starter with Adjustab le Current Range
(5)
Availa ble Cat. No. s
.
(8)
Minimum Enclosure
Volu me (i n.3)
(6)(7)
(9)
Rockwell Automation Publication 20D-IN024C-EN-P - July 201345
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Table 13 - 240 Volt AC Input Frames 1…6 Drive Protection Devices
(1) Minimum protection device size is the lowest rated device that supplies maximum protection with out nuisance tripping.
(2) Maximum protection device size is the hig hest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Maximum allowable rating by US NEC. Exac t size must be chosen for each installation.
(5) Motor Circuit Protector - instantaneo us trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(6) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground
systems.
(8) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Applic ation Ratings
(9) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in t his column. Application specific thermal
considerations may require a larger enclosure.
.
(6)(7)
3)(9)
Table 14 - 400 Volt AC Input Frames 1…6 Drive Protection Devices
46Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
kW RatingInput
Ratings
NDHDAmps kVAMin
Frame
Dual Element
Time Delay Fuse
(3)
Max
Non-Time Delay
Fuse
(4)
Min
Circuit
Breaker
(5)
(6)
Max
Max
Motor
(5)
Circuit
Protector
(6)
Max
(8)
140M Motor Starter with Adjustable Current Range
(7)
Availa ble Cat. No. s
(10)
(8)(9)
Minimum Enclosure
3)(11)
Volu me ( in.
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Drive Cat.
No.
20DC085
kW RatingInput
Ratings
NDHDAmps kVAMin
Dual Element
Time Delay Fuse
(3)
Max
Non-Time Delay
Fuse
(4)
Min
Circuit
Breaker
(5)
(6)
Max
Max
Motor
(5)
Circuit
Protector
(6)
Max
(8)
140M Motor Starter with Adjustable Current Range
(7)
Availa ble Cat. No. s
(10)
Frame
(1)
4 45–81.456.4 110200110300300150 – – – –
Minimum Enclosure
Volu me ( in.
(8)(9)
3)(11)
–3768.947.8 9017590275300100 – – – –
20DC1055 55–100.5 69.6125225125400300150 – – – –
–4581.456.4 110175110300300150 – – – –
20DC1255 55–121.1 83.9 150275150500375250 – – – –
–4510163.7125200125375375150 – – – –
20DC1405 75–135.6 94200300200400400250 – – – –
–5512169.6150225150300300150 – – – –
20DC1706 90–164.6 114250375250600500250 – – – –
–7513694200300200550400250 – – – –
(2)
20DC205
6 110–198.5 13825045 0250600600400 – – – –
–901641142503752 50600500250 – – – –
20DC2606 132 –254.7 166350550350750750400 – – – –
–110199138250450250600600400 – – – –
(1) 20DC085 current rating is limited to 45 degrees C ambi ent.
(2) 20DC205 current rating is limited to 40 degrees C ambi ent.
(3) Minimum protection device size is the lowest rated device that supplies maximum protection with out nuisance tripping.
(4) Maximum protection device size is the hig hest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(5) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(6) Maximum allowable rating by US NEC. Exac t size must be chosen for each installation.
(7) Motor Circuit Protector - instantaneo us trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(8) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(9) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground
systems.
(10) The AIC ratings of the Bull etin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings
(11) When usin g a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal
considerations may require a larger enclosure.
.
Table 15 - 480 Volt AC Input Frames 1…6 Drive Protection Devices
(1) Minimum protecti on device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Maximum allowable rating by U S NEC. Exact size must be chosen for each installation.
(5) Motor Circuit Protector - inst antaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(6) Bul letin 140M with adjustable current range should have the current trip set to the minimu m range that the device will not trip.
(7) Manua l Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(8) The AIC ratin gs of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings.
(9) When using a Manu al Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger
enclosure.
Table 16 - 600 Volt AC Input Frames 1…6 Drive Protection Devices
(1) Minimum protecti on device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Maximum allowable rating by U S NEC. Exact size must be chosen for each installation.
(5) Motor Circuit Protector - inst antaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(6) Bul letin 140M with adjustable current range should have the current trip set to the minimu m range that the device will not trip.
(7) Manua l Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(8) The AIC ratin gs of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings.
(9) When using a Manu al Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger
enclosure.
(6)(7)
Minimum Enclosure
Volu me (i n.3)
(9)
48Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Table 17 - 690 Volt AC Input Frames 5 & 6 Drive Protection Devices
Drive
Cat. No.
20DF052545–46.959.56011060175175–
20DF060555–57.768.98012580225225–
20DF082575–79.094.4100200100375375–
20DF098590–94.7113125200125375375–
20DF1196110–11513815025015 0400––
20DF1426132–139165.9175300175450––
(1) Minimum protection device size is the lowest rated device that supplies maximum protection with out nuisance tripping.
(2) Maximum protection device size is the hig hest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Maximum allowable rating by US NEC. Exac t size must be chosen for each installation.
(5) Motor Circuit Protector - instantaneo us trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
kW RatingInput RatingsDual Elem ent Time Delay
NDHDAmpskVAMin
Frame
–37.540.148.0509050150150–
–4546.959.56011060175175–
–5557.768.98012580225225–
–7579.094.4100200100375375–
–9092.911312520012 5375––
–110115137150250150400––
Fuse
(1)
Max
(2)
Non-Time Delay FuseCircuit Breaker
Min
(2)
Max
(3)
Max
(3)
Motor Circuit Protector
(4)
Max
(5)
Table 18 - 325 Volt DC Input Frames 1…6 Drive Protection Devices
Drive Cat. No.Frame HP RatingDC Input RatingsFuseNon-Time Delay
(1) Catalog number corresponds to output amps for these drives. Drive must be programmed to lower voltage to obtain higher currents
shown at right.
(2) Catalog number corresponds to drives with precharge only.
(3) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Ar t 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Ferraz Shawmut Type HSJ, all sizes. For any other devices, pleas e contact the factor y.
(1) Also applies to “P” voltage class. s must be applied in the (+) leg and (-) leg of the DC Common Bus.
(2) The power source to Common Bus inverters must be derived from AC voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.
Table 20 - 650 Volt DC Input Frames 1…6 Drive Protection Devices
Drive Cat. No.Frame HP RatingDC Input RatingsFuseNon-Time Delay
50Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Drive Cat. No.Frame HP RatingDC Input RatingsFuseNon-Time Delay
NDHDAmps
6150–198400HSJ400
–125171.2400HSJ400
6200–272400HSJ400
20DJ180
20DJ248
(1)
(1)
(2)
–150198400HSJ400
(1) Also applies to “R” voltage class. s must be applied in the (+) leg and (-) leg of the DC Common Bus.
(2) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Ar t 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.
Table 21 - 810 Volt DC Input Frames 1…6 Drive Protection Devices
Drive Cat. No.Frame HP Rating DC Input RatingsFuseNon-Time Delay
(1) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Ar t 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.
(1) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Ar t 430-18 (NEC).
Battery supplies or MG sets are not included. The following devices were validated to break current of the derived power DC Bus:
Disconnects: Allen-Bradley Bulletin No. 1494, 30 to 400 A; Bulletin No. 194, 30 to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. s:
Bussmann Type JKS, all sizes; Type 170M, Case Sizes 1, 2 and 3, or Ferraz Shawmut Type HSJ, all sizes. For any other devices, please
contact the factory.
Rockwell Automation Publication 20D-IN024C-EN-P - July 201351
(1)
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
IMPORTANT
Step 5: Control and I/O
Wiring
Important points to remember about control and I/O wiring:
• Always use copper wire.
• Wire with an insulation rating of 600V or greater is recommended.
• Control and signal wires should be separated from power wires by at least
0.3 meters (1 foot).
