Rockwell Automation 20D-700H, 20D-700S User Manual

Page 1
Installation Instructions
PowerFlex 700H and 700S AC Drives Frame 9 Main Fan Capacitor Replacement Kit
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive
parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, “Guarding Against Electrostatic Damage” or any other applicable ESD protection guide.
ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should perform maintenance/repair of the system. Failure to comply may result in personal injury and/or equipment damage.
ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
PFLEX-IN024B-EN-P
Page 2
PowerFlex 700H and 700S AC Drives Frame 9 Main Fan Capacitor Replacement Kit
What This Kit Includes
Tools That You Need
Photo ID# Part Description Quantity
1Fan capacitor 1 2 Fan capacitor, fuse holder and fan bracket 1 3 Fan inverter cover 1 4 Fan capacitor nut (M12) 1 5 Fan capacitor lock washer (M12) 1 6 Stirring fan screws (M4 x 16 mm) 2 7 Fuse holder and fan inverter cover screws (M4 x 8 mm) 3 8 Fan capacitor, fuse holder and fan bracket screws (M5 x 10 mm) 2 9 Connector screw (M3 x 8 mm - for SAF option only) 1
#2 POZIDRIV® screwdriver
19 mm Wrench
Fuse puller
Nose pliers
POZIDRIV® is a registered trademark of the Phillips Screw Company
What You Need to Do
Step 1: Remove power from the drive
Step 2: Remove the lower protective cover
Step 3: Remove the existing fan capacitor
Step 4: Install the new fan capacitor and bracket
2 Rockwell Automation Publication PFLEX-IN024B-EN-P - September 2011
Page 3
Step: 1 Remove Power from the Drive
PowerFlex 700H and 700S AC Drives Frame 9 Main Fan Capacitor Replacement Kit
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the DC bus voltage at the DC+ & DC- terminals. The voltage must be zero.
ATTENTION: Remove power before making or breaking cable connections. When you remove or insert a cable connector with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
sending an erroneous signal to your system’s field devices, causing
unintended machine motion
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
1. Turn off and lock out input power. Wait five minutes.
2. Verify that there is no voltage at the drive’s input power terminals.
3. Measure the DC bus voltage at the DC+ & DC- terminals on the power
terminal block. The voltage must be zero.
Step: 2 Remove the Lower Protective Cover
L1 L2 L3
I
O
Remove the eight POZIDRIV screws that secure the bottom protective cover to the drive and remove the cover. Tightening torque for re-assembly is 3 N
m (27 lbin.).
L1 L2 L3 L1 L2 L3 U/T1 V/T2 W/T3 U/T1 V/T2 W/T3
Rockwell Automation Publication PFLEX-IN024B-EN-P - September 2011 3
Page 4
PowerFlex 700H and 700S AC Drives Frame 9 Main Fan Capacitor Replacement Kit
Step: 3 Remove the Existing Fan Capacitor
1. If necessary, remove the cables from the input power terminals (L1, L2 and L3).
2. Remove the M4 x 8 mm POZIDRIV screw that secures the fan inverter cover to the drive frame and remove the cover. Discard the existing fan inverter cover and screw -- new parts are provided in the kit.
X2 X8
=
S1
ON
4
3
2
1
X7
X5
X4
X1
X6
4 Rockwell Automation Publication PFLEX-IN024B-EN-P - September 2011
Page 5
PowerFlex 700H and 700S AC Drives Frame 9 Main Fan Capacitor Replacement Kit
IMPORTANT
Mark all connections and wires before removing to avoid incorrect wiring during reassembly.
3. Remove the fuses from the fuse holder.
4. Disconnect the four fuse signal wires (black and red pairs) connected to
the top and bottom of the fuse holder.
IMPORTANT
Note that the red wires connect to the left side terminal on the fuse holder and the black wires connect to the right side terminal on the fuse holder.
5. Disconnect the stirring fan power wires.
Red wire Black wire
Disconnect fuse signal wires from fuse holder
Remove fuses from fuse holder
Disconnect fuse signal wires from fuse holder
Red wire Black wire
Disconnect stirring fan power wires
6. Remove the two M5 x 10 mm POZIDRIV screws that secure the fan capacitor, fuse holder and fan bracket to the drive frame, and lift the bracket out of the drive. Note that the fan capacitor is still connected to the drive circuitry. Discard the two M5 x 10 mm screws -- new hardware is provided in the kit.