• For CE compliance, 115 volt digital input wiring must be shielded or must
not exceed 30 meters (98 feet) in length.
• To maintain electrical safety for all user-accessible low voltage circuits
(SELV and PELV circuits), I/O terminals designated for 24V or lower
voltage must not be connected to a circuit of higher voltage or a circuit
that is not adequately insulated from dangerous voltages with double or
reinforced insulation within other connected equipment or wiring.
• To provide electrical safety for user-accessible low voltage I/O circuits that
are referenced to earth (PELV circuits) and that may be touched
simultaneously, care should be taken to provide a common earth reference
for all equipment connected to the drive.
I/O terminals labeled “(–)” or “Common” are not referenced to earth ground
and are designed to greatly reduce common mode interference. Grounding
these terminals can cause signal noise.
ATT EN TI ON : Hazard of personal injury or equipment damage exists when
using bipolar input sources. Noise and drift in sensitive input circuits can cause
unpredictable changes in motor speed and direction. Use speed command
parameters to help reduce input source sensitivity.
Control and I/O Wiring Recommendations
TypeWire Type(s)DescriptionMin Insulation Rating
(1) (1)(2)
Signal
Digital I/O
Safety Inputs
Homing Inputs
(1) If the wires are short and contained within a cabinet that has no sensitive circuits, the use of shielded wire may not be necessar y, but is always recommende d.
(2) I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are designed to greatly reduce common mode interference. Grounding these terminals can cause signal noise.
Standard Analog I/O–0.750 mm2(18AWG), twisted pair, 100% shield with drain.300V,
Remote Pot–0.750 mm
Encoder/
Pulse I/O
< 30 m (100 ft)
Encoder/
Pulse I/O
30 to 152 m
(100 to 500 ft)
Encoder/
Pulse I/O
152 to 259 m
(500 to 850 ft)
Un-shielded–Per US NEC or applicable national or local code.300V,
52Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Main Control Board DIP Switch Settings
AT TE NT IO N: The DIP switches for Digital Inputs 4…6 are set to 24V DC at the
factory. If you are running a 115V AC input application, the switches must be set
as indicated below before applying power to the drive or damage to the main
control board may occur.
Table 23 - Switch and Jumper Settings
FunctionDefaultSwitchOpenClosedNotes
HW Enable Jumper (P22) pins 2-4
Gate Enable Jumper
(P13)
Analog Input 1VoltageS5-2VoltageCurrentChange with Power Off
Analog Input 2VoltageS5-1Voltage CurrentChange with Power Off
Digital Inputs 4-6
Volt age
Digital Input 1 Voltage24V DCS3-124V DC12V DCChange with Power Off
Digital Input 2 Voltage24V DCS3-224V DC12V DCChange with Power Off
Encoder Supply Voltage 12V DCS2-412V DC5V DCChange with Power Off
Encoder Signal A Voltage 12V DCS2-112V DC5V DC
Encoder Signal B Voltage 12V DCS2-212V DC5V DC
Encoder Signal Z Voltage 12V DCS2-312V DC5V DC
FunctionDownSwitchUpCenterNotes
DriveLogix ProcessorRUNS1ProgRemoteProcessor Mode
HW Enbl
Jumper on
pins 15-16
24V DCS4-1,
SHUNT
Jumper
SHUNT
Jumper
S4-2
pins 2-4
HW Enbl
No JmprJumper on
115V AC24V DCChange with Power Off
pins 1-3
No Enbl
pins 15-16
No Jmpr = HW Enbl
See Hard ware Enable Circuitry on
page 54
for configuration.
No Jmpr = Gate disable or SafeOff/Second Encoder board is
(1)
present
Typically, set all switches the same
(1) Refer to publication 20D-UM007, DriveGuard® Safe-Off Option for PowerFlex® 700S Phase II AC Drives and PowerFlex 700L Liquid-
Cooled AC Drives, for more information on the Safe-Off Option board, or publication, 20D-IN009
Encoder Option Card for PowerFlex® 700S Drives with Phase II Control, for more information on the Second Encoder Option board.
Installation Instructions - Second
Please note there are two separate values for an encoder.
Rockwell Automation Publication 20D-IN024C-EN-P - July 201353
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
12
FRONT
TOP VIEW
SIDE VIEW
Up = Open = Off
Down = Closed = On
SWITCH S5
FRONT
TOP VIEW
SIDE VIEW
Up = Open = Off
Down = Closed = On
SWITCH S2
12
3 4
12
FRONT
TOP VIEW
SIDE VIEW
Up = Open = Off
Down = Closed = On
SWITCH S3
12
FRONT
TOP VIEW
SIDE VIEW
Up = Open = Off
Down = Closed = On
SWITCH S4
= HW Enable
= No HW Enable
JUMPER P22
12
34
12
34
16
15
JUMPER P13
= Gate Enabled
16
15
= Gate Disabled
SWITCH S1
RUNPROGREMOTE
UpDownCenter
Figure 17 - Main Control Board Dip Switches
54Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
Hardware Enable Circuitry
By default, digital input 6 is configured for hardware enable input. This is for
applications requiring the drive to be disabled without software interpretation.
With the “HW Enable Jumper (Shunt)” on the pins closest to the circuit board
(2-4), digital input 6 is configured as a “dedicated” hardware enable. If this
configuration is not required, the “HW Enable Jumper (Shunt)” may be moved
to the out board pins (1-3), making digital input 6 user programmable via
parameter 830 [Dig In6 Sel]. See Figure 17
on page 54.
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
IMPORTANT
TB1 Terminals
TB2 Terminals
I/O Terminals
Terminal blocks TB1 and TB2 contain connection points for all inputs, outputs
and standard encoder connections. When installed, both terminal blocks reside
on the main control board. These components are provided with the drive but are
not factory installed.
Make the terminal block wire connections.
For NEMA/UL Type 1 applications, all wiring must be routed through the
conduit plate on the drive. Route any wires from the expanded cassette to the
base cassette and out of the drive.
When wiring is complete, install the connector plug.
Table 24 - Control & Encoder Terminal Block Specifications
NameDescriptionWires Size Range
Maximum MinimumMaximumRecommended
I/O Terminal BlocksSignal & Encoder power
connections
1.5 mm
(16 AWG)
2
(1)
0.14 mm
(28 AWG)
2
Tor que
0.25 N•m
(2.2 lb•in)
0.22 N•m
(1.9 lb•in)
(1) Maximum/minimum sizes the terminal block accepts - these are not recommendations.
Figure 18 - Main Control Board I/O Terminal Locations
Rockwell Automation Publication 20D-IN024C-EN-P - July 201355
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
1
2
3
4
5
6
7
8
9
12
10
11
13
14
15
16
17
18
19
20
21
22
23
24
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Table 25 - TB1 Terminals
Terminal SignalFactor y
Default
1Analog Input 1 Comm.(Volt)Bipolar, differential input, ±10V, 0…20 mA, 13 bit + sign
2Analog Input 1 (+/-)800
3ShieldNAAnalog Input Shield
4Analog Input 2 Comm.(Volt)Bipolar, differential input, ±10V, 0…20 mA, 13 bit + sign
5Analog Input 2 (+/-)806
6Analog Input 3 [NTC-] Comm.(Volt)Differential input, 0…10V, 10 bit (for motor control mode FOC2, this is the
7Analog Input 3 [NTC+]812
8ShieldNAAnalog Output Shield
9Analog Output 1 (-)(Volt)Bipolar, differential output, ±10V, 0…20 mA, 11 bit + sign
10Analog Output 1 (+)
11Analog Output 2 (-)(Volt)839, 840
12Analog Output 2 (+)
13+10V ReferenceNARating: 20 mA maximum load (Recommend 5 Ω pot)
14Reference CommonNA
15-10V ReferenceNA
16Encoder ANANormal current draw per channel: 20 mA230-233
17Encoder A (Not)NA
18Encoder BNA
19Encoder B (Not)NA
20Encoder ZNA
21Encoder Z (Not)NA
22Encoder Reference (+)NA12 or 5V DC power supply for primary encoder interface
23Encoder Reference (-)NA
24Encoder ShieldNAConnection point for encoder shield
(1) The analog inputs are not isolated. However, the analog inputs can be connected in series when using current mode. Note that at 20 mA the voltage source must be capable of providing 10V DC at the
drive terminals for one drive - - 20V DC is required for two drives and 30V DC is required for three drives.