7. Disconnect the capacitor wires from the connectors labelled “Blue” and “Brown”.
Rockwell Automation Publication PFLEX-IN024B-EN-P - September 2011 5
Page 6
PowerFlex 700H and 700S AC Drives Frame 9 Main Fan Capacitor Replacement Kit
X2 X8
S1
ON
4
3
2
1
X7
X5
X4
X1
X6
Remove screws and bracket
Disconnect fan capacitor wires from connectors labelled “Blue” and “Brown”
6 Rockwell Automation Publication PFLEX-IN024B-EN-P - September 2011
Page 7
PowerFlex 700H and 700S AC Drives Frame 9 Main Fan Capacitor Replacement Kit
IMPORTANT
Note the orientation of the air flow direction arrow on the fan housing before removal. The fan must be installed facing the same direction when re-installed.
8. Remove the two M4 x 16 mm POZIDRIV screws that secure the stirring fan to the bracket and remove the fan. Save the fan for reuse. Discard the two M4 x 16 mm screws -- new hardware is provided in the kit.
9. Remove the two M4 x 8 mm POZIRDRIV screws that secure the fuse holder to the bracket and remove the fuse holder. Save the fuseholder for reuse. Discard the two M4 x 8 mm screws -- new hardware is provided in the kit.
10. Discard the existing fan capacitor and bracket.
Remove screws and fuse holder
Remove screws and stirring fan. Note direction of air flow arrow.
Rockwell Automation Publication PFLEX-IN024B-EN-P - September 2011 7
Page 8
PowerFlex 700H and 700S AC Drives Frame 9 Main Fan Capacitor Replacement Kit
Step: 4 Install the New Fan Capacitor and Bracket
Install the new fan capacitor and bracket in the reverse order of removal.
1. Secure the new fan capacitor to the new bracket using the new M12 lock washer and M12 nut provided in the kit. Tightening torque is 12 N (106 lb
in.).
Secure new capacitor to new bracket with lock washer and nut
2. Secure the existing fuse holder to the bracket using the two new M4 x 8 mm POZIDRIV screws provided in the kit. Tightening torque is 2 N (18 lb
in.).
3. Verify that the air flow arrow on the fan points in the same direction as was noted before removal, and secure the existing stirring fan to the bracket using the two new M4 x 16 mm POZIDRIV screws. Tightening torque is
m (13 lbin.).
1.5 N
m
m
Verify that the fan blades turn freely
Verify that the power wires are located nearest to the bracket
4. Install the existing fuses in the fuse holder.
Verify that the air flow arrow on fan points in the correct direction.
5. Connect the blue fan capacitor wire to the connector labelled “Blue” and the brown fan capacitor wire to the connector labelled “Brown”.
8 Rockwell Automation Publication PFLEX-IN024B-EN-P - September 2011
Page 9
PowerFlex 700H and 700S AC Drives Frame 9 Main Fan Capacitor Replacement Kit
6. Connect the upper red and black pair of fuse wires (from X2 on the fan inverter circuit board) to the top of the fuse holder. Verify that the proper color wire is connected to the appropriate terminal on the fuse holder. See step 4
on page 5.
7. Insert the capacitor wires into the chassis so that they do not interfere with the stirring fan blades, insert the bracket with the fan capacitor, fuse holder and stirring fan into the drive chassis and secure the bracket with the two M5 x 10 mm POZIDRIV screws provided in the kit. Tightening torque is 4 N
m (35 lbin.).
8. Connect the bottom red and black pair of fuse wires to the bottom of the fuse holder. Verify that the proper color wire is connected to the appropriate terminal on the fuse holder. See step 4
on page 5.
9. Connect the stirring fan power wires to the connector on the stirring fan.
10. Secure the new fan inverter cover to the drive chassis using the new M4 x 8
mm POIDRIV screw provided in the kit. Tightening torque is 2 N
in.).
(17 lb
m
Rockwell Automation Publication PFLEX-IN024B-EN-P - September 2011 9
Page 10
*PN-125204*
PN-125204
U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, E-mail: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives
www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street,
/
Middle East/Africa: Rockwell Automati
Europe Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
on,
Publication PFLEX-IN024B-EN-P – September 2011
Supersedes Publication PFLEX-IN024A-E N-P - June 2011 Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in USA.
Milwaukee, WI 53204-2496 USA,
Pegasus Park, De Kleetlaan 12a,
Tel:
(1) 414.382.2000, Fax: (1) 414.382.4444
1831 Diegem, Belgium,
Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Loading...