DescriptionRelated
Parameter(s)
20 kΩ impedance at Volt; 500 Ω impedance at mA
(1)
20 kΩ impedance at Volt; 500 Ω impedance at mA
temperature adaptation input).
832, 833
2 kΩ minimum load
Rating: 300 mA maximum
Table 26 - TB2 Terminals
Terminal SignalFactory
Default
124V DC Common (-)NADrive supplied 24V DC logic input power
224V DC Source (+)NA
3Digital Output 124V DC Open Collector (sinking logic)
4Digital Output 1/2 ComNACommon for Digital Output 1 & 2
5Digital Output 224V DC Open Collector (sinking logic)
6Relay Output 3 (NC)Relay contact output
7Relay Output 3 ComNA
8Relay Output 3 (NO)
9Digital Input 1-3 ComNACommon for Digital Inputs 1-3
10Digital Input 1High speed 12V or 24V DC
11Digital Input 2826
12Digital Input 3Load:15 mA at 24V DC sourcing827
13Digital Input 4-6 ComNACommon for Digital Inputs 4-6
14Digital Input 4Load: 10 mA at 24V DC sinking/sourcing
(1) Digital Inputs 1 and 2 are configured for 12V or 24V DC via DIP switches S3-1 and S3-2, respecti vely. 24V DC is the default setting.
56Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
15Digital Input 5829
16Digital Input 6HW
Enable
DescriptionRelated
Parameter (s)
Rating: 300 mA maximum load
816, 847
Rating: Internal Source = 150 mA max
External Source = 750 mA
851, 852
Rating: Internal Source = 150 mA max
External Source = 750 mA
856, 857
Rating: 115V AC or 24V DC = 2 A max
Inductive/Resistive
(1)
, sinking
825
Load:15 mA at 24V DC
828
Load: 7.5 mA at 115V AC
Note: The 115 VAC Digital Inputs can withstand 2 mA of leakage current
without turning on. If an output device has a leakage current greater than 2 mA
830
a burden resistor is requ ired. A 68.1 Ω resistor with a 0.5 watt rating should be
used to keep the 115 VAC output below 2 mA.
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
-Signal or Source Common
+Signal
Shield / Common
1
2
3
4
5
6
7
8
9
10
11
12
-
+
-
+
I/O Wiring Examples
Table 27 - TB1 Analog Input/Output and Encoder Wiring Examples
Supports 5V DC or 12V DC differential encoders
with internal power supply.
Used as primary closed loop feedback.
Internal SupplyUsing Encoder 0 as speed feedback:
13
14
15
16
17
18
19
20
21
22
23
24
Encoder
A
A-
B
B-
Z
Z-
+
-
Par 222 [Mtr Fdbk Sel Pri] = 0 “Encoder 0” (default)
Par 232 [Encoder0 PPR] = Pulses/Rev for installed encoder
External Supply
58Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
Table 28 - TB2 Digital Input/Output Wiring Examples
24V dc
Com
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
24V dc
Com
1
2
3
4
5
6
7
8
Input/OutputConnection Example
Digital Inputs used for enable and
precharge control.
Note: 24V DC supply - supports only on-board
digital inputs. Do not use for circuits outside the
drive.
Note: The factory default for all digital inputs is
24V DC.
To use 115V AC on digital inputs 4…6 see
Tab le 23
on page 53.
Note: Digital inputs 1…3 are always 12V DC or
24V DC.
Sourcing Digital Inputs - Internal Power SupplySourcing and Sinking Definitions
Com
1
24V dc
2
3
4
5
6
7
8
Sourcing Digital Outputs - Internal Power Supply
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
The digital inputs and digital outputs of the PowerFlex 700S AC drive
support Sourcing or Sinking configuration. Typically, digital inputs
are sourcing devices and digital outputs are sinking devices. The
following definitions apply throughout this section:
9
10
11
12
13
14
15
16
• Sourcing a Digital Input - The digital input common (return) is
connected to the power supply common. Applying a positive
voltage to the digital input causes it to activate (pull up).
• Sinking a Digital Input - The digital input common (return) is
connected to the power supply positive voltage. Applying 0V or
common to the digital input causes it to activate (pull down).
• Sourcing a Digital Output - The digital output common
(return) is connected to the power supply common. The device to
be controlled by the digital output is connect to the positive
voltage and the device common is connected to the digital
output.
Com
1
24V dc
2
3
4
5
6
7
8
• Sinking a Digital Output - The digital output common (return)
is connected to the power supply positive voltage. The digital
output is connect to the device to be controlled and the device
common is connected to the power supply common.
Note: Digital inputs 1…3 can only be configured as sourcing inputs.
Digital inputs 4…6 can be configured as sourcing or sinking inputs.
Sinking Digital Inputs - Internal Power Supply
Sinking Digital Output - Internal Power Supply
Rockwell Automation Publication 20D-IN024C-EN-P - July 201359
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
24V dc
Com
Run
Enable
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
24V dc
Com
Start
Enable
Stop
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
Input/OutputConnection Example
Digital Outputs used with 24V DC Relays -
Sourcing Digital Outputs • Sourcing a Digital Output - The digital output common
External Power Supply
Note: Digital Inputs 1-3 are always 12V or 24V
DC.
1
2
3
4
5
6
7
8
Sinking Digital Outputs
1
2
3
4
5
6
7
8
24V DCCommon
24V DCCommon
(return) is connected to the power supply common. The device to
be controlled by the digital output is connect to the positive
voltage and the device common is connected to the digital
output.
• Sinking a Digital Output - The digital output common (return)
is connected to the power supply positive voltage. The digital
output is connect to the device to be controlled and the device
common is connected to the power supply common.
Digital Inputs
24V DC
Digital Inputs
24V DC
Sourcing Digital Inputs - Internal Power Supply, 2-Wire Control Required Parameter Changes:
• Set Par 829 [Dig In5 Sel] to value 7 - “Run”.
• Par 153 [Control O ptions], b it 8 “3WireCont rol” is autom atically
set to “Off” (0) for 2-wire control.
• Set Par 168 [Normal Stop Mode] for the desired stopping mode:
0 = Ramp Stop
1 = CurLim Stop
2 = Coast Stop
Sourcing Digital Inputs- Internal Power Supply, 3-Wire• Set Par 829 [Dig In5 Sel] to value 14 - “Normal Stop”.
• Set Par 828 [Dig In4 Sel] to value 5 - “Start”.
• Par 153 [Control O ptions], b it 8 “3WireCont rol” is autom atically
set to “On” (1) for 3-wire control.
• Set Par 168 [Normal Stop Mode] for the desired stopping mode:
0 = Ramp Stop
1 = CurLim Stop
2 = Coast Stop
60Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
IMPORTANT
DriveLogix 5730 Controller Option
Refer to the DriveLogix 5730 Controller for PowerFlex 700S Drives with Phase
II Control User Manual, publication 20D-UM003
, for details on using and
configuring this option.
The DriveLogix controller option ships with the battery installed, but
disconnected. You must connect the battery while installing the drive.
DriveLogix5730 Controller Specifications
AT TE NT IO N: This product contains a 3V Lithium battery if the DriveLogix
Controller option board is installed. Perchlorate Material - special handling may
apply. See www.dtsc.ca.gov/hazardouswaste/perchlorate
CategorySpecific ation
Serial portRS-232, fully isolated
DF1, DH-485, ASCII
38.4 kilobit/s maximum
Optional embedded EtherNet/IP RJ-45 or 100BaseT
10/100 MB/s
Connectivity options
(these options require the Logix
Expansion Board and Expanded
Cassette)
User memory1.5 MB
Non-volatile memory1784-CF64 CompactFlash
Maximum number of I/O banks2
Maximum number of I/O modules16
Battery1769-BA
Serial cable1756-CP3 directly to controller
Compact I/O Cable20D-DL2-CR3
• NetLinx communication daughtercards
(ControlNet, EtherNet/IP, DeviceNet, Third Part y)
• Compact I/O connection
• CompactFlash (memory card)
(8 modules per bank or 4 max on either side of the power supply)
1747-CP3 directly to controller
20D-DL2-CL3
DriveGuard® Safe Torque Off with Second Encoder Option
Refer to the DriveGuard Safe Torque Off Option for PowerFlex® 700S Phase II
AC Drives and PowerFlex 700L Liquid-Cooled AC Drives User Manual,
publication 20D-UM007
board.
Refer to Appendix J “Instructions for ATEX Approved PowerFlex 700S Phase II
Drives in Group II Category (2) Applications with ATEX Approved Motors”, in
the PowerFlex 700S Drive with Phase II Control Programming Manual,
publication 20D-PM001
Rockwell Automation Publication 20D-IN024C-EN-P - July 201361
, for details on installing and configuring this option
, for details on ATEX approved applications.
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Second Encoder Feedback Option
Second Encoder Feedback Option Specifications
ConsiderationDescription
InputDual Channel Plus Marker, Isolated with differential transmitter Output (Line Drive)
Incremental, Dual Channel Quadrature type
Encoder Voltage Supply5V DC or 12V DC 320 mA per channel
5V DC requires an external power supply.
12 V DC minimum high state voltage of 7V DC, maximum low state voltage of 0.4V DC
Maximum Input Frequency400 kHz
Recommended Cables for the Second Encoder Feedback Option Card
Cable Type and LengthWire Type(s)Description
Encoder/Pulse I/O
Less 30.5 m (100 ft)
Encoder/Pulse I/O
30.5 m (100 ft) to 152.4 m (500
ft)
Encoder/Pulse I/O
152.4 m (500 ft) to 259.1 m (850
ft)
(1) Belden 9730 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9728 (or equivalent).
(2) Belden 8790 is 1 shielded pair.
(3) Belden 9892 is 3 individually shielded pairs (3 channel), 0.33 mm2 (22 AWG) plus 1 shielded pair 0.5 mm2 (20 AWG) for power.
(4) Belden 9773 is 3 individually shielded pairs (2 channel plus power). If 3 channel is required, use Belden 9774 (or equivalent).
Second Encoder Feedback Option Terminal Designations
Term. No. SignalDescription
1…4–Not connected.
Refer to DriveGuard® Safe Torque Off with Second
Encoder Option on page 61
5AQuadrature A input
6Not A
7BQuadrature B input
8Not B
9ZMarker Pulse
10Not Z
11PowerDC Power for encoder interface
12Common
13ShieldConnection point for encoder cable shield
.
2 (3)
62Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
OPEN
1
FRONT - TOP VIEW
SIDE VIEW
UP = OPEN = OFF
DOWN = CLOSED= ON
S1
2 3 4
Second Encoder Feedback Option Wiring Examples
Differential Encoder with Internal Supply
A
Not A
B
Not B
Z
Not Z
Powe r
Common
Differential Encoder with External Supply
A
Not A
B
Not B
Z
Not Z
Powe r
Common
P1Encoder
1
2
3
4
5
6
7
8
9
10
11
12
13
P1Encoder
1
2
3
4
5
6
7
8
9
10
11
12
13
N/C
N/C
N/C
N/C
A
Not A
B
Not B
Z
Not Z
Powe r
Common
Shield
N/C
N/C
N/C
N/C
A
Not A
B
Not B
Z
Not Z
Powe r
Common
Shield
Second Encoder Feedback Option DIP Switch Settings
Encoder Voltage Supply11.5V DC @ 130 mA
Hi-Resolution FeedbackSine/Cosine 1V P-P Offset 2.5
Maximum Cable Length90 m (295 ft)
Maximum Frequency
(Encoder Speed)
RS-485 InterfaceThe Hi-Resolution Feedback Option card obtains the following information via the
12.5 μs/cycle
(4687.5 rpm for encoders with 1024 sine cycles per revolution)
(9375 rpm for encoders with 512 sine cycles per revolution)
Hiperface RS-485 interface shortly after powerup:
• Address
• Command Number
• Mode
• Number of turns
• Number of Sine/Cos cycles
• Checksum
Encoders Supported by the Stegmann Hi-Resolution Encoder Feedback Option
Card
Please note that encoders must be ordered as “Single Ended” so that the RS485 channel has the proper termination network installed at the factory.
Hi-Resolution Encoder Model ResolutionComment
Stegmann SINCOS SCS-60, SCS-70,
SCM-60, and SCM-70
Stegmann SINCOS SCS-KIT-101
and SCM-KIT-101
Stegmann SINCOS SRS-50, SRS-60,
SRM-50, and SRM-60
Stegmann SINCOS SRS/SRM 251024 sine cycles per revolutionSRS25 and SRM25 have built-in mechanical
Stegmann SINCOS SRS6601024 sine cycles per revolutionHollow-shaft up to 14 mm diameter
Stegmann SINCOS SHS-170512 sine cycles per revolution. While the software supports this encoder,
Allen-Bradley 842HR1024 sine cycles per revolutionHas built-in mechanical turns counter. IP65
Hiperface® SINCOS®, SINCODER® and LINCODER® are registered trademarks of Stegmann Inc.
512 sine cycles per revolution.SCM-60 and SCM-70 have built-in
mechanical turns counter.
1024 sine cycles per revolution. SCM-60 and SCM-70 have built-in
mechanical turns counter.
1024 sine cycles per revolution.SRM-50 and SRM-60 have built-in
the SHS-170 draws excessive current and
should only be used with an external power
supply.
Protection Class. Size 25 square flange
mounting.
64Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
TIP
12 3 4 5 6 7 8 9 10 11 12
Wiring the Stegmann Hi-Resolution Feedback Option Card to an Encoder
Terminal block P1 contains connection points for a Stegmann Hiperface®
encoder. This terminal block resides on the Hi-Resolution Encoder Feedback
Option card.
Remember to route wires through the sliding access panel at the bottom of the
control assembly.
12POWER COMMONPower supply for encoder interface.
11POWER
10REFSINNegative Sine signal.
9+SINPositive Sine signal.
8REFCOSNegative Cosine signal.
7+COSPositive Cosine signal.
6SHIELDConnection point for encoder cable
5SHIELD
4N/CNot connected.
3N/C
2DATA+ (RS 485)Positive DH485 terminal.
1DATA- (RS 485)Negative DH485 terminal.
shield.
Rockwell Automation Publication 20D-IN024C-EN-P - July 201365
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
+SIN
REFSIN
+COS
REFCOS
DATA+ (RS-485)
DATA- (RS 485)
POWER
COMMON
TS+
TS-
A
B
C
D
E
F
N
P
R
S
BK
WH/BK
RD
WH/RD
GN
WH/GN
OR
WH/GY
BK
WH/BK
RD
WH/RD
GN
WH/GN
OR
WH/GY
12
11
10
9
8
7
6
5
4
3
2
1
POWER COMMON
POWER
N/C
N/C
+SIN
REFSIN
+COS
REFCOS
SHIELD
SHIELD
DATA+ (RS 485)
DATA- (RS 485)
Hi-Res Feedback Option Board
ENCODER
Recommended Cables and Wiring Diagrams for the Stegmann Hi-Resolution
Feedback Option Card
If you are using this motor and feedback device:Use this cable:See this wiring diagram:
Allen-Bradley MPL-A/B3xx, -A/B4xx, -A/B45xx, -A/B5xx, and -A/B6xx motors
with embedded Stegmann rotary encoder
Allen-Bradley MPL-A/B3xx, -A/B4xx, -A/B45xx, -A/B5xx, and -A/B6xx motors
with embedded Stegmann rotary encoder
HPK-Series motors with embedded Stegmann rotary encoderAllen-Bradley 2090-XXNFMF-SXXFigure 20
Allen-Bradley 1326AB-BXXXX-21ML and -21MKXL motors with embedded
Stegmann rotary encoder
Allen-Bradley 1326AB-BXXXX-M2L, -M2KXL, -S2L and -S2KXL motors with
embedded Stegmann rotary encoder
Allen-Bradley MPL-A5xx and all MPL-Bxxx motors with embedded Stegmann
rotary encoder
Allen-Bradley 1326AB-BXXXX-M2L, -M2KXL, -S2L and -S2KXL motors with
embedded Stegmann rotary encoder
Allen-Bradley MPL-A5xx and all MPL-Bxxx motors with embedded Stegmann
rotary encoder
Allen-Bradley MPL-A3xx - MPL-A45xx and all MPG series motors with
embedded Stegmann rotary encoder
Allen-Bradley MPL-A3xx - MPL-A45xx and all MPG series motors with
embedded Stegmann rotary encoder
Any other motor with external Stegmann SHS-170 rotary encoderStegmann shielded twisted-pair cable with 12-pin DIN style connectorFigure 26 on page 69
Any other motor with external Stegmann SCS-60, SCS-70, SCM-60 or SCM-70,
+SIN
REFSIN
+COS
REFCOS
DATA+ (RS-485)
DATA- (RS 485)
POWER
COMMON
TS+
TS-
A
B
C
D
E
F
N
P
R
S
BK
WH/BK
RD
WH/RD
GN
WH/GN
OR
WH/GY
BK
WH/BK
RD
WH/RD
GN
WH/GN
OR
WH/GY
12
11
10
9
8
7
6
5
4
3
2
1
POWER COMMON
POWER
N/C
N/C
+SIN
REFSIN
+COS
REFCOS
SHIELD
SHIELD
DATA+ (RS 485)
DATA- (RS 485)
Hi-Res Feedback Option Board
ENCODER
+SIN
REFSIN
+COS
REFCOS
DATA+ (RS-485)
DATA- (RS 485)
POWER
COMMON
TS+
TS-
A
B
C
D
E
F
N
P
R
S
BK
BK/WH
RD
WH/RD
GN
WH/GN
OR
WH/OR
BU
WH/BU
BK
BK/WH
RD
WH/RD
GN
WH/GN
OR
WH/OR
BU
WH/BU
12
11
10
9
8
7
6
5
4
3
2
1
POWER COMMON
POWER
N/C
N/C
+SIN
REFSIN
+COS
REFCOS
SHIELD
SHIELD
DATA+ (RS 485)
DATA- (RS 485)
Hi-Res Feedback Option Board
ENCODER
Figure 20 - HPK-Series motors with 2090-XXNFMF-SXX cable
Note: Thermal switch cannot be accessed by using 2090-XXNFMF-SXX cable.
Figure 21 - 1326AB-BXXXX-21ML, and -21MKXL motors with a 1326-CECU-XXL-XXX cable
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
ENCODERHi-Res Feedback Option Board
POWER
A
POWER COMMON
B
REFSIN
C
+SIN
D
REFCOS
E
+COS
F
DATA+ (RS-485)
G
DATA- (RS-485)
H
SHIELD
I
OVERALL SHIELD
J
POWER COMMON
POWER
REFSIN
+SIN
REFCOS
+COS
SHIELD
SHIELD
N/C
N/C
DATA+ (RS 485)
DATA- (RS 485)
12
11
10
WH
BK
BK
9
8
7
6
5
4
3
2
1
RD
BK
BU
BK
GN
BK
WH
BK
RD
BK
BU
BK
GN
Figure 22 - MPL-A5xx and all MPL-Bxxx motors or 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motors with 2090-CDNFDMP-SXX cable
Rockwell Automation Publication 20D-IN024C-EN-P - July 201367
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
+SIN
REFSIN
+COS
REFCOS
DATA+ (RS-485)
DATA- (RS 485)
POWER
COMMON
TS+
TS-
A
B
C
D
E
F
N
P
R
S
BK
WH/BK
RD
WH/RD
GN
WH/GN
OR
WH/GY
BK
WH/BK
RD
WH/RD
GN
WH/GN
OR
WH/GY
12
11
10
9
8
7
6
5
4
3
2
1
POWER COMMON
POWER
N/C
N/C
+SIN
REFSIN
+COS
REFCOS
SHIELD
SHIELD
DATA+ (RS 485)
DATA- (RS 485)
Hi-Res Feedback Option Board
ENCODER
+SIN
REFSIN
+COS
REFCOS
DATA+ (RS-485)
DATA- (RS 485)
POWER
COMMON
TS+
TS-
A
B
C
D
E
F
K
L
R
S
BK
BK/WH
RD
WH/RD
GN
WH/GN
GY
WH/GY
BK
BK/WH
RD
WH/RD
GN
WH/GN
GY
WH/GY
12
11
10
9
8
7
6
5
4
3
2
1
POWER COMMON
POWER
N/C
N/C
+SIN
REFSIN
+COS
REFCOS
SHIELD
SHIELD
DATA+ (RS 485)
DATA- (RS 485)
Hi-Res Feedback Option Board
ENCODER
+SIN
REFSIN
+COS
REFCOS
DATA+ (RS-485)
DATA- (RS 485)
POWER
COMMON
TS+
TS-
A
B
C
D
E
F
K
L
R
S
BK
BK/WH
RD
WH/RD
GN
WH/GN
GY
WH/GY
BU
WH/BU
BK
BK/WH
RD
WH/RD
GN
WH/GN
GY
WH/GY
BU
WH/BU
12
11
10
9
8
7
6
5
4
3
2
1
POWER COMMON
POWER
N/C
N/C
+SIN
REFSIN
+COS
REFCOS
SHIELD
SHIELD
DATA+ (RS 485)
DATA- (RS 485)
Hi-Res Feedback Option Board
ENCODER
Stegmann Hi-Resolution Feedback Option Card Connection Examples
Figure 23 - MPL-A5xx and all MPL-Bxxx Motor or 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motor with 2090-XXNFMP-SXX cable
Note: Thermal switch cannot be accessed by using 2090-XXNFMP-SXX cable.
Figure 24 - MPL-A3xx - MPL-A45xx and all MPG series motors with 2090-XXNFMP-SXX cable
Note: Thermal switch cannot be accessed by using 2090-XXNFMP-SXX cable.
Figure 25 - MPL-A3xx - MPL-A45xx and all MPG series motors with 2090-UXNFDMP-SXX cable
68Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
Stegmann Hi-Resolution Feedback Option Card Connection Examples
Figure 26 - Stegmann shielded twisted-pair cable with 12-pin DIN style connector
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
POWER COMMON
POWER
REFSIN
+SIN
REFCOS
+COS
SHIELD
SHIELD
N/C
N/C
DATA+ (RS 485)
DATA- (RS 485)
Hi-Res Feedback Option Board
12
11
10
9
8
7
6
5
4
3
2
1
BU
RD
BN
WH
BK
PK
GY
GN
Figure 27 - Stegmann shielded twisted-pair cable with 10-pin MS style connector
70Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Allen-Bradley servo motors may be ordered with factory installed resolvers. The
list of factory installed resolvers below are supported by the 700S Resolver
Feedback Option card.
Motor / Resolver TypeCompatible Parameter 277
1326 AB 230V Primary ResolverNoNot SupportedReceiver type resolver - not supported
1326 AB 460V Primary ResolverYes9 - 1326Ax 460vTransmitter type resolver - supported
1326 AB 460V Secondary ResolverYes13 - ReservedSecondary resolver is geared to motor -
1326AD 230V Rare Earth Primary
Resolver
1326AH 460V Explosion Proof Motor
Primary Resolver
1326AH 460V Explosion Proof Motor
Secondary Resolver
NoNot SupportedReceiver type resolver - not supported
Yes9 - 1326Ax 460vTransmitter type resolver - supported
YesN/ASecondary resolver is geared to motor -
Yes9 - 1326Ax 460vTransmitter type resolver - supported
[Reslvr0 Type Sel]
Configuratio n
Notes
not intended for motor speed / position
feedback
Transmitter type resolver - supported
not intended for motor speed / position
feedback
Transmitter type resolver - supported
Recommended Cable for the Resolver Feedback Card
Rockwell Automation strongly recommends the use of Reliance Electric 417900207CG or Belden 9730 cable for installation, or an equivalent cable that meets
these specifications:
• Three twisted pairs, 80° C, 300V
• Chrome FPR jacket, plenum rated
• Conductor size: 18 AWG
• Twists per inch: 2 or 3 twists per inch of wire lay per pair
• Capacitance per pair: not to exceed 30 pF per foot +/- 0.3 pF as read on a
GEN_RAD model 1658 RLC Digibridge or equivalent
• Capacitance difference pair-to-pair: not to exceed 0.6 pF per foot as read
on a GEN_RAD Model 1658 RLC Digibridge or equivalent
• Resistance per 1000 feet: 17.15Ω +/- 10%
• Inductance per 1000 feet: 0.13 mH +/- 10% as read on a GEN_RAD
model 1658 RLC Digibridge or equivalent
• Insulation thickness: 0.008 in.
• Conductor stranding 16/30
• Jacket thickness: 0.018 in.
Rockwell Automation Publication 20D-IN024C-EN-P - July 201371
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
REF HIGH 8
SHIELD 7
REF LOW 6
SIN HIGH 5
SHIELD 4
SIN LOW 3
COS HIGH 2
COS LOW 1
REF
+-
SIN COS
+
+
-
-
-
+
-
+
-
+
-
+
+
-
-
+
REF HIGH 8
SHIELD 7
REF LOW 6
SIN HIGH 5
SHIELD 4
SIN LOW 3
COS HIGH 2
COS LOW 1
REF
+-
SIN COS
+
+
-
-
-
+
-
+
-
+
+
-
-
+
-
+
Resolver Feedback Option Terminal Designations
TerminalSignalDescription
1COS LOWNegative Cosine signal
2COS HIGHPositive Cosine signal
123 45 6 78
3SIN LOWNegative Sine signal
4SHIELDConnection point for resolver cable shield
5SIN HIGHPositive Sine signal
6REF LOWNegative Reference signal
7SHIELDConnection point for resolver cable shield
8REF HIGHPositive Reference signal
Resolver Feedback Option Connection Examples
Resolver Interface - Clockwise Rotation = Count Up
REF HIGH 8
SHIELD 7
REF LOW 6
SIN HIGH 5
SHIELD 4
SIN LOW 3
COS HIGH 2
COS LOW 1
+
-
+
-
+
-
+
-
+
-
+
-
+
REF
SIN COS
-
Resolver Interface - Clockwise Rotation = Count Down (Reverse Polarity of Sine or Cosine Signals)
+-
-
+
72Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
1543287691312111016151417
Multi-Device Interface (MDI) Feedback Option
MDI Option Specifications
ConsiderationDescription
Rotary Encoder Voltage Supply11.5V DC @ 130 mA
Rotary Encoder Hi-Resolution FeedbackSine/Cosine 1V P-P Offset 2.5
Rotary Encoder Maximum Cable Length90m (295 ft)
Linear Encoder Maximum Cable Length245m (800 ft)
Rotary Encoder RS-485 InterfaceThe MDI Option card obtains the following information via the
Hiperface RS-485 interface shor tly after powerup:
• Address
• Command Number
• Mode
• Number of turns
• Number of Sine/Cos cycles
• Checksum
Registration InputsHigh speed 12…24V DC sinking digital inputs
MDI Feedback Option Terminal Designations
Terminal SignalDescription
1CHASSIS GNDConnection point for cable shields
2REGISTRATION-Negative terminal for Linear Sensor registration strobe
3REGISTRATION+Positive terminal for Linear Sensor registration strobe
4REGISTRATION-Negative terminal for Rotary Encoder registration strobe
5REGISTRATION+Positive terminal for Rotary Encoder registration strobe
6DATA-Negative SSI terminal for Linear Sensor inter face
7DATA+Positive SSI terminal for Linear Sensor interface
8CLOCK-Negative Clock terminal for Linear Sensor interface
9CLOCK+Positive Clock terminal for Linear Sensor interface
10DATA- (RS485)Negative DH485 terminal for Rotary Encoder interface
11DATA+ (RS485)Positive DH485 terminal for Rotary Encoder interface
12+COSPositive Cosine signal for Rotary Encoder interface
13REFCOSNegative Cosine signal for Rotar y Encoder interface
14+SINNegative Sine signal for Rotary Encoder interface
15REFSINPositive Sine signal for Rotary Encoder interface
16POWERPower supply for Rotary Encoder interface
17POWER COMMON
Linear Sensors Supported by the MDI Option
Temposonics® R-Series Linear sensors with MTS® part numbers ending in
1S2G1102 work with the MDI Option.
Part Number
Character
1Input Voltage = +24V DC
SSSI output
2Data Length = 24 Bits
GOutp ut Format = Gray Code
1Resolution = 0.005 mm
1Per formance = Standard
02Scale Orientation = Forward-acting Synchronized
Temposonics® is a registered trademark of MTS Systems Corporation.
Rockwell Automation Publication 20D-IN024C-EN-P - July 201373
Characteristic
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
IMPORTANT
Rotary Encoders Supported by the MDI Option
Please note that encoders must be ordered as “Single Ended” so that the RS485 channel has the proper termination network installed at the factory.
Rotary Encoder ModelResolutionComment
Stegmann SINCOS SCS-60, SCS-70,
SCM-60, and SCM-70
Stegmann SINCOS SCS-KIT-101
and SCM-KIT-101
Stegmann SINCOS SRS-50, SRS-60,
SRM-50, and SRM-60
Stegmann SINCOS SRS/SRM 251024 sine cycles per revolutionSRS25 and SRM25 have built-in mechanical
Stegmann SINCOS SRS6601024 sine cycles per revolutionHollow-shaft up to 14 mm diameter
Stegmann SINCOS SHS-170512 sine cycles per revolution. While the software supports this encoder,
Allen-Bradley 842HR1024 sine cycles per revolutionHas built-in mechanical turns counter. IP65
512 sine cycles per revolution.SCM-60 and SCM-70 have built-in
mechanical turns counter.
1024 sine cycles per revolution. SCM-60 and SCM-70 have built-in
mechanical turns counter.
1024 sine cycles per revolution.SRM-50 and SRM-60 have built-in
the SHS-170 draws excessive current and
should only be used with an external power
supply.
Protection Class. Size 25 square flange
mounting.
SINCOS®, SINCODER® and LINCODER® are registered trademarks of Stegmann Inc.
Recommended Cables and Wiring Diagrams for the MDI Option Card
If you are using this motor and feedback device:Use this cable:See this wiring diagram:
Allen-Bradley MPL-A/B3xx, -A/B4xx, -A/B45xx, -A/B5xx, and -A/B6xx
motors with embedded Stegmann rotary encoder
Allen-Bradley MPL-A/B3xx, -A/B4xx, -A/B45xx, -A/B5xx, and -A/B6xx
motors with embedded Stegmann rotary encoder
HPK-Series motors with embedded Stegmann rotary encoderAllen-Bradley 2090-XXNFMF-SXXFigure 3 1 on page 75
Temposonics R-Series Linear sensors with MTS part numbers ending in
1S2G1102
Allen-Bradley 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motors
with embedded Stegmann rotary encoder
Allen-Bradley MPL-A5xx and MPL-Bxxx motors motors with embedded
Stegmann rotary encoder
Allen-Bradley 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motors
with embedded Stegmann rotary encoder
Allen-Bradley MPL-A5xx and MPL-Bxxx motors motors with embedded
Stegmann rotary encoder
Allen-Bradley MPL-A3xx - MPL-A45xx and all MPG series motors with
embedded Stegmann rotary encoder
Allen-Bradley MPL-A3xx - MPL-A45xx and all MPG series motors with
embedded Stegmann rotary encoder
Any other motor with external Stegmann SHS-170 rotary encoderStegmann shielded twisted-pair cable with 12-pin DIN style connectorFig ure 37 on page 77
Any other motor with external Stegmann SCS-60, SCS-70, SCM-60 or
Any other motor with external Stegmann SCS-Kit 101 or SCK-Kit 101
rotar y encoder
Any other motor with external Stegmann SRS660 rotary encoderIs available only with pre-attached Stegmann shielded twisted-pair cable of
Allen-Bradley 2090-CFBM7E7-CDAFXXFigure 3 0
Allen-Bradley 2090-CFMB7DF-CDAFXXFigure 3 0 on page 75
Mating MTS molded extension cable for RG connector or integral P cableFigure 32 on page 75
Allen-Bradley 2090-CDNFDMP-SXXFigure 3 3 on page 76
Allen-Bradley 2090-CDNFDMP-SXXFigure 3 3 on page 76
Allen-Bradley 2090-XXNFMP-SXXFig ure 34 on page 76
Allen-Bradley 2090-XXNFMP-SXXFig ure 34 on page 76
Allen-Bradley 2090-XXNFMP-SXXFig ure 35 on page 76
Allen-Bradley 2090-UXNFDMP-SXXFigure 36 on page 77
Stegmann shielded twisted-pair cable with 10-pin MS style connectorFigure 3 8 on page 77
Stegmann shielded twisted-pair cable with 8-pin Berg style connectorFi gure 39 on page 78
various lengths
on page 75
Figure 4 0 on page 78
74Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
+SIN
REFSIN
+COS
REFCOS
DATA+ (RS-485)
DATA- (RS 485)
POWER
COMMON
TS+
TS-
A
B
C
D
E
F
N
P
R
S
BK
WH/BK
RD
WH/RD
GN
WH/GN
OR
WH/GY
BK
WH/BK
RD
WH/RD
GN
WH/GN
OR
WH/GY
12
11
10
9
8
7
6
5
4
3
2
1
POWER COMMON
POWER
N/C
N/C
+SIN
REFSIN
+COS
REFCOS
SHIELD
SHIELD
DATA+ (RS 485)
DATA- (RS 485)
Hi-Res Feedback Option Board
ENCODER
+SIN
REFSIN
+COS
REFCOS
DATA+ (RS-485)
DATA- (RS 485)
POWER
COMMON
TS+
TS-
A
B
C
D
E
F
N
P
R
S
BK
BK/WH
RD
WH/RD
GN
WH/GN
OR
WH/GY
BK
BK/WH
RD
WH/RD
GN
WH/GN
OR
WH/GY
ENCODER
12
11
10
9
8
7
6
5
4
3
2
1
Rotary Encoder +COS
Rotary Encoder DATA+ (RS485)
Rotary Encoder REGISTRATION-
Linear Sensor REGISTRATION+
Linear Sensor CLOCK+
Rotary Encoder DATA- (RS485)
Linear Sensor DATA+
Linear Sensor CLOCK-
Linear Sensor DATA-
Rotary Encoder REGISTRATION+
Linear Sensor REGISTRATION-
CHASSIS GND
MDI Feedback Option Board
17
16
15
14
13
Rotary Encoder POWER COMMON
Rotary Encoder POWER
Rotary Encoder +SIN
Rotary Encoder REFSIN
Rotary Encoder REFCOS
POWER
COMMON
No Connection
DC Ground
+24 Vdc
(-) CLOCK
(+) CLOCK
(+) DATA
(-) DATA
7
6
5
4
3
2
1
LINEAR SENSOR
12
11
10
9
8
7
6
5
4
3
2
1
Rotary Encoder +COS
Rotary Encoder DATA+ (RS485)
Rotary Encoder REGISTRATION-
Linear Sensor REGISTRATION+
Linear Sensor CLOCK+
Rotary Encoder DATA- (RS485)
Linear Sensor DATA+
Linear Sensor CLOCK-
Linear Sensor DATA-
Rotary Encoder REGISTRATION+
Linear Sensor REGISTRATION-
CHASSIS GND
MDI Feedback Option Board
17
16
15
14
13
Rotary Encoder POWER COMMON
Rotary Encoder POWER
Rotary Encoder +SIN
Rotary Encoder REFSIN
Rotary Encoder REFCOS
GY
PK
GY
PK
GN
YE
YE
GN
WH
RD or BN
WH
RD or BN
EXTERNAL
24 Vdc
POWER
SUPPLY
MDI Option Card Connection Examples
Figure 30 - All MPL-A/B3xx, -A/B4xx, -A/B45xx, -A/B5xx, and -B6xx motors with 2090-CFBM7E7-CDAFXX or 2090-CFBM7DF-CDAFXX cable
Note: Thermal switch cannot be accessed by using 2090-CFBM7X7-CDAFXX cable.
Figure 31 - HPK-Series motors with 2090-XXNFMF-SXX cable
Note: Thermal switch cannot be accessed by using 2090-XXNFMF-SXX cable.
Figure 32 - Linear Sensor connections with MDI RG connector or P integral cable
Rockwell Automation Publication 20D-IN024C-EN-P - July 201375
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
12
11
10
9
8
7
6
5
4
3
2
1
Rotary Encoder +COS
Rotary Encoder DATA+ (RS485)
Rotary Encoder REGISTRATION-
Linear Sensor REGISTRATION+
Linear Sensor CLOCK+
Rotary Encoder DATA- (RS485)
Linear Sensor DATA+
Linear Sensor CLOCK-
Linear Sensor DATA-
Rotary Encoder REGISTRATION+
Linear Sensor REGISTRATION-
CHASSIS GND
MDI Feedback Option Board
17
16
15
14
13
Rotary Encoder POWER COMMON
Rotary Encoder POWER
Rotary Encoder +SIN
Rotary Encoder REFSIN
Rotary Encoder REFCOS
+SIN
REFSIN
+COS
REFCOS
DATA+ (RS-485)
DATA- (RS 485)
POWER
COMMON
TS+
TS-
A
B
C
D
E
F
N
P
R
S
BK
BK/WH
RD
WH/RD
GN
WH/GN
OR
WH/OR
BU
WH/BU
BK
BK/WH
RD
WH/RD
WH/OR
OR
BU
WH/BU
ROTARY ENCODER
GN
WH/GN
12
11
10
9
8
7
6
5
4
3
2
1
Rotary Encoder +COS
Rotary Encoder DATA+ (RS485)
Rotary Encoder REGISTRATION-
Linear Sensor REGISTRATION+
Linear Sensor CLOCK+
Rotary Encoder DATA- (RS485)
Linear Sensor DATA+
Linear Sensor CLOCK-
Linear Sensor DATA-
Rotary Encoder REGISTRATION+
Linear Sensor REGISTRATION-
CHASSIS GND
MDI Feedback Option Board
17
16
15
14
13
Rotary Encoder POWER COMMON
Rotary Encoder POWER
Rotary Encoder +SIN
Rotary Encoder REFSIN
Rotary Encoder REFCOS
+SIN
REFSIN
+COS
REFCOS
DATA+ (RS-485)
DATA- (RS 485)
POWER
COMMON
TS+
TS-
A
B
C
D
E
F
N
P
R
S
BK
BK/WH
RD
WH/RD
GN
WH/GN
OR
WH/GY
BK
BK/WH
RD
WH/RD
WH/GY
OR
ROTARY ENCODER
GN
WH/GN
MDI Option Card Connection Examples
Figure 33 - Rotary Encoder connections for MPL-A5xx and MPL-Bxxx motors or 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motors with 2090-
CDNFDMP-SXX cable
Figure 34 - Rotary Encoder connections for MPL-A5xx and MPL-Bxxx motors or 1326AB-BXXXX-M2L, -M2KXL, -S2L, and -S2KXL motors with 2090XXNFMP-SXX cable
Note: Thermal switch cannot be accessed by using 2090-XXNFMP-SXX cable.
Figure 35 - Rotary Encoder connections for MPL-A3xx - MPL-A45xx and all MPG series motors with 2090-XXNFMP-SXX cable
Note: Thermal switch cannot be accessed by using 2090-XXNFMP-SXX cable.
Rotary Encoder POWER COMMON
Rotary Encoder DATA+ (RS485)
Rotary Encoder DATA- (RS485)
Rotary Encoder REGISTRATION+
Rotary Encoder REGISTRATION-
Linear Sensor REGISTRATION+
Linear Sensor REGISTRATION-
76Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
Rotary Encoder POWER
Rotary Encoder REFSIN
Rotary Encoder +SIN
Rotary Encoder REFCOS
Rotary Encoder +COS
Linear Sensor CLOCK+
Linear Sensor CLOCK-
Linear Sensor DATA+
Linear Sensor DATA-
CHASSIS GND
MDI Feedback Option Board
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
WH/GY
GY
BK/WH
BK
WH/RD
RD
GN
WH/GN
BK/WH
RD
WH/RD
GN
WH/GN
GY
WH/GY
BK
ROTARY ENCODER
+SIN
A
REFSIN
B
+COS
C
REFCOS
D
DATA+ (RS-485)
E
DATA- (RS 485)
F
POWER
N
COMMON
P
TS+
R
TS-
S
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
12
11
10
9
8
7
6
5
4
3
2
1
Rotary Encoder +COS
Rotary Encoder DATA+ (RS485)
Rotary Encoder REGISTRATION-
Linear Sensor REGISTRATION+
Linear Sensor CLOCK+
Rotary Encoder DATA- (RS485)
Linear Sensor DATA+
Linear Sensor CLOCK-
Linear Sensor DATA-
Rotary Encoder REGISTRATION+
Linear Sensor REGISTRATION-
CHASSIS GND
MDI Feedback Option Board
17
16
15
14
13
Rotary Encoder POWER COMMON
Rotary Encoder POWER
Rotary Encoder +SIN
Rotary Encoder REFSIN
Rotary Encoder REFCOS
+SIN
REFSIN
+COS
REFCOS
DATA+ (RS-485)
DATA- (RS 485)
POWER
COMMON
TS+
TS-
A
B
C
D
E
F
K
L
R
S
BK
BK/WH
RD
WH/RD
GN
WH/GN
GY
WH/GY
BU
WH/BU
BK
BK/WH
RD
WH/RD
GN
WH/GN
GY
WH/GY
BU
WH/BU
ENCODER
12
11
10
9
8
7
6
5
4
3
2
1
Rotary Encoder +COS
Rotary Encoder DATA+ (RS485)
Rotary Encoder REGISTRATION-
Linear Sensor REGISTRATION+
Linear Sensor CLOCK+
Rotary Encoder DATA- (RS485)
Linear Sensor DATA+
Linear Sensor CLOCK-
Linear Sensor DATA-
Rotary Encoder REGISTRATION+
Linear Sensor REGISTRATION-
CHASSIS GND
MDI Feedback Option Board
17
16
15
14
13
Rotary Encoder POWER COMMON
Rotary Encoder POWER
Rotary Encoder +SIN
Rotary Encoder REFSIN
Rotary Encoder REFCOS
POWER
N/C
POWER COMMON
SHIELD
+COS
DATA- (RS 485)
REFSIN
+SIN
DATA+ (RS 485)
REFCOS
A
I
B
J
H
F
C
G
E
D
RD
BU
WH
BN
PK
BK
ROTARY ENCODER
BU
RD
BN
BK
GY
GN
WH
PK
GY
GN
MDI Option Card Connection Examples
Figure 36 - Rotary Encoder connections for MPL-A3xx - MPL-A45xx and all MPG series motors with 2090-UXNFDMP-SXX cable
Figure 37 - Stegmann shielded twisted-pair cable with 12-pin DIN style connector
ROTARY ENCODER
POWER
12
N/C
11
POWER COMMON
10
SHIELD
9
+COS
8
DATA- (RS 485)
7
REFSIN
6
+SIN
5
N/C
4
N/C
3
DATA+ (RS 485)
2
REFCOS
1
Rotary Encoder POWER COMMON
Rotary Encoder POWER
Rotary Encoder REFSIN
Rotary Encoder +SIN
Rotary Encoder REFCOS
Rotary Encoder +COS
Rotary Encoder DATA+ (RS485)
Rotary Encoder DATA- (RS485)
Linear Sensor CLOCK+
Linear Sensor CLOCK-
Linear Sensor DATA+
Linear Sensor DATA-
Rotary Encoder REGISTRATION+
Rotary Encoder REGISTRATION-
Linear Sensor REGISTRATION+
Linear Sensor REGISTRATION-
CHASSIS GND
MDI Feedback Option Board
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
BU
RD
BN
WH
BK
PK
GY
GN
RD
BU
PK
GN
BN
WH
GY
BK
Figure 38 - Rotary Encoder connections with Stegmann shielded twisted-pair cable and 10-pin MS style connector
Rockwell Automation Publication 20D-IN024C-EN-P - July 201377
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
78Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
Notes:
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Rockwell Automation Publication 20D-IN024C-EN-P - July 201379
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacic: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
www.rockwel lautomation.com
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support/
and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to
make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
TechConnect support programs. For more information, contact your local distributor or Rockwell Automation
representative, or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada1.440.646.3434
Outside United States or CanadaUse the Wo rldwi de Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell
Automation representative.
New Product Satisfaction Return
, you can find technical manuals, a knowledge base of FAQs, technical
.
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.
Outside United StatesPlease contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
, available at http://www.rockwellautomation.com/literature/.